NOTICE EXSITING WORK TO REMAIN SHOWN LIGHT. EXISTING WORK TO BE REMOVED SHOWN DARK AND DASHED. NEW WORK SHOWN DARK. MAINTAIN MINIMUM CLEARANCE OF 10'-0" BETWEEN OUTDOOR AIR INTAKES WITH PLUMBING BENTS, EXHAUST FANS AND FLUE VENTS. FC-1 2000 320 BUILDING A & D UNIT WITH ELECT CONNECTION SUPPLY CFM OSA CFM DOUBLE LINE DUCT WITH 1" THICK 1.5 LB DENSITY DUCT LINER POINT OF CONNECTION TO EXISTING. VERIFY EXACT SIZE AND LOCATION IF FIELD PRIOR TO START OF WORK. BUILDING A ONLY INSTALL NEW THERMOSTAT & EXTEND TO NEW UNIT. 2. EXISTING RETURN AIR REGISTER TO REMAIN. EXISTING RETURN AIR DUCT UP TO ROOF TO REMAIN. 3. NEW EF-1 SWITCH. 4. PROVIDE NEW FULL SIZE KRUEGER EGC RETURN AIR GRILLE WITH 1"x1"x1" CUBES IN PLACE OF EXISTING SUPPLY DIFFUSER. 5. EXISTING SUPPLY GRILLE AIR BALANCE TO AIR FLOW NOTED. 6. 3/4" DRAIN DOWN FROM ABOVE. 7. REMOVE EXISTING RETURN REGISTER. CLEAN DUCT INTERIOR & REGISTER. RE-INSTALL REGISTER FOR RE-USE. 8. PRECHARGED REFRIGERANT TUBING UP THRU ROOF TO UNIT (FURNISH WITH UNIT). SIZE PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE 1" ARMSTRONG AP2000 25/50 ELASTOMERIC INSULATION FOR VAPOR PIPING. PROVIDE UV PROTECTION FOR PIPING INSTALLED OUTDOORS. 9. REFER TO THRU WALL FIRE DAMPER DETAIL 1-(M2.02). 10. FULL SIZE DRAIN FROM UNIT WITH VENTED P-TRAP. 11. 3/4" DRAIN DOWN IN WALL, TIE INTO TAILPIECE OF LAVATORY/SERVICE SINK. PROVIDE CHROME PLATED ESCUTCHEON AT WALL PENETRATION. 12. REFER TO INTERIOR SOFFIT DETAIL 2-(M2.02). 13. SUPPLY GRILLE TO MATCH EXISTING. 14. OUTSIDE AIR GRILLE TO MATCH EXISTING. 15. 3/4" DRAIN DOWN. 16. OSA DUCT OPENING. 17. 8" x 8" OSA DUCT UP. 18. REROUTE PLUMBING VENT PIPING BELOW ROOF DECK TO NEW VTR LOCATION SHOWN. PARTIAL FIRST FLOOR PLAN - BUILDINGS A & D BUILDING A & D BUILDING A ONLY B BUILDING A AND D BID DOCUMENTS A 1. UNLV DORMITORY HVAC AND ROOFING REPLACEMENT KEY NOTES PARTIAL SECOND FLOOR PLAN - BUILDINGS A & D DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 FULL HEIGHT RATED WALL 15031 (REFER TO ARCHITECTURAL PLANS FOR CONSTRUCTION AND RATING) CLEARANCE PER MANUFACTURER'S INSTRUCTIONS 3" MINIMUM, 6" MAXIMUM (TYPICAL ALL SIDES) ANGLE IRON 1-1/2" x 1-1/2" 16 GAUGE GALVANIZED STEEL 1" MINIMUM NUTS OR TACK OR SPOT DUCT WELDS AT 6" ON CENTER UNDERSIDE OF STRUCTURE OR #10 SHEET METAL SCREWS ACCESS DOOR AND IDENTIFICATION MECHANICAL CODE 606.5 FIRE DAMPER STEEL STUD BRACING @ 48" O.C. EXISTING CEILING 6" PER 2009 UNIFORM RECTANGULAR OR P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 M202.dwg, 1/13/2016 12:08:29 PM BUILDING A & D 5/8" TYPE "X" GYPSUM BOARD 3 5/8" METAL STUDS FIRE DAMPER SLEEVE - GAUGE PER PLAIN 'S' SLIP BREAKAWAY MANUFACTURER'S JOINT CONNECTION PER RECOMMENDATION MANUFACTURER'S INSTRUCTIONS SEE CEILING PLAN PARTIAL FLOOR PLANS BUILDINGS A&D DYNAMIC RATED FIRE DAMPER EQUAL TO GREENHECK MODEL DFD-150X WITH FACTORY SLEEVE C PARTIAL THIRD FLOOR PLAN - BUILDINGS A & D 1 FIRE DAMPER DETAIL 2 INTERIOR SOFFIT DETAIL M2.02 ELECTRICAL SPECIFICATIONS A. CONDITIONS 1. FURNISH AND INSTALL A COMPLETELY WIRED AND OPERATIONAL ELECTRICAL SYSTEM AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN, INCLUDING BUT NOT LIMITED TO, THESE MAJOR ITEMS. A. B. C. LIGHTING FIXTURES AS INDICATED AND SPECIFIED ON THE PLANS. ELECTRICAL PANELS, SERVICE, CONDUIT, WIRING, ETC. FOR ALL OUTLETS AND EQUIPMENT. TELEPHONE OUTLETS AND CONDUIT AS INDICATED. B. CODES, REGULATIONS AND STANDARDS 1. THE INSTALLATION SHALL COMPLY WITH APPLICABLE LOCAL AND STATE CODES AND ORDINANCES WITH THE REGULATIONS OF THE CURRENTLY ACCEPTED EDITION OF THE NATIONAL ELECTRIC CODE AND WITH THE REQUIREMENTS OF THE POWER, TELEPHONE, AND CATV COMPANIES FURNISHING SERVICES TO THIS INSTALLATION. 2. 9. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONS STANDARDS. THE NATIONAL ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS. UNDERWRITER LABORATORIES INCORPORATED STANDARDS. AMERICAN NATIONAL STANDARDS INSTITUTE. STATE PUBLIC WORKS BOARD CURRENT ADOPTED STANDARDS. ALL CONDUIT SYSTEMS SHALL HAVE A CODE SIZED COPPER GROUND CONDUCTOR INCREASE CONDUIT SIZE AS REQUIRED. 10. CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. VERIFY ROOF TYPE WITH CONTRACTOR PRIOR TO THE INSTALLATION. T F PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED CONSTRUCTION AND SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE EXISTING UTILITIES, AND WORKING CONDITIONS TO BE ENCOUNTERED, ETC. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE WITH THIS CONDITIONS AFTER BIDDING. 2. 1. 2. EACH SWITCH, LIGHT, RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED WITH A CODE GAUGE, GALVANIZED STEEL OUTLET BOX. JUNCTION AND PULL BOXES SHALL BE CODE GAUGE, GALVANIZED STEEL. OUTLET BOXES SHALL BE OF THE ONE PIECE KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER RING. PLASTER RINGS SHALL BE SET TO PROJECT NOT MORE THAN 1/8" FROM WALL SURFACE TO RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL. SINGLE GANG RINGS SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR 4" BOXES IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED FOR UNFINISHED MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK COURSE. BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST IRON OR STEEL WITH WATERTIGHT GASKETED COVERS. WHERE BOXES ARE INSTALLED IN FLOORS WITH TILE OR CARPET FLOOR COVERING, COVERS SHALL BE OF THE RECESSED TYPE TO ACCOMMODATE THE FLOOR COVERING. 1. 2. 3. 3. 4. DELIVER MATERIALS AND EQUIPMENT TO THE PROJECT IN THE MANUFACTURER'S ORIGINAL, UNOPENED, LABELED CONTAINERS. PROTECT AGAINST MOISTURE, TAMPERING OR DAMAGE FROM IMPROPER HANDLING OR STORAGE. CONTRACTORS SHALL PROTECT AND BE RESPONSIBLE FOR ANY DAMAGE TO WORK OR MATERIALS UNTIL FINAL ACCEPTANCE BY THE OWNER, AND SHALL MAKE GOOD WITHOUT COST TO THE OWNER, ANY DAMAGE OR LOSS THAT MAY OCCUR DURING THIS PERIOD. ARRANGE FOR TIMELY DELIVERY OF MATERIALS AND EQUIPMENT TO THE JOB SITE IN ORDER TO MINIMIZE THE LENGTH OF TIME BETWEEN DELIVERY AND INSTALLATION. COVER AND PROTECT ANY MATERIAL WHICH MAY BE AFFECTED BY THE WEATHER WHILE IN TRANSIT OR STORED AT THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE OR NOT INSTALLED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS MAY BE REJECTED BY THE ENGINEER. KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR RUBBISH CAUSED BY EMPLOYEES OR WORK UNDER THIS DIVISION OF THE SPECIFICATIONS. AT THE COMPLETION OF THE WORK REMOVE ALL SURPLUS MATERIALS, TOOLS, ETC., AND LEAVE THE PREMISES BROOM-CLEAN.' F. DRAWINGS 1. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND LOCATIONS OF THE ELECTRICAL WORK. DATA PRESENTED ON THESE DRAWINGS ARE AS ACCURATE AS PLANNING CAN DETERMINE, BUT FIELD VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND ADJUST ALL WORK TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. THE ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER ALL OTHER DRAWINGS. DISCREPANCIES BETWEEN DIFFERENT PLANS, OR BETWEEN DRAWINGS AND SPECIFICATIONS, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE THE DATE OF BID OPENING. IF DISCREPANCIES ARE NOT REPORTED, THE CONTRACTOR SHALL BID THE GREATER QUANTITY OR BETTER QUALITY, AND ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD MEASURE AND CONFIRM MOUNTING HEIGHTS AND LOCATION OF ELECTRICAL EQUIPMENT WITH RESPECT TO COUNTERS, RADIATION, ETC. DO NOT SCALE DISTANCES OFF THE ELECTRICAL DRAWINGS, USE ACTUAL BUILDING DIMENSIONS. COOPERATE WITH THE OTHER TRADES SO THAT THE INSTALLATION OF THE ELECTRICAL OUTLETS AND EQUIPMENT WILL BE PROPERLY COORDINATED. CONDUIT, LIGHTING FIXTURES, AND OTHER EQUIPMENT LOCATIONS SHALL BE CHECKED WITH OTHER TRADES TO AVOID CONFLICT WITH THE PIPING, DUCTWORK, STEEL, BEAMS, OR OTHER OBSTRUCTIONS. CAREFULLY CHECK THE LOCATIONS OF THE OUTLET BOXES AND DETERMINE THAT THEY HAVE NOT BEEN DISTURBED DURING THE INSTALLATION OF MATERIALS OF OTHER TRADES. 2. COORDINATE HVAC EQUIPMENT CONNECTION REQUIREMENTS WITH HVAC CONTRACTOR. PART II - PRODUCTS AND EXECUTION A. MATERIALS 1. ALL CONDUCTORS SHALL BE COPPER. 2. NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT SYSTEM IS COMPLETE. USE MINERALAC NO. 100 OR EQUIVALENT AS A LUBRICANT TO FACILITATE THE INSTALLATION OF THE CONDUCTORS IN THE CONDUIT SYSTEM. 3. SPLICES IN EXTERIOR PULL BOXES AND MANHOLES SHALL BE WEATHERPROOF USING "SCOTCHCAST" SPLICE KIT OR APPROVED EQUAL. SEAL ENDS OF CONDUITS AND DUCTS WITH "DUCTSEAL" OR APPROVED EQUAL. 4. PROVIDE SOLID CONDUCTOR FOR 10 AWG AND SMALLER. 5. TYPE MC IS NOT PERMITTED. USE EMT FOR USE AS FEEDERS, BRANCH CIRCUITS, POWER, LIGHTING, CONTROL, AND SIGNALS. IT MAY BE USED CONCEALED OR EXPOSED, INDOOR OR OUTDOOR. IF IDENTIFIED FOR SUCH USE IT MAY BE USED AS DIRECT BURIAL OR CABLE TRAY OR ANY RACEWAY. IT CAN BE INSTALLED IN WALLS EITHER DAMP OR WET LOCATION, IN WET LOCATIONS WHERE REQUIREMENTS ARE MET. INSTALL PER ART. 320 OF THE N.E.C. ALL MATERIALS SHALL BE NEW AND OF QUALITY AS SPECIFIED ON THE PLANS OR SPECIFICATIONS AND MUST CARRY THE UNDERWRITER'S LABORATORIES APPROVAL COVERING THE PURPOSE FOR WHICH THEY ARE USED, IN ADDITION TO MEETING ALL REQUIREMENTS OF THE CURRENT APPLICABLE CODES AND REGULATIONS. 2. 3. 4. P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 EG101.dwg, 1/13/2016 12:08:39 PM 5. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC CONDUIT EXCEPT AS PERMITTED BELOW. RGS, WITH 20 MIL PVC COATING WILL BE USED WHEN IN CONTACT WITH EARTH. IMC MAY BE USED IN INDOOR LOCATIONS NOT IN CONTACT WITH THE EARTH. EMT MAY BE USED IN INDOOR LOCATIONS NOT IN CONTACT WITH EARTH, NOT IN CONCRETE SLABS OR WALLS AND NOT SUBJECT TO DAMAGE. PVC MAY BE USED IN OR BELOW CONCRETE AND DIRECT BURIED IN EARTH. FLEXIBLE STEEL CONDUIT SHALL BE USED FOR INDOOR FINAL CONNECTIONS TO EQUIPMENT IN LENGTHS NOT TO EXCEED 12". LIQUID-TIGHT FLEXIBLE STEEL CONDUIT SHALL BE FOR OUTDOOR FINAL CONNECTIONS TO EQUIPMENT NOT TO EXCEED 36". WHERE CONDUIT ENTERS OUTLET BOXES, FIXTURES OR CABINETS, FIRMLY FASTEN WITH STEEL SET SCREW COMPRESSION CONNECTORS, OR DOUBLE LOCKNUTS FOR GRC. ALL CONNECTIONS SHALL HAVE BUSHINGS OR INSULATED THROAT CONNECTORS. FIRMLY FASTEN CONDUIT TO THE BUILDING CONSTRUCTION. RUN EXPOSED CONDUIT PARALLEL TO THE BUILDING LINES, SUPPORTED BY APPROPRIATE HANGERS (UNISTRUT, T & B OR APPLETON, OR EQUAL). COVER METALLIC CONDUIT IN CONTACT WITH EARTH WITH POLYETHYLENE TAPED SPIRAL WRAPPED, 1/2 LAPPED TO PROVIDE 20 MIL. THICKNESS. TAPE SHALL BE SCOTCH NO. 50 TAPE. CONDUIT AND DUCTS NOT UNDER BUILDINGS AND FEEDER DUCTS SHALL BE INSTALLED PER N.E.C. 300-5. MAKE JOINTS WITH COMPOUND TO BE WATERTIGHT. PANELBOARD FLUSH MOUNTED V CLASSROOM WIRELESS CEILING ENCLOSURE (CEILING) (1) CAT 6 DATA AND (1) CAT 6 (POE) DATA SWITCHBOARD P PROJECTOR MOUNT (WALL) TERMINAL CABINET CS CEILING SPEAKER TRANSFORMER TS TEACHER STATION DATA OUTLET @+ 18" AFF UNLESS NOTED OTHERWISE a 6. ALL EMPTY CONDUIT SYSTEMS SHALL HAVE A NYLON FULL STRING TO FACILITATE INSTALLATION OF FUTURE WIRE. 7. SCHEDULE 40 PVC CONDUIT SHALL BE PERMITTED UNDERGROUND WITH PROPER FITTINGS, ALL UL APPROVED AND CEMENTED JOINTS. PENETRATIONS THOUGH FLOOR SLABS AND BENDS GREATER THAN 22" SHALL BE WRAPPED RIGID GALVANIZED STEEL ELBOWS. CLG E. WIRING DEVICES 1. 2. 3. 4. WALL SWITCHES SHALL BE SPECIFICATION GRADE AC SILENT TYPE SWITCHES, 20A, 120/277 VOLT. SEE ARCHITECTURAL SPECIFICATIONS FOR COLOR. 46" RECEPTACLES SHALL BE SPECIFICATIONS GRADE, DUPLEX TYPE, NEMA 5-20R, 20 AMPERE, 120 VOLT GROUNDED TYPE. SPECIAL APPLICATION RECEPTACLES SHALL BE INDICATED ON PLANS. MOUNT WITH THE GROUND DOWN. SEE ARCHITECTURAL SPECIFICATIONS FOR COLOR. DEVICE PLATES SHALL BE EQUAL TO SIERRA SMOOTH-LINE NYLON WALL PLATES. COLOR SHALL BE THE SAME AS THE DEVICE COLOR UNLESS OTHERWISE NOTED. RECEPTACLES IN OUTDOOR AND WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY MARKED AS U.L LISTED SUITABLE FOR WET LOCATIONS WHILE IN USE, EQUAL TO TAYMAC SPECIFICATION GRADE. C 46" F. SYSTEM GROUNDING 1. 2. COMPUTER OUTLET (WIREMOLD) ASTRONOMICAL TIME CLOCK (MOUNT AT 5'-0"AFF MAX) WL COMPUTER OUTLET (WIRELESS) W GENERAL WIRELESS ENCLOSURE, WALL MOUNTED CLG GENERAL WIRELESS ENCLOSURE, CEILING MOUNTED (1) CAT 6 (POE) DATA CLG ACTIVE CEILING ENCLOSURE, CEILING MOUNTED CLG PASSIVE CEILING ENCLOSURE, CEILING MOUNTED SOLENOID VALVE W THERMOSTAT W JUNCTION BOX A DIVISION 15 EQUIPMENT E FOOD SERVICE EQUIPMENT BRANCH CIRCUIT CONSISTING OF 2 #12 PLUS GROUND IN MINIMUM SIZE CONDUIT PHOTOCELL HOME RUN TO PANELBOARD OR DEVICE - NUMBER OF ARROWHEADS INDICATE NUMBER OF CIRCUITS MANHOLE OR PULLBOX BRANCH CIRCUIT - SHORT SLASHES INDICATE NUMBER OF PHASE OR SWITCH LEGS LONG SLASHES INDICATE NUMBER OF NEUTRAL AND GROUND LONG SLASH WITH DOT INDICATES ISOLATED GROUND. CEILING MOUNTED FLUORESCENT FIXTURE - LOWER CASE LETTER DENOTES SWITCHING. UPPER CASE LETTER DENOTES FIXTURE TYPE. DASHED LINES REPRESENTS EXISTING. WALL MOUNTED FIXTURE (HID SHOWN) CONDUIT IN SLAB OR UNDERGROUND HID FIXTURE CONDUIT RISER UP FLUORESCENT FIXTURE CONDUIT RISER DOWN FLUORESCENT STRIP FIXTURE INTERRUPTER SWITCH EMERGENCY LIGHTING UNIT FUSE EXIT FIXTURE - SHADES AREA DENOTES LIGHTED FACE - ARROW DENOTES DIRECTION CIRCUIT BREAKER M G. GUARANTEE KW EXISTING TELEPHONE OUTLET @ +18" AFF UNLESS NOTED OTHERWISE (1) CAT 6 ANALOG PHONE OUTLET (W - INDICATES MOUNTED IN SURFACE RACEWAY) MOTOR OUTLET DUPLEX RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE EXISTING TELEPHONE OUTLET AT +46" AFF (1) CAT 6 ANALOG PHONE OUTLET FLOOR MOUNTED DUPLEX RECEPTACLE TELEPHONE OUTLET, COUNTER HEIGHT (1) CAT 6 ANALOG PHONE OUTLET QUADRAPLEX COMPUTER RECEPTACLE AT +18" AFF, UNLESS NOTED OTHERWISE. RECEPTACLE AND COVER TO BE GREY TELEPHONE OUTLET, COUNTER HEIGHT (1) CAT 6 ANALOG PHONE OUTLET GFCI RECEPTACLE QUADRUPLEX RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE DUPLEX COMPUTER RECEPTACLE AT +18" AFF, UNLESS NOTED OTHERWISE. RECEPTACLE AND COVER TO BE GREY. SPECIAL PURPOSE RECEPTACLE MULTIOUTLET ASSEMBLY TELEPHONE OUTLET AT +46" AFF (1) CAT 6 ANALOG PHONE OUTLET SINGLE POLE SWITCH @ +48" AFF UNLESS NOTED OTHERWISE 3 THREE WAY SWITCH @ +48" AFF UNLESS NOTED OTHERWISE TELEPHONE OUTLET @ +18" AFF UNLESS NOTED OTHERWISE (1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE 4 FOUR WAY SWITCH @ +48" AFF UNLESS NOTED OTHERWISE K KEY OPERATED SWITCH @ +48" AFF UNLESS NOTED OTHERWISE TELEPHONE OUTLET, COUNTER HEIGHT (1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE D DIMMER OPERATED SWITCH @ +48" AFF UNLESS NOTED OTHERWISE P SWITCH WITH PILOT LIGHT @ +48" AFF UNLESS NOTED OTHERWISE TELEPHONE OUTLET AT +46" AFF (1) CAT 6 VoIP PHONE OUTLET) IN ONE FACEPLATE M MOTION SENSOR SWIITCH @ +48" AFF UNLESS NOTED OTHERWISE T DIGITAL TIMER SWITCH @ +48" AFF UNLESS NOTED OTHERWISE. 1 SOUND SYSTEM CONTROL AND AMPLIFIER CABINET MS CEILING MOUNTED MOTION SENSOR 2 INTERCOM / CLOCK BOX WITH CALL SWITCH MOUNTED BELOW AT 48" AFF. PP POWER PACK FOR MOTION SENSOR C 46" HORN 3. THE CONTRACTOR SHALL SUBMIT SEVEN(7) IDENTICAL BOUND SETS OF SHOP DRAWINGS ON THE FOLLOWING ITEMS: A. LIGHTING FIXTURE CUTES AND PERFORMANCE DATA. B. OUTLINE AND DATA SHEETS OF EACH PANELBOARD AND SWITCHBOARD C. OUTLINE DRAWINGS OF ALL SWITCHGEAR. SUBMIT ITEMS AT ONE TIME IN A NEAT AND ORDERLY MANNER WITHIN 15 DAYS OF AWARD OF CONTRACT. PARTIAL SUBMITTALS WILL NOT BE ACCEPTABLE. I. RECORD AND AS-BUILT DRAWINGS 1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE JOB SITE FOR THE EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL WORK INSTALLED AND TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON THE DRAWINGS. 2. AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE DRAWINGS, SHOWING ALL AS-BUILT CONDITIONS, SHALL BE DELIVERED TO THE OWNER FOR ACCEPTANCE PRIOR TO FINAL PAYMENT. GENERATOR SINGLE RECEPTACLE @ +18" AFF UNLESS NOTED OTHERWISE H. SHOP DRAWINGS AND APPROVALS 2. G EXISTING TELEPHONE OUTLET, COUNTER HEIGHT (1) CAT 6 ANALOG PHONE OUTLET INDIVIDUAL SPEAKER OR SPEAKER IN CONTROL MODULE THE ITEMS SPECIFIED HEREIN AND ON DRAWINGS ARE USED AS A STANDARD OF QUALITY. ANY MATERIALS OF EQUAL QUALITY AND AESTHETIC VALUE WILL BE GIVEN CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO APPROVAL WILL BE GIVEN TO A SPECIFIC CATALOG NUMBER MODEL, OR TYPE OF EQUIPMENT, PRIOR TO BIDDING. AFTER BIDDING, THE DECISION OF THE ARCHITECT AND/OR ENGINEER DETERMINING EQUAL MATERIALS WILL BE FINAL. KILOWATT HOUR DEMAND METER CURRENT TRANSFORMERS GUARANTEE ALL MATERIAL FURNISH AND ALL WORKMANSHIP PERFORMED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF WORK. ANY DEFECTS DEVELOPING WITHIN THIS PERIOD, TRACEABLE TO MATERIAL FURNISHED AS A PART OF THIS SECTION OR WORKMANSHIP PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE. 1. METERING TRACK LIGHTING WITH FIXTURE(S) TELEPHONE TERMINAL BOARD 4' X 8' X 3/4" FIRE TREATED PLYWOOD GROUNDING SHALL COMPLY WITH REQUIREMENTS OF ARTICLE 250. ALL EXPOSED NONCURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC RACEWAY SYSTEMS, METALLIC CABLE ARMOR, GROUNDING CONDUCTOR OF NONMETALLIC SHEATHED CABLES, GROUNDING CONDUCTOR IN NONMETALLIC RACEWAYS, AND GROUNDED CONDUCTORS OF THE WIRING SYSTEM SHALL BE GROUNDED. GROUNDING CONDUCTOR (NEUTRAL) OF THE WIRING SYSTEM SHALL BE CONNECTED TO THE SYSTEM GROUNDING CONDUCTORS AT A SINGLE PLACE IN EACH SYSTEM BY REMOVABLE BONDING JUMPERS, SIZED ACCORDING TO THE APPLICABLE PROVISIONS OF THE NATIONAL ELECTRICAL CODE. THE GROUNDED CONDUCTOR (NEUTRAL) TO THE GROUNDING CONDUCTOR CONNECTION SHALL BE LOCATED IN THE ENCLOSURE FOR THE SYSTEM'S OVERCURRENT PROTECTION OR WHERE OTHERWISE INDICATED ON THE PLANS OR SPECIFICATIONS. COMPUTER OUTLET OR SPECIAL PURPOSE COMMUNICATIONS, CEILING MOUNTED W EMERGENCY CONNECTED FIXTURE (FLUORESCENT SHOWN) C DATA OUTLET 6" ABOVE BACKSPLASH OF COUNTER DISCONNECT SWITCH NON-FUSIBLE CONTROL STATION CLOCK (IN CONTROL MODULE) INFRARED REPEATER (ALS SYSTEM) MP MICROPHONE OUTLET FIRE ALARM DEVICE - NUMBER REFERS TO DEVICE SCHEDULE STANDARD ABBREVIATIONS SYMBOL DESCRIPTION SYMBOL DESCRIPTION A AMPERE MCB MAIN CIRCUIT BREAKER AFF ABOVE FINISHED FLOOR MECH. MECHANICAL AF ARC FAULT, AMP FUSE MIN. MINIMUM AFG ABOVE FINISHED GRADE MLO MAIN LUGS ONLY AIC AMPERE INTERRUPTING CAPACITY MTD MOUNTED AL ALUMINUM NC NORMALLY CLOSED ARCH'L. ARCHITECTURAL NEC NATIONAL ELECTRICAL CODE AS AMP SWITCH NECA NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION AWG AMERICAN WIRE GAUGE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION BC BARE COPPER NEUT NEUTRAL BLDG BUILDING NFC NATIONAL FIRE CODE C CONDUIT NF NON-FUSIBLE CAB CABINET NIC NOT IN CONTRACT CAT CATALOG/CATEGORY NL NIGHT LIGHT C/B CIRCUIT BREAKER NO NORMALLY OPEN CKT CIRCUIT NPCO NEVADA POWER COMPANY CLG CEILING NTS NOT TO SCALE CO, EC CONDUIT ONLY OCP OVERCURRENT PROTECTION COMM COMMUNICATION P CU COPPER DEMO FITTINGS AND CONDUIT BODIES SHALL BE STEEL. NO DIECAST FITTINGS. CONDUIT SIZES SHALL BE AS REQUIRED BY CODE AND AS INDICATED OR SPECIFIED. PROVIDE PULL BOXES AT INTERVALS PER THE N.E.C. C POLE MOUNTED FIXTURE (DOUBLE ARM, 2 FIXTURES) B. CONDUIT 1. BOXES FOR TELEPHONE COMPUTER, T.V., FIRE ALARM, SECURITY, AND SIMILAR SYSTEMS SHALL BE MINIMUM 4" SQUARE AND 2-1/8" DEEP AND PROVIDED WITH PULL STRINGS. 1. G. COOPERATION WITH OTHER CONTRACTORS 1. P D.WIRE E. CLEANUP 1. BOXES INSTALLED FOR THE ALARM, COMPUTER, AND SECURITY SYSTEM SHALL BE PROVIDED WITH APPROPRIATE COVER PLATES AND PULL STRINGS. ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS. D. STORAGE AND HANDLING OF MATERIAL MEDIA CENTER OUTLETS (WALL MOUNTED) DISCONNECT SWITCH FUSIBLE (SHADED AREAS INDICATES VENDOR FURNISHED) C. INSPECTION OF SITE 1. M COMBINATION MOTOR STARTER (SHADED AREAS INDICATE VENDOR FURNISHED) C. OUTLET, PULL, AND JUNCTION BOXES DESCRIPTION PANELBOARD SURFACE MOUNTED MOTOR STARTER 11. CONDUITS TO BE ROUTED ON THE SURFACE OF THE STRUCTURE, SHALL BE PARALLEL AND PERPENDICULAR TO THE STRUCTURE. BEFORE THIS INSTALLATION TAKES PLACE, VERIFY WITH ARCHITECT. THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS AND CODES ARE MINIMUM REQUIREMENTS. A. B. C. D. E. CONDUITS AND OUTLETS SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE EXCEPT THAT CERTAIN MOTOR AND LIGHTING FEEDER CONDUITS MAY BE RUN EXPOSED IN CERTAIN AREAS AS INDICATED ON THE DRAWINGS. CONDUIT SHOWN TO BE INSTALLED IN CABINETS, AND CASEWORK SHALL BE RUN AS DIRECTED BY THE ARCHITECT. SYMBOL SYMBOL BUILDING A AND D BID DOCUMENTS 8. DESCRIPTION UNLV DORMITORY HVAC AND ROOFING REPLACEMENT SYMBOL 09-29-15 PERMIT SET PART I - GENERAL LEGEND SHEET NO SHEET DESCRIPTION EG1.01 ELECTRICAL SPECIFICATIONS, LEGEND AND ABBREVIATIONS POLE E1.01 ELECTRICAL DEMOLITION & NEW ROOF PLAN - BUILDING A PH PHASE E1.02 ELECTRICAL DEMOLITION & NEW ROOF PLAN - BUILDING D DEMOLITION/DEMOLISH PNL PANEL DISC DISCONNECT PV PV PHOTOVOLTAIC E2.01 ELECTRICAL FLOOR PLANS FIRST FLOOR - BUILDING A & D DN DOWN PVC POLYVINYL CHLORIDE E2.02 ELECTRICAL FLOOR PLANS SECOND FLOOR - BUILDING A & D DWG DRAWING PWR POWER E2.03 ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING A & D EA EACH QTY QUANTITY ELECT. ELECTRICAL RECEP RECEPTACLE E3.01 DEMOLITION SINGLE LINE DIAGRAMS - BUILDINGS A & D ELEV ELEVATOR REQ'D REQUIRED E3.02 SINGLE LINE DIAGRAMS, LOAD CALC, PANEL - BUILDINGS A & D EM EMERGENCY RSC RIGID STEEL CONDUIT EMT ELECTRICAL METALLIC TUBING SCHED SCHEDULE E4.01 ELECTRICAL DETAILS EQUIP EQUIPMENT SECT SECTION (E), EXIST EXISTING SP SINGLE POLE FBO FURNISHED BY OTHERS SN SOLID NEUTRAL FF FINISHED FLOOR SPEC SPECIFICATION FIXT FIXTURE SW SWITCH FLEX FLEXIBLE METALLIC CONDUIT (STEEL) SWBD SWITCHBOARD FLUOR FLUORESCENT SWGR SWITCH GEAR FT FEET OR FOOT SYS SYSTEM GFA GROUND FAULT ALARM TEMP TEMPORARY GFCI GROUND FAULT CIRCUIT INTERRUPTER TELE TELEPHONE GND GROUND T-STAT THERMOSTAT HP HORSEPOWER TTB TELEPHONE TERMINAL BACKBOARD HVAC HEATING, VENTILATING & AIR CONDITIONING TTC TELEPHONE TERMINAL CABINET IBC INTERNATIONAL BUILDING CODE TYP. TYPICAL IMC INTERMEDIATE METAL CONDUIT UBC UNIFORM BUILDING CODE DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 15031 ELECTRICAL SPECS, LEGEND AND ABBREVIATIONS EG1.01 A EXISTING HVAC TO BE DEMOLISHED AND RETURNED TO OWNER. REMOVE EXISTING WIRE FOR POWER AND CONTROLS BACK TO POINT OF CONNECTION AND MAINTAIN EXISTING CIRCUIT FOR THE INSTALLATION OF NEW MECHANICAL. 2. DAMAGED EXISTING WP RECEPTACLE. DISCONNECT AND RECONNECT WITH NEW WP RECEPTACLE AS REQUIRED. 3. EXISTING HEAT PUMP TO REMAIN. ELECTRICAL DEMOLITION ROOF PLAN - BUILDING A KEY NOTES 1. COORDINATE EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND POWER CONNECTION LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. PROVIDE N3R DISCONNECT SWITCH (RK5 FUSES PER MANUFACTURER'S RECOMMENDATIONS) AS SHOWN ON PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION ROUGH-IN. (TYPICAL) 3. EXISTING RECEPTACLE. PROVIDE NEW GFCI (WR RATED) AND WEATHERPROOF COVER. 4. MAINTAIN EXISTING CIRCUIT. 5. INTERCONNECTED WITH CORRESPONDING INDOOR UNIT. MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. BUILDING A AND D BID DOCUMENTS 1. UNLV DORMITORY HVAC AND ROOFING REPLACEMENT DEMOLITION KEY NOTES GENERAL NOTES 1. SEE E4.01 FOR TYPICAL ROOF DETAILS. DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E101.dwg, 1/13/2016 12:09:04 PM 15031 ELECTRICAL DEMOLITION & NEW ROOF PLAN BUILDING A B ELECTRICAL NEW ROOF PLAN - BUILDING A E1.01 A EXISTING HVAC TO BE DEMOLISHED AND RETURNED TO OWNER. REMOVE EXISTING WIRE FOR POWER AND CONTROLS BACK TO POINT OF CONNECTION AND MAINTAIN EXISTING CONDUIT FOR THE INSTALLATION OF NEW MECHANICAL. 2. DAMAGED EXISTING WP RECEPTACLE. DISCONNECT AND RECONNECT WITH NEW WP RECEPTACLE AS REQUIRED. ELECTRICAL DEMOLITION ROOF PLAN - BUILDING D KEY NOTES 1. COORDINATE EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND POWER CONNECTION LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. PROVIDE N3R DISCONNECT SWITCH (RK5 FUSES PER MANUFACTURER'S RECOMMENDATIONS) AS SHOWN ON PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION ROUGH-IN. (TYPICAL) 3. EXISTING RECEPTACLE. PROVIDE NEW GFCI (WR RATED) AND WEATHERPROOF COVER. 4. MAINTAIN EXISTING CIRCUIT. 5. INTERCONNECTED WITH CORRESPONDING INDOOR UNIT. MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. BUILDING A AND D BID DOCUMENTS 1. UNLV DORMITORY HVAC AND ROOFING REPLACEMENT DEMOLITION KEY NOTES GENERAL NOTES 1. SEE E4.01 FOR TYPICAL ROOF DETAILS. DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E102.dwg, 1/13/2016 12:09:12 PM 15031 ELECTRICAL DEMOLITION & NEW ROOF PLAN BUILDING D B ELECTRICAL NEW ROOF PLAN - BUILDING D E1.02 KEY NOTES 2 3 1. COORDINATE EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND POWER CONNECTION LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. PROVIDE NEMA 1 DISCONNECT SWITCH PER MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION ROUGH-IN. 3. INDOOR UNIT FAN MOTOR POWER INTERCONNECTED WITH OUTDOOR UNIT. SEE ROOF PLAN FOR CONTINUATION AND MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL WIRES AS INDICATED ON MECHANICAL DRAWINGS. 5. LOCATION OF EXISTING ELECTRICAL ROOMS SHOWN FOR INFORMATION ONLY. 1 5 UNLV DORMITORY HVAC AND ROOFING REPLACEMENT 4 4 A ELECTRICAL FIRST FLOOR PLAN - BUILDING A BUILDING A AND D BID DOCUMENTS 5 2 3 1 5 DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E201.dwg, 1/13/2016 12:09:20 PM 15031 4 4 ELECTRICAL FIRST FLOOR PLANS BUILDINGS A&D A ELECTRICAL FIRST FLOOR PLAN - BUILDING D E2.01 KEY NOTES 1. COORDINATE EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND POWER CONNECTION LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. PROVIDE NEMA 1 DISCONNECT SWITCH PER MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION ROUGH-IN. 3. INDOOR UNIT FAN MOTOR POWER INTERCONNECTED WITH OUTDOOR UNIT. SEE ROOF PLAN FOR CONTINUATION AND MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL WIRES AS INDICATED ON MECHANICAL DRAWINGS. 5. LOCATION OF EXISTING ELECTRICAL ROOMS SHOWN FOR INFORMATION ONLY. 2 3 4 3 2 A ELECTRICAL SECOND FLOOR PLAN - BUILDING A 4 BUILDING A AND D BID DOCUMENTS 4 UNLV DORMITORY HVAC AND ROOFING REPLACEMENT 1 DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 2 3 15031 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E202.dwg, 1/13/2016 12:09:29 PM 4 3 2 A ELECTRICAL SECOND FLOOR PLAN - BUILDING D ELECTRICAL SECOND FLOOR PLANS BUILDINGS A&D E2.02 4 4 4 4 1 2 3 A ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING A COORDINATE EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND POWER CONNECTION LOCATIONS WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. PROVIDE NEMA 1 DISCONNECT SWITCH PER MANUFACTURER'S RECOMMENDATIONS AS SHOWN ON PLAN. VERIFY LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION ROUGH-IN. 3. INDOOR UNIT FAN MOTOR POWER INTERCONNECTED WITH OUTDOOR UNIT. SEE ROOF PLAN FOR CONTINUATION AND MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. THERMOSTAT FOR HVAC CONTROLS. PROVIDE CONTROL WIRES AS INDICATED ON MECHANICAL DRAWINGS. BUILDING A AND D BID DOCUMENTS PANEL MD (SEE SINGLE LINE FOR CONDUIT AND WIRE SIZES) 1. UNLV DORMITORY HVAC AND ROOFING REPLACEMENT KEY NOTES DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E203.dwg, 1/13/2016 12:09:37 PM 15031 PANEL MD (SEE SINGLE LINE FOR CONDUIT AND WIRE SIZES) 4 4 4 4 1 2 3 B ELECTRICAL FLOOR PLANS THIRD FLOOR - BUILDING D ELECTRICAL FLOOR PLANS THIRD FLOOR BUILDINGS A&D E2.03 KEY NOTES 1. EXISTING HVAC TO BE REMOVED AND RETURNED TO OWNER. 2. DISCONNECT CONDUITS FROM HVAC UNIT AND PULL WIRE BACK TO EXISTING POINT OF CONNECTION. 3. EXISTING JBOX TO BE REMOVED. DISCONNECT AND CAP CONDUIT AND ABANDON IN PLACE. 4. LEAVE SWITCH AND FUSE IN SWITCHBOARD AND LABEL AS SPARE. 5. DISCONNECT AND REMOVE EXISTING BREAKER AND FUSE IN PREPARATION FOR NEW PANEL. (E) MAIN SWBD "MSA" 1200A BUS N.P.C.O XFMR. (E) 1200AF (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 100AS (E) 60AS (E) 60AS (E) 100AS KRP-C 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 1200AS 200AF 200AF 200AF 200AF 200AF 200AF 200AF 60AF 100A 200A 3P LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 FRN-R FRN-R LPN-RK1 M T SPARE 1"C 4"C BLDG. STEEL J PNL PNL PNL PNL PNL PNL (E) (E) (E) (E) (E) (E) A B C D E F J (E) TYP TYP J J A J ELEV. CONTROLLER J DEMOLITION SINGLE LINE DIAGRAM - BUILDING A KEY NOTES 1. EXISTING HVAC TO BE REMOVED AND RETURNED TO OWNER. 2. DISCONNECT CONDUITS FROM HVAC UNIT AND PULL WIRE BACK TO EXISTING POINT OF CONNECTION. 3. EXISTING JBOX TO BE REMOVED. DISCONNECT AND CAP CONDUIT AND ABANDON IN PLACE. 4. NOT USED 5. DISCONNECT AND REMOVE EXISTING SWITCH AND FUSE IN PREPARATION FOR NEW PANEL. BUILDING A AND D BID DOCUMENTS (ON ROOF) UNLV DORMITORY HVAC AND ROOFING REPLACEMENT CW (E) MAIN SWBD "MSB" 800A BUS (E) 800AF N.P.C.O XFMR. KRP-C M T 800AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 100AS (E) 100AS (E) 60AS 3P 3P 3P 3P 3P 3P 3P 200A 200AF 200AF 200AF 70AF 90AF 60AF LP8-RK1 LP8-RK1 LP8-RK1 LP8-RK1 FRN-R 3P LPN-RK1 SPARE DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 1"C 15031 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E301.dwg, 1/13/2016 12:09:45 PM 4"C CW BLDG. STEEL J TYP PNL (E) A PNL (E) B PNL (E) C J PNL (E) D (E) J ELEV. CONTROLLER DEMOLITION SINGLE LINE DIAGRAMS BUILDINGS A&D B DEMOLITION SINGLE LINE DIAGRAM - BUILDING D E3.01 KEY NOTES (E) (E) SHUNT TRIP (E) NVENERGY XFMR. (E) MAIN SWBD "MSA" RE-USE EXISTING 200A FUSE AND BREAKER. 2. CAP CONDUIT AND ABANDON IN PLACE ON THE ROOF. 1200A BUS (E) 1200AF (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS KRP-C 3P 3P 3P 3P 3P 3P 1200AS 200AF 200AF 200AF 200AF 200AF 200AF 3P LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 LPN-RK1 M T 1. (E) 100AS (E) 60AS (E) 60AS (E) 100AS 3P 3P 3P 3P 3P 200AF 200AF 60AF 100A 200A LPN-RK1 FRN-R FRN-R LPN-RK1 200AS CW GENERAL NOTES A. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED SHORT CIRCUIT CALCULATIONS. THE AIC RATING INDICATED FOR EACH DEVICE IS ADEQUATE TO PROTECT THE EQUIPMENT AND THE ELECTRICAL SYSTEM. B. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED VOLTAGE DROP CALCULATIONS AND ALL BRANCH CIRCUITS AND FEEDERS IN COMPLIANCE WITH NEC 210-19(A) FPN NO. 4. C. ALL EQUIPMENT SHOWN LIGHT ON THE SINGLE LINE DIAGRAM IS EXISTING AND TO REMAIN UNLESS NOTED OTHERWISE. BLDG. STEEL SPARE PNL PNL PNL PNL PNL PNL (E) (E) (E) (E) (E) (E) A C B D E SPARE (E) 4#3/0, 1#6, 2-1/2"C F ELEV. CONTROLLER NEW PANEL MA A SINGLE LINE DIAGRAM, LOAD CALC AND PANEL - BUILDING A KEY NOTES 1. (E) MAIN SWBD "MSB" (E) SHUNT TRIP (E) NVENERGY XFMR. T 800A BUS (E) 800AF (E) KRP-C M 800AS (E) 200AS (E) 200AS (E) 200AS (E) 200AS 200AS (E) 100AS (E) 60AS 3P 3P 3P 3P 3P 3P 3P 200A 200AF 200AF 200AF 200AF 90AF 60AF LP8-RK1 LP8-RK1 LP8-RK1 LP8-RK1 FRN-R 3P LPN-RK1 SPARE CW BUILDING A AND D BID DOCUMENTS GENERAL NOTES A. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED SHORT CIRCUIT CALCULATIONS. THE AIC RATING INDICATED FOR EACH DEVICE IS ADEQUATE TO PROTECT THE EQUIPMENT AND THE ELECTRICAL SYSTEM. B. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED VOLTAGE DROP CALCULATIONS AND ALL BRANCH CIRCUITS AND FEEDERS IN COMPLIANCE WITH NEC 210-19(A) FPN NO. 4. (E) ELEV. CONTROLLER BLDG. STEEL DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 4#3/0, 1#6, 2"C P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E302.dwg, 1/13/2016 12:10:00 PM MODIFY EXISTING BUS TO ACCEPT NEW BREAKER UNLV DORMITORY HVAC AND ROOFING REPLACEMENT 225A PNL (E) A PNL (E) B PNL (E) C PNL (E) D C. ALL EQUIPMENT SHOWN LIGHT ON THE SINGLE LINE DIAGRAM IS EXISTING AND TO REMAIN UNLESS NOTED OTHERWISE. 15031 NEW PANEL MD 225A SINGLE LINE DIAGRAMS, LOAD CALCS, PANEL - BLDGS A&D B SINGLE LINE DIAGRAM, LOAD CALC AND PANEL - BUILDING D E3.02 CONDUIT, WIRE SIZE AND GROUNDING FOR HVAC UNITS HACR BRKR SIZE CONDUIT & WIRE SIZE TERMINATE ON SUPPLIED GROUNDING LUG INSIDE EQUIPMENT GROUND BUSHING EQUIPMENT GROUNDING CONDUCTOR GROUNDING STRAP CONDUIT BOTTOM PANEL OF HVAC UNIT (TYPICAL) TYP. ROOFTOP HVAC EQUIPMENT CONNECTION DETAIL AND GROUNDING DETAIL/SCHEDULE 2 DUCT SMOKE DETECTOR DIAGRAM (NOT USED) RIGID STEEL CONDUIT CONCRETE INSERT CAST IN SLAB FOR NEW CONSTRUCTION. HILTI HVA EPOXY WITH THREADED STUD FOR EXISTING SLAB. FILL PAN WITH PITCH COUNTERFLASH ALL AROUND 20 GA. GALV. PIPE STRAP OVERSIZED TO ALLOW FOR PIPE EXPANSION NO.10 x 1 1/2 "GALV.WOOD SCREW 4" X 4" X 18" (MIN) TREATED WOOD RUNNER GALVANIZED UNISTRUT TWO-PIECE CONDUIT CLAMP GALVANIZED UNISTRUT WALL BRACKET 3/8 " GALVANIZED ALL THREAD RODS INSERT CAST IN NEW CONCRETE OR HILTI HVA EPOXY WITH THREADED STUD IN EXISTING. ROOF CONDUIT PITCH PAN WITH BOTTOM TWO-PIECE CONDUIT CLAMP CONDUIT ROOFING FLASHING SUPPLIED BY ELECTRICAL CONTRACTOR INSTALLED BY ROOFING CONTRACTOR. (SEE ARCHITECTURAL DETAILS FOR ADDTL INFO) SECURE CONDUIT WITH TWO PIECE PIPE CLAMPS CONCRETE INSERT CAST IN SLAB OR HILTI HVA EPOXY W/ THREADED STUD FOR EXISTING. VARIES EQ INSULATION EQ GALVANIZED UNISTRUT BUILDING STRUCTURE 1/2" U-BOLT SEE ARCH. PLANS FOR ROOF AND STRUCTURE CONSTRUCTION STRUCTURAL SUPPORT GALVANIZED CHANNEL 5'-0" ON CENTER MAXIMUM NOTE: PLACE PIPE SUPPORTS ON MAXIMUM 5'-0" CENTERS AND ON ALL SIDES OF FITTINGS. 3 CONDUIT ROOF SUPPORT 4 HORIZONTAL CONDUIT SUPPORT 5 VERTICAL CONDUIT SUPPORT 6 HORIZONTAL CONDUIT SUPPORT 7 CONDUIT ROOF PENETRATION BUILDING A AND D BID DOCUMENTS 1 UNLV DORMITORY HVAC AND ROOFING REPLACEMENT HVAC GROUNDING DETAIL DG KOCH ASSOCIATES 2000 S. JONES #110 LAS VEGAS, NV 89146 (702) 221-5160 FAX 221-5165 P:\2015_Jobs\15031 UNLV Dormitory HVAC and Roofing Replacement\DWG_BLDG DEPT\15031 PHASE 1 E401.dwg, 1/13/2016 12:10:13 PM 15031 ELECTRICAL DETAILS E4.01