Submittal Review Project: Metro CareRing Project #: #2185.00 General Contractor: Contractor: Date: Reviewed by: May 20, 2014 Eric Nielsen Items Submitted: Submittal Number: Specification Section: No Exception Taken Rejected Make Corrections Noted Revise and Resubmit Submit Specified Item Architect to Comment Panelboards #13J2024-0016 #26.2416 This review is only for the limited purpose of checking for general conformance with the design concept and the information shown in the Construction Documents. The review shall not include review of the accuracy or completeness of details, such as quantities, dimensions, weights or gauges, fabrication processes, construction means or methods, coordination of the work with other trades or construction safety precautions, all of which are the sole responsibility of the Contractor. General Notes: 1. None. Type Panel 'MDP' Panel 'LM1A' Panel 'LP1A' Panel 'LM1B' Panel 'LP1B' Panel 'LP2A' Panel 'LM2A' Surge Protection Device CT / Main Disconnect Comments No Comments. Quantity of 20A/1P QOB-VH is (16); Quantity of 15A/1P QOB-VH is (6) No Comments. Quantity of 20A/1P QOB-VH is (7); Quantity of 20A/1P-PS QOB-VH is (15) No Comments. No Comments. No Comments. Surge Protection Device voltage shall be for a 120/208V 3Ph grounded Wye system. Catalog number #SL3-100-208-3Y-MNB-M1-F Action NE MC NE MC NE NE NE MC Confirm that cabinet enclosure is NEMA 3R, and that the submitted Utility CT metering compartment is compatible with Xcel Energy metering standards NE Kindly inform our office if any portion of this document is missing or unreadable. Page 1 of 1 NE R MC RR S AC TRANSMITTAL 5995 Greenwood Plaza Blvd. Suite 100 Greenwood Village, CO 80111-4710 303-571-5377 303-629-7467 (fax) PROJECT: TO: DATE: 05/12/2014 Metro CareRing-Hunger Relief Center Barker Rinker Seacat & Architecture 3457 Ringsby Ct #200 Denver CO 80216 ATTN: Joel Hermann Ph/Fax: 303-455-1366 No. 13J2024-0016 RE: JOB: WE ARE SENDING: SUBMITTED FOR: 260500-Electrical 13J2024 ACTION TAKEN: Shop Drawings Approval Approved as Submitted Letter Your Use Approved as Noted Prints As Requested Returned After Loan Change Order Review and Comment Resubmit Submit Plans SENT VIA: Samples Returned Specifications / Product Data Attached Returned for Corrections Other: Separate Cover Via: Due Date: 05/26/2014 NOTES: Item Package Code Submittal Submittal Submittal 260500 260500 260500 262416-01 262416-02 262416-03 Rev. Copies Date 1 1 1 05/12/2014 05/12/2014 05/12/2014 Description Status Panelboards - Product Data- 208 Panelboards - Shop Drawings- 208 Panelboards - Schedules Architect Review Architect Review Architect Review CC: Signed: Brady McQuinn Submittal Stamp Sheet Project: Metro CareRing Hunger Relief Center Project Address: 1100 18th Ave. Denver, CO 80218 Phipps’ Job #: 13J2024 Subcontractor / Supplier Specification Section Submittal Date Submitted For: Accent Electrical 26 24 16 05/12/2014 APPROVAL Gerald H. Phipps, Inc.: RESUBMITTAL RECORD ONLY Architect: SUBMITTED GH Phipps Construction Companies GH Phipps has reviewed, approved, and herby submits the attached in accordance with the contract documents. Note to Subcontractor/Material Supplier: Subcontractor/Material Supplier remains responsible for the confirmation and correlation of dimensions at the jobsite; fabrication processes and construction techniques; coordination of the work with the work of other trades; and satisfactory performance of the work. BRADY MCQUINN, Project Engineer Engineer: Refer to Submittal Review Sheet Reviewed By: Eric Nielsen, PE 05/20/2014 4:07:00 PM NOTES: X Brady McQuinn Project Engineer Gear Submittal Package Cover Sheet Accent Electric Job # I1433 7223 W. 118th Place, Unit L, Broomfield, CO 80020 Date of Submission: 4/22/14 Approval Needed By: 5/9/14 Metro CareRing 100 E 18th Ave Denver, CO Submitted By: Office Phone: Mobile: Fax: Email: Issac Benoit (Project Manager) 303.466.8966 (O) 303.908.6853 (C) 303.466.8955 (F) Issac@Accentes.com CSI Section CSI Description 26 2416 Panelboards Comments / Contents Inlcudes – Square D Panelboards, Current Tech SPD, AMP Combo CT Disconnect with Fuses METRO CARE RING HUNGER RELIEF GEAR SUBMITTAL FOR APPROVAL 3/26/2014 Contractor / Installer: Accent Electrical Services Attention: Steve Schweikert Salesman: Coleton Shifflet cshifflet@ceddenver.com 303.817.8693 Consolidated Electrical Distributors 2405 W. 5th Ave Denver, CO 80204 www.ceddenver.shopced.com Consolidated Electrical Distributors, Inc 2405 W. 5th Avenue Denver CO. 80204 Phone: 303-623-1233 Fax: 303-623-2266 March 26, 2014 TO: ACCENT ELECTRICAL SERVICES ATTN: STEVE SCHWEIKERT PROJECT: METRO CARE RING HUNGER RELIEF Thank you for the order. We will do our best to service it properly and ask for your help with the following: Attached is 1 set of submittal drawings for the above referenced project. Please review them and advise us of any discrepancies. These drawings are for approval. Please return one stamped approved original set to us with your release. If approved drawings can not be returned, a letter or email will suffice referring to this order and stating “Waive approved drawings, release as ordered.” TYPE QTY DESCRIPTION MANUFACTURER MPD 1 I-LINE PANELBOARD SQUARE D LM1A 1 NQ PANELBOARD SQUARE D LP1A 1 NQ PANELBOARD SQUARE D LM1B 1 NQ PANELBOARD SQUARE D LP1B 1 NQ PANELBOARD SQUARE D LP2A 1 NQ PANELBOARD SQUARE D LM2A 1 NQ PANELBOARD SQUARE D SPD 1 SL3-100-480-3Y-MNB-M1-F POWER SIFTOR CURRENT TECH MCT 1 MCT368L COMBO CT/DISCONNECT AMP MCT 3 KRPC1200SP CLASS L FUSES BUSSMANN 16 -- 20A/1P QOB-VH 6 - 15A/1P QOB-VH 7 -- 20A/1P QOB-VH 15 -- 20A/1P-PS QOB-VH SL 3 Type 1 SPD TM Surge Select ® Optimum PROTECTION P R O T E C T I O N Why Selenium? • Selenium is the only technology that protects critical loads and downstream equipment from catastrophic overvoltages. • Selenium provides additional protection to loads – lower clamping voltage than MOV only systems. • Selenium conducts small routine transients – extending MOV life and ultimately the life of the unit. Model Number Scheme (SL3 ) TM E.g.: SL3-300-208-3Y-MDT-M6E-F2 kA Rating Available SL3 kA Ratings: 050, 080, 100, 125, 150, 200, 250, 300 TM Voltage (Consult factory for additional Voltages) Select SL3 Offers Double Protection, Superior Quality The innovative Select SL3 provides outstanding performance in all power quality surge events including temporary over voltages. ® TM ® The Select SL3 product line combines selenium cells with the Current Technology patented Failure-Free Integrated Suppression Module (ISM ) to deliver the industry’s best surge suppression performance. The ISM contains individual thermally fused and protected MOVs, surge-rated copper busing, robust filtering and advanced remote communications capabilities in a thermoplastic polycarbonate rated UL 94V-0 housing. ® TM TM 208120/208 240120/240 380220/380 480277/480 600347/600 Configuration (Consult factory for additional Configurations) 1G 1 Phase, Grounded 2G 2 Phase, Grounded, Split Phase 3Y 3 Phase, Grounded Wye 3R3 Phase, Grounded High Resistance 3H3 Phase, Grounded, High Leg Delta 3D 3 Phase, Grounded Delta Enclosure MNMetal Without Disconnect MD*Metal With Disconnect SNStainless Steel Without Disconnect SD*Stainless Steel With Disconnect *Not available on 50, 80 or 100kA units 4 Filter Option Optional Feature Monitoring Enclosure Cable Entry Configuration Voltage Model kA Rating SL3 — 300 — 208 — 3Y — MDT — M6E — F 2 Cable Entry TTop Feed BBottom Feed Monitoring M0No local monitoring (see remote MxX stand-alone option) M1LED/Phase + Audible Alarm, Dry Relay Contacts M2M1 + Surge Counter M3Advanced Monitoring, Character Display, Modbus RTU M4EM3 + Ethernet, Modbus TCP M5Advanced Monitoring, Graphics Display, Modbus RTU M6EM5 + Ethernet, Modbus TCP Filter FFilter NNo Filter Optional Features 2Test Port 4 Enhanced Selenium Stand-Alone Options (To Be Ordered As Separate Items) DTS DTS-2 Diagnostic Test Set MxXRemote Monitor Extension M1X through M6EX HPI HPI Cable For more information go to tnbpowersolutions.com/current_technology SL 3 TM Surge P R O T E C T I O N 20-Year Best In Industry Warranty 1 Selenium: The Only Acceptable Solution for Service Entrance Applications Using a proprietary engineering process known as Seamless Technology , Current Technology combines selenium with MOVs, polypropylene capacitors and precise component geometry to deliver the industry’s best suppression, highest tested single pulse surge current capacity ratings and – most importantly – longest product life. Current Technology’s patented seamless technology is the industry’s only power reliability design concept to take advantage of selenium’s proven, longlasting suppression capabilities, which safeguard today’s busiest facilities with the most trusted and reliable protection available. TM 2 1 ISM (Reference page 10) 2 Selenium Cells B A Patented seamless technology uses selenium cells combined with MOVs to provide Dual Listed Secondary Surge Arrester superior bi-directional surge suppression. When coordinated as the “first line of defense” inside Select SL3 suppression filter systems, selenium cells conduct routine, long duration surges, repetitive impulses and temporary over voltages, minimizing MOV wear and tear while protecting down stream equipment. M The result: superior quality, maximum performance and dramatically extended product life. 2 SPD Installation TypicalType Surge Suppressor Installation ® Transformer Transformer M Meter Meter Type 1 Surge Suppressor Fire Pump Valuable Type 1 Protection to Switchgear Surge suppression equipment is designed to protect sensitive electronic equipment from electrical transients. A surge suppressor is installed on the load side of the main service disconnect, providing limited protection to the switchgear – one of the most expensive elements of an electrical installation. Switchgear Fire Pump Switchgear SPD Surge Suppressor Protection main As a Type 1 SPD, the Select SL3 may be installed in front of the With Selectservice 2, you can choose to install the TVSS as a secondary surge arrester (A) or as a surge disconnect, intercepting external surges before they flow through the mainsuppressor discon-(B). A nect. In this way, the main disconnect and downstream breakers are protected from Type 1 SPD Installation damage by transients that could otherwise cause them to trip, shutting off power to Dual Listed Secondary Surge Arrester an entire electrical system, or leaving the system at risk to damage from additional transients. ® ® B Typical Surge Sup Transformer M Meter Why TYPE 1 Listing? • Select SL3 provides protection before the main service entrance, increasing protection for downstream loads. • Select SL3 allows greater installation flexibility. Type 1 Surge Suppressor ® ® Protection Switchgear Fire Pump Switchgear With Select®2, you can choose to install the TVSS as a seconda or as a surge suppressor (B). 5 CT Bussmann® LOW-PEAK® Time-Delay Fuses KRP-C Class L – 600 Volt 601-2000A Dimensional Data All other tolerances (± 0.02) 1350A to 1600A 1800A to 2000A .38" 5.75" 801A to 1200A 8.63" (± 0.09) 6.75" 10.75" (± 0.09) 601A to 800A 0.63" (± 0.03) All Slots and Holes .38" .44" .5" 3.75" Terminal: Width (± 0.06) Thickness (± 0.03) Catalog Symbol: KRP-C-SP Time-Delay – 4 seconds (minimum) at 500% rated current Current-Limiting Ampere Rating: 601 to 2000 Amperes‡ Voltage Rating: 600 Volts AC (or less) 300 Volts DC (or less) Interrupting Rating: 300,000A RMS Sym. (UL) Interrupting Rating: 100,000A DC (UL) Agency Approvals: UL Listed – Special Purpose£, Guide JFHR, File E56412 CSA Certified – (200,000 AIR), Class 1422-02, File 53787 Class L per CSA C22.2, No. 248.10 ‡Use KRP-CL for current ratings below 601 amps. *601-3000A is rated 340 VDC and 50 KAIC. £Meets all performance requirements of UL Standard 248-10 for Class L fuses. Ampere Ratings† Catalog Number KRP-C-601SP KRP-C-650SP KRP-C-700SP KRP-C-750SP KRP-C-800SP KRP-C-801SP KRP-C-900SP KRP-C-1000SP KRP-C-1100SP KRP-C-1200SP Weight** Ctn. Qty. Lbs. Kg. 1 1 3.75 4.5 1.7 2.041 Catalog Number KRP-C-1350SP KRP-C-1400SP KRP-C-1500SP KRP-C-1600SP KRP-C-1800SP KRP-C-1900SP KRP-C-2000SP Ctn. Qty. Weight** Lbs. Kg. 1 6.50 2.948 1 8.5 3.85 2" 2" 2.5" 2.53" Max. 2.5" 2.78" Max. 2.38" 2.75" 3" 3.03" Max. 3.5" 3.53" Max. General Information: • All-purpose silver-linked fuse for both overload and shortcircuit protection for high capacity systems (mains and large feeders). • Time-delay (minimum of four seconds at five times amp rating) for close sizing. • Current-limiting action of the fuse generally affords considerable reduction in bus bracing. • Interrupting rating of 300,000 amperes complies with NEC Sections 110-9 and 230-65 for today’s large capacity systems. • O-ring seals maximize pressure build-up during currentlimiting action and ensure filler retention. • High grade silica-sand filler; accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc. • 99.9% pure silver fuselinks. The high conductivity of silver gives low watt loss and low operating temperature at normal current levels; maximizes total clearing I2t fault energy let-through. • Selective coordination (blackout prevention). • Glass melamine tube. • Silver-plated end bells. CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. **Weight per carton. †Special purpose rating of 300,000 AIR. 11-12-99 A99119 Rev. A Form No. KRP-C-601-2000 Page 1 of 3 BIF Doc #1008 CED DENVER 2405 W 5TH AVE DENVER, CO 80204 303-623-1233