NOTICE
EXSITING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK
TO BE REMOVED SHOWN DARK AND DASHED. NEW WORK
SHOWN DARK.
MAINTAIN MINIMUM CLEARANCE OF 10'-0" BETWEEN
OUTDOOR AIR INTAKES WITH PLUMBING BENTS, EXHAUST
FANS AND FLUE VENTS.
FC-1
2000
320
BUILDING A & D
UNIT WITH ELECT CONNECTION
SUPPLY CFM
OSA CFM
DOUBLE LINE DUCT WITH
1" THICK 1.5 LB DENSITY
DUCT LINER
POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE
AND LOCATION IF FIELD PRIOR TO START OF WORK.
BUILDING A ONLY
INSTALL NEW THERMOSTAT & EXTEND TO NEW UNIT.
2.
EXISTING RETURN AIR REGISTER TO REMAIN. EXISTING
RETURN AIR DUCT UP TO ROOF TO REMAIN.
3.
NEW EF-1 SWITCH.
4.
PROVIDE NEW FULL SIZE KRUEGER EGC RETURN AIR
GRILLE WITH 1"x1"x1" CUBES IN PLACE OF EXISTING
SUPPLY DIFFUSER.
5.
EXISTING SUPPLY GRILLE AIR BALANCE TO AIR FLOW
NOTED.
6.
3/4" DRAIN DOWN FROM ABOVE.
7.
REMOVE EXISTING RETURN REGISTER. CLEAN DUCT
INTERIOR & REGISTER. RE-INSTALL REGISTER FOR
RE-USE.
8.
PRECHARGED REFRIGERANT TUBING UP THRU ROOF TO
UNIT (FURNISH WITH UNIT). SIZE PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE 1" ARMSTRONG AP2000
25/50 ELASTOMERIC INSULATION FOR VAPOR PIPING.
PROVIDE UV PROTECTION FOR PIPING INSTALLED
OUTDOORS.
9.
REFER TO THRU WALL FIRE DAMPER DETAIL 1-(M2.02).
10.
FULL SIZE DRAIN FROM UNIT WITH VENTED P-TRAP.
11.
3/4" DRAIN DOWN IN WALL, TIE INTO TAILPIECE OF
LAVATORY/SERVICE SINK. PROVIDE CHROME PLATED
ESCUTCHEON AT WALL PENETRATION.
12.
REFER TO INTERIOR SOFFIT DETAIL 2-(M2.02).
13.
SUPPLY GRILLE TO MATCH EXISTING.
14.
OUTSIDE AIR GRILLE TO MATCH EXISTING.
15.
3/4" DRAIN DOWN.
16.
OSA DUCT OPENING.
17.
8" x 8" OSA DUCT UP.
18.
REROUTE PLUMBING VENT PIPING BELOW ROOF DECK TO
NEW VTR LOCATION SHOWN.
PARTIAL FIRST FLOOR PLAN - BUILDINGS A & D
BUILDING A & D
BUILDING A ONLY
B
BUILDING A AND D
BID DOCUMENTS
A
1.
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
KEY NOTES
PARTIAL SECOND FLOOR PLAN - BUILDINGS A & D
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
FULL HEIGHT RATED WALL
15031
(REFER TO ARCHITECTURAL PLANS
FOR CONSTRUCTION AND RATING)
CLEARANCE PER
MANUFACTURER'S
INSTRUCTIONS
3" MINIMUM, 6" MAXIMUM
(TYPICAL ALL SIDES)
ANGLE IRON 1-1/2" x 1-1/2"
16 GAUGE GALVANIZED STEEL
1" MINIMUM
NUTS OR TACK OR SPOT
DUCT
WELDS AT 6" ON CENTER
UNDERSIDE OF STRUCTURE
OR #10 SHEET METAL SCREWS
ACCESS DOOR AND
IDENTIFICATION
MECHANICAL
CODE 606.5
FIRE
DAMPER
STEEL STUD BRACING @ 48" O.C.
EXISTING CEILING
6"
PER 2009 UNIFORM
RECTANGULAR OR
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 M202.dwg, 1/13/2016 12:08:29 PM
BUILDING A & D
5/8" TYPE "X" GYPSUM BOARD
3 5/8" METAL STUDS
FIRE DAMPER
SLEEVE - GAUGE PER
PLAIN 'S' SLIP BREAKAWAY
MANUFACTURER'S
JOINT CONNECTION PER
RECOMMENDATION
MANUFACTURER'S INSTRUCTIONS
SEE CEILING PLAN
PARTIAL
FLOOR PLANS
BUILDINGS
A&D
DYNAMIC RATED FIRE DAMPER
EQUAL TO GREENHECK MODEL
DFD-150X WITH FACTORY SLEEVE
C
PARTIAL THIRD FLOOR PLAN - BUILDINGS A & D
1
FIRE DAMPER DETAIL
2
INTERIOR SOFFIT DETAIL
M2.02
ELECTRICAL SPECIFICATIONS
A. CONDITIONS
1.
FURNISH AND INSTALL A COMPLETELY WIRED AND OPERATIONAL ELECTRICAL SYSTEM AS SHOWN ON THE DRAWINGS
AND SPECIFIED HEREIN, INCLUDING BUT NOT LIMITED TO, THESE MAJOR ITEMS.
A.
B.
C.
LIGHTING FIXTURES AS INDICATED AND SPECIFIED ON THE PLANS.
ELECTRICAL PANELS, SERVICE, CONDUIT, WIRING, ETC. FOR ALL OUTLETS AND EQUIPMENT.
TELEPHONE OUTLETS AND CONDUIT AS INDICATED.
B. CODES, REGULATIONS AND STANDARDS
1.
THE INSTALLATION SHALL COMPLY WITH APPLICABLE LOCAL AND STATE CODES AND ORDINANCES WITH THE
REGULATIONS OF THE CURRENTLY ACCEPTED EDITION OF THE NATIONAL ELECTRIC CODE AND WITH THE
REQUIREMENTS OF THE POWER, TELEPHONE, AND CATV COMPANIES FURNISHING SERVICES TO THIS INSTALLATION.
2.
9.
THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONS STANDARDS.
THE NATIONAL ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS.
UNDERWRITER LABORATORIES INCORPORATED STANDARDS.
AMERICAN NATIONAL STANDARDS INSTITUTE.
STATE PUBLIC WORKS BOARD CURRENT ADOPTED STANDARDS.
ALL CONDUIT SYSTEMS SHALL HAVE A CODE SIZED COPPER GROUND CONDUCTOR INCREASE CONDUIT SIZE AS REQUIRED.
10. CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE.
INSTALLATION SHALL BE WATERTIGHT. VERIFY ROOF TYPE WITH CONTRACTOR PRIOR TO THE INSTALLATION.
T
F
PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED
CONSTRUCTION AND SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE EXISTING UTILITIES, AND WORKING
CONDITIONS TO BE ENCOUNTERED, ETC. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE WITH THIS
CONDITIONS AFTER BIDDING.
2.
1.
2.
EACH SWITCH, LIGHT, RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED WITH A CODE GAUGE, GALVANIZED STEEL OUTLET
BOX. JUNCTION AND PULL BOXES SHALL BE CODE GAUGE, GALVANIZED STEEL. OUTLET BOXES SHALL BE OF THE ONE PIECE
KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER RING. PLASTER RINGS SHALL BE SET TO PROJECT NOT MORE THAN
1/8" FROM WALL SURFACE TO RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL. SINGLE GANG
RINGS SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR 4" BOXES IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED
FOR UNFINISHED MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK COURSE.
BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST IRON OR STEEL WITH WATERTIGHT GASKETED
COVERS. WHERE BOXES ARE INSTALLED IN FLOORS WITH TILE OR CARPET FLOOR COVERING, COVERS SHALL BE OF THE
RECESSED TYPE TO ACCOMMODATE THE FLOOR COVERING.
1.
2.
3.
3.
4.
DELIVER MATERIALS AND EQUIPMENT TO THE PROJECT IN THE MANUFACTURER'S ORIGINAL, UNOPENED, LABELED
CONTAINERS. PROTECT AGAINST MOISTURE, TAMPERING OR DAMAGE FROM IMPROPER HANDLING OR STORAGE.
CONTRACTORS SHALL PROTECT AND BE RESPONSIBLE FOR ANY DAMAGE TO WORK OR MATERIALS UNTIL FINAL
ACCEPTANCE BY THE OWNER, AND SHALL MAKE GOOD WITHOUT COST TO THE OWNER, ANY DAMAGE OR LOSS THAT
MAY OCCUR DURING THIS PERIOD.
ARRANGE FOR TIMELY DELIVERY OF MATERIALS AND EQUIPMENT TO THE JOB SITE IN ORDER TO MINIMIZE THE
LENGTH OF TIME BETWEEN DELIVERY AND INSTALLATION.
COVER AND PROTECT ANY MATERIAL WHICH MAY BE AFFECTED BY THE WEATHER WHILE IN TRANSIT OR STORED AT
THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE OR NOT INSTALLED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS MAY BE REJECTED BY THE ENGINEER.
KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR RUBBISH CAUSED BY EMPLOYEES OR
WORK UNDER THIS DIVISION OF THE SPECIFICATIONS. AT THE COMPLETION OF THE WORK REMOVE ALL SURPLUS
MATERIALS, TOOLS, ETC., AND LEAVE THE PREMISES BROOM-CLEAN.'
F. DRAWINGS
1.
THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND LOCATIONS OF THE ELECTRICAL WORK. DATA
PRESENTED ON THESE DRAWINGS ARE AS ACCURATE AS PLANNING CAN DETERMINE, BUT FIELD VERIFICATION OF ALL
DIMENSIONS, LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL ARCHITECTURAL,
STRUCTURAL, AND MECHANICAL DRAWINGS AND ADJUST ALL WORK TO MEET THE REQUIREMENTS OF CONDITIONS
SHOWN. THE ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER ALL OTHER DRAWINGS. DISCREPANCIES
BETWEEN DIFFERENT PLANS, OR BETWEEN DRAWINGS AND SPECIFICATIONS, OR REGULATIONS AND CODES
GOVERNING THE INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE THE
DATE OF BID OPENING. IF DISCREPANCIES ARE NOT REPORTED, THE CONTRACTOR SHALL BID THE GREATER
QUANTITY OR BETTER QUALITY, AND ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD. CONTRACTOR SHALL BE
RESPONSIBLE TO FIELD MEASURE AND CONFIRM MOUNTING HEIGHTS AND LOCATION OF ELECTRICAL EQUIPMENT
WITH RESPECT TO COUNTERS, RADIATION, ETC. DO NOT SCALE DISTANCES OFF THE ELECTRICAL DRAWINGS, USE
ACTUAL BUILDING DIMENSIONS.
COOPERATE WITH THE OTHER TRADES SO THAT THE INSTALLATION OF THE ELECTRICAL OUTLETS AND EQUIPMENT
WILL BE PROPERLY COORDINATED. CONDUIT, LIGHTING FIXTURES, AND OTHER EQUIPMENT LOCATIONS SHALL BE
CHECKED WITH OTHER TRADES TO AVOID CONFLICT WITH THE PIPING, DUCTWORK, STEEL, BEAMS, OR OTHER
OBSTRUCTIONS.
CAREFULLY CHECK THE LOCATIONS OF THE OUTLET BOXES AND DETERMINE THAT THEY HAVE NOT BEEN
DISTURBED DURING THE INSTALLATION OF MATERIALS OF OTHER TRADES.
2.
COORDINATE HVAC EQUIPMENT CONNECTION REQUIREMENTS WITH HVAC CONTRACTOR.
PART II - PRODUCTS AND EXECUTION
A. MATERIALS
1.
ALL CONDUCTORS SHALL BE COPPER.
2.
NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT SYSTEM IS COMPLETE. USE MINERALAC NO. 100
OR EQUIVALENT AS A LUBRICANT TO FACILITATE THE INSTALLATION OF THE CONDUCTORS IN THE CONDUIT SYSTEM.
3.
SPLICES IN EXTERIOR PULL BOXES AND MANHOLES SHALL BE WEATHERPROOF USING "SCOTCHCAST" SPLICE KIT OR
APPROVED EQUAL. SEAL ENDS OF CONDUITS AND DUCTS WITH "DUCTSEAL" OR APPROVED EQUAL.
4.
PROVIDE SOLID CONDUCTOR FOR 10 AWG AND SMALLER.
5.
TYPE MC IS NOT PERMITTED. USE EMT FOR USE AS FEEDERS, BRANCH CIRCUITS, POWER, LIGHTING, CONTROL, AND SIGNALS.
IT MAY BE USED CONCEALED OR EXPOSED, INDOOR OR OUTDOOR. IF IDENTIFIED FOR SUCH USE IT MAY BE USED AS DIRECT
BURIAL OR CABLE TRAY OR ANY RACEWAY. IT CAN BE INSTALLED IN WALLS EITHER DAMP OR WET LOCATION, IN WET
LOCATIONS WHERE REQUIREMENTS ARE MET. INSTALL PER ART. 320 OF THE N.E.C.
ALL MATERIALS SHALL BE NEW AND OF QUALITY AS SPECIFIED ON THE PLANS OR SPECIFICATIONS AND MUST CARRY
THE UNDERWRITER'S LABORATORIES APPROVAL COVERING THE PURPOSE FOR WHICH THEY ARE USED, IN ADDITION
TO MEETING ALL REQUIREMENTS OF THE CURRENT APPLICABLE CODES AND REGULATIONS.
2.
3.
4.
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 EG101.dwg, 1/13/2016 12:08:39 PM
5.
ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC CONDUIT EXCEPT AS PERMITTED BELOW. RGS, WITH 20 MIL PVC
COATING WILL BE USED WHEN IN CONTACT WITH EARTH. IMC MAY BE USED IN INDOOR LOCATIONS NOT IN CONTACT
WITH THE EARTH. EMT MAY BE USED IN INDOOR LOCATIONS NOT IN CONTACT WITH EARTH, NOT IN CONCRETE SLABS
OR WALLS AND NOT SUBJECT TO DAMAGE. PVC MAY BE USED IN OR BELOW CONCRETE AND DIRECT BURIED IN EARTH.
FLEXIBLE STEEL CONDUIT SHALL BE USED FOR INDOOR FINAL CONNECTIONS TO EQUIPMENT IN LENGTHS NOT TO
EXCEED 12". LIQUID-TIGHT FLEXIBLE STEEL CONDUIT SHALL BE FOR OUTDOOR FINAL CONNECTIONS TO EQUIPMENT
NOT TO EXCEED 36".
WHERE CONDUIT ENTERS OUTLET BOXES, FIXTURES OR CABINETS, FIRMLY FASTEN WITH STEEL SET SCREW
COMPRESSION CONNECTORS, OR DOUBLE LOCKNUTS FOR GRC. ALL CONNECTIONS SHALL HAVE BUSHINGS OR
INSULATED THROAT CONNECTORS. FIRMLY FASTEN CONDUIT TO THE BUILDING CONSTRUCTION. RUN EXPOSED
CONDUIT PARALLEL TO THE BUILDING LINES, SUPPORTED BY APPROPRIATE HANGERS (UNISTRUT, T & B OR
APPLETON, OR EQUAL).
COVER METALLIC CONDUIT IN CONTACT WITH EARTH WITH POLYETHYLENE TAPED SPIRAL WRAPPED, 1/2 LAPPED TO
PROVIDE 20 MIL. THICKNESS. TAPE SHALL BE SCOTCH NO. 50 TAPE. CONDUIT AND DUCTS NOT UNDER BUILDINGS AND
FEEDER DUCTS SHALL BE INSTALLED PER N.E.C. 300-5. MAKE JOINTS WITH COMPOUND TO BE WATERTIGHT.
PANELBOARD FLUSH MOUNTED
V
CLASSROOM WIRELESS CEILING ENCLOSURE (CEILING) (1) CAT 6 DATA AND (1) CAT 6 (POE) DATA
SWITCHBOARD
P
PROJECTOR MOUNT (WALL)
TERMINAL CABINET
CS
CEILING SPEAKER
TRANSFORMER
TS
TEACHER STATION
DATA OUTLET @+ 18" AFF UNLESS NOTED OTHERWISE
a
6.
ALL EMPTY CONDUIT SYSTEMS SHALL HAVE A NYLON FULL STRING TO FACILITATE INSTALLATION OF FUTURE WIRE.
7.
SCHEDULE 40 PVC CONDUIT SHALL BE PERMITTED UNDERGROUND WITH PROPER FITTINGS, ALL UL APPROVED AND
CEMENTED JOINTS. PENETRATIONS THOUGH FLOOR SLABS AND BENDS GREATER THAN 22" SHALL BE WRAPPED RIGID
GALVANIZED STEEL ELBOWS.
CLG
E. WIRING DEVICES
1.
2.
3.
4.
WALL SWITCHES SHALL BE SPECIFICATION GRADE AC SILENT TYPE SWITCHES, 20A, 120/277 VOLT. SEE ARCHITECTURAL
SPECIFICATIONS FOR COLOR.
46"
RECEPTACLES SHALL BE SPECIFICATIONS GRADE, DUPLEX TYPE, NEMA 5-20R, 20 AMPERE, 120 VOLT GROUNDED TYPE.
SPECIAL APPLICATION RECEPTACLES SHALL BE INDICATED ON PLANS. MOUNT WITH THE GROUND DOWN. SEE ARCHITECTURAL
SPECIFICATIONS FOR COLOR.
DEVICE PLATES SHALL BE EQUAL TO SIERRA SMOOTH-LINE NYLON WALL PLATES. COLOR SHALL BE THE SAME AS THE DEVICE
COLOR UNLESS OTHERWISE NOTED.
RECEPTACLES IN OUTDOOR AND WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY
MARKED AS U.L LISTED SUITABLE FOR WET LOCATIONS WHILE IN USE, EQUAL TO TAYMAC SPECIFICATION GRADE.
C
46"
F. SYSTEM GROUNDING
1.
2.
COMPUTER OUTLET (WIREMOLD)
ASTRONOMICAL TIME CLOCK (MOUNT AT 5'-0"AFF MAX)
WL
COMPUTER OUTLET (WIRELESS)
W
GENERAL WIRELESS ENCLOSURE, WALL MOUNTED
CLG
GENERAL WIRELESS ENCLOSURE, CEILING MOUNTED (1) CAT 6 (POE) DATA
CLG
ACTIVE CEILING ENCLOSURE, CEILING MOUNTED
CLG
PASSIVE CEILING ENCLOSURE, CEILING MOUNTED
SOLENOID VALVE
W
THERMOSTAT
W
JUNCTION BOX
A
DIVISION 15 EQUIPMENT
E
FOOD SERVICE EQUIPMENT
BRANCH CIRCUIT CONSISTING OF 2 #12 PLUS GROUND IN MINIMUM SIZE CONDUIT
PHOTOCELL
HOME RUN TO PANELBOARD OR DEVICE - NUMBER OF ARROWHEADS INDICATE NUMBER OF CIRCUITS
MANHOLE OR PULLBOX
BRANCH CIRCUIT - SHORT SLASHES INDICATE NUMBER OF PHASE OR SWITCH
LEGS LONG SLASHES INDICATE NUMBER OF NEUTRAL AND GROUND
LONG SLASH WITH DOT INDICATES ISOLATED GROUND.
CEILING MOUNTED FLUORESCENT FIXTURE - LOWER CASE LETTER DENOTES
SWITCHING. UPPER CASE LETTER DENOTES FIXTURE TYPE.
DASHED LINES REPRESENTS EXISTING.
WALL MOUNTED FIXTURE (HID SHOWN)
CONDUIT IN SLAB OR UNDERGROUND
HID FIXTURE
CONDUIT RISER UP
FLUORESCENT FIXTURE
CONDUIT RISER DOWN
FLUORESCENT STRIP FIXTURE
INTERRUPTER SWITCH
EMERGENCY LIGHTING UNIT
FUSE
EXIT FIXTURE - SHADES AREA DENOTES LIGHTED FACE - ARROW DENOTES DIRECTION
CIRCUIT BREAKER
M
G. GUARANTEE
KW
EXISTING TELEPHONE OUTLET @ +18" AFF UNLESS NOTED OTHERWISE
(1) CAT 6 ANALOG PHONE OUTLET (W - INDICATES MOUNTED IN SURFACE RACEWAY)
MOTOR OUTLET
DUPLEX RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE
EXISTING TELEPHONE OUTLET AT +46" AFF
(1) CAT 6 ANALOG PHONE OUTLET
FLOOR MOUNTED DUPLEX RECEPTACLE
TELEPHONE OUTLET, COUNTER HEIGHT
(1) CAT 6 ANALOG PHONE OUTLET
QUADRAPLEX COMPUTER RECEPTACLE AT +18" AFF, UNLESS NOTED OTHERWISE. RECEPTACLE AND COVER TO BE GREY
TELEPHONE OUTLET, COUNTER HEIGHT
(1) CAT 6 ANALOG PHONE OUTLET
GFCI RECEPTACLE
QUADRUPLEX RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE
DUPLEX COMPUTER RECEPTACLE AT +18" AFF, UNLESS NOTED OTHERWISE. RECEPTACLE AND COVER TO BE GREY.
SPECIAL PURPOSE RECEPTACLE
MULTIOUTLET ASSEMBLY
TELEPHONE OUTLET AT +46" AFF
(1) CAT 6 ANALOG PHONE OUTLET
SINGLE POLE SWITCH @ +48" AFF UNLESS NOTED OTHERWISE
3
THREE WAY SWITCH @ +48" AFF UNLESS NOTED OTHERWISE
TELEPHONE OUTLET @ +18" AFF UNLESS NOTED OTHERWISE
(1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE
4
FOUR WAY SWITCH @ +48" AFF UNLESS NOTED OTHERWISE
K
KEY OPERATED SWITCH @ +48" AFF UNLESS NOTED OTHERWISE
TELEPHONE OUTLET, COUNTER HEIGHT
(1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE
D
DIMMER OPERATED SWITCH @ +48" AFF UNLESS NOTED OTHERWISE
P
SWITCH WITH PILOT LIGHT @ +48" AFF UNLESS NOTED OTHERWISE
TELEPHONE OUTLET AT +46" AFF
(1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE
M
MOTION SENSOR SWIITCH @ +48" AFF UNLESS NOTED OTHERWISE
T
DIGITAL TIMER SWITCH @ +48" AFF UNLESS NOTED OTHERWISE.
1
SOUND SYSTEM CONTROL AND AMPLIFIER CABINET
MS
CEILING MOUNTED MOTION SENSOR
2
INTERCOM / CLOCK BOX WITH CALL SWITCH MOUNTED BELOW AT 48" AFF.
PP
POWER PACK FOR MOTION SENSOR
C
46"
HORN
3.
THE CONTRACTOR SHALL SUBMIT SEVEN(7) IDENTICAL BOUND SETS OF SHOP DRAWINGS ON THE FOLLOWING ITEMS:
A.
LIGHTING FIXTURE CUTES AND PERFORMANCE DATA.
B.
OUTLINE AND DATA SHEETS OF EACH PANELBOARD AND SWITCHBOARD
C.
OUTLINE DRAWINGS OF ALL SWITCHGEAR.
SUBMIT ITEMS AT ONE TIME IN A NEAT AND ORDERLY MANNER WITHIN 15 DAYS OF AWARD OF CONTRACT. PARTIAL
SUBMITTALS WILL NOT BE ACCEPTABLE.
I. RECORD AND AS-BUILT DRAWINGS
1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE JOB SITE FOR THE EXCLUSIVE PURPOSE OF
MAINTAINING A RECORD OF ALL WORK INSTALLED AND TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON THE
DRAWINGS.
2.
AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE DRAWINGS, SHOWING ALL AS-BUILT CONDITIONS, SHALL
BE DELIVERED TO THE OWNER FOR ACCEPTANCE PRIOR TO FINAL PAYMENT.
GENERATOR
SINGLE RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE
H. SHOP DRAWINGS AND APPROVALS
2.
G
EXISTING TELEPHONE OUTLET, COUNTER HEIGHT
(1) CAT 6 ANALOG PHONE OUTLET
INDIVIDUAL SPEAKER OR SPEAKER IN CONTROL MODULE
THE ITEMS SPECIFIED HEREIN AND ON DRAWINGS ARE USED AS A STANDARD OF QUALITY. ANY MATERIALS OF EQUAL
QUALITY AND AESTHETIC VALUE WILL BE GIVEN CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO
APPROVAL WILL BE GIVEN TO A SPECIFIC CATALOG NUMBER MODEL, OR TYPE OF EQUIPMENT, PRIOR TO BIDDING. AFTER
BIDDING, THE DECISION OF THE ARCHITECT AND/OR ENGINEER DETERMINING EQUAL MATERIALS WILL BE FINAL.
KILOWATT HOUR DEMAND METER
CURRENT TRANSFORMERS
GUARANTEE ALL MATERIAL FURNISH AND ALL WORKMANSHIP PERFORMED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL
ACCEPTANCE OF WORK. ANY DEFECTS DEVELOPING WITHIN THIS PERIOD, TRACEABLE TO MATERIAL FURNISHED AS A PART OF THIS
SECTION OR WORKMANSHIP PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE.
1.
METERING
TRACK LIGHTING WITH FIXTURE(S)
TELEPHONE TERMINAL BOARD 4' X 8' X 3/4" FIRE TREATED PLYWOOD
GROUNDING SHALL COMPLY WITH REQUIREMENTS OF ARTICLE 250. ALL EXPOSED NONCURRENT CARRYING METALLIC
PARTS OF ELECTRICAL EQUIPMENT, METALLIC RACEWAY SYSTEMS, METALLIC CABLE ARMOR, GROUNDING CONDUCTOR OF
NONMETALLIC SHEATHED CABLES, GROUNDING CONDUCTOR IN NONMETALLIC RACEWAYS, AND GROUNDED CONDUCTORS
OF THE WIRING SYSTEM SHALL BE GROUNDED.
GROUNDING CONDUCTOR (NEUTRAL) OF THE WIRING SYSTEM SHALL BE CONNECTED TO THE SYSTEM GROUNDING
CONDUCTORS AT A SINGLE PLACE IN EACH SYSTEM BY REMOVABLE BONDING JUMPERS, SIZED ACCORDING TO THE
APPLICABLE PROVISIONS OF THE NATIONAL ELECTRICAL CODE. THE GROUNDED CONDUCTOR (NEUTRAL) TO THE
GROUNDING CONDUCTOR CONNECTION SHALL BE LOCATED IN THE ENCLOSURE FOR THE SYSTEM'S OVERCURRENT
PROTECTION OR WHERE OTHERWISE INDICATED ON THE PLANS OR SPECIFICATIONS.
COMPUTER OUTLET OR SPECIAL PURPOSE COMMUNICATIONS, CEILING MOUNTED
W
EMERGENCY CONNECTED FIXTURE (FLUORESCENT SHOWN)
C
DATA OUTLET 6" ABOVE BACKSPLASH OF COUNTER
DISCONNECT SWITCH NON-FUSIBLE
CONTROL STATION
CLOCK (IN CONTROL MODULE)
INFRARED REPEATER (ALS SYSTEM)
MP
MICROPHONE OUTLET
FIRE ALARM DEVICE - NUMBER REFERS TO DEVICE SCHEDULE
STANDARD ABBREVIATIONS
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
A
AMPERE
MCB
MAIN CIRCUIT BREAKER
AFF
ABOVE FINISHED FLOOR
MECH.
MECHANICAL
AF
ARC FAULT, AMP FUSE
MIN.
MINIMUM
AFG
ABOVE FINISHED GRADE
MLO
MAIN LUGS ONLY
AIC
AMPERE INTERRUPTING CAPACITY
MTD
MOUNTED
AL
ALUMINUM
NC
NORMALLY CLOSED
ARCH'L.
ARCHITECTURAL
NEC
NATIONAL ELECTRICAL CODE
AS
AMP SWITCH
NECA
NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
AWG
AMERICAN WIRE GAUGE
NEMA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
BC
BARE COPPER
NEUT
NEUTRAL
BLDG
BUILDING
NFC
NATIONAL FIRE CODE
C
CONDUIT
NF
NON-FUSIBLE
CAB
CABINET
NIC
NOT IN CONTRACT
CAT
CATALOG/CATEGORY
NL
NIGHT LIGHT
C/B
CIRCUIT BREAKER
NO
NORMALLY OPEN
CKT
CIRCUIT
NPCO
NEVADA POWER COMPANY
CLG
CEILING
NTS
NOT TO SCALE
CO, EC
CONDUIT ONLY
OCP
OVERCURRENT PROTECTION
COMM
COMMUNICATION
P
CU
COPPER
DEMO
FITTINGS AND CONDUIT BODIES SHALL BE STEEL. NO DIECAST FITTINGS.
CONDUIT SIZES SHALL BE AS REQUIRED BY CODE AND AS INDICATED OR SPECIFIED. PROVIDE PULL BOXES AT
INTERVALS PER THE N.E.C.
C
POLE MOUNTED FIXTURE (DOUBLE ARM, 2 FIXTURES)
B. CONDUIT
1.
BOXES FOR TELEPHONE COMPUTER, T.V., FIRE ALARM, SECURITY, AND SIMILAR SYSTEMS SHALL BE MINIMUM 4" SQUARE AND
2-1/8" DEEP AND PROVIDED WITH PULL STRINGS.
1.
G. COOPERATION WITH OTHER CONTRACTORS
1.
P
D.WIRE
E. CLEANUP
1.
BOXES INSTALLED FOR THE ALARM, COMPUTER, AND SECURITY SYSTEM SHALL BE PROVIDED WITH APPROPRIATE COVER
PLATES AND PULL STRINGS.
ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS.
D. STORAGE AND HANDLING OF MATERIAL
MEDIA CENTER OUTLETS (WALL MOUNTED)
DISCONNECT SWITCH FUSIBLE (SHADED AREAS INDICATES VENDOR FURNISHED)
C. INSPECTION OF SITE
1.
M
COMBINATION MOTOR STARTER (SHADED AREAS INDICATE VENDOR FURNISHED)
C. OUTLET, PULL, AND JUNCTION BOXES
DESCRIPTION
PANELBOARD SURFACE MOUNTED
MOTOR STARTER
11. CONDUITS TO BE ROUTED ON THE SURFACE OF THE STRUCTURE, SHALL BE PARALLEL AND PERPENDICULAR TO THE
STRUCTURE. BEFORE THIS INSTALLATION TAKES PLACE, VERIFY WITH ARCHITECT.
THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS AND CODES ARE MINIMUM REQUIREMENTS.
A.
B.
C.
D.
E.
CONDUITS AND OUTLETS SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE EXCEPT THAT CERTAIN MOTOR AND
LIGHTING FEEDER CONDUITS MAY BE RUN EXPOSED IN CERTAIN AREAS AS INDICATED ON THE DRAWINGS. CONDUIT SHOWN
TO BE INSTALLED IN CABINETS, AND CASEWORK SHALL BE RUN AS DIRECTED BY THE ARCHITECT.
SYMBOL
SYMBOL
BUILDING A AND D
BID DOCUMENTS
8.
DESCRIPTION
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
SYMBOL
09-29-15 PERMIT SET
PART I - GENERAL
LEGEND
SHEET NO
SHEET DESCRIPTION
EG1.01
ELECTRICAL SPECIFICATIONS, LEGEND AND ABBREVIATIONS
POLE
E1.01
ELECTRICAL DEMOLITION & NEW ROOF PLAN - BUILDING A
PH
PHASE
E1.02
ELECTRICAL DEMOLITION & NEW ROOF PLAN - BUILDING D
DEMOLITION/DEMOLISH
PNL
PANEL
DISC
DISCONNECT
PV
PV PHOTOVOLTAIC
E2.01
ELECTRICAL FLOOR PLANS FIRST FLOOR - BUILDING A & D
DN
DOWN
PVC
POLYVINYL CHLORIDE
E2.02
ELECTRICAL FLOOR PLANS SECOND FLOOR - BUILDING A & D
DWG
DRAWING
PWR
POWER
E2.03
ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING A & D
EA
EACH
QTY
QUANTITY
ELECT.
ELECTRICAL
RECEP
RECEPTACLE
E3.01
DEMOLITION SINGLE LINE DIAGRAMS - BUILDINGS A & D
ELEV
ELEVATOR
REQ'D
REQUIRED
E3.02
SINGLE LINE DIAGRAMS, LOAD CALC, PANEL - BUILDINGS A & D
EM
EMERGENCY
RSC
RIGID STEEL CONDUIT
EMT
ELECTRICAL METALLIC TUBING
SCHED
SCHEDULE
E4.01
ELECTRICAL DETAILS
EQUIP
EQUIPMENT
SECT
SECTION
(E), EXIST
EXISTING
SP
SINGLE POLE
FBO
FURNISHED BY OTHERS
SN
SOLID NEUTRAL
FF
FINISHED FLOOR
SPEC
SPECIFICATION
FIXT
FIXTURE
SW
SWITCH
FLEX
FLEXIBLE METALLIC CONDUIT (STEEL)
SWBD
SWITCHBOARD
FLUOR
FLUORESCENT
SWGR
SWITCH GEAR
FT
FEET OR FOOT
SYS
SYSTEM
GFA
GROUND FAULT ALARM
TEMP
TEMPORARY
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
TELE
TELEPHONE
GND
GROUND
T-STAT
THERMOSTAT
HP
HORSEPOWER
TTB
TELEPHONE TERMINAL BACKBOARD
HVAC
HEATING, VENTILATING & AIR CONDITIONING
TTC
TELEPHONE TERMINAL CABINET
IBC
INTERNATIONAL BUILDING CODE
TYP.
TYPICAL
IMC
INTERMEDIATE METAL CONDUIT
UBC
UNIFORM BUILDING CODE
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
15031
ELECTRICAL
SPECS, LEGEND
AND
ABBREVIATIONS
EG1.01
A
EXISTING HVAC TO BE DEMOLISHED AND RETURNED TO OWNER.
REMOVE EXISTING WIRE FOR POWER AND CONTROLS BACK TO POINT
OF CONNECTION AND MAINTAIN EXISTING CIRCUIT FOR THE
INSTALLATION OF NEW MECHANICAL.
2.
DAMAGED EXISTING WP RECEPTACLE. DISCONNECT AND RECONNECT
WITH NEW WP RECEPTACLE AS REQUIRED.
3.
EXISTING HEAT PUMP TO REMAIN.
ELECTRICAL DEMOLITION ROOF PLAN - BUILDING A
KEY NOTES
1.
COORDINATE EXACT LOCATIONS OF MECHANICAL
EQUIPMENT AND POWER CONNECTION LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
2.
PROVIDE N3R DISCONNECT SWITCH (RK5 FUSES PER
MANUFACTURER'S RECOMMENDATIONS) AS SHOWN ON
PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO INSTALLATION ROUGH-IN. (TYPICAL)
3.
EXISTING RECEPTACLE. PROVIDE NEW GFCI (WR RATED)
AND WEATHERPROOF COVER.
4.
MAINTAIN EXISTING CIRCUIT.
5.
INTERCONNECTED WITH CORRESPONDING INDOOR UNIT.
MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
BUILDING A AND D
BID DOCUMENTS
1.
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
DEMOLITION KEY NOTES
GENERAL NOTES
1.
SEE E4.01 FOR TYPICAL ROOF DETAILS.
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E101.dwg, 1/13/2016 12:09:04 PM
15031
ELECTRICAL
DEMOLITION &
NEW ROOF
PLAN BUILDING A
B
ELECTRICAL NEW ROOF PLAN - BUILDING A
E1.01
A
EXISTING HVAC TO BE DEMOLISHED AND RETURNED TO OWNER.
REMOVE EXISTING WIRE FOR POWER AND CONTROLS BACK TO POINT
OF CONNECTION AND MAINTAIN EXISTING CONDUIT FOR THE
INSTALLATION OF NEW MECHANICAL.
2.
DAMAGED EXISTING WP RECEPTACLE. DISCONNECT AND RECONNECT
WITH NEW WP RECEPTACLE AS REQUIRED.
ELECTRICAL DEMOLITION ROOF PLAN - BUILDING D
KEY NOTES
1.
COORDINATE EXACT LOCATIONS OF MECHANICAL
EQUIPMENT AND POWER CONNECTION LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
2.
PROVIDE N3R DISCONNECT SWITCH (RK5 FUSES PER
MANUFACTURER'S RECOMMENDATIONS) AS SHOWN ON
PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO INSTALLATION ROUGH-IN. (TYPICAL)
3.
EXISTING RECEPTACLE. PROVIDE NEW GFCI (WR RATED)
AND WEATHERPROOF COVER.
4.
MAINTAIN EXISTING CIRCUIT.
5.
INTERCONNECTED WITH CORRESPONDING INDOOR UNIT.
MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
BUILDING A AND D
BID DOCUMENTS
1.
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
DEMOLITION KEY NOTES
GENERAL NOTES
1.
SEE E4.01 FOR TYPICAL ROOF DETAILS.
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E102.dwg, 1/13/2016 12:09:12 PM
15031
ELECTRICAL
DEMOLITION &
NEW ROOF
PLAN BUILDING D
B
ELECTRICAL NEW ROOF PLAN - BUILDING D
E1.02
KEY NOTES
2
3
1.
COORDINATE EXACT LOCATIONS OF MECHANICAL
EQUIPMENT AND POWER CONNECTION LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
2.
PROVIDE NEMA 1 DISCONNECT SWITCH PER
MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON
PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO INSTALLATION ROUGH-IN.
3.
INDOOR UNIT FAN MOTOR POWER INTERCONNECTED WITH
OUTDOOR UNIT. SEE ROOF PLAN FOR CONTINUATION AND
MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
4.
THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL
WIRES AS INDICATED ON MECHANICAL DRAWINGS.
5.
LOCATION OF EXISTING ELECTRICAL ROOMS SHOWN FOR
INFORMATION ONLY.
1
5
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
4
4
A
ELECTRICAL FIRST FLOOR PLAN - BUILDING A
BUILDING A AND D
BID DOCUMENTS
5
2
3
1
5
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E201.dwg, 1/13/2016 12:09:20 PM
15031
4
4
ELECTRICAL
FIRST FLOOR
PLANS BUILDINGS
A&D
A
ELECTRICAL FIRST FLOOR PLAN - BUILDING D
E2.01
KEY NOTES
1.
COORDINATE EXACT LOCATIONS OF MECHANICAL
EQUIPMENT AND POWER CONNECTION LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
2.
PROVIDE NEMA 1 DISCONNECT SWITCH PER
MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON
PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO INSTALLATION ROUGH-IN.
3.
INDOOR UNIT FAN MOTOR POWER INTERCONNECTED WITH
OUTDOOR UNIT. SEE ROOF PLAN FOR CONTINUATION AND
MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
4.
THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL
WIRES AS INDICATED ON MECHANICAL DRAWINGS.
5.
LOCATION OF EXISTING ELECTRICAL ROOMS SHOWN FOR
INFORMATION ONLY.
2
3
4
3
2
A
ELECTRICAL SECOND FLOOR PLAN - BUILDING A
4
BUILDING A AND D
BID DOCUMENTS
4
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
1
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
2
3
15031
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E202.dwg, 1/13/2016 12:09:29 PM
4
3
2
A
ELECTRICAL SECOND FLOOR PLAN - BUILDING D
ELECTRICAL
SECOND
FLOOR PLANS BUILDINGS
A&D
E2.02
4
4
4
4
1
2
3
A
ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING A
COORDINATE EXACT LOCATIONS OF MECHANICAL
EQUIPMENT AND POWER CONNECTION LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
2.
PROVIDE NEMA 1 DISCONNECT SWITCH PER
MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON
PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR
PRIOR TO INSTALLATION ROUGH-IN.
3.
INDOOR UNIT FAN MOTOR POWER INTERCONNECTED
WITH OUTDOOR UNIT. SEE ROOF PLAN FOR
CONTINUATION AND MECHANICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
4.
THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL
WIRES AS INDICATED ON MECHANICAL DRAWINGS.
BUILDING A AND D
BID DOCUMENTS
PANEL MD
(SEE SINGLE LINE FOR
CONDUIT AND WIRE SIZES)
1.
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
KEY NOTES
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E203.dwg, 1/13/2016 12:09:37 PM
15031
PANEL MD
(SEE SINGLE LINE FOR
CONDUIT AND WIRE SIZES)
4
4
4
4
1
2
3
B
ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING D
ELECTRICAL
FLOOR PLANS
THIRD FLOOR BUILDINGS
A&D
E2.03
KEY NOTES
1.
EXISTING HVAC TO BE REMOVED AND RETURNED TO
OWNER.
2.
DISCONNECT CONDUITS FROM HVAC UNIT AND PULL WIRE
BACK TO EXISTING POINT OF CONNECTION.
3.
EXISTING JBOX TO BE REMOVED. DISCONNECT AND CAP
CONDUIT AND ABANDON IN PLACE.
4.
LEAVE SWITCH AND FUSE IN SWITCHBOARD AND LABEL AS
SPARE.
5.
DISCONNECT AND REMOVE EXISTING BREAKER AND FUSE
IN PREPARATION FOR NEW PANEL.
(E)
MAIN SWBD "MSA"
1200A BUS
N.P.C.O XFMR.
(E)
1200AF
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
100AS
(E)
60AS
(E)
60AS
(E)
100AS
KRP-C
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
1200AS
200AF
200AF
200AF
200AF
200AF
200AF
200AF
60AF
100A
200A
3P
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
FRN-R
FRN-R
LPN-RK1
M
T
SPARE
1"C
4"C
BLDG. STEEL
J
PNL
PNL
PNL
PNL
PNL
PNL
(E)
(E)
(E)
(E)
(E)
(E)
A
B
C
D
E
F
J
(E)
TYP
TYP
J
J
A
J
ELEV.
CONTROLLER
J
DEMOLITION SINGLE LINE DIAGRAM - BUILDING A
KEY NOTES
1.
EXISTING HVAC TO BE REMOVED AND RETURNED TO
OWNER.
2.
DISCONNECT CONDUITS FROM HVAC UNIT AND PULL WIRE
BACK TO EXISTING POINT OF CONNECTION.
3.
EXISTING JBOX TO BE REMOVED. DISCONNECT AND CAP
CONDUIT AND ABANDON IN PLACE.
4.
NOT USED
5.
DISCONNECT AND REMOVE EXISTING SWITCH AND FUSE IN
PREPARATION FOR NEW PANEL.
BUILDING A AND D
BID DOCUMENTS
(ON ROOF)
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
CW
(E)
MAIN SWBD "MSB"
800A BUS
(E)
800AF
N.P.C.O XFMR.
KRP-C
M
T
800AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
100AS
(E)
100AS
(E)
60AS
3P
3P
3P
3P
3P
3P
3P
200A
200AF
200AF
200AF
70AF
90AF
60AF
LP8-RK1
LP8-RK1
LP8-RK1
LP8-RK1
FRN-R
3P
LPN-RK1
SPARE
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
1"C
15031
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E301.dwg, 1/13/2016 12:09:45 PM
4"C
CW
BLDG. STEEL
J
TYP
PNL
(E)
A
PNL
(E)
B
PNL
(E)
C
J
PNL
(E)
D
(E)
J
ELEV.
CONTROLLER
DEMOLITION
SINGLE LINE
DIAGRAMS BUILDINGS
A&D
B
DEMOLITION SINGLE LINE DIAGRAM - BUILDING D
E3.01
KEY NOTES
(E)
(E)
SHUNT
TRIP
(E)
NVENERGY XFMR.
(E)
MAIN SWBD "MSA"
RE-USE EXISTING 200A FUSE AND BREAKER.
2.
CAP CONDUIT AND ABANDON IN PLACE ON THE ROOF.
1200A BUS
(E)
1200AF
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
KRP-C
3P
3P
3P
3P
3P
3P
1200AS
200AF
200AF
200AF
200AF
200AF
200AF
3P
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
LPN-RK1
M
T
1.
(E)
100AS
(E)
60AS
(E)
60AS
(E)
100AS
3P
3P
3P
3P
3P
200AF
200AF
60AF
100A
200A
LPN-RK1
FRN-R
FRN-R
LPN-RK1
200AS
CW
GENERAL NOTES
A.
THE DESIGN PROFESSIONAL HAS PERFORMED ALL
REQUIRED SHORT CIRCUIT CALCULATIONS. THE
AIC RATING INDICATED FOR EACH DEVICE IS
ADEQUATE TO PROTECT THE EQUIPMENT AND THE
ELECTRICAL SYSTEM.
B.
THE DESIGN PROFESSIONAL HAS PERFORMED ALL
REQUIRED VOLTAGE DROP CALCULATIONS AND
ALL BRANCH CIRCUITS AND FEEDERS IN
COMPLIANCE WITH NEC 210-19(A) FPN NO. 4.
C.
ALL EQUIPMENT SHOWN LIGHT ON THE SINGLE
LINE DIAGRAM IS EXISTING AND TO REMAIN
UNLESS NOTED OTHERWISE.
BLDG. STEEL
SPARE
PNL
PNL
PNL
PNL
PNL
PNL
(E)
(E)
(E)
(E)
(E)
(E)
A
C
B
D
E
SPARE
(E)
4#3/0, 1#6,
2-1/2"C
F
ELEV.
CONTROLLER
NEW
PANEL
MA
A
SINGLE LINE DIAGRAM, LOAD CALC AND PANEL - BUILDING A
KEY NOTES
1.
(E)
MAIN SWBD "MSB"
(E)
SHUNT
TRIP
(E)
NVENERGY XFMR.
T
800A BUS
(E)
800AF
(E)
KRP-C
M
800AS
(E)
200AS
(E)
200AS
(E)
200AS
(E)
200AS
200AS
(E)
100AS
(E)
60AS
3P
3P
3P
3P
3P
3P
3P
200A
200AF
200AF
200AF
200AF
90AF
60AF
LP8-RK1
LP8-RK1
LP8-RK1
LP8-RK1
FRN-R
3P
LPN-RK1
SPARE
CW
BUILDING A AND D
BID DOCUMENTS
GENERAL NOTES
A.
THE DESIGN PROFESSIONAL HAS PERFORMED ALL
REQUIRED SHORT CIRCUIT CALCULATIONS. THE
AIC RATING INDICATED FOR EACH DEVICE IS
ADEQUATE TO PROTECT THE EQUIPMENT AND THE
ELECTRICAL SYSTEM.
B.
THE DESIGN PROFESSIONAL HAS PERFORMED ALL
REQUIRED VOLTAGE DROP CALCULATIONS AND
ALL BRANCH CIRCUITS AND FEEDERS IN
COMPLIANCE WITH NEC 210-19(A) FPN NO. 4.
(E)
ELEV.
CONTROLLER
BLDG. STEEL
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
4#3/0, 1#6,
2"C
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E302.dwg, 1/13/2016 12:10:00 PM
MODIFY EXISTING BUS TO ACCEPT NEW BREAKER
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
225A
PNL
(E)
A
PNL
(E)
B
PNL
(E)
C
PNL
(E)
D
C.
ALL EQUIPMENT SHOWN LIGHT ON THE SINGLE
LINE DIAGRAM IS EXISTING AND TO REMAIN
UNLESS NOTED OTHERWISE.
15031
NEW
PANEL
MD
225A
SINGLE LINE
DIAGRAMS,
LOAD CALCS,
PANEL - BLDGS
A&D
B
SINGLE LINE DIAGRAM, LOAD CALC AND PANEL - BUILDING D
E3.02
CONDUIT, WIRE SIZE AND
GROUNDING FOR HVAC UNITS
HACR
BRKR
SIZE
CONDUIT &
WIRE SIZE
TERMINATE ON SUPPLIED
GROUNDING LUG INSIDE
EQUIPMENT
GROUND BUSHING
EQUIPMENT GROUNDING
CONDUCTOR
GROUNDING STRAP
CONDUIT
BOTTOM PANEL OF
HVAC UNIT (TYPICAL)
TYP. ROOFTOP HVAC EQUIPMENT CONNECTION DETAIL AND GROUNDING DETAIL/SCHEDULE
2
DUCT SMOKE DETECTOR DIAGRAM (NOT USED)
RIGID STEEL CONDUIT
CONCRETE INSERT CAST IN SLAB FOR NEW
CONSTRUCTION. HILTI HVA EPOXY WITH
THREADED STUD FOR EXISTING SLAB.
FILL PAN WITH PITCH
COUNTERFLASH ALL AROUND
20 GA. GALV. PIPE STRAP
OVERSIZED TO ALLOW FOR
PIPE EXPANSION
NO.10 x 1 1/2 "GALV.WOOD
SCREW
4" X 4" X 18" (MIN)
TREATED WOOD RUNNER
GALVANIZED UNISTRUT
TWO-PIECE
CONDUIT CLAMP
GALVANIZED UNISTRUT
WALL BRACKET
3/8 " GALVANIZED ALL
THREAD RODS
INSERT CAST IN NEW CONCRETE
OR HILTI HVA EPOXY WITH
THREADED STUD IN EXISTING.
ROOF
CONDUIT
PITCH PAN WITH BOTTOM
TWO-PIECE
CONDUIT CLAMP
CONDUIT
ROOFING
FLASHING SUPPLIED BY ELECTRICAL
CONTRACTOR INSTALLED BY ROOFING
CONTRACTOR. (SEE ARCHITECTURAL
DETAILS FOR ADDTL INFO)
SECURE CONDUIT WITH TWO
PIECE PIPE CLAMPS
CONCRETE INSERT CAST IN SLAB
OR HILTI HVA EPOXY W/ THREADED
STUD FOR EXISTING.
VARIES
EQ
INSULATION
EQ
GALVANIZED UNISTRUT
BUILDING STRUCTURE
1/2" U-BOLT
SEE ARCH. PLANS FOR
ROOF AND STRUCTURE
CONSTRUCTION
STRUCTURAL
SUPPORT
GALVANIZED CHANNEL
5'-0" ON CENTER MAXIMUM
NOTE: PLACE PIPE SUPPORTS ON MAXIMUM 5'-0"
CENTERS AND ON ALL SIDES OF FITTINGS.
3
CONDUIT ROOF SUPPORT
4
HORIZONTAL CONDUIT SUPPORT
5
VERTICAL CONDUIT SUPPORT
6
HORIZONTAL CONDUIT SUPPORT
7
CONDUIT ROOF PENETRATION
BUILDING A AND D
BID DOCUMENTS
1
UNLV DORMITORY HVAC AND
ROOFING REPLACEMENT
HVAC GROUNDING DETAIL
DG KOCH ASSOCIATES
2000 S. JONES #110
LAS VEGAS, NV 89146
(702) 221-5160
FAX 221-5165
P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E401.dwg, 1/13/2016 12:10:13 PM
15031
ELECTRICAL
DETAILS
E4.01