262416- Panelboards- Reviewed AAN

advertisement
Submittal Review
Project:
Metro CareRing
Project #:
#2185.00
General Contractor:
Contractor:
Date:
Reviewed by:
May 20, 2014
Eric Nielsen
Items Submitted:
Submittal Number:
Specification Section:
No Exception Taken
Rejected
Make Corrections Noted
Revise and Resubmit
Submit Specified Item
Architect to Comment
Panelboards
#13J2024-0016
#26.2416
This review is only for the limited purpose of checking for general conformance with the design concept and the information
shown in the Construction Documents. The review shall not include review of the accuracy or completeness of details, such as
quantities, dimensions, weights or gauges, fabrication processes, construction means or methods, coordination of the work with
other trades or construction safety precautions, all of which are the sole responsibility of the Contractor.
General Notes:
1. None.
Type
Panel 'MDP'
Panel 'LM1A'
Panel 'LP1A'
Panel 'LM1B'
Panel 'LP1B'
Panel 'LP2A'
Panel 'LM2A'
Surge
Protection
Device
CT / Main
Disconnect
Comments
No Comments.
Quantity of 20A/1P QOB-VH is (16); Quantity of 15A/1P QOB-VH is (6)
No Comments.
Quantity of 20A/1P QOB-VH is (7); Quantity of 20A/1P-PS QOB-VH is (15)
No Comments.
No Comments.
No Comments.
Surge Protection Device voltage shall be for a 120/208V 3Ph grounded Wye
system. Catalog number #SL3-100-208-3Y-MNB-M1-F
Action
NE
MC
NE
MC
NE
NE
NE
MC
Confirm that cabinet enclosure is NEMA 3R, and that the submitted Utility CT
metering compartment is compatible with Xcel Energy metering standards
NE
Kindly inform our office if any portion of this document is missing or unreadable.
Page 1 of 1
NE
R
MC
RR
S
AC
TRANSMITTAL
5995 Greenwood Plaza Blvd.
Suite 100
Greenwood Village, CO 80111-4710
303-571-5377
303-629-7467 (fax)
PROJECT:
TO:
DATE: 05/12/2014
Metro CareRing-Hunger Relief Center
Barker Rinker Seacat & Architecture
3457 Ringsby Ct #200
Denver CO 80216
ATTN:
Joel Hermann
Ph/Fax:
303-455-1366
No. 13J2024-0016
RE:
JOB:
WE ARE SENDING:
SUBMITTED FOR:
260500-Electrical
13J2024
ACTION TAKEN:
Shop Drawings
Approval
Approved as Submitted
Letter
Your Use
Approved as Noted
Prints
As Requested
Returned After Loan
Change Order
Review and Comment
Resubmit
Submit
Plans
SENT VIA:
Samples
Returned
Specifications / Product Data
Attached
Returned for Corrections
Other:
Separate Cover Via:
Due Date: 05/26/2014
NOTES:
Item
Package
Code
Submittal
Submittal
Submittal
260500
260500
260500
262416-01
262416-02
262416-03
Rev. Copies Date
1
1
1
05/12/2014
05/12/2014
05/12/2014
Description
Status
Panelboards - Product Data- 208
Panelboards - Shop Drawings- 208
Panelboards - Schedules
Architect Review
Architect Review
Architect Review
CC:
Signed:
Brady McQuinn
Submittal Stamp Sheet
Project: Metro CareRing Hunger Relief Center
Project Address: 1100 18th Ave. Denver, CO 80218
Phipps’ Job #: 13J2024
Subcontractor / Supplier
Specification Section
Submittal Date
Submitted For:
Accent Electrical
26 24 16
05/12/2014
APPROVAL
Gerald H. Phipps, Inc.:
RESUBMITTAL
RECORD ONLY
Architect:
SUBMITTED
GH Phipps
Construction Companies
GH Phipps has reviewed, approved, and herby submits the
attached in accordance with the contract documents.
Note to Subcontractor/Material Supplier:
Subcontractor/Material Supplier remains responsible for the
confirmation and correlation of dimensions at the jobsite;
fabrication processes and construction techniques;
coordination of the work with the work of other trades; and
satisfactory performance of the work.
BRADY MCQUINN, Project Engineer
Engineer:
Refer to
Submittal Review Sheet
Reviewed By: Eric Nielsen, PE
05/20/2014 4:07:00 PM
NOTES:
X
Brady McQuinn
Project Engineer
Gear Submittal Package
Cover Sheet
Accent Electric Job # I1433
7223 W. 118th Place, Unit L, Broomfield, CO 80020
Date of Submission: 4/22/14
Approval Needed By:
5/9/14
Metro CareRing
100 E 18th Ave Denver, CO
Submitted By:
Office Phone:
Mobile:
Fax:
Email:
Issac Benoit (Project Manager)
303.466.8966 (O)
303.908.6853 (C)
303.466.8955 (F)
Issac@Accentes.com
CSI Section
CSI Description
26 2416
Panelboards
Comments / Contents
Inlcudes – Square D Panelboards,
Current Tech SPD, AMP Combo CT
Disconnect with Fuses
METRO CARE RING HUNGER RELIEF
GEAR SUBMITTAL FOR APPROVAL
3/26/2014
Contractor / Installer:
Accent Electrical Services
Attention:
Steve Schweikert
Salesman:
Coleton Shifflet
cshifflet@ceddenver.com
303.817.8693
Consolidated Electrical Distributors
2405 W. 5th Ave
Denver, CO 80204
www.ceddenver.shopced.com
Consolidated Electrical Distributors, Inc
2405 W. 5th Avenue
Denver CO. 80204
Phone: 303-623-1233 Fax: 303-623-2266
March 26, 2014
TO:
ACCENT ELECTRICAL SERVICES
ATTN:
STEVE SCHWEIKERT
PROJECT: METRO CARE RING HUNGER RELIEF
Thank you for the order. We will do our best to service it properly and ask for your help with the
following:
Attached is 1 set of submittal drawings for the above referenced project. Please review them and
advise us of any discrepancies.
These drawings are for approval. Please return one stamped approved original set to us with
your release. If approved drawings can not be returned, a letter or email will suffice referring to
this order and stating “Waive approved drawings, release as ordered.”
TYPE
QTY
DESCRIPTION
MANUFACTURER
MPD
1
I-LINE PANELBOARD
SQUARE D
LM1A
1
NQ PANELBOARD
SQUARE D
LP1A
1
NQ PANELBOARD
SQUARE D
LM1B
1
NQ PANELBOARD
SQUARE D
LP1B
1
NQ PANELBOARD
SQUARE D
LP2A
1
NQ PANELBOARD
SQUARE D
LM2A
1
NQ PANELBOARD
SQUARE D
SPD
1
SL3-100-480-3Y-MNB-M1-F POWER SIFTOR
CURRENT TECH
MCT
1
MCT368L COMBO CT/DISCONNECT
AMP
MCT
3
KRPC1200SP CLASS L FUSES
BUSSMANN
16 -- 20A/1P QOB-VH
6 - 15A/1P QOB-VH
7 -- 20A/1P QOB-VH
15 -- 20A/1P-PS QOB-VH
SL 3
Type 1 SPD
TM
Surge
Select
®
Optimum PROTECTION
P R O T E C T I O N
Why Selenium?
• Selenium is the only technology that protects critical loads
and downstream equipment from catastrophic overvoltages.
• Selenium provides additional protection to loads –
lower clamping voltage than MOV only systems.
• Selenium conducts small routine transients –
extending MOV life and ultimately the life of the unit.
Model Number Scheme (SL3 )
TM
E.g.: SL3-300-208-3Y-MDT-M6E-F2
kA Rating
Available SL3 kA Ratings:
050, 080, 100, 125, 150, 200,
250, 300
TM
Voltage
(Consult factory for additional Voltages)
Select SL3 Offers Double Protection,
Superior Quality
The innovative Select SL3 provides outstanding performance in
all power quality surge events including temporary over voltages.
®
TM
®
The Select SL3 product line combines selenium cells with
the Current Technology patented Failure-Free Integrated
Suppression Module (ISM ) to deliver the industry’s best
surge suppression performance. The ISM contains individual
thermally fused and protected MOVs, surge-rated copper
busing, robust filtering and advanced remote communications
capabilities in a thermoplastic polycarbonate rated UL 94V-0
housing.
®
TM
TM
208120/208
240120/240
380220/380
480277/480
600347/600
Configuration
(Consult factory for additional Configurations)
1G 1 Phase, Grounded
2G 2 Phase, Grounded, Split Phase
3Y 3 Phase, Grounded Wye
3R3 Phase, Grounded
High Resistance
3H3 Phase, Grounded, High Leg Delta
3D 3 Phase, Grounded Delta
Enclosure
MNMetal Without Disconnect
MD*Metal With Disconnect
SNStainless Steel
Without Disconnect
SD*Stainless Steel With Disconnect
*Not available on 50, 80 or 100kA units
4
Filter Option
Optional Feature
Monitoring
Enclosure
Cable Entry
Configuration
Voltage
Model
kA Rating
SL3 — 300 — 208 — 3Y — MDT — M6E — F 2
Cable Entry
TTop Feed
BBottom Feed
Monitoring
M0No local monitoring
(see remote MxX
stand-alone option)
M1LED/Phase + Audible Alarm,
Dry Relay Contacts
M2M1 + Surge Counter
M3Advanced Monitoring,
Character Display, Modbus RTU
M4EM3 + Ethernet, Modbus TCP
M5Advanced Monitoring,
Graphics Display, Modbus RTU
M6EM5 + Ethernet, Modbus TCP
Filter
FFilter
NNo Filter
Optional Features
2Test Port
4
Enhanced Selenium
Stand-Alone Options
(To Be Ordered As Separate Items)
DTS DTS-2 Diagnostic Test Set
MxXRemote Monitor Extension
M1X through M6EX
HPI HPI Cable
For more information go to tnbpowersolutions.com/current_technology
SL 3
TM
Surge
P R O T E C T I O N
20-Year Best In Industry Warranty
1
Selenium: The Only Acceptable Solution for
Service Entrance Applications
Using a proprietary engineering process known as Seamless Technology , Current
Technology combines selenium with MOVs, polypropylene capacitors and precise
component geometry to deliver the industry’s best suppression, highest tested
single pulse surge current capacity ratings and – most importantly – longest
product life. Current Technology’s patented seamless technology is the industry’s
only power reliability design concept to take advantage of selenium’s proven, longlasting suppression capabilities, which safeguard today’s busiest facilities with the
most trusted and reliable protection available.
TM
2
1
ISM (Reference page 10)
2
Selenium Cells
B
A
Patented seamless technology uses selenium cells combined with MOVs to provide
Dual Listed Secondary Surge Arrester
superior bi-directional surge suppression. When coordinated as the “first line of
defense” inside Select SL3 suppression filter systems, selenium cells conduct
routine, long duration surges, repetitive impulses and temporary over voltages,
minimizing MOV wear and tear while protecting down stream equipment.
M
The result: superior quality, maximum performance and dramatically
extended product life.
2 SPD
Installation
TypicalType
Surge
Suppressor
Installation
®
Transformer
Transformer
M Meter
Meter
Type 1
Surge
Suppressor
Fire
Pump
Valuable Type 1 Protection to Switchgear
Surge suppression equipment is designed to protect sensitive electronic equipment
from electrical transients. A surge suppressor is installed on the load side of the main
service disconnect, providing limited protection to the switchgear – one of the most
expensive elements of an electrical installation.
Switchgear
Fire
Pump
Switchgear
SPD
Surge
Suppressor
Protection
main
As a Type 1 SPD, the Select SL3 may be installed in front of the
With
Selectservice
2, you can choose to install the TVSS as a secondary surge arrester (A)
or
as
a surge
disconnect, intercepting external surges before they flow through the
mainsuppressor
discon-(B).
A
nect. In this way, the main disconnect and downstream breakers are protected from
Type 1 SPD Installation
damage by transients that could otherwise cause them to trip, shutting off power to
Dual Listed Secondary Surge Arrester
an entire electrical system, or leaving the system at risk to damage from additional
transients.
®
®
B
Typical Surge Sup
Transformer
M Meter
Why TYPE 1 Listing?
• Select SL3 provides protection before the main service entrance, increasing
protection for downstream loads.
• Select SL3 allows greater installation flexibility.
Type 1
Surge
Suppressor
®
®
Protection
Switchgear
Fire
Pump
Switchgear
With Select®2, you can choose to install the TVSS as a seconda
or as a surge suppressor (B).
5
CT
Bussmann®
LOW-PEAK® Time-Delay Fuses
KRP-C
Class L – 600 Volt
601-2000A
Dimensional Data
All other tolerances (± 0.02)
1350A
to
1600A
1800A
to
2000A
.38"
5.75"
801A
to
1200A
8.63"
(± 0.09)
6.75"
10.75"
(± 0.09)
601A
to
800A
0.63" (± 0.03)
All Slots and Holes
.38"
.44"
.5"
3.75"
Terminal:
Width (± 0.06)
Thickness (± 0.03)
Catalog Symbol: KRP-C-SP
Time-Delay – 4 seconds (minimum) at 500% rated current
Current-Limiting
Ampere Rating: 601 to 2000 Amperes‡
Voltage Rating: 600 Volts AC (or less) 300 Volts DC (or less)
Interrupting Rating: 300,000A RMS Sym. (UL)
Interrupting Rating: 100,000A DC (UL)
Agency Approvals:
UL Listed – Special Purpose£, Guide JFHR, File E56412
CSA Certified – (200,000 AIR), Class 1422-02, File 53787
Class L per CSA C22.2, No. 248.10
‡Use KRP-CL for current ratings below 601 amps.
*601-3000A is rated 340 VDC and 50 KAIC.
£Meets all performance requirements of UL Standard 248-10 for Class L fuses.
Ampere Ratings†
Catalog
Number
KRP-C-601SP
KRP-C-650SP
KRP-C-700SP
KRP-C-750SP
KRP-C-800SP
KRP-C-801SP
KRP-C-900SP
KRP-C-1000SP
KRP-C-1100SP
KRP-C-1200SP
Weight**
Ctn.
Qty. Lbs.
Kg.
1
1
3.75
4.5
1.7
2.041
Catalog
Number
KRP-C-1350SP
KRP-C-1400SP
KRP-C-1500SP
KRP-C-1600SP
KRP-C-1800SP
KRP-C-1900SP
KRP-C-2000SP
Ctn.
Qty.
Weight**
Lbs.
Kg.
1
6.50
2.948
1
8.5
3.85
2"
2"
2.5"
2.53"
Max.
2.5"
2.78"
Max.
2.38"
2.75"
3"
3.03"
Max.
3.5"
3.53"
Max.
General Information:
• All-purpose silver-linked fuse for both overload and shortcircuit protection for high capacity systems (mains and
large feeders).
• Time-delay (minimum of four seconds at five times amp
rating) for close sizing.
• Current-limiting action of the fuse generally affords
considerable reduction in bus bracing.
• Interrupting rating of 300,000 amperes complies with
NEC Sections 110-9 and 230-65 for today’s large capacity
systems.
• O-ring seals maximize pressure build-up during currentlimiting action and ensure filler retention.
• High grade silica-sand filler; accelerates response of fuse to
short-circuits by having quenching effect upon the fuse arc.
• 99.9% pure silver fuselinks. The high conductivity of silver
gives low watt loss and low operating temperature at normal current levels; maximizes total clearing I2t fault energy
let-through.
• Selective coordination (blackout prevention).
• Glass melamine tube.
• Silver-plated end bells.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
**Weight per carton.
†Special purpose rating of 300,000 AIR.
11-12-99
A99119
Rev. A
Form No. KRP-C-601-2000
Page 1 of 3
BIF Doc #1008
CED DENVER
2405 W 5TH AVE
DENVER, CO 80204
303-623-1233
Download