2 1 4 3 GENERAL NOTES: SOUTH EAST RISER SW RISER (AREA A) 5 1. SE RISER (AREA B) ALL EQUIPMENT IS EXISTING UNLESS NOTED OTHERWISE. PENTHOUSE ROBERT A.M. ST E RN T LP4A 30KVA 480V 480/277V, 3PH, 4W LRP 4A 7 LRP 4A 8 LRP 4A 9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P SPARE 125A/3P T LDP 4SE 150KVA 480V 208/120V, 3PH, 4W T LDP 4SW 150KVA 480V 208/120V, 3PH, 4W FA18A 500A/3P T 400/3 225A LPS RK (#1/0CU)1"C LDP 4SW 600A, 208/120V, 3PH, 4W 22,000 AIC F12 F12 G T RP4A 30KVA 480V 208/120V, 3PH, 4W RP4A FA8A LRP 3A 1 LRP 3A 2 LRP 3A 3 LRP 3A 4 LRP 3A 5 LRP 3A 6 LRP 3A 7 LRP 3A 8 #250KCMIL F9 FA9 FA9 FA9 FA9 FA9 FA9 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P LP3A FA5 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P KEY NOTES: TO STAR LINE BUSWAY SYSTEM. RP4B T PROJECT FOR LP4B F5 LP3B 125A/3P FA18A LRP 3B 1 LRP 3B 2 LRP 3B 3 LRP 3B 4 LRP 3B 5 LRP 3B 6 LRP 3B 7 LRP 3B 8 LRP 3B 9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 FA9 (#6CU)3/4"C F12 400/3 225A LPS RK 500A/3P (#1/0CU)1"C LDP 3SW 600A, 208/120V, 3PH, 4W 22,000 AIC T LDP 3SE 150 KVA 480V 208/120V, 3PH, 4W F12 T G T 500A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 3415 COLORADO AVE BOULDER, COLORADO 80303 FA18A 400/3 225A LPS RK G SYSTEMS BIOTECHNOLOGY BUILDING RP3B FA5 100/3 70A LPS RK F5 T T 4TH FLOOR FA5 T LP3B 45KVA 480V 480/277V, 3PH, 4W T LDP 3SW 150 KVA 480V 208/120V, 3PH, 4W FA5 CU Project No.: CP007722 (#1/0CU)1"C LDP 3SE 600A, 208/120V, 3PH, 4W 22,000 AIC #250KCMIL RP2A 125A/3P 125A/3P (#6CU)3/4"C 125A/3P Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 FA13A 100/3 70A LPS RK FA9 125A/3P LRP 4B 9 FA13A (#2CU)3/4"C T LP3A 45KVA 480V 480/277V, 3PH, 4W (#6CU)3/4"C SPARE 200A SPACE 200A SPACE 200A SPACE FA9 LRP 4B 8 1 200/3 125A LPS RK F5 FA9 FA9 LRP 4B 7 LDP 4SE 600A, 208/120V, 3PH, 4W 22,000 AIC 100/3 70A LPS RK T LRP 3A 9 LRP 4B 6 D T RP3A 45KVA 480V 208/120V, 3PH, 4W RP3A LRP 4B 5 (#1/0CU)1"C (#6CU)3/4"C FA9 LRP 4B 4 FA18A T RP4B 75KVA 480V 208/120V, 3PH, 4W 100/3 50A LPS RK D 500A/3P 400/3 225A LPS RK G F4 T T LRP 4B 3 200A SPACE LRP 4A 6 LRP 4B 2 200A SPACE LRP 4A 5 LRP 4B 1 200A SPACE LRP 4A 4 HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203 1256 200A SPACE LRP 4A 3 SOUTH WEST RISER SPARE LRP 4A 2 SPARE 200A SPACE 200A SPACE 200A SPACE (#6CU)3/4"C 200A SPACE 100/3 50A LPS RK LRP 4A 1 FAULT CALCULATION SCHEDULES (AMPS) 3RD FLOOR ALL THE EQUIPMENT MUST BE FULLY RATED FOR SHORT CIRCUIT VALUES SHOWN BELOW. SERIES RATING EQUIPMENT SHALL NOT BE PERMITED. LP2A LRP 2B 1 LRP 2B 2 LRP 2B 3 LRP 2B 4 LRP 2B 5 LRP 2B 6 LRP 2B 7 LRP 2B 8 LRP 2B 9 C C FA9 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P FA18A 500A/3P 400/3 225A FUSES (#1/0CU)1"C LDP 2SW 600A, 208/120V, 3PH, 4W 22,000 AIC T DIM 45 KVA 480V 208/120V, 3PH, 4W DP 1 SPARE SPARE 400A SPACE 400A SPACE 400A SPACE FA16 1 FA16 1 FA16 FA21A T F15 FA16 (#3/0CU)1"C 125/3 SERVER DIST BOARD SDB 1 800A, 208/120V, 3PH, 4W 22,000 AIC 225/3 400/3 400/3 400/3 400/3 800/3P RPBB KPB UPS A 225KW, 0.9PF, 480/480V, 3PH, 3W 10/28/2013 1:40:19 PM T RPBB 112.5 KVA 480V 208/120V, 3PH, 4W 1 200A SPACE 400A SPACE FA16 (#2CU)3/4"C 400/3 FA13 T RP1AE 75 KVA 480V 208/120V, 3PH, 4W 600/3 500 RPN RK F11 F4 200/3 FA13 T 400/3 250 RPN RK FA13 FA18A T F10 SHOP FA18A FA8A 2 T 200A SPACE 200A SPACE 200A SPACE SPARE FA9 G #250KCMIL RP1B LRP 1B 1 (#6CU)3/4"C T (#2CU)3/4"C (#1/0CU)1"C T T AV NOISE ISOLATION 30 KVA 480V 208/120V, 3PH, 4W F12 T KPB 150 KVA 480V 208/120V, 3PH, 4W 50/3 225/3 F9 LRP 1B 5 LRP 1B 6 LRP 1B 7 FA9 FA9 FA9 FA9 FA9 FA9 FA9 2 (#2CU)3/4"C 500A/3P T 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P MAIN GND BUS TO MSG2 TO MSG1 TO MTGB KEY 1 53648 29 2 39303 30 AVAILABLE 3 31 4 32 5 33 6 34 7 35 8 36 9 37 10 38 11 39 12 40 13 41 14 42 15 43 16 44 17 45 18 46 19 47 20 48 21 49 PROJECT PRINCIPAL 22 50 PROJECT MANAGER 23 51 PROJECT DESIGNER MARK LDP 1SE 600A, 208/120V, 3PH, 4W 22,000 AIC NEW EQUIPMENT UPS B F15 T SDB 2 225KVA 480V 208/120V, 3PH, 4W, K 13 FA21A T (#3/0CU)1"C TO SBDB 2 E 005 LANDSCAPE ARCHITECT 26 CIVIL ENGINEER 27 STRUCTURAL ENGINEER 28 MECHANICAL ENGINEER ELECTRICAL ENGINEER INTERIOR DESIGNER EQUIPMENT PLANNER BASED ON INFINITE IMPEDANCE ON THE PRIMARY. THE AVAILABLE FAULT CURRENTS ON THE SECONDARY OF A TRANSFORMER IS AS FOLLOWS: 30 KVA (5.3%Z)= 1572A 45KVA (4.9%Z)= 2551A 75KVA (5.4%Z)= 3858A 112.5KVA (4.9%Z)=6378A 150KVA 5.3%Z)= 7862A DRAWN BY Author 800/3 800 LPN RK 1 FA21A 800/3 1 FA16 400/3 1 FA16 1 FA16 400/3 400/3 FA16 400/3 225/3 125/3 EXISTING ONE LINE DIAGRAM SERVER DIST BOARD SDB 2 800A, 208/120V, 3PH, 4W 22,000 AIC (#2CU)3/4"C Addendum 03 BID PACKAGE DESCRIPTION PROJECT ARCHITECT 25 (150KVA OR LESS) (#1/0CU)1"C 10/28/2013 09/24/2013 DATE PROJECT NUMBER CP007722 B TO MSG2 B E 003 A 125/3 SCALE 1/8" = 1' 0" BASEMENT DISTRIBUTION BOARD "BDB" 800A, 480/277V, 3PH, 4W . TO MSG2 B BASEMENT 1 2 1 TRANSFORMERS FA18A UPS B 225 KW, 0.9 PF. 480 480V, 3PH, 3W T SHOP TO MSG2 A 75 KVA E 003 480V 208/120V, 3PH, 4W F9 125/3 LRP 1B 4 FA9 T LDP 1SE 150KVA 480V 208/120V, 3PH, 4W 400/3 225A LPS RK LRP 1B 3 AVAILABLE 24 200/3 125A LPS RK F12 LRP 1B 2 LP1B 1ST FLOOR UPS A FA8A 225/3 SPACE A G 400/3 250 LPN RK TO SBDB 1 E 005 FA12 FA16A RP2B F5 LPBB LTG CNTL PANEL 225/3 RP1AE FA13 TAP FEEDER 100/3 100 LPN RK RPBA RP1AW FA12 100/3 70A LPS RK FA21A KP1 WIRE GUTTER 800/3 800 LPN RK 1 AV2 F5 FA9 T SDB 1 225KVA 480V 208/120V, 3PH, 4W, K 13 1 T AV1 T 480V, 1000A FEEDER BUS, 3P, 3W FA9 FA13 FA8A DP 3 FA9 NEW EQUIPMENT 480V, 1000A FEEDER BUS, 3P, 3W DP 2 LDP 2SE 600A, 208/120V, 3PH, 4W 22,000 AIC 2ND FLOOR 480V, 1000A PLUG IN BUS, 3P, 3W NEW EQUIPMENT (#6CU)3/4"C 125A/3P 125A/3P G F9 NEW EQUIPMENT 125A/3P LP2B (#2CU)3/4"C T LP1B 75KVA 480V 480/277V, 3PH, 4W B 125A/3P FA13A G 200/3 WITH DOUBLE LUGS ON LOAD SIDE 150 LPN RK 125A/3P T 200/3 125A LPS RK #250KCMIL 125A/3P (#1/0CU)1"C T RP2B 75KVA 480V 208/120V, 3PH, 4W FA13A F9 125A/3P FA18A 400/3 225A LPS RK F12 T 125A/3P 200A SPACE 125A/3P 125A/3P 200A SPACE 125A/3P 125A/3P 200A SPACE 125A/3P T LDP 2SW 150 KVA 480V 208/120V, 3PH, 4W 500A/3P T FA9 SPARE FA9 T LDP 2SE 150KVA 480V 208/120V, 3PH, 4W F12 FA9 SPARE FA9 LRP 2A 9 FA9 KEY 400A SPACE FA9 LRP 2A 8 FA9 SPARE FA9 LRP 2A 7 FA9 400A SPACE FA9 LRP 2A 6 FA9 400A SPACE FA9 LRP 2A 5 FA9 SPARE FA9 LRP 2A 4 SPARE 200A SPACE 200A SPACE 200A SPACE FA9 LRP 2A 3 12" X 3" X 1/4" COPPER BUS BAR ON STAND OFF INSULATORS (TYP) FA9 SPARE LRP 2A 2 FA9 480V, 1000A PLUG IN BUS, 3P, 3W LRP 2A 1 C:\Revit Projects\2013\Project Path\CU System Biotech DV13082_PWR_E13_jimmy.youssef.rvt ARCHITECTS E F4 T 200A SPACE FA4 SPARE LP4A E 2 3 4 5 E 004 2 1 4 3 GENERAL NOTES: 5 1. DURING DEMOLITION AND NEW CONSTRUCTION THE CONTINUATION OF BUILDING SYSTEMS MAY BE NECESSARY. TRACE AND IDENTIFY EXISTING LIGHTING AND POWER WIRING IN AREAS PRIOR TO DEMOLITION AND MAINTAIN NECESSARY SYSTEMS OPERATION FOR SIMULTANEOUS OCCUPANCY AND MAKE PERMANENT IF REQUIRED FOR OPERATION OF FINAL CONFIGURATION. 2. DASHED THIN LINEWEIGHT DEVICES ARE EXISTING TO BE DEMOLISHED, SOLID THIN LIGHTWEIGHT DEVICES AND TAGGED WITH '(E)' ARE EXISTING TO REMAIN. DEVICES TAGGED WITH '(R)' ARE EXISTING TO BE RELOCATED. ROBERT A.M. ST E RN 3. OWNER HAS FIRST RIGHT TO ALL E SALVAGED DEVICES. PROPERLY DISCARD OF ALL UNWANTED SALVAGED DEVICES. E ARCHITECTS 4. ELECTRICAL CONTRACTOR SHALL DISCONNECT ALL NECESSARY EQUIPMENT TO MAKE IT SAFE FOR DEMOLITION. HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203 1256 5. DEVICES AND EQUIPMENT TO BE DEMOLISHED SHALL BE REMOVED, INCLUDING ALL RELATED CONDUCTORS, RACEWAY, JUNCTION AND SPLICE BOXES UP TO THE PANELBOARD. THE CONTRACTOR SHALL IDENTIFY ALL DEMOLISHED AND ABANDONED BRANCH CIRCUITS. THESE SHALL BE NOTED AS SPARE ON PANELBOARD DIRECTORIES. THIS INCLUDES IDENTIFYING EXISTING ABANDONED AND SPARE CIRCUITS THAT ARE CURRENTLY IDENTIFIED AS USED. J 1 / E 101C 6. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID. 7 CUH 1 CBB130A 1 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 RP1C:41 (PART) K VESTIBULE CRB180B CRB180B TO CUH 1 TO TO RP1B:50 VESTIBULE RP1B:53 CRB190A 1 FCU 8 CRB130 1 PROJECT FOR RP1B:59 J J D 36 DN RP1B:32 J J TO FCU 8 RP1B:57 8 3 RP1B:55 CRB130 2 UP CRB130A 2 CRB190A 2 DN +60" DN TO RP1B:34,36 J SMART BOX CODE BLUE 3 J L J 1 24 4 3 J (E) 6 POWER SUPPLY (E) KEY NOTES POWER SUPPLY SBRP1B 1:17 (PART) 1 5 J RP1B:23 2 3 RP1B:2,4,6 RP1B:18 12 (E) A/V 10 5 5 COMPUTER LAB 6 J 3 RP1B:29 PRINTER 6 TO 7 UH 2 B12 1 +6"AFF 22 J MDF ROOM TO RP1B:46 B100 21 RP1B RP1B:48 TO F/A AUX PANEL FCU 6 ERB:12 (PART) 6 6 (E) 1000A BUS RPBM:75 (PART) (E) N 63 N.2 T UH 2 B12 2 5 2 1 TO GND BAR LP1B COMPUTER LAB 3 MARK ELEV 2 B115 ELB145 RP1B:7,9,11 2 11 CORR. CRB110 1 PROJECT PRINCIPAL J (E) PROJECT MANAGER RP1B:26,28,30 B SBRP1B 1:17 (PART) ELB143 CIVIL ENGINEER STRUCTURAL ENGINEER J MECHANICAL ENGINEER RP1B:12 5 J ELECTRICAL ENGINEER RPBA:65,67,69 INTERIOR DESIGNER B141 P EQUIPMENT PLANNER 7 A171F 17 15 21 J PROG MAN OFFICE PROG MAN OFFICE HR OFFICE A171E A171D A171C 5 HR OFFICE 1 DRAWN BY Author ERB:22 (PART) J 1 A171B BUDGET BUDGET A130 A133 ERB:22 (PART) 3 5 RPBA:76 (PART) 7 1 / E 101A 67 AREA D 5 1 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23.2 ELECTRICAL POWER PLAN FIRST FLOOR AREA B 1/8" = 1' 0" ELECTRICAL DEMO POWER PLAN FIRST FLOOR AREA B AREA C A AREA B A SCALE 1/8" = 1' 0" AREA A 10/28/2013 1:42:09 PM C:\Revit Projects\2013\Project Path\CU System Biotech DV13082_PWR_E13_jimmy.youssef.rvt JC 28 SMART BOX COO OFFICE PROJECT ARCHITECT LANDSCAPE ARCHITECT 5 RPBA:76 (PART) Addendum 03 BID PACKAGE DESCRIPTION PROJECT DESIGNER ELEV 3 9 RP1B:13,15,17 15 10/28/2013 09/24/2013 DATE PROJECT NUMBER CP007722 RP1B:61,63 5 B DN 2 75 KVA RP1B:1,3,5 J UP B149 30 5 STB191 SBRP1B 1:14 B149 1 ELEC 3 3 J (E) J EL1 J 9 STAIR B100 2 RP1B:27 CU Project No.: CP007722 TRP S:7,9 J (E) 3415 COLORADO AVE BOULDER, COLORADO 80303 TRPS 10,12 FCU 1 TO RP1B:19,21 9 EXISTING CONNECTION TO FIRE/SMOKE DAMPER. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR. EXISTING CEILING PROJECTOR. EXISTING CONNECTION TO SECURITY DOOR POWER SUPPLY. EXISTING NEMA 6 30R RECEPTACLES. 3#10, 1#10G. EXISTING CONNECTION TO MOTORIZED SHADE AND CONTROLS. EXISTING CONDUIT ROUGH IN FOR FUTURE INSTALLATION OF FLOORBOX RECEPTACLES AND BRANCH CONDUCTORS. EXISTING RECEPTACLE BELOW CEILING FOR BIRD CONTROL POWER SUPPLY. COORDIATE EXACT LOCATION WITH ARCHITECT/ENGINEER PRIOR TO ROUGH IN. C EXISTING CONNECTION TO DOOR OPERATOR. EXISTING ROUGH IN AND CONNECTIONS TO PUSH BUTTON CONTROLLER. EXISTING EQUIPMENT AND CIRCUITING TO BE DEMOLISHED. 4 +6"AFF 3 SBRP1B 1:12 M.2 TRP S:6,8 B148 4 +6"AFF TRP S CORRIDOR PRINTER TO +6"AFF B100 1 J 5 8 TRP S:2,4 3 9 FCU 1 M 4 5 J 6 TRP S:1,3,5 +6"AFF POWER SUPPLY (E) FCU 6 B148 1 J RP1B:25 (E) B12 RP1B:14,16 5 SHELLED RP1B:20,22,24 16 RPBM:75 (PART) 6 RP1B:8,10,12 B120 C (E) 6 4 2 J POWER SUPPLY SYSTEMS BIOTECHNOLOGY BUILDING CUH 1 CUH 1 TO K.5 CRB180B RP1B:52 8 3 D DNDN VESTIBULE AREA AW 1 2 3 4 5 AREA AE ED 101B 1 2 4 3 GENERAL NOTES: 5 1. REFER TO EL/001 THROUGH EL/003 FOR LIGHT FIXTURE SCHEDULE. 2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL FIXTURE LOCATIONS WITHIN A CEILING OR CEILING GRID. FOR AREAS WITHOUT CEILINGS, FIXTURE LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN, CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL AND STRUCTURAL ELEMENTS. ROBERT A.M. 3. ALL SURFACE MOUNTED CONDUIT SHALL BE ROUTED PERPENDICULAR AND PARALLEL TO BEAMS AND COLUMNS. ALL CONDUIT ROUTING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION AND INSTALLED IN A NEAT AND CONSISTENT MANNER. ALLE SURFACE MOUNTED CONDUIT WHERE EXPOSED TO PUBLIC AREAS SHALL BE PAINTED. PAINT COLOR TO BE DETERMINED BY THE ARCHITECT. E ST E RN ARCHITECTS HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203/1256 4. ALL FLUORESCENT BALLASTS SHALL BE ELECTRONIC. ALSO PROVIDE 0/10V DIMMABLE BALLASTS WHERE NOTED PER LIGHTING CONTROL. Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 5. ELECTRICAL CONTRACTOR SHALL BE FIELD VERIFY EXACT FIXTURE LENGTHS FOR ALL CONTINUOUS LINEAR FLUORESCENT AND QUARTZ FIXTURES. FOR COVES, PROVIDE CONTINUOUS ILLUMINATION WITH 6" MAXIMUM DISTANCE BETWEEN END OF FIXTURE AND WALL. 6. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR FOR PLACEMENT OF FIXTURES WITHIN MECHANICAL ROOMS. 7. ALL DEVICES, REOUGH IN BOXES, LIGHT FIXTURES, ETC. IN VIVARIUM WHICH PENETRATE CEILINGS OF WALLS SHALL BE SEALED INTERNALLY AND EXTERNALLY. KEY NOTES 1 S 2 VESTIBULE D 3 CRA100 3 3 PRE FUNCTION TELE STORAGE A102 A103 A/V EQ ROOM/STOR A100 LP1B:6 (PART) 3 4 A107 DP/2:9 DP/2:7 T 2 (E) 1 9 F6C 9 EL1:8 F13 F16 F13 (E) (E) 1 9 F16 X1 8 DP/2:13 X1 f F13 DP/2:10 F19A f f s 3 C y F12B m Q1 F12B F26A j DP/2:5 F26A Q1 o F13C C g Z F13C F13C f 3 F13C f f F13C F13C g F13B h F13C F19A F13C f DP/2:21 X1 DP/2:19 DP/2:22 L4 k F13C F13B f F13C f 2 g F13C BB STORAGE STOR 1 F16 LP1B:6 (PART) A109 A104C F13C 6 L4 k (E) 6 F13C X1 2 1 9 X1 F13C g (E) 2 6 1 g F13C F16 X1 6 b g Q1 e DP/2:18 9 a f f X1 F12B DP/2:14 f F12B 4 F13C 2 F13C n CU Project No.: CP007722 F13C F19A s DP/2:15 PROVIDE A 6/BUTTON WALL STATION FOR SCENE CONTROL IN CLASSROOM. EXISTING EXIT SIGN SHALL BE REMOVED AND RE/INSTALLED AFTER CEILNG HAS BEEN INSTALLED. MAINTAIN EXISTING CIRCUITING. F13C F13C F13C e n Q1 3415 COLORADO AVE BOULDER, COLORADO 80303 Q1 F13B r F13C F12B f f f h F13B o SYSTEMS BIOTECHNOLOGY BUILDING g Q1 d F19A PROJECT FOR F13C t F19A s F13B f Q1 d p k h A108 p Q1 4 F13C F13C F13C DP/2:3 DP/2:16 9 g F13C 122F19A SEAT CLASSROOM F12B F19A F13C F13B DP/2:4 q X g NA Q1 c q U 8 h Q1 7 F13B F13C F13B Q1 F13B g F13C f c Q1 6 F13C DP/2:1 F13C DP/2:8 F19A J g F13C DP/2:2 DP/2:6 F13C f 2 DP/2:11 X1 DP/2:17 F13B L4 k 2 f F13C 7 9 F13 F16 A104 L4 k 7 J 65 SEAT CLASSROOM (E) J DP/2:20 7 5 8 F16 1 STOR. A101 9 PROVIDE WALL MOUNTED OCCUPANCY SENSOR WITH MANUAL ON/OFF CONTROL FOR AREA LIGHTING. CIRCUIT FIXTURES THROUGH SENSOR. PROVIDE VERTICAL LED L4 FIXTURES MOUNTED IN ARCHITECTURAL WALL D SLOT. SEE ARCHITECTURAL DETAIL 4B ON SHEET A/560. REFER TO BASE BUILDING LIGHTING SHEET FOR DESIGN IN THIS AREA. CONTRACTOR TO COORDINATE CEILING HUNG PROJECTORS AND OTHER CEILING MOUNTED AV EQUIPMENT WITH LIGHT FIXTURES. EXISTING CEILING MOUNTED 360 DEGREE OCCUPANCY SENSOR FOR AREA LIGHTING. PROVIDE CEILING MOUNTED 360 DEGREE OCCUPANCY SENSOR FOR AREA LIGHTING. PROVIDE CUSTOM UL/924 LISTED TRANSFER RELAY TO ENERGIZE EMERGENCY FIXTURES UPON LOSS OF NORMAL POWER. PROVIDE 277V NORMAL UNSWITCHED HOT/LEG TO DEVICE FOR SENSING NORMAL POWER AND 120V SWITCH RELAY FOR EMERGENCY CIRCUIT. MOUNT DEVICE ABOVE CEILING. F13C g MARK 10/28/2013 09/24/2013 DATE Addendum 03 BID PACKAGE DESCRIPTION PROJECT NUMBER CP007722 1 PROJECT PRINCIPAL STORAGE PROJECT MANAGER F16 A105 PROJECT DESIGNER B B PROJECT ARCHITECT LANDSCAPE ARCHITECT CIVIL ENGINEER STRUCTURAL ENGINEER MECHANICAL ENGINEER ELECTRICAL ENGINEER INTERIOR DESIGNER EQUIPMENT PLANNER 0 1.5 2 DRAWN BY Author 3 ELECTRICAL LIGHTING PLAN / FIRST FLOOR / AREA AW / ALT 3 1 1/8" = 1'/0" AREA D AREA C A AREA B A ELECTRICAL LIGHTING PLAN / FIRST FLOOR / AREA AW SCALE 1/8" = 1'/0" AREA A 10/28/2013 1:37:34 PM C:\Revit Projects\2013\Project Path\CU System Biotech DV8094_LTG13_jimmy.youssef.rvt 1 1.3 AREA AW 1 2 3 4 5 AREA AE EL 101AW A3 ABBREVIATIONS SYMBOL SCHEDULE TELECOMMUNICATION SYSTEM NOTATION SYMBOL SYMBOL DESCRIPTION TELECOM OUTLET SUBSCRIPT -+XY" AC BC DP FB SR W WAP SUBSCRIPT DESCRIPTION -NON-STANDARD HEIGHT ABOVE COUNTER BELOW COUNTER DISPLAY PANEL FLOOR BOX SURFACE RACEWAY WALL TELEPHONE WIRELESS ACCESS POINT ELECTRICAL TECHNOLOGY SYSTEM NOTATION MOUNTING DETAILS NOTES FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/COUNTER FLUSH/WALL FLOOR BOX WALL FLUSH/WALL WALL 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 1/T-501 LAB DWGS 4/ET-501, 4/T-501 -- 8 8 8 8 8 8 -7 1 SYMBOL SYMBOL DESCRIPTION UP TELECOM OUTLET (CEILING) -P WAP -PROJECTOR INTERFACE WIRELESS ACCESS POINT TELECOM OUTLET - VOICE/DATA (FIELD COORDINATED) -AV B ELEC ELV EMR F FACP M SEC -AUDIOVISUAL BUILDING AUTOMATION ELECTRICAL ELEVATOR EMERGENCY PHONE FURNITURE FIRE ALARM CONTROL MECHANICAL/HVAC SECURITY TELECOM OUTLET - VOICE/DATA (FIELD COORDINATED) (CEILING) TELECOM OUTLET - AV SIGNAL -AV S -AUDIOVISUAL SECURITY -+XY" AC FB -NON-STANDARD HEIGHT ABOVE COUNTER FLOOR BOX CEILING CEILING -- 5/ET-501, 5/T-501 -10/ET-501, 10/T-501 8 1 1 FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/WALL -FURNITURE FLUSH/WALL FLUSH/WALL FLUSH/WALL 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 --3/T-501, 1/T-501 4/ET-501, 4/T-501 4/ET-501, 4/T-501, 1/T-501 -- 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 CEILING ABOVE CEILING LADDER RACK 5/ET-501, 5/T-501 5/ET-501, 5/T-501 -- 1 1 1 FLUSH/WALL FLUSH/WALL FLUSH/WALL FLOOR BOX ----- ----- P FSD SUBSCRIPT J -- WALL 5/ET-502, 5/T-502, 1/ET-503, 1/T-503 -- PLENUM BOX -- -- CEILING -- -- UTILITY POLE -- -- -- -- -- PULL BOX -- -- -- -- 16 CABLE PATHWAY FIRESTOP DEVICE -- -- WALL 9/ET-501, 9/T-501 6,10 8-INCH TRAY 12-INCH TRAY 18-INCH TRAY 24-INCH TRAY ABOVE CEILING BELOW FLOOR LOWER TIER UPPER TIER --------- 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 3/ET-503, 3/T-503 3/ET-503, 3/T-503 3/ET-503, 3/T-503 11 11 11 11 11 11 11 11 8 12 18 24 AC BF LT UT BUSHED CONDUIT -- -- -- -- -- BUSHED CONDUIT SLEEVE -- -- -- -- -- CAPPED CONDUIT OR DUCT -- -- -- -- -- CONDUIT UP -- -- -- -- -- CONDUIT DOWN -- -- -- -- -- GROUND CONNECTION -- -- -- -- -- 4/ET-501 3/T-501, 2/ET-502, 2/T-502, -1 CEILING -- -- CATV OUTLET -- -- -- 4/ET-501, 4/T-501 1 CABLE RUNWAY -- -- -- 3/T-502, 4/T-502 -- CABLING UP -- -- -- -- -- CONDUIT UNDERFLOOR OR UNDERSLAB -- -- -- -- -- CABLING DOWN -- -- -- -- -- CONDUIT UNDERGROUND -- -- -- -- -- SURFACE RACEWAY -- -- -- -- -- J-HOOK PATHWAY -- -- -- -- -- CABLE TERMINUS -- -- -- -- -- CABLE LOOP -- -- -- -- -- GROUND CONNECTION -- -- -- -- -- -FC SYMBOL DESCRIPTION SUBSCRIPT SUBSCRIPT DESCRIPTION MOUNTING DETAILS NOTES SYMBOL S SEE DETAILS -- DOOR 1/ET-504, 1/T-504 -- -- WALL -- -- VS VIDEO SURVEILLANCE SYSTEM - HEAD END -- -- WALL -- -- PROXIMITY READER S FIXED SECURITY CAMERA (CEILING) FIXED SECURITY CAMERA (WALL) -M MAG SEE DETAILS -MULLION MOUNTED MEGNETIC READER WALL MULLION WALL --- --- -- CEILING 7/ET-501, 7/T-501 -- SEE DETAILS -- WALL 7/ET-501, 7/T-501 -- PTZ SECURITY CAMERA (ROOF) -- -- CEILING 7/ET-501, 7/T-501 -- PTZ SECURITY CAMERA -- -- WALL 7/ET-501, 7/T-501 -- EXIT BUTTON -- -- WALL -- -- SYMBOL DESCRIPTION S SUBSCRIPT KEY SWITCH -- -- WALL -- 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. CEILING CEILING --- 1 1 -- -- WALL 3/ET-505, 3/T-505 1 EQUIPMENT RACK (FLOOR) A B C FLOOR RACK - TYPE A FLOOR RACK - TYPE B FLOOR RACK - TYPE C FLOOR FLOOR FLOOR 2/T-505 2/T-505 -- 1 1 1 EQUIPMENT RACK (WALL) -- -- WALL 10/ET-502, 10/T-502, 1/T-502 1 VIDEO DISPLAY (WALL) A B C D 5/ET-503, 5/T-503 5/ET-503, 5/T-503 1/ET-505, 1/T-505 5/ET-502, 5/T-502 1 1 1 1,17 A B C D E F G H J 42-INCH 52-INCH 65-INCH DIGITAL SIGNAGE 84" x 84" MANUAL 96" x 96" MANUAL 108" x 108" MANUAL 90" x 144" ELECTRIC 135" x 216" ELECTRIC 75" x 120" ELECTRIC 69" x 110" ELECTRIC 70" x 70" MANUAL 87" x 139" ELECTRIC WALL WALL WALL WALL CEILING CEILING CEILING CEILING CEILING CEILING CEILING CEILING CEILING 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 1 1 1 1 1 1 1 1 1 FB1X FB6X W1X W2X W3X W4X 1 GANG TYPE X 6 GANG TYPE X 1 GANG TYPE X 2 GANG TYPE X 3 GANG TYPE X 4 GANG TYPE X FLOOR BOX FLOOR BOX WALL WALL WALL WALL 1/T-506 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 1 1 1 1 1 1 C1X 1 GANG TYPE X CEILING 1/T-506 1 PROJECTOR A B TYPE A TYPE B CEILING CEILING 4/ET-503, 4/T-503 6/ET-503, 6/T-503 1 1 CONTROL PANEL (WALL) A B C D TYPE A TYPE B TYPE C TYPE D WALL WALL WALL DESK 12/T-502 7/ET-502, 7/T-502, 9/T-503 7/ET-502, 7/T-502 -- 1 1 1 1 ANTENNA (WALL) A B ASSISTED LISTENING MICROPHONE WALL WALL --- 1 1 A FIXED AUDIOVISUAL CAMERA (CEILING) -- DOCUMENT CAMERA CEILING -- 1 A PTZ AUDIOVISUAL CAMERA (WALL) -- -- WALL 8/ET-502, 8/T-502 1 SCREEN SWITCH -- -- WALL -- 1,9 SMART LECTERN -- -- FLOOR -- -- CEILING MICROPHONE -- -- CEILING -- -- NOTES 7. NOTES LOUDSPEAKER (WALL) INTERFACE PLATE (CEILING) M 3. 4. 5. 6. DETAILS ACCESSIBLE CEILING NON ACCESSIBLE CEILING INTERFACE PLATE (WALL) CP 2. MOUNTING ABBREV. DEFINITION ABBREV. DEFINITION AC ACP ACS AO AOC AFF AHJ APC APPROX AR ARCH AV AVSC AWG BB BC BEP BI BLDG BO C CAB CAN CAT3 CAT5E CAT6 CAT6A CATV CC CER CO COAX COM CPV CR CT CV (D) DB DD DIA DVI DPDT DPS DNS DWG (E) ECL ECP EEB EF EL ELEC ELM ELR EMT ENCL EQPMT ER ES ESC ESO FACP FB FSD FLEX FUT G HB HC HDMI HO ID IDS IG IMC IP IR ISP LL ABOVE COUNTER ACCESS CONTROL PANEL ACCESS CONTROL SYSTEM AUTOMATIC OPERATOR AUTO OPENER CONTROLLER ABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTION ANGLE POLISHED CONNECTOR APPROXIMATELY AUXILIARY RELAY ARCHITECTURAL AUDIOVISUAL AUDIOVISUAL SYSTEMS CONTRACTOR AMERICAN WIRE GAUGE BACKBONE BELOW COUNTER BUILDING ENTRANCE PROTECTOR BIOMETRIC INTERFACE BUILDING BY OTHERS CONDUIT CABINET CONTROLLED AREA NETWORK CATEGORY 3 COPPER CABLE CATEGORY 5E COPPER CABLE CATEGORY 6 COPPER CABLE CATEGORY 6 AUGMENTED COPPER CABLE CABLE TELEVISION CONTACT CLOSURE CYLINDER ELECTRIC RETRACTION CONDUIT ONLY (NO CABLE) COAXIAL CABLE COMMON COMPONENT VIDEO CARD READER COUNT COMPOSITE VIDEO DEMOLISH DATA-GRADE COPPER BACKBONE DEAD DIAMETER DIGITAL VIDEO INTERFACE DOUBLE POLE, DOUBLE THROW DOOR POSITION SWITCH DATA NETWORK SWITCH DRAWING EXISTING ELECTRIC CYLINDER LOCK ELEVATOR CONTROL PANEL EMERGENCY EXIT BUTTON ENTRANCE FACILITY ELECTRIC LATCH ELECTRICAL ELECTRIC LATCH WITH LATCH MONITOR SWITCH ELECTRIC LATCH RETRACTION ELECTRICAL METALLIC TUBING ENCLOSURE (SPLICE) EQUIPMENT EQUIPMENT ROOM ELECTRIC STRIKE ELECTRICAL SYSTEMS CONTRACTOR ELECTRIC SOLENOID FIRE ALARM CONTROL PANEL FIBER BACKBONE FIRE STOP DEVICE FLEXIBLE FUTURE GROUND HANDICAP BUTTON HORIZONTAL CABLE HIGH DEFINITION MEDIA INTERFACE HOLD OPEN INSIDE DIAMETER INTRUSION DETECTION SYSTEM ISOLATED GROUND INTERMEDIATE METAL CONDUIT INTERNET PROTOCOL INFRARED INSIDE PLANT LINE LEVEL LEFT CHANNEL AUDIO LM LR LPS MAG MECH MFR MIC MIN ML MM MS (NL) NTS NVR OB OC OD OFCI OFOI OHM OPE OS OSP P PDS PEL PER PML PMR PP PR PREX PS (R) (RL) R REV REX RF RGB RI RM RMC RNC S SC SCHED SCNS SCPP SCPS SH SM SMR SN SP SPEC SPKR SPR SR SRV SSC STP SV TB TBB TBD TGB TMGB TR TSC TYP UG UON UPS USB V VLAN VB W WAP LINE LEVEL MONO AUDIO LINE LEVEL RIGHT CHANNEL AUDIO LOCK POWER SUPPLY. MAGNETIC LOCK MECHANICAL MANUFACTURER MICROPHONE LEVEL AUDIO MINIMUM MONITORED LATCH MULTIMODE FIBER OPTIC CABLE MONITORED STRIKE NEW LOCATION NOT TO SCALE NETWORK VIDEO RECORDER OVERRIDE BUTTON ON CENTER OUTSIDE DIAMETER OWNER FURNISHED, CONTRACTOR INSTALLED OWNER FURNISHED, OWNER INSTALLED RESISTIVE NETWORK OWNER PROVIDED EQUIPMENT OVERIDE SWITCH OUTSIDE PLANT PROJECTOR PROTECTIVE DISTRIBUTION SYSTEM PANIC DEVICE ELECTRIC LATCH PANIC DEVICE ELECTRIC ROD PANIC DEVICE MONITORED LATCH PANIC DEVICE MONITORED ROD PATCH PANEL(S) PAIR PANIC DEVICE REQUEST TO EXIT SWITCH POWER SUPPLY REMOVE REMOVE AND RELOCATE RISER REVISION REQUEST TO EXIT SWITCH RADIO FREQUENCY HIGH RESOLUTION VIDEO READER INTERFACE ROOM RIGID METALLIC CONDUIT RIGID NONMETALLIC CONDUIT STATION SECURITY CAMERA SCHEDULE SECURITY CAMERA NETWORK SWITCH SECURITY CAMERA PATCH PANEL SECURITY CAMERA POWER SUPPLY SURFACE HOUSING SINGLEMODE FIBER OPTIC CABLE SURFACE METAL RACEWAY SERIAL NETWORK MODULE SURGE PROTECTOR SPECIFICATION LOUDSPEAKER LEVEL AUDIO SURFACE PLASTIC RACEWAY SURFACE RACEWAY SERVER ROOM SECURITY SYSTEMS CONTRACTOR SHIELDED TWISTED PAIR CABLE S-VIDEO TERMINATION BLOCK(S) TELECOM BONDING BACKBONE TO BE DETERMINED TELECOM GROUNDING BUSBAR TELECOM MAIN GROUNDING BUSBAR TELECOMMUNICATIONS ROOM (IDF, FD) TELECOMMUNICATION SYSTEMS CONTRACTOR TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY UNIVERSAL SERIAL BUS VOICE VIRTUAL LOCAL AREA NETWORK VOICE-GRADE COPPER BACKBONE WALL MOUNTED WIRELESS ACCESS POINT SHEET# TITLE ET-001 ET-004 ET-101AW-A3 ET-101B-A3 ET-301 ET-307 ET-501 ET-503 A WORK SHALL COMPLY WITH THE GOVERNING REQUIREMENTS LISTED IN THE SPECIFICATIONS B DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD C ELECTRICAL CONTRACTOR SHALL PROVIDE PRIMARY RACEWAYS/PATHWAYS. RACEWAYS/PATHWAYS CONSIDERED TO BE PRIMARY ARE AS SHOWN ON THE ET-SERIES DRAWINGS D WORK REQUIRING UTILITY AND/OR COMMUNICATIONS OUTAGES SHALL BE COORDINATED WITH THE OWNER IN ADVANCE AND MUST BE PRE-APPROVED IN WRITING S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 RIMROCK GROUP Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT FURNISH | INSTALL CALLOUT SCHEDULE SHEET LIST SYMBOL ELECTRICAL TECHNOLOGY - TITLE SHEET 2 ELECTRICAL TECHNOLOGY - RISER DIAGRAMS ELECTRICAL TECHNOLOGY PLAN - FIRST FLOOR - AREA AW ELECTRICAL TECHNOLOGY PLAN - FIRST FLOOR - AREA B ENLARGED MDF ROOM ENLARGED TELECOM ROOM ELECTRICAL TECHNOLOGY - DETAILS ELECTRICAL TECHNOLOGY - DETAILS 2 X Y ENTITY RESPONSIBLE FOR INSTALLING ENTITY RESPONSIBLE FOR FURNISHING ENTITY -- IF COORDINATION IS REQUIRED PRIOR TO ROUGH-IN. LOCATION SHOWN MAY NOT REPRESENT THE FINAL LOCATION NECESSITATED BY FIELD CONDITIONS. FURTHERMORE, NON-TYPICAL REQUIREMENTS FOR ROUGH-IN BOXES, MOUNTING, SUPPORT, FACEPLATES AND/OR INTERFACES MAY BE NECESSARY. COORDINATE LOCATIONS AND REQUIREMENTS WITH RESPECTIVE TRADE(S), SHOP DRAWINGS, ARCHITECTURAL ELEVATIONS AND/OR OWNER PRIOR TO ROUGH-IN. PROVIDE AS REQUIRED FLOOR BOX LOCATIONS SHOWN ARE APPROXIMATE. PRIOR TO ROUGH-IN COORDINATE FINAL LOCATION WITH ARCHITECTURAL, STRUCTURAL, FURNITURE, AND OWNER REQUIREMENTS, AND WITH ALL OTHER TRADES WHICH WILL MAKE USE OF THE FLOOR BOX ELECTRICAL CONTRACTOR TO ROUTE CONDUIT TO ACCESSIBLE CEILING SPACE IN SAME ROOM SERVED BY THE DEVICE BOX AV CONTRACTOR TO ROUTE CABLE WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR MOUNTING ELECTRICAL CONTRACTOR TO PROVIDE CABLE PATHWAY FIRESTOP DEVICES FOR CABLE TRAY PASS-THRUS. ALL OTHER TRADES TO PROVIDE CABLE PATHWAY FIRESTOP DEVICES FOR THEIR RESPECTIVE CABLES PASSING THROUGH FIRE RATED BARRIERS ELECTRICAL CONTRACTOR TO MOUNT AT ADA COMPLIANT HEIGHT FOR WALL MOUNT TELEPHONES. TELECOM CONTRACTOR TO PROVIDE WALL MOUNT FACEPLATE WITH TELEPHONE MOUNTING STUDS PROVIDE CABLE QUANTITIES AND TYPES PER THE STATION CALLOUT ON THE T-SERIES TITLE SHEET MOUNT AT STANDARD SWITCH HEIGHT ABOVE FINISHED FLOOR FOR EACH CABLE PATHWAY FIRESTOP LOCATION SHOWN FEEDING CABLE TRAY, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE VOLUME OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THE VOLUME OF CABLE TRAY TO BE SERVED. FOR ALL OTHER FIRESTOP LOCATIONS, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE VOLUME OF THE DEVICE(S) IS GREATER THAN THE VOLUME OF ALL CABLES TO PASS THROUGH THE DEVICES, PLUS THE ADDITIONAL AMOUNT (PERCENTAGE) REQUIRED BY THE SPECIFICATIONS FOR FUTURE EXPANSION PROVIDE CABLE TRAY COMPLETE WITH ALL MATERIALS AND INCIDENTAL HARDWARE NECESSARY FOR A COMPLETE AND FULLY FUNCTIONAL CABLE TRAY SYSTEM, INCLUDING BUT NOT LIMITED TO STRAIGHT SECTIONS, T-JUNCTIONS AND RADIUS (ROUNDED) CORNERS CONFORMING TO TIA/EIA 569 BEND RADIUS REQUIREMENTS, EXPANSION JOINTS, SUPPORT HANGERS, CONNECTOR AND CLAMP ASSEMBLIES, CONNECTOR AND SPLICE PLATES, ETC. INSTALL IN ACCORDANCE WITH NEMA VE 2 (LATEST EDITION), TIA/EIA 569, AND MANUFACTURERS RECOMMENDATION AND INSTRUCTIONS. GROUND AND BOND PER NEC, MANUFACTURER REQUIREMENTS, AND TIA/EIA STANDARDS NOTUSED ELECTRICAL CONTRACTOR TO MOUNT AT ADA COMPLIANT HEIGHT ROUGH-IN PROVIDED BY ELECTRICAL CONTRACTOR, CABLING PROVIDED BY TELECOM CONTRACTOR, CAMERA AND HOUSING PROVIDED BY OWNER TERMINATE CABLE IN SURFACE MOUNT BISCUIT WITHIN RACO DEVICE BOX REFER TO SIZING CHART IN SPECIFICATIONS. SECTION 270533 PART 2.5 SYSTEMS LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED (OFOI) SUBSCRIPT DESCRIPTION A B PROJECTION SCREEN (CEILING) IF 1. FLUSH/WALL FLUSH/WALL LOUDSPEAKER (CEILING) 2 KS EMPTY FLEXIBLE CONDUIT AUDIOVISUAL SYSTEM NOTATION -- S 1,2 1,2 1,2 -- ACCESS CONTROL SYSTEM - HEAD END S 7/ET-503, 7/T-503 6/ET-501, 6/T-501 8/ET-501, 8/T-501 -- AS S FLOOR FLOOR FLOOR -- 11-GANG 4-GANG FLEXIBLE CONDUIT TELECOM OUTLET - AV SIGNAL (CEILING) ACCESS CONTROLLED DOOR X NOTES WALL BOX SECURITY SYSTEM NOTATION SYMBOL DETAILS 11 4 FC DEVICE BOX SR MOUNTING FLOOR BOX CABLE TRAY # AA SUBSCRIPT DESCRIPTION PROJECT NOTES EC ELECTRICAL CONTRACTOR TC TELECOM CONTRACTOR AC AUDIOVISUAL CONTRACTOR SC SECURITY CONTRACTOR GC GENERAL CONTRACTOR LC LOW VOLTAGE/SPECIALTY CONTRACTOR BO BY OTHERS O OWNER 2 1 MARK 10/28/2013 09/24/2013 DATE DESCRIPTION SYMBOL - DRAWING ANNOTATION SYMBOL DESCRIPTION # KEY NOTE # DRAWING NOTE # EQUIPMENT SCHEDULE NUMBER # REVISION NUMBER SECTION OR ELEVATION TAG * SECTION OR ELEVATION LETTER # REFERENCE DRAWING NUMBER * # REFERENCE TAG * REFERENCE LETTER # REFERENCE DRAWING NUMBER * # A D * # C B ROOM WALL ELEVATION BUBBLE REFERENCE NUMBER * # REFERENCE DRAWING NUMBER WALL ELEVATION REFERENCE CONTINUATION LINE TELECOM AREA BOUNDARY LINE EQUIPMENT SCHEDULE ID CR200 CR201 CR210 CR220 CR231 CR232 CR307 CR341 CR400 CR435 CR515 CR520 CR530 CR600 EE102 EE105 EE110 FS100 TE045 TE046 TE048 TE225 TE348 TE372 TE566 TE600 GB010 GB020 DESCRIPTION CABLE RUNWAY STRAIGHT SECTION - GRAY (STANDARD RUNG SPACING) CABLE RUNWAY STRAIGHT SECTION (ALTERNATE RUNG SPACING) CORNER BRACKET RADIUS DROP ELEVATION KIT RACK-TO-RUNWAY MOUNTING PLATE EQUIPMENT RACK (7' 2-POST) WITH INSTALLATION KIT SERVER CABINET (750mm) HORIZONTAL POWER STRIP BLANK PANEL INSERT CABINET CABLE TROUGH (750MM CABINET) VERTICAL MANAGEMENT SECTION (DOUBLE-SIDED, WIDE) INTERBAY PATCH CORD ORGANIZER BACKBOARD L5-20 RECEPTACLE L21-20 RECEPTACLE CS8365 RECEPTACLE CABLE PATHWAY FIRESTOPPING DEVICE VOICE CABLE COPPER PATCH PANEL - CAT 5E (96 PORT, 4U) UTILITY COPPER PATCH PANEL - CAT 5E (48 PORT, 2U) HORIZONTAL COPPER PATCH PANEL - CAT 5E (48 PORT, 2U) DATA GRADE COPPER PATCH PANEL - CAT 6 (48 PORT, 2U) RACK MOUNT FIBER PATCH PANEL (48/96 PORT, 2U) RACK MOUNT FIBER PATCH PANEL (72/144 PORT, 4U) TERMINATION BLOCK - 66-STYLE BUILDING ENTRANCE PROTECTOR TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) 2 ELECTRICAL TECHNOLOGY TITLE SHEET ET-001 S T E RN (1) 2-INCH CONDUIT ROOF ROOF TR-4A B448 TR-4A B448 CABLE TRAY HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 12 AC (12) 4-INCH CONDUITS Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 RIMROCK GROUP Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com (4) 4-INCH CONDUITS FOURTH FLOOR FOURTH FLOOR TR-3A B348 TR-3B D347 ALT 4 TR-3A B348 TR-3B D347 ALT 4 TR-2A B248 TR-2B D247 ALT 4 MDF/TR-1A B148 TR-1B D147 ALT 4 TR-0B D1B47 ALT 4 CABLE TRAY 12 AC 12 AC 12 AC (12) 4-INCH CONDUITS (12) 4-INCH CONDUITS (4) 4-INCH CONDUITS THIRD FLOOR (4) 4-INCH CONDUITS TR-2A B248 TR-2B D247 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT THIRD FLOOR ALT 4 CABLE TRAY 12 AC 12 AC 12 AC (12) 4-INCH CONDUITS (12) 4-INCH CONDUITS (4) 4-INCH CONDUITS SECOND FLOOR TR-1D A102 TR-1C A115A (4) 4-INCH CONDUITS MDF/TR-1A B148 (3) 1-INCH CONDUITS FOR FUTURE USE TR-1B D147 (6) 4-INCH CONDUITS ALT 4 TR-1D A102 ALT 3 TR-1C A115A CABLE TRAY 16 AC 16 AC (6) 4-INCH CONDUITS SECOND FLOOR FSD 16 AC 16 AC 12 AC (12) 4-INCH CONDUITS CABLE TRAY (5) 4-INCH CONDUITS (4) 4-INCH CONDUITS (4) 4-INCH CONDUITS P (4) 4-INCH CONDUITS FIRST FLOOR GEN STORAGE SERVER ROOM B1B58 TR-0A B1B50 (4) 4-INCH CONDUITS EQUIPMENT ROOM C1B90C TR-0B D1B47 FIRST FLOOR ALT 4 SERVER ROOM B1B58 SECURITY B1B52 CABLE TRAY (1) 2-INCH INTERMEDIATE METALLIC CONDUIT (IMC) FSD GEN STORAGE AB130 12 AC P (12) 4-INCH CONDUITS (2) 4-INCH INTERMEDIATE METALLIC CONDUITS (IMC) AND (2) 4-INCH RIGID CONDUITS 2 1 MARK (1) 4-INCH INTERMEDIATE METALLIC CONDUIT (IMC) AND (2) 4-INCH RIGID CONDUITS BASEMENT 10/28/2013 09/24/2013 DATE DESCRIPTION BASEMENT TO VAULTS TO UCB VAULT (4) 4-INCH CONDUITS 1 (3) 4-INCH CONDUITS (1) 2-INCH CONDUIT TO SITE EMERGENCY PHONE 2 TELECOMMUNICATION AND DATA PATHWAY - RISER DIAGRAM GENERAL NOTES KEY NOTES DRAWING NOTES A SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 1 BONDING CONDUCTOR TO EQUIPMENT GROUNDING SYSTEM. BOND (ACEG) TO NEAREST LOW VOLTAGE ELECTRICAL DISTRIBUTION SYSTEM - GROUNDING RISER BUSBAR. BOND PER NEC AND SPECIFICATIONS. REFER TO SPECIFICATIONS FOR CONDUCTOR SIZING 2 BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT), ROUTE TO INTERSYSTEM BONDING TERMINATION. BOND PER NEC AND SPECIFICATIONS. REFER TO SPECIFICATIONS FOR CONDUCTOR SIZING B C D REFER TO THE ENLARGED TELECOM ROOMS IN THE T-SERIES DRAWINGS FOR CONDUIT, CABLE PATHWAY FIRESTOP DEVICE, AND SLEEVE PENETRATION/TERMINATION LOCATIONS INSTALLATION OF GROUNDING AND BONDING SYSTEM SHALL COMPLY WITH TIA/EIA-607 GROUNDING AND BONDING STANDARD, NEC AND SPECIFICATIONS COORDINATE WITH TELECOM CONTRACTOR PRIOR TO INSTALLING PATHWAYS, RACEWAYS, EQUIPMENT OR MATERIALS WITHIN TELECOM AND/OR OTHER COMMUNICATIONS ROOMS. REFER TO ENLARGED TELECOM ROOMS IN T-SERIES DRAWINGS FOR LOCATIONS WITHIN ROOMS FOR EACH CABLE PATHWAY FIRESTOP LOCATION SHOWN FEEDING CABLE TRAY, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE VOLUME OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THE VOLUME OF CABLE TRAY TO BE SERVED 51 CONDUITS TO ROOF. FIRESTOP, CAP AND SEAL WATERTIGHT AT ROOF 67 OUTSIDE PLANT CONDUITS 3 TELECOMMUNICATIONS BONDING BACKBONE (TBB). BOND PER NEC AND SPECIFICATIONS. REFER TO SPECIFICATIONS FOR CONDUCTOR SIZING 4 SEE SECURITY RISER DIAGRAM ON ET-005 FOR ADDITIONAL CONDUITS ENTERING THIS ROOM 5 CONDUIT TO VAULT THROUGH GENERAL STORAGE ROOM A1B30 6 PROVIDE ENCLOSURE(S) FOR THE (3) 4-INCH AND (1) 2-INCH OSP CONDUITS ENTERING FROM BELOW ON WALL 'A' TO TRANSITION TO WALL 'D' AND THEN UP THROUGH THE CEILING INTO MDF/TR-1A. PROVIDE ENCLOSURE(S) FOR THE (4) 4-INCH HORIZONTAL CONDUITS FROM GENERAL STORAGE A1B30 ENTERING THROUGH WALL 'A' TO TRANSITION TO (4) 4-INCH VERTICAL CONDUITS EXTENDING UP THROUGH THE CEILING INTO MDF/TR-1A. SIZE THE ENCLOSURES ACCORDINGLY TO SATISFY CABLE BEND RADII. COORDINATE THE INSTALLATION AND SIZING OF ENCLOSURES WITH UCB ITS AND THE TELECOMMUNICATIONS CONTRACTOR. PROVIDE ENCLOSURES THAT DO NOT REDUCE THE INTEGRITY OF THE INTERMEDIATE METALLIC CONDUIT (IMC) SYSTEM ELECTRICAL TECHNOLOGY - GROUNDING DIAGRAM ELECTRICAL TECHNOLOGY RISER DIAGRAMS 2 ET-004 GENERAL NOTES SEE SYMBOL SCHEDULE (ON THE TITLE SHEET) FOR IMPORTANT INSTALLATION NOTES AND DETAILS SPECIFIC TO EACH SYMBOL USED ON THIS SHEET B REFER TO DETAIL DRAWING(S) FOR ADDITIONAL STRUCTURAL SUPPORT, MOUNTING, AND RACEWAY REQUIREMENTS C UNLESS OTHERWISE NOTED, REFER TO ARCHITECTURAL DRAWINGS, DETAILS AND/OR SPECIFICATIONS FOR DEVICE BOX MOUNTING HEIGHTS D 0 1 1.3 1.5 AW 2 A 3 MATCHLINE TR-1D BOUNDARY AREA OF WORK AREA OF WORK PROVIDE PULL BOXES FOR CONDUIT RUNS AT INTERVALS REQUIRED PER THE SPECIFICATIONS. DO NOT INSTALL CONDUITS INTO A PULL BOX IN SUCH A WAY AS TO OBSTRUCT THE INSTALLATION OF FUTURE FEEDER CONDUITS INTO OR OUT OF THE PULL BOX F UNLESS OTHERWISE NOTED, RACEWAY FOR TELECOM OUTLETS SHALL CONSIST OF 1-INCH CONDUIT FROM EACH TELECOM OUTLET BOX (I.E. DEVICE BOX, BACK BOX, ETC.) TO CABLE TRAY F1 AREA AW S +84" (2) 4-INCH CONDUITS (AV) (4) 4-INCH CONDUITS (2) 4 CON (1) 4-INCH CONDUIT (4) 4-INCH CONDUITS W P TR-1D 1 TELE STOR (1) 1-INCH CONDUIT (TYPICAL) +120" B S A S (1) 1-INCH CONDUIT (TYPICAL) A WAP (1) 1 1/4-INCH CONDUIT IF (TYPICAL) W2D B AT MOVABLE LAB BENCH LOCATIONS, CONTRACTOR SHALL INSTALL CONDUIT FROM CABLE TRAY TO CONTRACTOR PROVIDED 4-SQUARE DEEP BOX IN CEILING AT LAB SERVICE PANEL. PROVIDE GROMMET IN SERVICE PANEL IN CEILING. REFER TO LAB EQUIPMENT DRAWINGS FOR ADDITIONAL INFORMATION K ROUTE CONDUITS FROM SECURITY DOORS ON GROUND FLOOR TO SECURITY ROOM B1B52 L ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED M ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO THE LACK OF COORDINATION WITH ARCHITECT N ALL CAMERA HEIGHT REQUIREMENTS ARE TO BE REFERENCED FROM THE FINISHED FLOOR OF LEVEL WHICH THE CAMERA IS LOCATED. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS (1) 3/4-INCH CONDUIT A X NA IF +120" B S +84" 11 A S FB6D +84" J MATCHLINE 2 IF 110-SEAT CLASSROOM B S B B B P B S AW +120" S S P A108 P B +120" IF (1) 3/4-INCH CONDUIT (TYPICAL) DN IF A W2D (1) 3/4-INCH CONDUIT (TYPICAL) 11 FB6E W2D A FB6E IF A +120" IF 11 (1) 3/4-INCH CONDUIT (TYPICAL) (1) 1-INCH CONDUIT (TYPICAL) (1) 3/4-INCH CONDUIT (TYPICAL) IF S P A104 B TR-1D BOUNDARY 60-SEAT CLASSROOM S B B B J 11 S J S +84" IF B FB6D PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 1 THE AUDIOVISUAL SYSTEMS IN THIS AREA WILL BE LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED 2 ELECTRICAL CONTRACTOR TO COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR PRIOR TO INSTALLATION 67 OUTSIDE PLANT CONDUITS C1A P 2 B IF S Empowered Business - Quiet Technology KEY NOTES IF Z B C1A A IF W2D RIMROCK GROUP W2D S S TR-1C BOUNDARY S Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT C1A J IF U W2D S C1A W S +120" S TR-1D BOUNDARY DN B B (1) 1-INCH CONDUIT (TYPICAL) B (1) 3/4-INCH CONDUIT IF A C2D A107 (1) 2-INCH CONDUIT DN (TYPICAL) WAP P J A A/V EQ ROOM/STOR A103 A101 T 12 AC AV 12-INCH ABOVE CEILING CABLE TRAY ET-307 A102 STOR. DN COORDINATE WITH TELECOM CONTRACTOR PRIOR TO INSTALLING EQUIPMENT OR MATERIALS WITHIN TELECOM AND/OR OTHER COMMUNICATIONS ROOMS. REFER TO T-SERIES ENLARGED TELECOM ROOM DRAWINGS FOR LOCATIONS WITHIN ROOMS P C1A C2D H F1 A100 CRA100 OVERHEAD CABLE TRAY SHALL NOT BE INSTALLED OVER HARD LID (NON-ACCESSIBLE) CEILINGS. TRANSITION CABLE TRAY TO 4-INCH CONDUIT SLEEVES OVER HARD LID CEILINGS. PROVIDE SLEEVES IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE CROSS-SECTIONAL AREA OF THE SLEEVES IS GREATER THAN OR EQUAL TO THE CROSS-SECTIONAL AREA OF CABLE TRAY TO BE SERVED +84" PRE-FUNCTION VESTIBULE G S S HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 COORDINATE CABLE TRAY INSTALLATION WITH OTHER TRADES PRIOR TO INSTALLATION. REFER TO SPECIFICATIONS FOR SPECIFIC ACCESSIBILITY AND MINIMUM CLEARANCE REQUIREMENTS E R.6 2 S T E RN A +84" B S B S B S DN WAP BB DN WAP STORAGE A109 M2A M1A M1B DN DN AREA OF WORK AREA OF WORK STOR 2 A105 2 1 MARK 10/28/2013 09/24/2013 DATE DESCRIPTION N 1 ELECTRICAL TECHNOLOGY PLAN - FIRST FLOOR - AREA AW 8' 4' 0 1/8" = 1'-0" 8' AREA D AREA C AREA B ELECTRICAL TECHNOLOGY PLAN FIRST FLOOR AREA AW AREA A AREA AW AREA AE ET-101AW-A3 GENERAL NOTES SEE SYMBOL SCHEDULE (ON THE TITLE SHEET) FOR IMPORTANT INSTALLATION NOTES AND DETAILS SPECIFIC TO EACH SYMBOL USED ON THIS SHEET B REFER TO DETAIL DRAWING(S) FOR ADDITIONAL STRUCTURAL SUPPORT, MOUNTING, AND RACEWAY REQUIREMENTS C UNLESS OTHERWISE NOTED, REFER TO ARCHITECTURAL DRAWINGS, DETAILS AND/OR SPECIFICATIONS FOR DEVICE BOX MOUNTING HEIGHTS D 9 10 11 12 13 15 ELEV (SECURITY-ACS) WAP 17 18 19 20 21 22 23 23.2 CHBE OFFICE ELC101 SR 16 B STOR C120 TR-1B BOUNDARY F1 +84" MDF/TR-1A BOUNDARY F UNLESS OTHERWISE NOTED, RACEWAY FOR TELECOM OUTLETS SHALL CONSIST OF 1-INCH CONDUIT FROM EACH TELECOM OUTLET BOX (I.E. DEVICE BOX, BACK BOX, ETC.) TO CABLE TRAY C2B OVERHEAD CABLE TRAY SHALL NOT BE INSTALLED OVER HARD LID (NON-ACCESSIBLE) CEILINGS. TRANSITION CABLE TRAY TO 4-INCH CONDUIT SLEEVES OVER HARD LID CEILINGS. PROVIDE SLEEVES IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE CROSS-SECTIONAL AREA OF THE SLEEVES IS GREATER THAN OR EQUAL TO THE CROSS-SECTIONAL AREA OF CABLE TRAY TO BE SERVED H COORDINATE WITH TELECOM CONTRACTOR PRIOR TO INSTALLING EQUIPMENT OR MATERIALS WITHIN TELECOM AND/OR OTHER COMMUNICATIONS ROOMS. REFER TO T-SERIES ENLARGED TELECOM ROOM DRAWINGS FOR LOCATIONS WITHIN ROOMS J AT MOVABLE LAB BENCH LOCATIONS, CONTRACTOR SHALL INSTALL CONDUIT FROM CABLE TRAY TO CONTRACTOR PROVIDED 4-SQUARE DEEP BOX IN CEILING AT LAB SERVICE PANEL. PROVIDE GROMMET IN SERVICE PANEL IN CEILING. REFER TO LAB EQUIPMENT DRAWINGS FOR ADDITIONAL INFORMATION K ROUTE CONDUITS FROM SECURITY DOORS ON GROUND FLOOR TO SECURITY ROOM B1B52 L ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED M ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO THE LACK OF COORDINATION WITH ARCHITECT N ALL CAMERA HEIGHT REQUIREMENTS ARE TO BE REFERENCED FROM THE FINISHED FLOOR OF LEVEL WHICH THE CAMERA IS LOCATED. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS K MDF/TR-1A BOUNDARY F1 MATCHLINE B G +84" S S C (6) 4-INCH CONDUITS C1D PROVIDE PULL BOXES FOR CONDUIT RUNS AT INTERVALS REQUIRED PER THE SPECIFICATIONS. DO NOT INSTALL CONDUITS INTO A PULL BOX IN SUCH A WAY AS TO OBSTRUCT THE INSTALLATION OF FUTURE FEEDER CONDUITS INTO OR OUT OF THE PULL BOX C121 SR PASSAGE VESTIBULE CRB180A VESTIBULE (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING DNDN CRB180B DNDN DNDN K.5 C1C MAG P STB181 IF DN 2 DN D S +120" W3A MDF/TR-1A BOUNDARY AREA OF WORK 1 4 A S A 1 4 A P 1 SR SR W3A W3A SR SR A A B160A S 2 H S C2A 1 SR SR (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING A SR SR SR SR 1 (6) 4-INCH CONDUITS SR SR B148 ET-301 A SR SR SR SR MDF/TR-1A SR SR S MDF/TR-1A BOUNDARY B151 COMPUTER LAB 12 AC SR 12 AC H W3A 12 AC FS 4 2 A 12 AC C2A SR UP FS SR SR SR SR 16 AC 16 AC 2 S M1A TEACHING LAB CLASSROOM SR WAP 2 A 2 1 MARK FS B159 SR SR SR SR ELB143 2 2 SR 2 STORAGE 16 AC B171A SR JC A M1A B141 AREA OF WORK AREA OF WORK P HR OFFICE A171D A171C A171B C1A MDF/TR-1A BOUNDARY BUDGET A130 B 2 BUDGET MATCHLINE A133 RY HR OFFICE 16 AC SR PROG MAN OFFICE DESCRIPTION SR FS AV W3A 10/28/2013 09/24/2013 DATE SR MATCHLINE IF DN N.2 S ELEV 11 REFERENCE LAB DRAWINGS FOR SERVICE CARRIER N 2 A P 1 2 FS SR 14 B COORDINATE FINAL LOCATIONS WITH FURNITURE DRAWINGS AND SPECIFICATIONS SR C2A 4 1 1 IF ELB145 11 OUTSIDE PLANT CONDUITS FS S SR A STAIR 12 AC A A S 12 AC FS P 4 C1B A S B115 1 67 DRAWING NOTES B171 SHARED EQUIP. ROOM ELEV A WAP ChBE TEACHING LABS A 4 AV B155 A ELECTRICAL CONTRACTOR TO COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR PRIOR TO INSTALLATION M.2 STB191 IF STORAGE ROOM B149 S 2 SR CORRIDOR CRB150 12 AC S FS ELEC 4 THE AUDIOVISUAL SYSTEMS IN THIS AREA WILL BE LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED M SR F1 +84" (6) 4-INCH CONDUITS 1 1 S B180 FS B160B AREA B 12 AC SR SR SR BIOENGINEERING TEACHING LABORATORY WAP CORRIDOR SR SR SR C2E A SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET A SR S AUTOCLAVE C1A IF SR SR A A SR BIOCHEMISTRY TEACHING LABORATORY CRB110 4 1 SR SR 4 B160 STUDENT STUDY S KEY NOTES A SR 4 P B160C W 1 S IF SR S B100 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com A S S A C2A PREP LAB 4 MDF ROOM 4 1 A S A 2 B120 EMR SR SR 4 4 COMPUTER LAB A SR SR A H 4 P WAP S SR SR A IF 16 AC C2A 1 SR SR AV IF SR IF 4 IF 4 AV 16" x 4" CABLE TRAY 1 4 S A Empowered Business - Quiet Technology SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT SR TEACHING LAB STORAGE C2B MDF/TR-1A BOUNDARY B 1 4 14 B L AREA OF WORK AV 16 AC MDF/TR-1A BOUNDARY STAIR UP AV RIMROCK GROUP C2D C1E KS Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 C1D CRB180 C2D HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 COORDINATE CABLE TRAY INSTALLATION WITH OTHER TRADES PRIOR TO INSTALLATION. REFER TO SPECIFICATIONS FOR SPECIFIC ACCESSIBILITY AND MINIMUM CLEARANCE REQUIREMENTS E C MATCHLINE S T E RN A A AREA D N 1 ELECTRICAL TECHNOLOGY PLAN - FIRST FLOOR - AREA B 8' 4' 0 1/8" = 1'-0" 8' AREA C AREA B ELECTRICAL TECHNOLOGY PLAN FIRST FLOOR AREA B AREA A AREA AW AREA AE ET-101B-A3 13 14 15 S T E RN M COLUMN COLUMN TYP 2B ET-301 HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 TYP 2A ET-301 (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING M.2 TYP Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 FRONT OF RACKS (6) 4-INCH CONDUITS RIMROCK GROUP Empowered Business - Quiet Technology (6) 4-INCH CONDUITS 2A 6" A 3 ET-301 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com ET-301 TYP D ENLARGED MDF/TR-1A RACK ELEVATIONS (B148) B C ELEC PANEL 18" x 24" TYP TYP TYP TYP W N 1 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT ENLARGED MDF/TR-1A (B148) ET-301 2' 1' 0 1/2" = 1'-0" 2' 2B ENLARGED MDF/TR-1A RACK ELEVATIONS (B148) ET-301 COLUMN 489BCC1-100 QWEST COLUMN COLUMN ELEC PANEL 18" x 24" UCB UTILITY COLUMN TYP 8' 7'-4" TYP 12 WALL "A" KEY NOTES A SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET B C BOND ALL NON-CURRENT CARRYING METALLIC CABLE TRAY, RACEWAY, EQUIPMENT, AND MATERIALS TO THE NEAREST TGB OR TMGB ALL SPACE ON WALLS AND IN RACKS/FRAMES/CABINETS IS RESERVED UNLESS OTHERWISE NOTED (INCLUDING SPACE WHICH APPEARS 'EMPTY' ON THE DRAWINGS). NO EQUIPMENT MAY BE INSTALLED IN THESE SPACES (BY ANY TRADE) WITHOUT THE ENGINEER'S PRIOR WRITTEN APPROVAL 1 SPACE RESERVED FOR FIRE ALARM / BAS FIBER PATCH PANEL 2 SPACE RESERVED FOR WIRELESS EQUIPMENT 3 SPACE RESERVED FOR ACTIVE ELECTRONICS 4 SPACE RESERVED FOR CATV EQUIPMENT 5 POWER RECEPTACLE AT 6-INCHES ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. REFERENCE ELECTRICAL DRAWINGS FOR TYPE AND CIRCUITRY 12 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 13 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 14 SPACE RESERVED FOR FUTURE EQUIPMENT 15 TERMINATES UCB BACKBONE CABLE 16 TERMINATES UTILITY BACKBONE CABLE 17 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN RIGHT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 18 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 50 WALL SPACE OBSTRUCTED BY EQUIPMENT 51 CONDUITS TO ROOF. FIRESTOP, CAP AND SEAL WATERTIGHT AT ROOF 53 CABLE RUNWAY USED TO SUPPORT CABLES TO/FROM SLEEVES. MOUNT VERTICALLY WITH CROSS-MEMBERS OUT FROM WALL DRAWING NOTES 1 TERMINATE THE OSP CONDUITS AS CLOSE TO THE BEP's AS POSSIBLE. BOND ALL METALLIC OSP CONDUITS TO THE TMGB PER THE 2008 NEC 67 61 2 1 MARK WALL "B" GENERAL NOTES DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD 13 3 10/28/2013 09/24/2013 DATE DESCRIPTION ENLARGED MDF/TR-1A WALL ELEVATIONS (B148) ET-301 ENLARGED MDF ROOM 55 INSTALL ALTERNATE SPACE CABLE RUNWAY SUCH THAT RADIUS DROPS ARE VERTICALLY ALIGNED WITH EACH VERTICAL CABLE MANAGEMENT CHANNEL 61 4-INCH CONDUIT SLEEVES FOR CABLE DISTRIBUTION TO/FROM FLOOR(S) ABOVE AND/OR BELOW. FILL ONE SLEEVE PRIOR TO FILLING NEXT SLEEVE. DO NOT MIX BACKBONE AND HORIZONTAL CABLES WITHIN THE SAME SLEEVE 63 SEE DETAIL DRAWING(S) FOR PROVISION OF CABLE PATHWAY FIRESTOP DEVICE(S) 67 OUTSIDE PLANT CONDUITS 79 20-FOOT FIBER SLACK COIL 95 WALL PHONE LOCATION 99 (2) 2-INCH CONDUITS FOR SECURITY ET-301 1.3 GENERAL NOTES A DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD B BOND ALL NON-CURRENT CARRYING METALLIC CABLE TRAY, RACEWAY, EQUIPMENT, AND MATERIALS TO THE NEAREST TGB OR TMGB C ALL SPACE ON WALLS AND IN RACKS/FRAMES/CABINETS IS RESERVED UNLESS OTHERWISE NOTED (INCLUDING SPACE WHICH APPEARS 'EMPTY' ON THE DRAWINGS). NO EQUIPMENT MAY BE INSTALLED IN THESE SPACES (BY ANY TRADE) WITHOUT THE ENGINEER'S PRIOR WRITTEN APPROVAL S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 (4) 4-INCH CONDUITS W TYP TYP ELEC RIMROCK GROUP TYP 44 43 A 42 41 2 TYP 43 A SYSTIMAX FIBER ISP 1000 G2 42 41 40 39 B ET-307 38 TYP 37 36 35 C 34 33 32 40 38 37 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 35 34 33 C HUBBELL (MCCBP350) BLANK PANEL INSERT 32 A D 3 ET-307 B 5 TYP C 28 27 E 26 25 24 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER HUBBELL (UDX48E) 48-PORT PATCH PANEL HUBBELL (MCCBP350) BLANK PANEL INSERT 23 22 21 20 19 18 17 BLANK 16 15 31 6" VERTICAL WIRE MANAGEMENT 6" VERTICAL WIRE MANAGEMENT 31 D 29 43 HUBBELL (MCCBP350) BLANK PANEL INSERT 41 30 42 40 39 38 SPACE RESERVED FOR EQUIPMENT 37 36 HUBBELL (MCCBP350) BLANK PANEL INSERT 35 SPACE RESERVED FOR EQUIPMENT 33 HUBBELL (MCCBP350) BLANK PANEL INSERT 31 29 28 27 26 25 24 23 22 21 20 19 BLANK 18 17 16 15 30 29 28 27 26 25 24 23 21 20 19 18 17 16 15 14 13 12 12 12 11 H SPACE RESERVED FOR FUTURE EQUIPMENT 10 11 11 10 10 9 I 9 I 7 6 4 HUBBELL MCCPSS19TS CPI (55053-503) 750 LB CAP 4 3 SPACE RESERVED FOR FIRE ALARM / BAS FIBER PATCH PANEL 2 SPACE RESERVED FOR WIRELESS EQUIPMENT 3 SPACE RESERVED FOR ACTIVE ELECTRONICS 4 SPACE RESERVED FOR CATV EQUIPMENT 5 POWER RECEPTACLE AT 6-INCHES ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. REFERENCE ELECTRICAL DRAWINGS FOR TYPE AND CIRCUITRY 12 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 13 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 7 6 5 SPACE RESERVED FOR FUTURE EQUIPMENT 2 1 1 8 5 J HUBBELL (P548UE) 48-PORT UTILITY CABLE 3 K SPACE RESERVED FOR FUTURE EQUIPMENT 2 1 9 HUBBELL (P5E96UE) 96-PORT PATCH PANEL VOICE BACKBONE 6 CPI 30162-703 5 J FUTURE 22 13 7 SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 32 14 8 KEY NOTES 34 13 HUBBELL (P5E96UE) 96-PORT PATCH PANEL VOICE BACKBONE PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com 44 14 8 CPI 30162-703 SPACE RESERVED FOR EQUIPMENT 36 EQUIPMENT SPACE RESERVED F0R 30 OWNER SWITCH EQUIPMENT 45 39 B 600G FIBER JACK Empowered Business - Quiet Technology R3 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 6" VERTICAL WIRE MANAGEMENT 44 R2 45 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 6" VERTICAL WIRE MANAGEMENT 45 HUBBELL MCCPSS19TS 4 CPI 30162-703 R1 TYP CPI 30162-703 T 3 2 1 CPI (55053-503) 750 LB CAP CPI (55053-503) 750 LB CAP 14 SPACE RESERVED FOR FUTURE EQUIPMENT 15 TERMINATES UCB BACKBONE CABLE 16 TERMINATES UTILITY BACKBONE CABLE 17 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN RIGHT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 18 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 50 WALL SPACE OBSTRUCTED BY EQUIPMENT 51 CONDUITS TO ROOF. FIRESTOP, CAP AND SEAL WATERTIGHT AT ROOF 53 CABLE RUNWAY USED TO SUPPORT CABLES TO/FROM SLEEVES. MOUNT VERTICALLY WITH CROSS-MEMBERS OUT FROM WALL U N 1 2 ENLARGED TR-1D (ROOM A102) ET-307 RACK ELEVATIONS TR-1D (ROOM A102) SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT ET-307 2' 1' 0 1/2" = 1'-0" 2' 55 INSTALL ALTERNATE SPACE CABLE RUNWAY SUCH THAT RADIUS DROPS ARE VERTICALLY ALIGNED WITH EACH VERTICAL CABLE MANAGEMENT CHANNEL 61 4-INCH CONDUIT SLEEVES FOR CABLE DISTRIBUTION TO/FROM FLOOR(S) ABOVE AND/OR BELOW. FILL ONE SLEEVE PRIOR TO FILLING NEXT SLEEVE. DO NOT MIX BACKBONE AND HORIZONTAL CABLES WITHIN THE SAME SLEEVE 63 SEE DETAIL DRAWING(S) FOR PROVISION OF CABLE PATHWAY FIRESTOP DEVICE(S) 67 OUTSIDE PLANT CONDUITS 79 20-FOOT FIBER SLACK COIL 95 WALL PHONE LOCATION 99 (2) 2-INCH CONDUITS FOR SECURITY 2 1 MARK 3 10/28/2013 09/24/2013 DATE DESCRIPTION WALL ELEVATIONS TR-1D (ROOM A102) ET-307 ENLARGED TELECOM ROOM ET-307 GENERAL NOTES A DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD B THE WORK DETAILED ON THIS SHEET MAY BE DEPENDENT UPON AND/OR MAY AFFECT THE WORK OF THE OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING COORDINATION ISSUES AND DEPENDENCIES BEFORE THEY ARISE. CHANGES NECESSITATED BY THE FAILURE OF THE CONTRACTOR TO COORDINATE WITH OTHER TRADES SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER TO CEILING TO CEILING THREADED ROD THREADED ROD ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EC EC 4"X4" DEVICE BOX EC EC 4" x 4" DEVICE EC EC BOX WITH 2 GANG MUD RING 1" CONDUIT HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 EC EC 1" CONDUIT WALL MOUNT EC EC SC SC EC EC Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 INSULATED THROAT BUSHING 12" MINIMUM BEND RADIUS 1 1/2" PIPE 1" CONDUIT SC SC EC EC 1" CONDUIT ACCESSIBLE CEILING FIXED DOME CAMERA 1" CONDUIT STATION CABLES EXIT CONDUIT DIRECTLY INTO CABLE TRAY. NO ADDITIONAL SUPPORT REQUIRED 6" x 6" x 4" ELECTRICAL BOX MOUNTED WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EC EC EC EC ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL 1" CONDUIT EC EC 6" x 6" x 4" ELECTRICAL BOX MOUNTED WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED S T E RN GROUNDING CONDUCTOR EC EC SC SC SC SC 1/4" FIXED DOME CAMERA EC EC SURGE PROTECTION DEVICE 1/2" CONDUIT GROUNDING CONDUCTOR SC SC RIMROCK GROUP BOND CONDUIT TO CABLE TRAY PENDANT MOUNTING BRACKET EC EC 1/2" CONDUIT Empowered Business - Quiet Technology 1" CONDUIT (MINIMUM) "TRAPEZE" TYPE SUPPORT BRACKET SC SC EC EC PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com EC EC EC EC 4" x 4" DEVICE BOX WITH 2 GANG MUD RING SC SC SURGE PROTECTION DEVICE "BASKET" TYPE CABLE TRAY SHOWN FOR ILLUSTRATION ONLY. SEE SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS FIXED DOME CAMERA SC SC CEILING LEVEL WALL WALL WALL WALL STRUCTURE EXTERIOR WALL MOUNTED CAMERA - TYPE F2 WALL MOUNTED CAMERA - TYPE F1 EXTERIOR WALL MOUNTED CAMERA - TYPE P 4" x 4" OUTLET BOX SUBSCRIPT SUBSCRIPT DEFINITION MOUNTING NOTES F1 FLUSH MOUNTED WALL -- F2 FLUSH MOUNTED EXTERIOR WALL -- P PENDANT MOUNTED EXTERIOR WALL -- EXTENSION RING MUDRING 4 ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL TYPICAL TELECOM RACEWAY AND OUTLET - DIRECT TO TRAY SCALE: NONE ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL 1 NOT USED 2 NOT USED SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT SCALE: NONE TO CEILING TO CEILING THREADED ROD THREADED ROD EC EC 4"X4" DEVICE BOX EC EC 1" CONDUIT EC EC STATION CABLES EXIT CONDUIT DIRECTLY INTO CABLE TRAY 4"X4" DEVICE BOX EC EC STRUCTURE MOUNTING BASE EC EC 1" CONDUIT EXTENSION RING WITH EC EC 2 GANG MUD RING EC EC THREADED ROD ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EXTENSION RING WITH EC EC 2 GANG MUD RING EC EC ACCESSIBLE CEILING 1" CONDUIT NON-ACCESSIBLE CEILING INSULATED THROAT BUSHING EC EC MINIMUM BEND RADIUS = 6 x INTERNAL DIAMETER POLE SC SC TO CEILING SUPPORT FIXED DOME SC SC CAMERA FIXED DOME SC SC CAMERA PENDANT MOUNTING SC SC BRACKET THREADED ROD FIXED DOME SC SC CAMERA ACCESSIBLE CEILING MOUNTED CAMERA - TYPE A NON-ACCESSIBLE CEILING MOUNTED CAMERA - TYPE N SURFACE MOUNT HOUSING "TRAPEZE" TYPE SUPPORT BRACKET CONDUIT TO CABLE TRAY (1" MIN) EXPOSED CEILING MOUNTED CAMERA - TYPE S "BASKET" TYPE CABLE TRAY SHOWN FOR ILLUSTRATION ONLY. SEE SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS DEVICE BOX CEILING GRID SCALE: NONE 4" MINIMUM CLEARANCE BETWEEN BOX AND CEILING TO DEVICE SUBSCRIPT SUBSCRIPT DEFINITION MOUNTING NOTES A FLUSH MOUNTED ACCESSIBLE CEILING -- N FLUSH MOUNTED NON-ACCESSIBLE CEILING -- S SURFACE MOUNTED EXPOSED CEILING -- SECURITY CAMERA DETAILS 7 5 SCALE: NONE WALL STRUCTURE HOLE FOR ANTENNA CEILING TILE TYPICAL PATHWAY/FIRESTOP DEVICE MOUNTING PLATE SHOWN WITH DOOR OPEN FOR CLARITY CABLE PATHWAY FIRESTOP DEVICE(S). PROVIDE DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USABLE VOLUME OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THE VOLUME OF CABLE TRAY TO BE SERVED 2 1 MARK ABOVE CEILING OUTLET/RACEWAY - DIRECT TO CABLE TRAY 3 SCALE: NONE FLEXIBLE CONDUIT TO SYSTEM FURNITURE (1 1/4" MINIMUM) (TELECOM) STUB TO CABLE TRAY PATCH CORD STUB TO CABLE TRAY 1 1/4" CONDUIT (DATA) SCALE: NONE 1 1/4" CONDUIT FOR AV TO CEILING SPACE ABOVE/BELOW WALL WALL RADIUS DROP GUIDE NOT USED 1 1/4" CONDUIT FOR AV TO CEILING SPACE ABOVE/BELOW NON-METALLIC RISER 1" CONDUIT TO CABLE TRAY DESCRIPTION 3/4" CONDUIT FOR POWER STUB TO CABLE TRAY FURNITURE FEED COVER 10/28/2013 09/24/2013 DATE WALL FLEXIBLE CONDUIT TO SYSTEM FURNITURE (1 1/4" MINIMUM) (TELECOM) 1 1/4" CONDUIT (AV) 1" CONDUIT (DATA) 3/4" CONDUIT (POWER) 1 1/4" CONDUIT (AV) ELECTRICAL TECHNOLOGY DETAILS RADIUS DROP GUIDE FLOOR BOX (SEE ENLARGED VIEW) NOTES: 1. SCREW CEILING BOX INTO CEILING GRID. REFER TO SPECIFICATIONS AND UCB STANDARDS FOR MOUNTING INSTRUCTIONS 2. ELECTRICAL TELECOM CONTRACTOR AND TELECOM CONTRACTOR SHALL COORDINATE TELECOM OUTLET PLACEMENT AND ENCLOSURE ORIENTATION WITH EACH OTHER AND OWNER PRIOR TO INSTALLATION OF WAP ENCLOSURE AND ASSOCIATED CONDUIT 3. TELECOM CONTRACTOR SHALL INSTALL CABLING, TERMINATE, TEST AND DOCUMENT PER SPECIFICATIONS 10 WIRELESS ACCESS ENCLOSURE - CEILING MOUNT SCALE: NONE CABLE TRAY FLOOR BOX (SEE ENLARGED VIEW) 1 1/4" CONDUIT TO CABLE TRAY (DATA) CABLE TRAY 1" CONDUIT FOR DATA TO CABLE TRAY FLOOR BOX ENLARGED VIEW FACING VIEW 9 TYPICAL CABLE PATHWAY FIRESTOP DEVICE FOR CABLE TRAY JUNCTION SCALE: NONE FLOOR BOX ENLARGED VIEW SIDE VIEW 8 FLOOR BOX - FLEXIBLE CONDUIT (FC) SCALE: NONE 6 FLOOR BOX - 4 GANG SCALE: NONE 2 ET-501 3/4" CONDUIT FOR DATA TO ACCESSIBLE CEILING MINIMUM BEND RADIUS = 6x INTERNAL DIAMETER INSULATED THROAT BUSHING 4 11/16" x 4 11/16" DEVICE BOX WITH 2 GANG MUD RING (AV) AUDIOVISUAL CABLES STUB CONDUIT 6-INCHES INTO ACCESSIBLE CEILING 'C' 4 11/16" x 4 11/16" OUTLET BOX WITH 1 GANG MUD RING (TELECOM) (1) 1 1/4" CONDUIT PROJECTOR POLE MOUNT TO CABLE TRAY GENERAL NOTES 4 11/16" x 4 11/16" DEVICE BOX WITH 2 GANG MUD RING (AV) 4 11/16" x 4 11/16" OUTLET BOX WITH 1 GANG MUD RING (TELECOM) (1) 1 1/4" CONDUIT PROJECTOR POLE MOUNT TO CABLE TRAY FRONT (1) 1" CONDUIT CEILING LEVEL 1 1/4" CONDUIT FOR AV TO ACCESSIBLE CEILING A DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD B THE WORK DETAILED ON THIS SHEET MAY BE DEPENDENT UPON AND/OR MAY AFFECT THE WORK OF THE OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING COORDINATION ISSUES AND DEPENDENCIES BEFORE THEY ARISE. CHANGES NECESSITATED BY THE FAILURE OF THE CONTRACTOR TO COORDINATE WITH OTHER TRADES SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER FRONT S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 (1) 1" CONDUIT DUPLEX POWER OUTLET DUPLEX POWER OUTLET Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 WALL STRUCTURE 1/2" CONDUIT FOR POWER ELECTRICAL CONDUIT ELECTRICAL CONDUIT TOP VIEW 'A' DEVICE TOP VIEW ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR PROJECTORS. COORDINATE WITH AV CONTRACTOR FOR LOCATION ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR PROJECTORS. COORDINATE WITH AV CONTRACTOR FOR LOCATION 3' 1. 1 3' ATTACH TO STRUCTURE EXTENSION RING NOTES: ATTACH TO STRUCTURE ATTACH TO STRUCTURE RECONFIGURE BASED ON SPECIFIC LOCATION REQUIREMENTS RIMROCK GROUP 1 1/4" CONDUIT FOR AV TO DEVICE BOX Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com TYPICAL WALL BOX DETAIL SCALE: NONE ATTACH TO STRUCTURE THREADED ROD THREADED ROD UNISTRUT UNISTRUT 'B' ELECTRICAL CONTRACTOR TO PROVIDE 2' x 3' UNISTRUT RECTANGLE CONDUITS SUBSCRIPT A B C DEFAULT 4 11/16" x 4 11/16" 2 GANG (2) 1 1/4" W1x 4 11/16" x 4 11/16" 1 GANG (1) 1 1/4" W2x 4 11/16" x 4 11/16" 2 GANG (2) 1 1/4" W3x 3 GANG -- (3) 1" W4x 4 GANG -- (4) 1" W6x 6 GANG -- (6) 1" ELECTRICAL CONTRACTOR TO PROVIDE 2' x 3' UNISTRUT RECTANGLE CONDUITS DEVICE BOXES DEVICE BOXES NON ACCESSIBLE CEILING ACCESSIBLE CEILING TO DECK POLE POLE NOTES: 1. 8 WORKING CLEARANCE FOR FACEPLATE DETAILS, REFERENCE: 1/T-505 PROJECTOR MOUNT TYPICAL AUDIOVISUAL RACEWAY AND OUTLET TO DECK 12" THREADED ROD (TYPICAL) PROJECTOR MOUNT SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT WORKING 12" CLEARANCE CABLE TRAY H SCALE: NONE 6" W TRAPEZE HANGER (TYPICAL) TOP OF CEILING OR EQUIPMENT FRONT VIEW FRONT VIEW NOTES: "BASKET" TYPE CABLE TRAY SHOWN IS FOR ILLUSTRATION ONLY. REFER TO SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS 9 NOT USED 6 SCALE: NONE WIDTH (W) OF CABLE WILL VARY. REFER TO DRAWINGS FOR SPECIFIC WIDTHS. PROVIDE TRAPEZE HANGERS IN WIDTHS TO FIT THE APPLICATION NOTES: NOTES: 1. COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR FOR PROJECTOR PLACEMENT PRIOR TO INSTALLING PROJECTOR STRUCTURAL SUPPORT 1. 2. COORDINATE PROJECTOR THROW WITH OWNER PRIOR TO INSTALLATION 2. COORDINATE PROJECTOR THROW WITH OWNER PRIOR TO INSTALLATION 3. ELECTRICAL CONTRACTOR SHALL ROUTE FLEX CONDUIT FROM PROJECTOR TO JUNCTION BOX LOCATED ABOVE STRUCTURAL SUPPORT. USE RIGID CONDUIT FOR ALL OTHER PROJECTOR CONDUIT REQUIREMENTS 3. ELECTRICAL CONTRACTOR SHALL ROUTE FLEX CONDUIT FROM PROJECTOR TO JUNCTION BOX LOCATED ABOVE STRUCTURAL SUPPORT. USE RIGID CONDUIT FOR ALL OTHER PROJECTOR CONDUIT REQUIREMENTS 4. MOUNT PROJECTOR IN SUCH A WAY AS NOT TO BE OBSTRUCTED BY LIGHT FIXTURES, SPRINKLER HEADS, ETC. 4. MOUNT PROJECTOR IN SUCH A WAY AS NOT TO BE OBSTRUCTED BY LIGHT FIXTURES, SPRINKLER HEADS, ETC. PROJECTOR MOUNT DETAIL - NON ACCESSIBLE CEILING 4 SCALE: NONE COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR FOR PROJECTOR PLACEMENT PRIOR TO INSTALLING PROJECTOR STRUCTURAL SUPPORT HEIGHT (H) OF CABLE TRAY IS CALLED OUT IN THE SPECIFICATIONS PROVIDE CABLE TRAY COMPLETE WITH ALL MATERIALS AND INCIDENTAL HARDWARE NECESSARY FOR A COMPLETE AND FULLY FUNCTIONAL CABLE TRAY SYSTEM, INCLUDING BUT NOT LIMITED TO STRAIGHT SECTIONS, T-JUNCTIONS AND RADIUS (ROUNDED) CORNERS CONFORMING TO TIA/EIA 569 BEND RADIUS REQUIREMENTS, EXPANSION JOINTS, SUPPORT HANGERS, CONNECTOR AND CLAMP ASSEMBLIES, CONNECTOR AND SPLICE PLATES, ETC. INSTALL IN ACCORDANCE WITH NEMA VE 2 (LATEST EDITION), TIA/EIA 569, AND MANUFACTURERS RECOMMENDATION AND INSTRUCTIONS PROJECTOR MOUNT DETAIL - ACCESSIBLE CEILING 2 SCALE: NONE TO ACCESSIBLE CEILING SPACE POWER CABLE TRAY - SINGLE TIER SCALE: NONE WOOD STUDS FINISHED CEILING (1) 3/4" CONDUIT FOR DATA ROUTE CONDUITS FOR DATA AND AV TO CABLE TRAY OR J-HOOK PATHWAY ABOVE ACCESSIBLE CEILING TO WALL 1 1/4" C (AV) TO WALL 2 1 MARK 1 ET-503 FLAT PANEL DISPLAY WALL MOUNT CL DESCRIPTION VARIES 6 GANG 1 1/4" C (AV) 10/28/2013 09/24/2013 DATE FLAT PANEL DISPLAY TO WALL 1 1/4" C (AV) WALL (2) 1 1/4" CONDUITS FOR AV FLAT PANEL DISPLAY WALL BOX ROUTE CONDUIT FOR POWER PER ELECTRICAL DRAWINGS WALL CL HORIZONTAL TEE 10" LONG RADIUS BEND 3 GANG # 1 GANG VARIES 1 GANG NOT USED (2) 1 1/4" CONDUITS SCALE: NONE FLOOR BOX (SEE ENLARGED VIEW) TO WALL TO WALL 1 1/4" C (AV) (2) 1 1/4" CONDUITS 3/4" C (POWER) 8" 50" AFF 1" C (DATA) CONCRETE FLOOR 4 11/16" X 4 11/16" BOX WITH 1 GANG MUD RING FLUSH MOUNTED INTO WALL 16" OC 36" AFF TO WALL T.B.D. 4 11/16" X 4 11/16" BOX WITH 2 GANG MUD RING FLUSH MOUNTED INTO WALL POWER OUTLET FLUSH MOUNTED INTO WALL FLOOR BOX ENLARGED VIEW FINISHED FLOOR HORIZONTAL CROSS NOTES: NOTES: 1. 2. 3. # NOT USED SCALE: NONE 7 MAINTAIN CONDUIT SEPARATION AS REQUIRED BY STRUCTURAL ENGIINEER. COORDINATE CONDUIT REQUIREMENT WITH STRUCTURAL ENGINEER/ARCHITECT PRIOR TO INSTALLATION PREFERRED FLOOR BOX AND CONDUIT INSTALLATION IS AS SHOWN. IF FIELD CONDITIONS DICTATE ALTERNATE INSTALLATION, CONDUITS CAN BE ROUTED FROM BOTTOM OF FLOOR BOX AND STUBBED INTO ACCESSIBLE CEILING SPACE BELOW. PATHWAY MUST BE PROVIDED WITHIN INTERSTITIAL WALL SPACE IN QUANTITIES SHOWN AND ROUTED INTO ACCESSIBLE CEILING SPACE ABOVE ROOM SERVICED BY FLOOR BOX. IF FIELD CONDITIONS DO NOT ALLOW FOR ALTERNATE INSTALLATION METHOD, THEN ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ENGINEER PRIOR TO INSTALLATION SCALE: NONE CEILING HEIGHTS MAY VARY. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS 2. WOOD STUDS LOCATED WITHIN INTERSTITIAL WALL SPACE. CENTER WOOD STUDS ON DISPLAY LOCATION. WOOD STUDS SHALL BE IN ADDITION TO OTHER WALL STRUCTURES AND/OR CONSTRUCTION METHODS NOTES: 3. MOUNTING HEIGHT OF DISPLAYS MAY VARY. REFER TO PLAN DRAWINGS FOR MOUNTING HEIGHTS 1. "BASKET" TYPE CABLE TRAY SHOWN IS FOR ILLUSTRATION ONLY. REFER TO SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS 4. DEVICE BOX AND CONDUIT LOCATIONS MAY VARY DUE TO FIELD CONDITIONS 2. ALL BENDS SHALL BE LONG RADIUS. 90-DEGREE OR ABRUPT BENDS ARE NOT ACCEPTABLE 3. ELECTRICAL GROUNDING AND BONDING: ALL CONNECTION HARDWARE SHALL BE CHECKED TO ENSURE THAT THEY ARE TIGHTENED AND THAT ALL CABLE TRAY SECTIONS ARE ELECTRICALLY CONTINUOUS AND/OR ELECTRICALLY GROUNDED TO ADJACENT TRAY SECTIONS AND BUILDING EARTH GROUND IN ACCORDANCE WITH GOVERNING REQUIREMENTS DRAWING NOTES: 1. ALL FLOOR BOX INSTALLS THAT PENETRATE ENTIRELY THROUGH THE FLOOR STRUCTURE SHALL HAVE FIRE TREATMENT TO MEET OR EXCEED FIRE RATING OF FLOOR STRUCTURE FLOOR BOX - 11 GANG 1. 5 CENTER LINE IS DENOTED FOR DEVICE BOXES AND NOT VIDEO DISPLAY MOUNT. CONTRACTOR SHALL LOCATE MOUNT AS REQUIRED TO PROVIDE BOTTOM OF SCREEN HEIGHT TYPICAL SMALL CONFERENCE ROOM DISPLAY WALL MOUNT DETAIL SCALE: NONE 3 ELECTRICAL TECHNOLOGY DETAILS CABLE TRAY BENDS AND JUNCTIONS SCALE: NONE 2 ET-503 ABBREVIATIONS SYMBOL SCHEDULE ELECTRICAL TECHNOLOGY SYSTEM NOTATION TELECOMMUNICATION SYSTEM NOTATION SYMBOL SYMBOL DESCRIPTION TELECOM OUTLET SUBSCRIPT -+XY" AC BC DP FB SR W WAP SUBSCRIPT DESCRIPTION -NON-STANDARD HEIGHT ABOVE COUNTER BELOW COUNTER DISPLAY PANEL FLOOR BOX SURFACE RACEWAY WALL TELEPHONE WIRELESS ACCESS POINT MOUNTING DETAILS NOTES FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/COUNTER FLUSH/WALL FLOOR BOX WALL FLUSH/WALL WALL 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 1/T-501 LAB DWGS 4/ET-501, 4/T-501 -- 8 8 8 8 8 8 -7 1 SYMBOL SYMBOL DESCRIPTION UP TELECOM OUTLET (CEILING) -P WAP -PROJECTOR INTERFACE WIRELESS ACCESS POINT TELECOM OUTLET - VOICE/DATA (FIELD COORDINATED) -AV B ELEC ELV EMR F FACP M SEC -AUDIOVISUAL BUILDING AUTOMATION ELECTRICAL ELEVATOR EMERGENCY PHONE FURNITURE FIRE ALARM CONTROL MECHANICAL/HVAC SECURITY TELECOM OUTLET - VOICE/DATA (FIELD COORDINATED) (CEILING) TELECOM OUTLET - AV SIGNAL -AV S -AUDIOVISUAL SECURITY -+XY" AC FB -NON-STANDARD HEIGHT ABOVE COUNTER FLOOR BOX SUBSCRIPT J -- -- WALL 5/ET-502, 5/T-502, 1/ET-503, 1/T-503 -- PLENUM BOX -- -- CEILING -- -- UTILITY POLE -- -- -- -- -- PULL BOX -- -- -- -- 16 CABLE PATHWAY FIRESTOP DEVICE -- -- WALL 9/ET-501, 9/T-501 6,10 8-INCH TRAY 12-INCH TRAY 18-INCH TRAY 24-INCH TRAY ABOVE CEILING BELOW FLOOR LOWER TIER UPPER TIER --------- 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 2/ET-503, 3/ET-503, 2/T-503, 3/T-503 3/ET-503, 3/T-503 3/ET-503, 3/T-503 3/ET-503, 3/T-503 11 11 11 11 11 11 11 11 FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/WALL FLUSH/WALL -FURNITURE FLUSH/WALL FLUSH/WALL FLUSH/WALL 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 4/ET-501, 4/T-501, 1/T-501 --3/T-501, 1/T-501 4/ET-501, 4/T-501 4/ET-501, 4/T-501, 1/T-501 -- 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 CEILING ABOVE CEILING LADDER RACK 5/ET-501, 5/T-501 5/ET-501, 5/T-501 -- 1 1 1 BUSHED CONDUIT -- -- -- -- -- BUSHED CONDUIT SLEEVE -- -- -- -- -- FLUSH/WALL FLUSH/WALL FLUSH/WALL FLOOR BOX ----- ----- CAPPED CONDUIT OR DUCT -- -- -- -- -- CONDUIT UP -- -- -- -- -- CONDUIT DOWN -- -- -- -- -- GROUND CONNECTION -- -- -- -- -- 4/ET-501 3/T-501, 2/ET-502, 2/T-502, -1 P FSD 8 12 18 24 AC BF LT UT CABLE TRAY # AA -- -- CEILING -- -- CATV OUTLET -- -- -- 4/ET-501, 4/T-501 1 CABLE RUNWAY -- -- -- 3/T-502, 4/T-502 -- CABLING UP -- -- -- -- -- CONDUIT UNDERFLOOR OR UNDERSLAB -- -- -- -- -- CABLING DOWN -- -- -- -- -- CONDUIT UNDERGROUND -- -- -- -- -- SURFACE RACEWAY -- -- -- -- -- J-HOOK PATHWAY -- -- -- -- -- CABLE TERMINUS -- -- -- -- -- CABLE LOOP -- -- -- -- -- GROUND CONNECTION -- -- -- -- -- MOUNTING DETAILS NOTES CEILING CEILING --- 1 1 -FC SYMBOL DESCRIPTION SUBSCRIPT SUBSCRIPT DESCRIPTION MOUNTING DETAILS NOTES SYMBOL S SEE DETAILS -- DOOR 1/ET-504, 1/T-504 -- WALL -- -- VS VIDEO SURVEILLANCE SYSTEM - HEAD END -- -- WALL -- -- PROXIMITY READER FIXED SECURITY CAMERA (CEILING) -M MAG SEE DETAILS -MULLION MOUNTED MEGNETIC READER WALL MULLION WALL --- --- -- CEILING 7/ET-501, 7/T-501 -- SEE DETAILS -- WALL 7/ET-501, 7/T-501 -- PTZ SECURITY CAMERA (ROOF) -- -- CEILING 7/ET-501, 7/T-501 -- PTZ SECURITY CAMERA -- -- WALL 7/ET-501, 7/T-501 -- EXIT BUTTON -- -- WALL -- -- FIXED SECURITY CAMERA (WALL) SYMBOL DESCRIPTION S SUBSCRIPT KEY SWITCH -- -- FLUSH/WALL FLUSH/WALL WALL -- SUBSCRIPT DESCRIPTION LOUDSPEAKER (CEILING) A B ACCESSIBLE CEILING NON ACCESSIBLE CEILING LOUDSPEAKER (WALL) -- -- WALL 3/ET-505, 3/T-505 1 EQUIPMENT RACK (FLOOR) A B C FLOOR RACK - TYPE A FLOOR RACK - TYPE B FLOOR RACK - TYPE C FLOOR FLOOR FLOOR 2/T-505 2/T-505 -- 1 1 1 EQUIPMENT RACK (WALL) -- -- WALL 10/ET-502, 10/T-502, 1/T-502 1 VIDEO DISPLAY (WALL) A B C D 42-INCH 52-INCH 65-INCH DIGITAL SIGNAGE PROJECTION SCREEN (CEILING) A B C D E F G H J 84" x 84" MANUAL 96" x 96" MANUAL 108" x 108" MANUAL 90" x 144" ELECTRIC 135" x 216" ELECTRIC 75" x 120" ELECTRIC 69" x 110" ELECTRIC 70" x 70" MANUAL 87" x 139" ELECTRIC ABBREV. DEFINITION ABBREV. DEFINITION AC ACP ACS AO AOC AFF AHJ APC APPROX AR ARCH AV AVSC AWG BB BC BEP BI BLDG BO C CAB CAN CAT3 CAT5E CAT6 CAT6A CATV CC CER CO COAX COM CPV CR CT CV (D) DB DD DIA DVI DPDT DPS DNS DWG (E) ECL ECP EEB EF EL ELEC ELM ELR EMT ENCL EQPMT ER ES ESC ESO FACP FB FSD FLEX FUT G HB HC HDMI HO ID IDS IG IMC IP IR ISP LL ABOVE COUNTER ACCESS CONTROL PANEL ACCESS CONTROL SYSTEM AUTOMATIC OPERATOR AUTO OPENER CONTROLLER ABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTION ANGLE POLISHED CONNECTOR APPROXIMATELY AUXILIARY RELAY ARCHITECTURAL AUDIOVISUAL AUDIOVISUAL SYSTEMS CONTRACTOR AMERICAN WIRE GAUGE BACKBONE BELOW COUNTER BUILDING ENTRANCE PROTECTOR BIOMETRIC INTERFACE BUILDING BY OTHERS CONDUIT CABINET CONTROLLED AREA NETWORK CATEGORY 3 COPPER CABLE CATEGORY 5E COPPER CABLE CATEGORY 6 COPPER CABLE CATEGORY 6 AUGMENTED COPPER CABLE CABLE TELEVISION CONTACT CLOSURE CYLINDER ELECTRIC RETRACTION CONDUIT ONLY (NO CABLE) COAXIAL CABLE COMMON COMPONENT VIDEO CARD READER COUNT COMPOSITE VIDEO DEMOLISH DATA-GRADE COPPER BACKBONE DEAD DIAMETER DIGITAL VIDEO INTERFACE DOUBLE POLE, DOUBLE THROW DOOR POSITION SWITCH DATA NETWORK SWITCH DRAWING EXISTING ELECTRIC CYLINDER LOCK ELEVATOR CONTROL PANEL EMERGENCY EXIT BUTTON ENTRANCE FACILITY ELECTRIC LATCH ELECTRICAL ELECTRIC LATCH WITH LATCH MONITOR SWITCH ELECTRIC LATCH RETRACTION ELECTRICAL METALLIC TUBING ENCLOSURE (SPLICE) EQUIPMENT EQUIPMENT ROOM ELECTRIC STRIKE ELECTRICAL SYSTEMS CONTRACTOR ELECTRIC SOLENOID FIRE ALARM CONTROL PANEL FIBER BACKBONE FIRE STOP DEVICE FLEXIBLE FUTURE GROUND HANDICAP BUTTON HORIZONTAL CABLE HIGH DEFINITION MEDIA INTERFACE HOLD OPEN INSIDE DIAMETER INTRUSION DETECTION SYSTEM ISOLATED GROUND INTERMEDIATE METAL CONDUIT INTERNET PROTOCOL INFRARED INSIDE PLANT LINE LEVEL LEFT CHANNEL AUDIO LM LR LPS MAG MECH MFR MIC MIN ML MM MS (NL) NTS NVR OB OC OD OFCI OFOI OHM OPE OS OSP P PDS PEL PER PML PMR PP PR PREX PS (R) (RL) R REV REX RF RGB RI RM RMC RNC S SC SCHED SCNS SCPP SCPS SH SM SMR SN SP SPEC SPKR SPR SR SRV SSC STP SV TB TBB TBD TGB TMGB TR TSC TYP UG UON UPS USB V VLAN VB W WAP LINE LEVEL MONO AUDIO LINE LEVEL RIGHT CHANNEL AUDIO LOCK POWER SUPPLY. MAGNETIC LOCK MECHANICAL MANUFACTURER MICROPHONE LEVEL AUDIO MINIMUM MONITORED LATCH MULTIMODE FIBER OPTIC CABLE MONITORED STRIKE NEW LOCATION NOT TO SCALE NETWORK VIDEO RECORDER OVERRIDE BUTTON ON CENTER OUTSIDE DIAMETER OWNER FURNISHED, CONTRACTOR INSTALLED OWNER FURNISHED, OWNER INSTALLED RESISTIVE NETWORK OWNER PROVIDED EQUIPMENT OVERIDE SWITCH OUTSIDE PLANT PROJECTOR PROTECTIVE DISTRIBUTION SYSTEM PANIC DEVICE ELECTRIC LATCH PANIC DEVICE ELECTRIC ROD PANIC DEVICE MONITORED LATCH PANIC DEVICE MONITORED ROD PATCH PANEL(S) PAIR PANIC DEVICE REQUEST TO EXIT SWITCH POWER SUPPLY REMOVE REMOVE AND RELOCATE RISER REVISION REQUEST TO EXIT SWITCH RADIO FREQUENCY HIGH RESOLUTION VIDEO READER INTERFACE ROOM RIGID METALLIC CONDUIT RIGID NONMETALLIC CONDUIT STATION SECURITY CAMERA SCHEDULE SECURITY CAMERA NETWORK SWITCH SECURITY CAMERA PATCH PANEL SECURITY CAMERA POWER SUPPLY SURFACE HOUSING SINGLEMODE FIBER OPTIC CABLE SURFACE METAL RACEWAY SERIAL NETWORK MODULE SURGE PROTECTOR SPECIFICATION LOUDSPEAKER LEVEL AUDIO SURFACE PLASTIC RACEWAY SURFACE RACEWAY SERVER ROOM SECURITY SYSTEMS CONTRACTOR SHIELDED TWISTED PAIR CABLE S-VIDEO TERMINATION BLOCK(S) TELECOM BONDING BACKBONE TO BE DETERMINED TELECOM GROUNDING BUSBAR TELECOM MAIN GROUNDING BUSBAR TELECOMMUNICATIONS ROOM (IDF, FD) TELECOMMUNICATION SYSTEMS CONTRACTOR TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY UNIVERSAL SERIAL BUS VOICE VIRTUAL LOCAL AREA NETWORK VOICE-GRADE COPPER BACKBONE WALL MOUNTED WIRELESS ACCESS POINT WALL WALL WALL WALL 5/ET-503, 5/T-503 5/ET-503, 5/T-503 1/ET-505, 1/T-505 5/ET-502, 5/T-502 1 1 1 1,17 CEILING CEILING CEILING CEILING CEILING CEILING CEILING CEILING CEILING 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 11/ET-502, 11/T-502 1 1 1 1 1 1 1 1 1 T-001 T-002 T-004 T-005 T-006 T-101AW-A3 T-101B-A3 T-301 T-307 T-401 T-404 T-501 T-503 TITLE INTERFACE PLATE (WALL) FB1X FB6X W1X W2X W3X W4X 1 GANG TYPE X 6 GANG TYPE X 1 GANG TYPE X 2 GANG TYPE X 3 GANG TYPE X 4 GANG TYPE X FLOOR BOX FLOOR BOX WALL WALL WALL WALL 1/T-506 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 8/ET-503, 8/T-503, 1/T-506 TECHNOLOGY - TITLE SHEET TECHNOLOGY SCHEDULES TECHNOLOGY - RISER DIAGRAMS TECHNOLOGY - RISER DIAGRAMS TECHNOLOGY - RISER DIAGRAMS TECHNOLOGY PLAN - FIRST FLOOR - AREA AW TECHNOLOGY PLAN - FIRST FLOOR - AREA B ENLARGED MDF ROOM ENLARGED TELECOM ROOM AUDIOVISUAL - ONE-LINE DIAGRAMS AUDIOVISUAL - ONE-LINE DIAGRAM TECHNOLOGY - DETAILS TECHNOLOGY - DETAILS 2 1 1 1 1 1 1 X INTERFACE PLATE (CEILING) 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 1/T-506 1 TYPE A TYPE B CEILING CEILING 4/ET-503, 4/T-503 6/ET-503, 6/T-503 1 1 CONTROL PANEL (WALL) A B C D TYPE A TYPE B TYPE C TYPE D WALL WALL WALL DESK 12/T-502 7/ET-502, 7/T-502, 9/T-503 7/ET-502, 7/T-502 -- 1 1 1 1 ANTENNA (WALL) A B ASSISTED LISTENING MICROPHONE WALL WALL --- 1 1 A FIXED AUDIOVISUAL CAMERA (CEILING) -- DOCUMENT CAMERA CEILING -- 1 A PTZ AUDIOVISUAL CAMERA (WALL) -- -- WALL 8/ET-502, 8/T-502 1 SCREEN SWITCH -- -- WALL -- 1,9 SMART LECTERN -- -- FLOOR -- -- CEILING MICROPHONE -- -- CEILING -- -- NOTES 2. CEILING A B M COORDINATION IS REQUIRED PRIOR TO ROUGH-IN. LOCATION SHOWN MAY NOT REPRESENT THE FINAL LOCATION NECESSITATED BY FIELD CONDITIONS. FURTHERMORE, NON-TYPICAL REQUIREMENTS FOR ROUGH-IN BOXES, MOUNTING, SUPPORT, FACEPLATES AND/OR INTERFACES MAY BE NECESSARY. COORDINATE LOCATIONS AND REQUIREMENTS WITH RESPECTIVE TRADE(S), SHOP DRAWINGS, ARCHITECTURAL ELEVATIONS AND/OR OWNER PRIOR TO ROUGH-IN. PROVIDE AS REQUIRED FLOOR BOX LOCATIONS SHOWN ARE APPROXIMATE. PRIOR TO ROUGH-IN COORDINATE FINAL LOCATION WITH ARCHITECTURAL, STRUCTURAL, FURNITURE, AND OWNER REQUIREMENTS, AND WITH ALL OTHER TRADES WHICH WILL MAKE USE OF THE FLOOR BOX ELECTRICAL CONTRACTOR TO ROUTE CONDUIT TO ACCESSIBLE CEILING SPACE IN SAME ROOM SERVED BY THE DEVICE BOX AV CONTRACTOR TO ROUTE CABLE WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR MOUNTING ELECTRICAL CONTRACTOR TO PROVIDE CABLE PATHWAY FIRESTOP DEVICES FOR CABLE TRAY PASS-THRUS. ALL OTHER TRADES TO PROVIDE CABLE PATHWAY FIRESTOP DEVICES FOR THEIR RESPECTIVE CABLES PASSING THROUGH FIRE RATED BARRIERS ELECTRICAL CONTRACTOR TO MOUNT AT ADA COMPLIANT HEIGHT FOR WALL MOUNT TELEPHONES. TELECOM CONTRACTOR TO PROVIDE WALL MOUNT FACEPLATE WITH TELEPHONE MOUNTING STUDS PROVIDE CABLE QUANTITIES AND TYPES PER THE STATION CALLOUT ON THE T-SERIES TITLE SHEET MOUNT AT STANDARD SWITCH HEIGHT ABOVE FINISHED FLOOR FOR EACH CABLE PATHWAY FIRESTOP LOCATION SHOWN FEEDING CABLE TRAY, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE VOLUME OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THE VOLUME OF CABLE TRAY TO BE SERVED. FOR ALL OTHER FIRESTOP LOCATIONS, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE VOLUME OF THE DEVICE(S) IS GREATER THAN THE VOLUME OF ALL CABLES TO PASS THROUGH THE DEVICES, PLUS THE ADDITIONAL AMOUNT (PERCENTAGE) REQUIRED BY THE SPECIFICATIONS FOR FUTURE EXPANSION PROVIDE CABLE TRAY COMPLETE WITH ALL MATERIALS AND INCIDENTAL HARDWARE NECESSARY FOR A COMPLETE AND FULLY FUNCTIONAL CABLE TRAY SYSTEM, INCLUDING BUT NOT LIMITED TO STRAIGHT SECTIONS, T-JUNCTIONS AND RADIUS (ROUNDED) CORNERS CONFORMING TO TIA/EIA 569 BEND RADIUS REQUIREMENTS, EXPANSION JOINTS, SUPPORT HANGERS, CONNECTOR AND CLAMP ASSEMBLIES, CONNECTOR AND SPLICE PLATES, ETC. INSTALL IN ACCORDANCE WITH NEMA VE 2 (LATEST EDITION), TIA/EIA 569, AND MANUFACTURERS RECOMMENDATION AND INSTRUCTIONS. GROUND AND BOND PER NEC, MANUFACTURER REQUIREMENTS, AND TIA/EIA STANDARDS NOTUSED ELECTRICAL CONTRACTOR TO MOUNT AT ADA COMPLIANT HEIGHT ROUGH-IN PROVIDED BY ELECTRICAL CONTRACTOR, CABLING PROVIDED BY TELECOM CONTRACTOR, CAMERA AND HOUSING PROVIDED BY OWNER TERMINATE CABLE IN SURFACE MOUNT BISCUIT WITHIN RACO DEVICE BOX REFER TO SIZING CHART IN SPECIFICATIONS. SECTION 270533 PART 2.5 SYSTEMS LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED (OFOI) 1 GANG TYPE X PROJECTOR CP 1. C1X SYMBOL - DRAWING ANNOTATION SYMBOL KEY NOTE # DRAWING NOTE # EQUIPMENT SCHEDULE NUMBER # REVISION NUMBER * REFERENCE TAG * REFERENCE LETTER # REFERENCE DRAWING NUMBER * # D # C ELECTRICAL CONTRACTOR SHALL PROVIDE PRIMARY RACEWAYS/PATHWAYS. RACEWAYS/PATHWAYS CONSIDERED TO BE PRIMARY ARE AS SHOWN ON THE ET-SERIES DRAWINGS D WORK REQUIRING UTILITY AND/OR COMMUNICATIONS OUTAGES SHALL BE COORDINATED WITH THE OWNER IN ADVANCE AND MUST BE PRE-APPROVED IN WRITING S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 RIMROCK GROUP Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT Y ENTITY EC ELECTRICAL CONTRACTOR TC TELECOM CONTRACTOR AC AUDIOVISUAL CONTRACTOR SC SECURITY CONTRACTOR GC GENERAL CONTRACTOR LC LOW VOLTAGE/SPECIALTY CONTRACTOR BO BY OTHERS OWNER 2 1 MARK 10/28/2013 09/24/2013 DATE DESCRIPTION (#) NUMBER OF CAT5E VOICE PORTS/CABLES (#) NUMBER CAT5E DATA PORTS/CABLES (#) NUMBER OF COAX CATV PORTS/CABLES XYZ - ## (#) OUTLET NUMBER EXAMPLES 110-01 1 VOICE, 1 DATA, 0 COAX, OUTLET #01 EQUIPMENT SCHEDULE A * C USAGE SECTION OR ELEVATION TAG * SECTION OR ELEVATION LETTER # REFERENCE DRAWING NUMBER # DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD STATION CALLOUTS DESCRIPTION # B ENTITY RESPONSIBLE FOR INSTALLING ENTITY RESPONSIBLE FOR FURNISHING O IF WORK SHALL COMPLY WITH THE GOVERNING REQUIREMENTS LISTED IN THE SPECIFICATIONS SYMBOL -IF A FURNISH | INSTALL CALLOUT SCHEDULE SHEET LIST SHEET# 2 KS EMPTY FLEXIBLE CONDUIT AUDIOVISUAL SYSTEM NOTATION -- S 1,2 1,2 1,2 8 1 1 -- S 7/ET-503, 7/T-503 6/ET-501, 6/T-501 8/ET-501, 8/T-501 5/ET-501, 5/T-501 -10/ET-501, 10/T-501 ACCESS CONTROL SYSTEM - HEAD END S FLOOR FLOOR FLOOR WALL BOX 11-GANG 4-GANG FLEXIBLE CONDUIT CEILING CEILING -- AS S NOTES TELECOM OUTLET - AV SIGNAL (CEILING) ACCESS CONTROLLED DOOR X DETAILS 11 4 FC SECURITY SYSTEM NOTATION SYMBOL MOUNTING FLOOR BOX DEVICE BOX SR SUBSCRIPT DESCRIPTION PROJECT NOTES B ROOM WALL ELEVATION BUBBLE REFERENCE NUMBER * # REFERENCE DRAWING NUMBER WALL ELEVATION REFERENCE CONTINUATION LINE 020-27 0 VOICE, 2 DATA, 0 COAX, OUTLET #27 100-34 1 VOICE, 0 DATA, 0 COAX, OUTLET #34 TELECOM AREA BOUNDARY LINE 001-47 0 VOICE, 0 DATA, 1 COAX, OUTLET #47 ID CR200 CR201 CR210 CR220 CR231 CR232 CR307 CR341 CR400 CR435 CR515 CR520 CR530 CR600 EE102 EE105 EE110 FS100 TE045 TE046 TE048 TE225 TE348 TE372 TE566 TE600 GB010 GB020 DESCRIPTION CABLE RUNWAY STRAIGHT SECTION - GRAY (STANDARD RUNG SPACING) CABLE RUNWAY STRAIGHT SECTION (ALTERNATE RUNG SPACING) CORNER BRACKET RADIUS DROP ELEVATION KIT RACK-TO-RUNWAY MOUNTING PLATE EQUIPMENT RACK (7' 2-POST) WITH INSTALLATION KIT SERVER CABINET (750mm) HORIZONTAL POWER STRIP BLANK PANEL INSERT CABINET CABLE TROUGH (750MM CABINET) VERTICAL MANAGEMENT SECTION (DOUBLE-SIDED, WIDE) INTERBAY PATCH CORD ORGANIZER BACKBOARD L5-20 RECEPTACLE L21-20 RECEPTACLE CS8365 RECEPTACLE CABLE PATHWAY FIRESTOPPING DEVICE VOICE CABLE COPPER PATCH PANEL - CAT 5E (96 PORT, 4U) UTILITY COPPER PATCH PANEL - CAT 5E (48 PORT, 2U) HORIZONTAL COPPER PATCH PANEL - CAT 5E (48 PORT, 2U) DATA GRADE COPPER PATCH PANEL - CAT 6 (48 PORT, 2U) RACK MOUNT FIBER PATCH PANEL (48/96 PORT, 2U) RACK MOUNT FIBER PATCH PANEL (72/144 PORT, 4U) TERMINATION BLOCK - 66-STYLE BUILDING ENTRANCE PROTECTOR TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) 2 TECHNOLOGY TITLE SHEET T-001 2 TECHNOLOGY - AUDIOVISUAL EQUIPMENT SCHEDULE DESCRIPTION MANUFACTURER PART NUMBER A11120 GOOSENECK MICROPHONE SHURE MX418/C A11235 WIRELESS LAVALIER MICROPHONE SHURE WL93 A11235.1 WIRELESS LAVALIER MICROPHONE TRANSMITTER SHURE ULX1 ULX54 ID TYPE A11265 WIRELESS MICROPHONE RECEIVER SHURE WIRELESS MICROPHONE RECEIVER ANTENNA SHURE As Required A11245 WIRELESS LAV MIC SYSTEM SHURE ULXS 14/85 A13340 DIGITAL SIGNAL PROCESSOR BIAMP AUDIAFLEX CM A13340.1 DIGITAL SIGNAL PROCESSOR INPUT MODULE BIAMP IP-2 A13340.2 DIGITAL SIGNAL PROCESSOR OUTPUT MODULE BIAMP OP2e A13340.3 DIGITAL SIGNAL PROCESSOR ECHO MODULE BIAMP AEC-2HD A14610 AUDIO AMPLIFIER CROWN CTS 4200 A11299.2 B A14330 SPECIAL RQMTS S T E RN AUDIO AMPLIFIER EXTRON XPA 2001-70V A15130 A CEILING SPEAKERTILE ARMSTRONG A-50 Accessible Ceiling A15150 B CEILING LOUDSPEAKER ATLAS SOUND FAP82T Non-Accessible Ceiling A15120 CEILING LOUDSPEAKER ATLAS SOUND FAP62T A15150.1 CEILING LOUDSPEAKER TRIM RING ATLAS SOUND FAPxx-TR A15481 70V LINE ARRAY COLUMN SPEAKER SYSTEM JBL CBT 70J-1 + 70JE-1 System A16110 ASSISTED LISTENING TRANSMITTER LISTEN LT-800-xxx ASSISTED LISTENING RACK MOUNT LISTEN LA-326 ASSISTED LISTENING ANTENNA LISTEN LA-122 A16120.1 ASSISTED LISTENING RECEIVER LISTEN LR-400 A16120.2 ASSISTED LISTENING RECEIVER: EAR SPEAKER LISTEN LA-164 A16120.3 ASSISTED LISTENING RECEIVER: SIGNAGE LISTEN LA-304 RIMROCK GROUP A16120.4 ASSISTED LISTENING RECEIVER: POWER LISTEN LA-361 Empowered Business - Quiet Technology A16161 ASSISTED LISTENING ADA PACKAGE - RF LISTEN LS-16-072-01 A21040 HD CAMERA VADDIO CLEARVIEW HD-18 A21040.1 HD CAMERA CCU VADDIO WALLVIEW CCU HD-18 A21040.2 CAMERA SHELF VADDIO 535-2000-xxx 440-5600-xxx A16110.1 A16110.2 A A21040.3 CAMERA VIDEO CABLE VADDIO A21240 DOCUMENT CAMERA WOLFVISION VZ-8PLUS A21340 DVD PLAYER/VCR LG RC897T A23505 AV PRESENTATION SWITCHER EXTRON IN1606 A24097 UTP AV TRANSMITTER EXTRON DTP HDMI 330 Tx A24197 UTP AV RECEIVER EXTRON DTP HDMI 330 Rx A25103 DIGITALMEDIA MATRIX SWITCHER CRESTRON DM-MD32x32 (Size Entire Switching System as Required) A25103.1 DIGITALMEDIA MATRIX SWITCHER INPUT CARD CRESTRON As Required A25103.50 DIGITALMEDIA MATRIX SWITCHER OUTPUT CARD CRESTRON As Required A25505 DIGITALMEDIA ROOM CONTROLLER CRESTRON DM-RMC-100 A25420 DIGITALMEDIA HDMI / RGB 8G UTP TRANSMITTER CRESTRON DM-TX-201-C A25522 DIGITALMEDIA HMDI 8G UTP ROOM CONTROLLER / SCALER CRESTRON DM-RMC-SCALER-C A25510 A28033 B A28033.1 A33382 H A33355 J DIGITALMEDIA TRANSMITTER DECORA CRESTRON DM-TX-200-C-2G PROJECTOR WITH STANDARD LENS EPSON G6750WU PROJECTOR LENS EPSON As Required CEILING PROJECTION SCREEN 70"X70" DA-LITE 85660 CEILING PROJECTION SCREEN SQUARE 87"x139" DA-LITE 34558 A33399.1 LOW VOLTAGE OPERATOR DA-LITE SINGLE LOW VOLT OPERATOR A33599.3 SCREEN SWITCH DA-LITE A41160 DESKTOP TOUCHPANEL CRESTRON TSW-1050 A42625 CONTROL PROCESSOR CRESTRON PRO3 MLC 104 IP PLUS L A45120 CONTROL PROCESSOR EXTRON EQUIPMENT RACK FLOOR MIDDLE ATLANTIC WR-44-32 A51200 EQUIPMENT RACK WALL TILTOUT EXTRON MLM-WB+ A63250 INTERFACE PLATE ENCLOSURE EXTRON CABLE CUBBY 600 A64200 FLAT PANEL DISPLAY WALL BOX FSR PWB-100-xxx A65110 UTP PATCH PANEL HUB/MOHAWK P5E24UE A66101 MICROPHONE AUDIO CABLE LIBERTY 22-1P--EZ-BLK or Plenum Equivalent A66103 LINE AUDIO CABLE LIBERTY 22-1P-EZ-BLK or Plenum Equivalent A66105 LOUDSPEAKER AUDIO CABLE LIBERTY 1x-2C-KO+-WHT or Plenum Equivalent A66201 COMPOSITE VIDEO CABLE DISTANCES UNDER 100' LIBERTY 20-CMR-VID-COAX-BLK or Plenum Equivalent A66203 COMPOSITE VIDEO CABLE DISTANCES OVER 100' LIBERTY 18-CMR-VID-COAX-BLK or Plenum Equivalent A66207 RGBHV VIDEO CABLE LIBERTY RGB5C-PVC or Plenum Equivalent A66209 HDMI CABLE LIBERTY E-HDM-M-xx / x or Plenum Equivalent A66305 CRESNET CABLE LIBERTY LLINX-U or Plenum Equivalent A66312 SP-BUS CABLE LIBERTY See Telecom Spec A66314 BIAMP CONTROL BUS CABLE LIBERTY LLINX-U or Plenum Equivalent A66315 INFRARED CABLE LIBERTY 22-1P-EZ-BLK or Plenum Equivalent A66320 RS-232 DATA CABLE LIBERTY 24-4P-SH-LIBII or Plenum Equivalent A51120 A A66335 CONTACT CLOSURE CABLE LIBERTY 1x-2C-WHT or Plenum Equivalent A66340 CONTACT CLOSURE CABLE LIBERTY 1x-2C-SH-WHT or Plenum Equivalent A66345 UNSHIELDED TWISTED PAIR LIBERTY See Telecom Spec A66350 UTP PATCH CORD LIBERTY See Telecom Spec A66380 AUDIOVISUAL DIGITALMEDIA CABLE CRESTRON DM-CBL-8G-P A66380.1 AUDIOVISUAL DIGITALMEDIA CABLE CONNECTOR, 20 PACK CRESTRON DM-8G-CONN-WG A66400 RADIO FREQUENCY CABLE BELDEN 8240 or Plenum Equivalent A66420 POWER SUPPLY CABLE BELDEN 5x0xUE or Plenum Equivalent A67000 MANUFACTURED VGA/AUDIO CABLE EXTRON VGA-A M-M MD/x A67001 MANUFACTURED HDMI CABLE EXTRON HDMI M-M Pro/x HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT 2 1 MARK 10/28/2013 09/24/2013 DATE DESCRIPTION TECHNOLOGY SCHEDULES T-002 ROOF TR-4A B448 GENERAL NOTES VB FB PP FB PP PP SM MM (1) 200-PR CAT3 (1) 100-PR CAT3 (1) 24-CT 50/125 MM (1) 24-CT SM A REFER TO SCHEMATIC DESIGN NARRATIVE FOR TELECOM SYSTEM DESIGN PARAMETERS. TELECOM SYSTEMS WILL CONFORM TO UCB STANDARDS B REFER TO ET-SERIES DRAWINGS FOR RACEWAY/PATHWAY RISER DIAGRAM C PRIOR TO PROCUREMENT AND INSTALLATION OF CABLE, PHYSICALLY VERIFY ON SITE THE TOTAL RUN LENGTH FOR EACH CABLE FROM ENDPOINT TO ENDPOINT, INCLUDING VERTICAL TRANSITIONS, REQUIRED CABLE SLACK, ETC. PRE-CUT/PRE-MANUFACTURED CABLES OF INSUFFICIENT LENGTH ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR D FOURTH FLOOR TR-3A B348 S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 SLEEVES AND/OR CONDUITS SHALL NOT BE SHARED BETWEEN BACKBONE AND HORIZONTAL CABLING. THE CONTRACTOR SHALL USE SEPARATE SLEEVES AND/OR CONDUITS FOR EACH Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 ALT 4 TR-3B D347 E EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL SYSTEM(S) RIMROCK GROUP VB FB PP FB PP PP SM MM (1) 200-PR CAT3 Empowered Business - Quiet Technology (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 100-PR CAT3 VB FB PP FB PP PP SM MM (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 24-CT SM DRAWING NOTES 1 REFER TO DRAWING NOTE 1 ON SHEET T-003 FOR SPLICING REQUIREMENTS 2 COORDINATE DUCT UTILIZATION WITH OWNER PRIOR TO INSTALLATION OF CABLE 3 96-PORT VOICE BACKBONE PATCH PANEL(S). TERMINATE 1 PR/PORT 4 CONTRACTOR SHALL PRE-TEST EXISTING TWO STRANDS OF SINGLEMODE CABLE FROM FIBER HUT TO MAIN CAMPUS. CONTRACTOR SHALL REPLACE 8 SINGLEMODE CONNECTORS WITH APC CONNECTORS EN ROUTE. CONTRACTOR SHALL RE-TEST SAME FIBER LINK TO VERIFY NO DEGRADATION OF CABLE. CONTRACTOR SHALL INCLUDE PRICING FOR 6-CT SINGLEMODE CABLE WITHIN STADIUM BUILDING (APPROXIMATELY 200-FEET); CONNECTORIZE, TEST, LABEL AND DOCUMENT 5 48-PORT UTILITY BACKBONE PATCH PANEL(S). TERMINATE 4-PAIRS/PORT 6 COIL UNTERMINATED FIBER AND ATTACH TO THE WALL FOR FUTURE USE BY OWNER. PROVIDE ENOUGH SLACK FOR A 20-FOOT SERVICE LOOP AND TO REACH THE NORTHEAST CORNER OF ROOM B1B54 (1) 24-CT 50/125 MM THIRD FLOOR TR-2A B248 ALT 4 TR-2B D247 VB FB PP FB PP PP SM MM (1) 200-PR CAT3 (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (2) 24-CT 50/125 MM (2) 24-CT SM (2) 200-PR CAT3 (1) 100-PR CAT3 VB FB PP FB PP PP SM MM (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 24-CT SM (1) 24-CT 50/125 MM SECOND FLOOR ALT 3 TR-1D A102 MDF/TR-1A B148 TR-1C A115A (3) 24-CT 50/125 MM (3) 24-CT SM (3) 200-PR CAT3 (1) 100-PR CAT3 FB PP FB PP VB FB PP FB PP FB PP VB FB PP FB PP PP SM MM PP SM MM MM PP SM MM (1) 200-PR CAT3 (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 24-CT SM (1) 24-CT 50/125 MM (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 2-CT 62.5/125 MM (10) 200-PR CAT3 (1) 100-PR CAT3 FACP (1) 2-CT 62.5/125 MM (11) 24-CT 50/125 MM (11) 24-CT SM SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT (2) 24-CT 50/125 MM (2) 24-CT SM (2) 200-PR CAT3 FACP VB ALT 4 TR-1B D147 STAIR HALL CRA112 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com VB FB PP FB PP PP SM MM (4) 24-CT 50/125 MM (4) 24-CT SM (4) 200-PR CAT3 (1) 200-PR CAT3 (1) 24-CT SM (1) 24-CT 50/125 MM (2) 24-CT 50/125 MM (2) 24-CT SM (2) 200-PR CAT3 FIRST FLOOR SERVER ROOM B1B58 TR-0A B1B50 ALT 4 TR-0B D1B47 (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (2) 24-CT 50/125 MM (2) 24-CT SM 200-PR CAT3 VB FB PP FB PP VB FB PP FB PP PP SM MM PP SM MM (1) 200-PR CAT3 (1) 24-CT SM (1) 24-CT 50/125 MM (1) 24-CT SM (1) 200-PR CAT3 (1) 24-CT SM (1) 24-CT 50/125 MM (1) 24-CT 50/125 MM (1) 24-CT SM (1) 24-CT 50/125 MM BASEMENT 2 1 MARK 1 10/28/2013 09/24/2013 DATE DESCRIPTION TECHNOLOGY ISP BACKBONE RISER DIAGRAM (FOR UCB ITS) T-004 LSTR (558) TR-112 MDF/TR-1A B148 TB16 (501) TR-1 (FIBER HUT) (2) 50-PR CAT3 (1) 50-PR CAT3 (1) 50-PR CAT3 BEP (1) 1800-PR OSP (EXISTING) FB PP FB PP SM MM (1) 24-CT SM OSP VB VB VB PP PP TB RACK R5 RACK R21 UCB UTILITY (1) 24-CT 62.5/125 MM OSP BEP UCB UTILITY (1) 100-PR OSP (1) 24-CT 62.5/125 MM OSP (NEW) (1) 24-CT SM OSP (NEW) (1) 1800-PR OSP (EXISTING) (1) 24-CT 62.5/125 MM OSP (NEW) (1) 24-CT SM OSP (NEW) (1) 100-PR OSP (NEW) VAULT MANHOLE 7163 2 FB PP FB PP FB PP FB PP SM MM SM MM (2) 24-CT SM OSP (1) 24-CT 62.5/125 MM OSP (NEW) (1) 24-CT SM OSP (NEW) (2) 24-CT 62.5/125 MM OSP VAULT MANHOLE 6747 (1) 24-CT SM OSP (1) 24-CT 62.5/125 MM OSP (NEW) (1) 24-CT SM OSP (NEW) (1) 24-CT 62.5/125 MM OSP TECHNOLOGY RISER DIAGRAMS TECHNOLOGY OSP BACKBONE RISER DIAGRAM (FOR UCB ITS AND UCB UTILITY) T-004 T-004 GENERAL NOTES A B C D E DRAWING NOTES REFER TO SCHEMATIC DESIGN NARRATIVE FOR TELECOM SYSTEM DESIGN PARAMETERS. TELECOM SYSTEMS WILL CONFORM TO UCB STANDARDS REFER TO ET-SERIES DRAWINGS FOR RACEWAY/PATHWAY RISER DIAGRAM 1 REFER TO SITE PLAN FOR APPROXIMATE QWEST SERVICE LOCATION 2 COORDINATE DUCT UTILIZATION WITH OWNER PRIOR TO INSTALLATION OF CABLE 3 48-PORT UTILITY BACKBONE PATCH PANEL(S). TERMINATE 4-PR/PORT S T E RN PRIOR TO PROCUREMENT AND INSTALLATION OF CABLE, PHYSICALLY VERIFY ON SITE THE TOTAL RUN LENGTH FOR EACH CABLE FROM ENDPOINT TO ENDPOINT, INCLUDING VERTICAL TRANSITIONS, REQUIRED CABLE SLACK, ETC. PRE-CUT/PRE-MANUFACTURED CABLES OF INSUFFICIENT LENGTH ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 SLEEVES AND/OR CONDUITS SHALL NOT BE SHARED BETWEEN BACKBONE AND HORIZONTAL CABLING. THE CONTRACTOR SHALL USE SEPARATE SLEEVES AND/OR CONDUITS FOR EACH Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL SYSTEM(S) RIMROCK GROUP Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com ROOF ROOF TR-4A B448 TR-4A B448 VB TB PP (1) 200-PR CAT3 (1) 100-PR CAT3 FOURTH FLOOR FOURTH FLOOR TR-3A B348 TR-3B D347 ALT 4 TR-3A B348 TR-3B D347 ALT 4 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT (1) 200-PR CAT3 (1) 100-PR CAT3 TB TB VB VB PP PP (1) 100-PR CAT3 (1) 100-PR CAT3 THIRD FLOOR (1) 200-PR CAT3 (1) 200-PR CAT3 THIRD FLOOR TR-2A B248 TR-2B D247 (2) 100-PR CAT3 ALT 4 TR-2A B248 TR-2B D247 (2) 200-PR CAT3 (1) 100-PR CAT3 TB TB SECOND FLOOR (1) 200-PR CAT3 VB VB PP PP (1) 100-PR CAT3 (1) 100-PR CAT3 ALT 4 (1) 200-PR CAT3 (1) 200-PR CAT3 SECOND FLOOR ALT 3 TR-1D A102 MDF/TR-1A B148 TR-1C A115A TR-1B D147 ALT 4 TR-1D A102 ALT 3 TR-1C A115A MDF/TR-1A B148 TR-1B D147 ALT 4 2 1 MARK (3) 100-PR CAT3 TB TB BEP (3) 200-PR CAT3 (2) 100-PR CAT3 TB TB (1) 100-PR CAT3 VB VB VB PP PP PP PP (4) 200-PR CAT3 (1) 100-PR CAT3 (10) 100-PR CAT3 (1) 100-PR OSP DESCRIPTION (2) 200-PR CAT3 VB (4) 100-PR CAT3 (1) 100-PR CAT3 10/28/2013 09/24/2013 DATE (1) 200-PR CAT3 (1) 200-PR CAT3 (10) 200-PR CAT3 (1) 200-PR CAT3 (2) 200-PR CAT3 TO QWEST SERVICE FIRST FLOOR FIRST FLOOR TR-0A B1B50 TR-0B D1B47 (1) 100-PR CAT3 ALT 4 TR-0A B1B50 TR-0B D1B47 (1) 200-PR CAT3 (1) 100-PR CAT3 TB TB (1) 100-PR CAT3 BASEMENT (1) 100-PR CAT3 ALT 4 (1) 200-PR CAT3 VB VB PP PP (1) 200-PR CAT3 (1) 200-PR CAT3 BASEMENT 1 T-005 TECHNOLOGY OSP AND ISP BACKBONE RISER DIAGRAM (FOR QWEST) 2 T-005 TECHNOLOGY ISP BACKBONE RISER DIAGRAM (FOR UCB UTILITY) TECHNOLOGY RISER DIAGRAMS T-005 ROOF TR-4A B448 GENERAL NOTES TO CATV OUTLET (TYPICAL) 14.2 dB 8-WAY TAP 20.4 dBmV A REFER TO SCHEMATIC DESIGN NARRATIVE FOR TELECOM SYSTEM DESIGN PARAMETERS. TELECOM SYSTEMS WILL CONFORM TO UCB STANDARDS B REFER TO ET-SERIES DRAWINGS FOR RACEWAY/PATHWAY RISER DIAGRAM C PRIOR TO PROCUREMENT AND INSTALLATION OF CABLE, PHYSICALLY VERIFY ON SITE THE TOTAL RUN LENGTH FOR EACH CABLE FROM ENDPOINT TO ENDPOINT, INCLUDING VERTICAL TRANSITIONS, REQUIRED CABLE SLACK, ETC. PRE-CUT/PRE-MANUFACTURED CABLES OF INSUFFICIENT LENGTH ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 FOURTH FLOOR D TR-3A B348 TR-3B D347 ALT 4 E 22.9 dBmV TO CATV OUTLET (TYPICAL) 17.8 dB 8-WAY TAP 8-WAY TAP 25.2 dBmV THIRD FLOOR TR-2B D247 ALT 4 TO CATV OUTLET (TYPICAL) 20.0 dB 8-WAY TAP TR-1C A115A MDF/TR-1A B148 TR-1B D147 ALT 4 26.4 dBmV 31.7 dBmV TO CATV OUTLET (TYPICAL) 8-WAY TAP 14.2 dB 19.2 dBmV TO CATV OUTLET (TYPICAL) 8-WAY TAP 17.8 dB 24.2 dBmV TO VAULT OPTICAL NODE RACK MOUNT FB PP SM 42.0 dBmV 4-WAY TAP 10.3 dB SINGLEMODE CABLE. ALL OPTICAL FIBER STRANDS CARRYING CATV SIGNALS SHALL BE TERMINATED WITH APC CONNECTORS 2 CATV TRUNK CABLE SHALL BE 0.500 HARD LINE PLENUM RATED 3 CATV DROP CABLE SHALL BE SERIES 6 (RG-6) 4 CATV TAP VALUES AND dBmV VALUES SHOWN ARE ILLUSTRATIVE ONLY AND BASED ON 550 MHz SYSTEM. COORDINATE WITH OWNER TO DETERMINE FINAL SYSTEM OUTPUT, TILT, SLOPE AND CABLE EQUALIZATION REQUIREMENTS PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com TO CATV OUTLET (TYPICAL) 17.8 dB SECOND FLOOR ALT 3 1 23.9 dBmV 29.2 dBmV TR-1D A102 Empowered Business - Quiet Technology 21.6 dBmV 27.7 dBmV 8-WAY TAP EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL SYSTEM(S) DRAWING NOTES 19.1 dBmV TR-2A B248 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 RIMROCK GROUP TO CATV OUTLET (TYPICAL) 14.2 dB SLEEVES AND/OR CONDUITS SHALL NOT BE SHARED BETWEEN BACKBONE AND HORIZONTAL CABLING. THE CONTRACTOR SHALL USE SEPARATE SLEEVES AND/OR CONDUITS FOR EACH 30.4 dBmV 37.9 dBmV 29.2 dBmV 31.7 dBmV 8-WAY TAP 26.4 2-WAY dBmV SPLITTER 23.9 dBmV 17.8 dB 8-WAY TAP TO CATV OUTLET (TYPICAL) 20.0 dB 4.3 dB TO CATV OUTLET (TYPICAL) SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT FIBER PATCH CORD 31.7 dBmV 21.6 dBmV 27.7 dBmV 31.7 dBmV FIRST FLOOR TR-0A B1B50 TR-0B D1B47 25.2 dBmV TO CATV OUTLET (TYPICAL) 8-WAY TAP ALT 4 19.1 dBmV 17.8 dB 8-WAY TAP 14.2 dB TO CATV OUTLET (TYPICAL) GROUND FLOOR 1 CATV DISTRIBUTION DIAGRAM T-006 FIRST FLOOR SERVER ROOM B1B58 2 1 MARK BB A01 BB B01 PP (48) 4-PR CAT6 (96) 4-PR CAT6 (144) 4-PR CAT6 (144) 4-PR CAT6 (96) 4-PR CAT6 PP (48) 4-PR CAT6 PP PP (48) 4-PR CAT6 BB B07 PP BB D06 PP (48) 4-PR CAT6 BB A07 (96) 4-PR CAT6 BB C06 PP PP (96) 4-PR CAT6 BB B06 BB D05 PP (96) 4-PR CAT6 BB A06 (144) 4-PR CAT6 BB C05 PP PP (144) 4-PR CAT6 BB B05 PP BB D04 PP (144) 4-PR CAT6 BB A05 (144) 4-PR CAT6 BB C04 PP PP (144) 4-PR CAT6 BB B04 PP BB D03 PP (144) 4-PR CAT6 BB A04 (96) 4-PR CAT6 BB C03 PP PP (96) 4-PR CAT6 BB B03 PP BB D02 PP (96) 4-PR CAT6 BB A03 (48) 4-PR CAT6 BB C02 PP PP (48) 4-PR CAT6 BB B02 PP (48) 4-PR CAT6 BB C07 PP DESCRIPTION BB D01 PP (48) 4-PR CAT6 BB A02 BB C01 PP 10/28/2013 09/24/2013 DATE BB D07 PP TECHNOLOGY RISER DIAGRAMS BASEMENT 2 T-006 SERVER ROOM (B1B58) INTERNAL RISER DIAGRAM T-006 GENERAL NOTES 0 1 1.3 1.5 2 AW 3 MATCHLINE TR-1D BOUNDARY AREA OF WORK AREA OF WORK AREA AW S +84" (2) 4-INCH CONDUITS (AV) (4) 4-INCH CONDUITS 021 - 419 100 - 405 P TR-1D TELE T-307 STOR 010 - 404 (1) 1-INCH CONDUIT (TYPICAL) B S A (1) 1-INCH CONDUIT (TYPICAL) TR-1D BOUNDARY (1) 1-INCH CONDUIT (TYPICAL) A WAP (1) 1 1/4-INCH CONDUIT IF (TYPICAL) W2D IF G REFER TO ET-SERIES DRAWINGS FOR PROVISION OF CONDUIT, BOXES AND OTHER PRIMARY RACEWAY H WAP OUTLET LOCATIONS SHOWN ARE APPROXIMATE, AND ARE NOT INTENDED TO INDICATE THE QUANTITY NOR THE FINAL LOCATIONS OF WIRELESS ACCESS POINTS. RATHER, WAP OUTLET LOCATIONS HAVE BEEN DISTRIBUTED TO ENSURE THAT WHEREVER A WIRELESS ACCESS POINT IS TO BE LOCATED, A WAP OUTLET WILL BE WITHIN PATCH CORD REACH OF THE WIRELESS ACCESS POINT J PROVIDE A WIRELESS ACCESS POINT ENCLOSURE FOR EACH WAP OUTLET LOCATION. COORDINATE FINAL ENCLOSURE LOCATIONS WITH OWNER AFTER OWNER HAS FINALIZED LOCATIONS BY WIRELESS SURVEY K UNLESS OTHERWISE NOTED, RACEWAY FOR TELECOM OUTLETS SHALL CONSIST OF 1-INCH CONDUIT FROM EACH TELECOM OUTLET BOX (I.E. DEVICE BOX, BACK BOX, ETC.) TO CABLE TRAY W L COORDINATE WITH ELECTRICAL CONTRACTOR TO FINALIZE EQUIPMENT LOCATIONS, DEVICE LOCATIONS AND CONDUIT ROUTING REQUIREMENTS PRIOR TO ELECTRICAL ROUGH-IN S U M CABLE TRAY SHOWN IS FOR TELECOMMUNICATIONS CABLES ONLY. CABLES THAT HAVE THE POTENTIAL TO INTERFERE WITH THE OPERATING CHARACTERISTICS AND/OR PERFORMANCE OF THE TELECOMMUNICATIONS CABLES SHALL NOT BE INSTALLED IN THE CABLE TRAY UNDER ANY CIRCUMSTANCES. CABLES WHICH ARE OPERATIONALLY COMPATIBLE WITH THE TELECOMMUNICATIONS CABLES (I.E. NO INTERFERENCE) MAY ONLY BE INSTALLED IN THE CABLE TRAY WITH THE PRIOR APPROVAL OF THE ENGINEER AND OWNER (1) 3/4-INCH CONDUIT A X NA +120" B S +84" 11 A S FB6D +84" 020 - 406 020 - 407 J MATCHLINE 2 S IF 110-SEAT CLASSROOM S B B B B S A108 P S 010 - 416 P B +120" IF (1) 3/4-INCH CONDUIT (TYPICAL) A W2D 11 W2D A IF FB6E A +120" FB6E IF 020 - 412 020 - 413 IF (1) 3/4-INCH CONDUIT (TYPICAL) IF B S B 60-SEAT CLASSROOM P P ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED R ALL CAMERA HEIGHT REQUIREMENTS ARE TO BE REFERENCED FROM THE FINISHED FLOOR OF LEVEL WHICH THE CAMERA IS LOCATED. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS W2D A A104 11 J S +84" S IF IF SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT B FB6D S 020 - 410 020 - 411 KEY NOTES SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 1 THE AUDIOVISUAL SYSTEMS IN THIS AREA WILL BE LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED 2 AUDIOVISUAL CONTRACTOR TO COORDINATE WITH OWNER AND ELECTRICAL CONTRACTOR PRIOR TO INSTALLATION. PROJECTOR STABILIZERS MAY BE REQUIRED DUE TO PROJECTOR POLE LENGTHS +84" B PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com S J S Empowered Business - Quiet Technology B 010 - 415 010 - 402 B RIMROCK GROUP C1A P 2 S B (1) 3/4-INCH CONDUIT (TYPICAL) W2D B Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 Z 020 - 408 020 - 409 IF (1) 1-INCH CONDUIT (TYPICAL) TR-1D BOUNDARY DN (1) 3/4-INCH CONDUIT (TYPICAL) 11 TR-1C BOUNDARY S AT MOVABLE LAB BENCH LOCATIONS, CONTRACTOR SHALL INSTALL CABLE IN CONDUITS FROM CABLE TRAY TO 4-SQUARE DEEP BOX ABOVE LAB BENCH FURNITURE, THEN THROUGH DUAL CHANNEL RACEWAY COMPARTMENT TO OUTLET LOCATION AW +120" S P 010 - 403 N C1A B C1A UNLESS OTHERWISE NOTED, TELECOM OUTLETS ORIGINATING ON THIS FLOOR SHALL TERMINATE IN A TELECOMMUNICATIONS ROOM ON THIS FLOOR, REGARDLESS OF THE PATH FOLLOWED BY THE CABLES B J IF F C2D 010 - 417 +120" S IF INSTALL BACKBONE CABLES IN CABLE TRAY PRIOR TO INSTALLING HORIZONTAL CABLES 100 - 428 DN B B T W2D A S C1A E HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 AV B (1) 3/4-INCH CONDUIT IF 020 - 418 A107 (1) 2-INCH CONDUIT DN (TYPICAL) WAP (4) 4-INCH CONDUITS A/V EQA ROOM/STOR A103 A101 +120" UNLESS OTHERWISE NOTED, REFER TO ARCHITECTURAL DRAWINGS, DETAILS AND/OR SPECIFICATIONS FOR DEVICE BOX MOUNTING HEIGHTS 12 AC 12-INCH ABOVE CEILING CABLE TRAY 1 A102 STOR. P D P W DN PRIOR TO INSTALLATION, VERIFY THE TOTAL RUN LENGTH FOR EACH HORIZONTAL CABLE FROM THE TELECOM OUTLET TO IT'S TELECOMMUNICATIONS ROOM, USING THE RACEWAYS (CONDUIT, SLEEVES, ETC) AS INSTALLED. FOR RUN LENGTHS WHICH EXCEED 270 FEET, INCLUDING UP/DOWN TRANSITIONS, REQUIRED CABLE SLACK, ETC., OBTAIN THE ENGINEER'S DIRECTION PRIOR TO PROCEEDING (2) 4 CON (1) 4-INCH CONDUIT C1A C2D C F1 A100 CRA100 REFER TO DETAIL DRAWING(S) FOR ADDITIONAL STRUCTURAL SUPPORT, MOUNTING, AND RACEWAY REQUIREMENTS +84" PRE-FUNCTION VESTIBULE B S S F1 SEE SYMBOL SCHEDULE (ON THE TITLE SHEET) FOR IMPORTANT INSTALLATION NOTES AND DETAILS SPECIFIC TO EACH SYMBOL USED ON THIS SHEET A R.6 2 S T E RN A S B S B S DN WAP DN BB 010 - 414 010 - 401 WAP STORAGE A109 M2A M1A M1B DN DN AREA OF WORK AREA OF WORK STOR 2 A105 2 1 MARK 10/28/2013 09/24/2013 DATE DESCRIPTION N 1 TECHNOLOGY PLAN - FIRST FLOOR - AREA AW 8' 4' 0 1/8" = 1'-0" 8' AREA D AREA C AREA B TECHNOLOGY PLAN FIRST FLOOR AREA AW AREA A AREA AW AREA AE T-101AW-A3 GENERAL NOTES 9 10 11 12 13 010 - 620 ELEV (SECURITY-ACS) WAP 16 17 18 19 20 21 22 23 C B 110 - 603 020 - 626 STOR 110 - 601 C120 TR-1B BOUNDARY F1 +84" MDF/TR-1A BOUNDARY C C2B REFER TO DETAIL DRAWING(S) FOR ADDITIONAL STRUCTURAL SUPPORT, MOUNTING, AND RACEWAY REQUIREMENTS C PRIOR TO INSTALLATION, VERIFY THE TOTAL RUN LENGTH FOR EACH HORIZONTAL CABLE FROM THE TELECOM OUTLET TO IT'S TELECOMMUNICATIONS ROOM, USING THE RACEWAYS (CONDUIT, SLEEVES, ETC) AS INSTALLED. FOR RUN LENGTHS WHICH EXCEED 270 FEET, INCLUDING UP/DOWN TRANSITIONS, REQUIRED CABLE SLACK, ETC., OBTAIN THE ENGINEER'S DIRECTION PRIOR TO PROCEEDING D UNLESS OTHERWISE NOTED, REFER TO ARCHITECTURAL DRAWINGS, DETAILS AND/OR SPECIFICATIONS FOR DEVICE BOX MOUNTING HEIGHTS E INSTALL BACKBONE CABLES IN CABLE TRAY PRIOR TO INSTALLING HORIZONTAL CABLES F UNLESS OTHERWISE NOTED, TELECOM OUTLETS ORIGINATING ON THIS FLOOR SHALL TERMINATE IN A TELECOMMUNICATIONS ROOM ON THIS FLOOR, REGARDLESS OF THE PATH FOLLOWED BY THE CABLES K MDF/TR-1A BOUNDARY G REFER TO ET-SERIES DRAWINGS FOR PROVISION OF CONDUIT, BOXES AND OTHER PRIMARY RACEWAY H WAP OUTLET LOCATIONS SHOWN ARE APPROXIMATE, AND ARE NOT INTENDED TO INDICATE THE QUANTITY NOR THE FINAL LOCATIONS OF WIRELESS ACCESS POINTS. RATHER, WAP OUTLET LOCATIONS HAVE BEEN DISTRIBUTED TO ENSURE THAT WHEREVER A WIRELESS ACCESS POINT IS TO BE LOCATED, A WAP OUTLET WILL BE WITHIN PATCH CORD REACH OF THE WIRELESS ACCESS POINT J PROVIDE A WIRELESS ACCESS POINT ENCLOSURE FOR EACH WAP OUTLET LOCATION. COORDINATE FINAL ENCLOSURE LOCATIONS WITH OWNER AFTER OWNER HAS FINALIZED LOCATIONS BY WIRELESS SURVEY C2D K UNLESS OTHERWISE NOTED, RACEWAY FOR TELECOM OUTLETS SHALL CONSIST OF 1-INCH CONDUIT FROM EACH TELECOM OUTLET BOX (I.E. DEVICE BOX, BACK BOX, ETC.) TO CABLE TRAY C1C L COORDINATE WITH ELECTRICAL CONTRACTOR TO FINALIZE EQUIPMENT LOCATIONS, DEVICE LOCATIONS AND CONDUIT ROUTING REQUIREMENTS PRIOR TO ELECTRICAL ROUGH-IN M CABLE TRAY SHOWN IS FOR TELECOMMUNICATIONS CABLES ONLY. CABLES THAT HAVE THE POTENTIAL TO INTERFERE WITH THE OPERATING CHARACTERISTICS AND/OR PERFORMANCE OF THE TELECOMMUNICATIONS CABLES SHALL NOT BE INSTALLED IN THE CABLE TRAY UNDER ANY CIRCUMSTANCES. CABLES WHICH ARE OPERATIONALLY COMPATIBLE WITH THE TELECOMMUNICATIONS CABLES (I.E. NO INTERFERENCE) MAY ONLY BE INSTALLED IN THE CABLE TRAY WITH THE PRIOR APPROVAL OF THE ENGINEER AND OWNER +84" S S B MATCHLINE C121 010 - 624 SEE SYMBOL SCHEDULE (ON THE TITLE SHEET) FOR IMPORTANT INSTALLATION NOTES AND DETAILS SPECIFIC TO EACH SYMBOL USED ON THIS SHEET 23.2 CHBE OFFICE ELC101 SR SR 15 F1 MATCHLINE B (6) 4-INCH CONDUITS C1D PASSAGE VESTIBULE CRB180A VESTIBULE (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING DNDN CRB180B DNDN DNDN K.5 C1E 011 - 600 P STB181 020 - 599 020 - 599A 010 - 599B 011 - 593 B 2 4 2 020 - 598 020 - 598A 010 - 598B 2 4 020 - 597 020 - 597A 010 - 597B A 4 2 SR SR B160A SR SR 020 - 096 A 020 - 080 020 - 084 020 - 071 020 - 072 A S C2A 010 - 079 H 020 - 086 020 - 077 4 COMPUTER LAB A 100 - 494 010 - 589 (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING 1 020 - 093 A MDF ROOM 020 - 493 (6) 4-INCH CONDUITS 020 - 087 SR SR B148 010 - 091 010 - 090 12 AC MDF/TR-1A BOUNDARY 16 AC 2 A 4 020 - 481 020 - 481A 010 - 481B A SHARED EQUIP. ROOM 020 - 016 020 - 017 020 - 014 020 - 015 A 4 B 020 - 480 020 - 480A 010 - 480B 011 - 867 11 2 IF AV W3A SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 12 AC 010 - 040 010 - 039 C1B 12 AC STAIR 12 AC UP N FS 060 - 012 020 - 033 020 - 034 SR 020 - 035 SR A S 020 - 037 2 1 MARK 060 - 009 SR SR 020 - 030 020 - 029 SR 020 - 028 SR SR 3 STORAGE FS B171A SR 010 - 006 JC A A171C HR 110 - 467 OFFICE 16 AC HR OFFICE 110 - 464 DESCRIPTION 020 - 026 020 - 027 3 3 SR 10/28/2013 09/24/2013 DATE SR M1A 010 - 007 AREA OF WORK 010 - 008 010 - 020 010 - 021 010 - 022 010 - 023 010 - 024 110 - 479 C1A 010 - 025 AREA OF WORK P MDF/TR-1A BOUNDARY BUDGET A130 MATCHLINE A133 A171B 110 - 475 B 2 BUDGET RY A171D 110 - 466 110 - 465 REFERENCE DETAIL 9 ON QL-703 FOR SERVICE CARRIER 3 SR PROG MAN 110 - 462 OFFICE 3 FS 010 - 005 B141 110 - 463 COORDINATE FINAL LOCATIONS WITH FURNITURE DRAWINGS AND SPECIFICATIONS M1A 020 - 031 ELB143 2 S B159 ELEV EACH WORKSTATION IN THE COMPUTER LAB WILL BE SUPPLIED WITH ONE DATA PORT. CONFIGURATION TBD BASED UPON FURNITURE LAYOUT 060 - 010 TEACHING LAB CLASSROOM SR 1 SR SR 020 - 036 3 3 A DRAWING NOTES FS SR AUDIOVISUAL CONTRACTOR TO COORDINATE WITH OWNER AND ELECTRICAL CONTRACTOR PRIOR TO INSTALLATION. PROJECTOR STABILIZERS MAY BE REQUIRED DUE TO PROJECTOR POLE LENGTHS DN B171 SR 2 FS FS N.2 P THE AUDIOVISUAL SYSTEMS IN THIS AREA WILL BE LIMITED TO INFRASTRUCTURE (CONDUIT, BOXES, BACKING AND POWER). EQUIPMENT WILL BE OWNER FURNISHED, OWNER INSTALLED M.2 IF 010 - 002 1 SR A C2A 020 - 488 020 - 488A 11 WAP S SR 010 - 004 WAP S 020 - 487 020 - 487A 010 - 487B 2 A KEY NOTES M 060 - 013 A S 010 - 003 010 - 495 4 020 - 486 020 - 486A 010 - 486B S 4 SR 16 AC A S 020 - 041 B180 ChBE TEACHING LABS FS 020 - 032 16 AC 010 - 489 020 - 054 FS 12 AC A 2 011 - 018 1 020 - 485 020 - 485A 010 - 485B SR A SR SR CORRIDOR 12 AC 4 AV ELB145 2 MATCHLINE 12 AC H W3A ELEV P 020 - 042 SR SR AUTOCLAVE 010 - 011 2 020 - 053 SR STB191 SR B155 4 ALL CAMERA HEIGHT REQUIREMENTS ARE TO BE REFERENCED FROM THE FINISHED FLOOR OF LEVEL WHICH THE CAMERA IS LOCATED. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS 020 - 043 010 - 038 A IF 020 - 052 CRB150 B115 020 - 482 020 - 482A 010 - 482B B B151 COMPUTER LAB C2A 020 - 057 SR IF STORAGE ROOM 020 - 491 4 R SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT SR SR BIOENGINEERING TEACHING LABORATORY B160B 12 AC 010 - 001 B149 2 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com 020 - 044 SR SR 010 - 019 S FS ELEC 020 - 484 020 - 484A 010 - 484B ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED P 020 - 051 020 - 055 AREA B CRB110 020 - 483 020 - 483A 010 - 483B S SR SR 020 - 056 A 020 - 075 WAP CORRIDOR S P A IF SR F1 +84" (6) 4-INCH CONDUITS 020 - 065 020 - 066 S 010 - 089 C2E 4 C2A 020 - 045 010 - 050 S C1A S A 010 - 067 B160 STUDENT STUDY 4 A A020 - 074 SR SR 020 - 088 SR MDF/TR-1A 020 - 076 SR SR SR 2 SR SR B160C BIOCHEMISTRY TEACHING LABORATORY W 100 - 098 2 Empowered Business - Quiet Technology 4 020 - 073 T-301 020 - 092 120 - 490 RIMROCK GROUP SR S B100 Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 A A 120 - 492 020 - 049 020 - 058 4 B120 EMR 020 - 059 S PREP LAB SR SR 2 S SR SR A WAP S A 020 - 046 SR SR 4 020 - 078 SR SR 020 - 094 020 - 063 020 - 064 4 P 020 - 085 SR SR AT MOVABLE LAB BENCH LOCATIONS, CONTRACTOR SHALL INSTALL CABLE IN CONDUITS FROM CABLE TRAY TO 4-SQUARE DEEP BOX ABOVE LAB BENCH FURNITURE, THEN THROUGH DUAL CHANNEL RACEWAY COMPARTMENT TO OUTLET LOCATION A IF 020 - 095 2 H 020 - 048 020 - 060 W3A 010 - 069 W3A N AV IF SR IF SR SR S 1 020 - 590 020 - 590A 010 - 590B C2A 2 4 4 011 - 062 010 - 068 AV 020 - 081 020 - 083 020 - 097 16" x 4" CABLE TRAY P 010 - 595 IF 020 - 596 020 - 596A 010 - 596B TEACHING LAB STORAGE C2B L AREA OF WORK 010 - 047 010 - 061 SR S A 2 010 - 082 A 020 - 591 020 - 591A 010 - 591B 2 MDF/TR-1A BOUNDARY 011 - 070 4 020 - 592 020 - 592A 010 - 592B S A 24 AREA OF WORK 16 AC AV S +120" 020 - 594 020 - 594A 010 - 594B W3A IF DN 2 DN D 16 AC MDF/TR-1A BOUNDARY KS STAIR UP AV MDF/TR-1A BOUNDARY MAG HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 C1D CRB180 C2D S T E RN A 110 - 478 A N 1 TECHNOLOGY PLAN - FIRST FLOOR - AREA B 8' 4' 0 1/8" = 1'-0" AREA D 8' AREA C AREA B TECHNOLOGY PLAN FIRST FLOOR AREA B AREA A AREA AW AREA AE T-101B-A3 13 14 15 S T E RN M COLUMN COLUMN TYP 2B T-301 HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 TYP 2A T-301 (5) 4-INCH CONDUITS OVER HARD LID FOR FUTURE E-WING M.2 TYP Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 FRONT OF RACKS (6) 4-INCH CONDUITS RIMROCK GROUP Empowered Business - Quiet Technology (6) 4-INCH CONDUITS 2A 6" A 3 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com T-301 TYP D ENLARGED MDF/TR-1A RACK ELEVATIONS (B148) B T-301 C ELEC PANEL 18" x 24" TYP TYP TYP TYP W N 1 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT ENLARGED MDF/TR-1A (B148) T-301 2' 1' 0 1/2" = 1'-0" 2' 2B ENLARGED MDF/TR-1A RACK ELEVATIONS (B148) T-301 COLUMN 489BCC1-100 QWEST COLUMN COLUMN ELEC PANEL 18" x 24" UCB UTILITY COLUMN TYP 8' 7'-4" TYP 12 WALL "A" GENERAL NOTES A B DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD BOND ALL NON-CURRENT CARRYING METALLIC CABLE TRAY, RACEWAY, EQUIPMENT, AND MATERIALS TO THE NEAREST TGB OR TMGB C SLEEVES AND/OR CONDUITS SHALL NOT BE SHARED BETWEEN BACKBONE AND HORIZONTAL CABLING. THE CONTRACTOR SHALL USE SEPARATE SLEEVES AND/OR CONDUITS FOR EACH D PROVIDE REQUIRED SLACK BY CIRCLING CABLE AROUND ROOM ON LADDER RACK, USING A ROUTE WHICH ENABLES THE REQUIRED SLACK LENGTH TO BE ATTAINED (I.E. NOT NECESSARILY THE MOST DIRECT ROUTE). WHENEVER POSSIBLE, USE A DIFFERENT/OPPOSITE ROUTE FOR HORIZONTAL CABLING THAN THAT OF THE ROUTE USED FOR BACKBONE CABLING. END-TO-END CABLE LENGTHS, INCLUDING SLACK LOOPS, SHALL NOT EXCEED TIA/EIA CABLE LENGTH LIMITATIONS E F G ALL SPACE ON WALLS AND IN RACKS/FRAMES/CABINETS IS RESERVED UNLESS OTHERWISE NOTED (INCLUDING SPACE WHICH APPEARS 'EMPTY' ON THE DRAWINGS). NO EQUIPMENT MAY BE INSTALLED IN THESE SPACES (BY ANY TRADE) WITHOUT THE ENGINEER'S PRIOR WRITTEN APPROVAL DO NOT TERMINATE CABLES UNTIL CABLE TERMINATION PLAN/ORDER HAS BEEN COORDINATED WITH AND APPROVED BY THE OWNER 13 DRAWING NOTES SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 1 RACKS LOCATED PER OWNER. AFTER INSTALLATION IT IS UNDERSTOOD THAT REAR OF RACKS WILL BE INACCESSIBLE 2 TERMINATE THE OSP CONDUITS AS CLOSE TO THE BEP's AS POSSIBLE. BOND ALL METALLIC OSP CONDUITS TO THE TMGB PER THE 2008 NEC 1 SPACE RESERVED FOR FIRE ALARM / BAS FIBER PATCH PANEL 2 SPACE RESERVED FOR WIRELESS EQUIPMENT 3 SPACE RESERVED FOR ACTIVE ELECTRONICS 4 SPACE RESERVED FOR CATV EQUIPMENT 5 POWER RECEPTACLE AT 6-INCHES ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. REFERENCE ELECTRICAL DRAWINGS FOR TYPE AND CIRCUITRY 12 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 13 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 14 SPACE RESERVED FOR FUTURE EQUIPMENT 15 TERMINATES UCB BACKBONE CABLE 16 TERMINATES UTILITY BACKBONE CABLE 17 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN RIGHT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 18 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 50 WALL SPACE OBSTRUCTED BY EQUIPMENT 51 CONDUITS TO ROOF. FIRESTOP, CAP AND SEAL WATERTIGHT AT ROOF 53 CABLE RUNWAY USED TO SUPPORT CABLES TO/FROM SLEEVES. MOUNT VERTICALLY WITH CROSS-MEMBERS OUT FROM WALL REFER TO RISER DIAGRAM FOR BACKBONE CABLING DISTRIBUTION AND TERMINATION 61 2 1 MARK WALL "B" KEY NOTES 67 3 10/28/2013 09/24/2013 DATE DESCRIPTION ENLARGED MDF/TR-1A WALL ELEVATIONS (B148) T-301 ENLARGED MDF ROOM 55 INSTALL ALTERNATE SPACE CABLE RUNWAY SUCH THAT RADIUS DROPS ARE VERTICALLY ALIGNED WITH EACH VERTICAL CABLE MANAGEMENT CHANNEL 61 4-INCH CONDUIT SLEEVES FOR CABLE DISTRIBUTION TO/FROM FLOOR(S) ABOVE AND/OR BELOW. FILL ONE SLEEVE PRIOR TO FILLING NEXT SLEEVE. DO NOT MIX BACKBONE AND HORIZONTAL CABLES WITHIN THE SAME SLEEVE 63 SEE DETAIL DRAWING(S) FOR PROVISION OF CABLE PATHWAY FIRESTOP DEVICE(S) 67 OUTSIDE PLANT CONDUITS 79 20-FOOT FIBER SLACK COIL 95 WALL PHONE LOCATION 99 (2) 2-INCH CONDUITS FOR SECURITY T-301 1.3 GENERAL NOTES A B BOND ALL NON-CURRENT CARRYING METALLIC CABLE TRAY, RACEWAY, EQUIPMENT, AND MATERIALS TO THE NEAREST TGB OR TMGB C SLEEVES AND/OR CONDUITS SHALL NOT BE SHARED BETWEEN BACKBONE AND HORIZONTAL CABLING. THE CONTRACTOR SHALL USE SEPARATE SLEEVES AND/OR CONDUITS FOR EACH D (4) 4-INCH CONDUITS W TYP S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 PROVIDE REQUIRED SLACK BY CIRCLING CABLE AROUND ROOM ON LADDER RACK, USING A ROUTE WHICH ENABLES THE REQUIRED SLACK LENGTH TO BE ATTAINED (I.E. NOT NECESSARILY THE MOST DIRECT ROUTE). WHENEVER POSSIBLE, USE A DIFFERENT/OPPOSITE ROUTE FOR HORIZONTAL CABLING THAN THAT OF THE ROUTE USED FOR BACKBONE CABLING. END-TO-END CABLE LENGTHS, INCLUDING SLACK LOOPS, SHALL NOT EXCEED TIA/EIA CABLE LENGTH LIMITATIONS Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 TYP E ELEC TYP 44 43 A 42 41 2 TYP 43 A SYSTIMAX FIBER ISP 1000 G2 42 41 40 39 B T-307 38 TYP 37 36 35 C 34 33 32 40 38 37 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 35 34 33 C HUBBELL (MCCBP350) BLANK PANEL INSERT 32 D 3 T-307 B 5 TYP C 27 E 26 25 24 HUBBELL (UDX48E) 48-PORT PATCH PANEL HUBBELL (MCCBP350) BLANK PANEL INSERT 23 22 21 20 19 18 17 BLANK 16 15 31 6" VERTICAL WIRE MANAGEMENT 6" VERTICAL WIRE MANAGEMENT A 28 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 43 HUBBELL (MCCBP350) BLANK PANEL INSERT 41 30 38 35 SPACE RESERVED FOR EQUIPMENT 33 HUBBELL (MCCBP350) BLANK PANEL INSERT 31 26 25 24 23 22 21 BLANK 18 17 16 15 30 29 28 27 26 25 24 23 21 20 19 18 17 16 15 13 12 12 11 H SPACE RESERVED FOR FUTURE EQUIPMENT 10 11 11 10 10 9 I 9 I 3 K SPACE RESERVED FOR FUTURE EQUIPMENT 2 1 HUBBELL MCCPSS19TS CPI (55053-503) 750 LB CAP 4 3 1 2 ENLARGED TR-1D (ROOM A102) T-307 T-307 2' 1' 0 1/2" = 1'-0" 2 SPACE RESERVED FOR WIRELESS EQUIPMENT 3 SPACE RESERVED FOR ACTIVE ELECTRONICS 4 SPACE RESERVED FOR CATV EQUIPMENT 5 POWER RECEPTACLE AT 6-INCHES ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. REFERENCE ELECTRICAL DRAWINGS FOR TYPE AND CIRCUITRY 12 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 13 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ENTIRE COLUMN, TOP TO BOTTOM, PRIOR TO PUNCHING DOWN ON RIGHT SIDE ENTIRE COLUMN, TOP TO BOTTOM. THEN PROCEED TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 14 SPACE RESERVED FOR FUTURE EQUIPMENT 15 TERMINATES UCB BACKBONE CABLE 16 TERMINATES UTILITY BACKBONE CABLE 17 TERMINATES QWEST COPPER HORIZONTAL (STATION) CABLE(S). PUNCH DOWN RIGHT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 18 TERMINATES QWEST COPPER BACKBONE. PUNCH DOWN LEFT SIDE ONLY, TOP TO BOTTOM, ENTIRE COLUMN BEFORE PROCEEDING TO THE NEXT COLUMN IN THE SAME FASHION, AS REQUIRED 50 WALL SPACE OBSTRUCTED BY EQUIPMENT 51 CONDUITS TO ROOF. FIRESTOP, CAP AND SEAL WATERTIGHT AT ROOF 53 CABLE RUNWAY USED TO SUPPORT CABLES TO/FROM SLEEVES. MOUNT VERTICALLY WITH CROSS-MEMBERS OUT FROM WALL 7 5 SPACE RESERVED FOR FUTURE EQUIPMENT HUBBELL MCCPSS19TS CPI (55053-503) 750 LB CAP 4 3 2 1 CPI (55053-503) 750 LB CAP U N SPACE RESERVED FOR FIRE ALARM / BAS FIBER PATCH PANEL 6 2 1 SOME KEY NOTES BELOW MAY NOT APPEAR ON THIS SHEET 1 8 5 J CPI 30162-703 4 KEY NOTES 9 HUBBELL (P5E96UE) 96-PORT PATCH PANEL VOICE BACKBONE 6 HUBBELL (P548UE) 48-PORT UTILITY CABLE FUTURE 22 12 5 J REFER TO RISER DIAGRAM FOR BACKBONE CABLING DISTRIBUTION AND TERMINATION 32 14 6 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com 34 13 7 Empowered Business - Quiet Technology 36 14 7 G 37 HUBBELL (MCCBP350) BLANK PANEL INSERT 27 8 DO NOT TERMINATE CABLES UNTIL CABLE TERMINATION PLAN/ORDER HAS BEEN COORDINATED WITH AND APPROVED BY THE OWNER 40 13 HUBBELL (P5E96UE) 96-PORT PATCH PANEL VOICE BACKBONE RIMROCK GROUP 39 28 19 F 42 SPACE RESERVED FOR EQUIPMENT 29 20 ALL SPACE ON WALLS AND IN RACKS/FRAMES/CABINETS IS RESERVED UNLESS OTHERWISE NOTED (INCLUDING SPACE WHICH APPEARS 'EMPTY' ON THE DRAWINGS). NO EQUIPMENT MAY BE INSTALLED IN THESE SPACES (BY ANY TRADE) WITHOUT THE ENGINEER'S PRIOR WRITTEN APPROVAL 44 14 8 CPI 30162-703 SPACE RESERVED FOR EQUIPMENT 36 EQUIPMENT 31 D 29 45 39 B 600G FIBER JACK SPACE RESERVED F0R 30 OWNER SWITCH EQUIPMENT R3 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 6" VERTICAL WIRE MANAGEMENT 44 R2 45 B-LINE SB-719-19-2XL-FB PATCH CORD ORGANIZER 6" VERTICAL WIRE MANAGEMENT 45 CPI 30162-703 R1 TYP CPI 30162-703 T DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD RACK ELEVATIONS TR-1D (ROOM A102) 2' SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT 55 INSTALL ALTERNATE SPACE CABLE RUNWAY SUCH THAT RADIUS DROPS ARE VERTICALLY ALIGNED WITH EACH VERTICAL CABLE MANAGEMENT CHANNEL 61 4-INCH CONDUIT SLEEVES FOR CABLE DISTRIBUTION TO/FROM FLOOR(S) ABOVE AND/OR BELOW. FILL ONE SLEEVE PRIOR TO FILLING NEXT SLEEVE. DO NOT MIX BACKBONE AND HORIZONTAL CABLES WITHIN THE SAME SLEEVE 63 SEE DETAIL DRAWING(S) FOR PROVISION OF CABLE PATHWAY FIRESTOP DEVICE(S) 67 OUTSIDE PLANT CONDUITS 79 20-FOOT FIBER SLACK COIL 95 WALL PHONE LOCATION 99 (2) 2-INCH CONDUITS FOR SECURITY 2 1 MARK 3 10/28/2013 09/24/2013 DATE DESCRIPTION WALL ELEVATIONS TR-1D (ROOM A102) T-307 ENLARGED TELECOM ROOM T-307 UTP AUDIOVISUAL TRANSMITTER / CAT5 RECEIVER A24200 RGB CAT5 CAT5 CAT5 CAT5 UTP AUDIOVISUAL CAT5 TRANSMITTER / RECEIVER A24200 PASS THRU RGB GENERAL NOTES LAPTOP OR PC (OFOI) RGB LL+LR A PROJECTOR A28095 (OFCI) EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL SYSTEM(S) S T E RN SERIAL [ 1A1 ] IF RA IF C2A B ALL POWER REQUIREMENTS INCLUDING BUT NOT LIMITED TO POWER SUPPLIES, POWER DISTRIBUTION AND POWER CORDS ARE TO BE PROVIDED BY CONTRACTOR UNLESS NOTED OTHERWISE C ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED CV RGB IF C2A IF RB HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 DRAWING NOTES SERIAL CONTROL MODULE A48100 NETWORKED ROOM CONTROLLER A48110 SP-BUS W3A DVD RECORDER / VCR W / DIGITAL TUNER A21340 (OFCI) TO CATV NETWORK (OFCI) IR NETWORKED ROOM CONTROL PUCK SERIAL A48120 SP-BUS CV QUANTITY OF SPEAKERS ON FLOOR PLANS 2 AUDIOVISUAL CONTRACTOR TO PROVIDE INPUT CABLES LONG ENOUGH TO REACH FURNITURE 3 TERMINATE AND COIL ADDITIONAL CABLE FOR FUTURE USE Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 CV RIMROCK GROUP Empowered Business - Quiet Technology LL LR AUDIO FOLLOW VIDEO PREAMP SWITCHER A48150 LM CEILING SPEAKER TILE A15130 (OFCI) SPKR MINI AUDIO AMPLIFIER A14450 PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com RGB LM LL+LR [ 1A1 ] CEILING SPEAKER TILE A15130 (OFCI) SPKR W3A RGB LAPTOP OR PC (OFOI) WALL RACK A48320 1 1 LL+LR TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - MEDIUM CONFERENCE ROOMS DVD/VCR A21340 (OFCI) TO CATV NETWORK (OFCI) T-401 LL + LR CV CV LL LL LR LR VIDEO DISPLAY A27277 IF W2C UTP AUDIOVISUAL TRANSMITTER (A24097) HDMI AUX INPUT CV LL+LR LAPTOP VGA LL+LR LM UTP AUDIOVISUAL RECEIVER (A24197) CATx CEILING PROJECTION SCREEN SQUARE 70"x70" (A33382) HDMI PROJECTOR (A28033) RS-232 IR REMOTE CONTROL WALL MODULE A48160 LM HDMI FIXED PC HDMI LL+LR LAPTOP AUDIO AMPLIFIER (A14330) 2 TO CATV NETWORK (OFCI) WALL BOX PASS THRU PWR SPKR 70V 8W 70V 8W CEILING LOUDSPEAKER (A15120) RS-232 AUDIOVISUAL PRESENTATION SWITCHER (A23505) IR CEILING LOUDSPEAKER (A15120) 4 SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - SMALL CONFERENCE ROOMS - TYPE A DISPLAY T-401 CONTROL PROCESSOR (A45120) RS-232 RGB RGB LAPTOP OR PC (OFOI) WIRELESS LAVALIER MICROPHONE SYSTEM (A11245) LM ASSISTED LISTENING ADA PACKAGE - RF (A16161) LM LL+LR DVD/VCR A21340 (OFCI) TO CATV NETWORK (OFCI) LL + LR CV CV LL LL LR LR VIDEO DISPLAY A27235 IF W2C TEACHER’S STATION EQUIPMENT RACK WALL TILTOUT (A51200) 2 IR REMOTE CONTROL WALL MODULE A48160 TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - ROOM # B159, B160, B180 CLASSROOM AND LABORATORY 2 T-401 IR TO CATV NETWORK (OFCI) WALL BOX PASS THRU PWR 2 1 MARK UTP AUDIOVISUAL TRANSMITTER / CAT5 RECEIVER A24200 RGB CAT5 CAT5 CAT5 CAT5 UTP AUDIOVISUAL CAT5 TRANSMITTER / RECEIVER A24200 PASS THRU RGB DESCRIPTION TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - SMALL CONFERENCE ROOMS - TYPE B DISPLAY T-401 LAPTOP OR PC (OFOI) RGB LL+LR 5 10/28/2013 09/24/2013 DATE PROJECTOR A28095 (OFCI) SERIAL [ 2A1 ] IF RA IF C2A CV TO DATA NETWORK (OFCI) RGB IF C2A IF RB WIRELESS LAVALIER MICROPHONE A11235 MIC WIRELESS LAVALIER MICROPHONE TRANSMITTER A11235.1 LAPTOP OR PC (OFOI) CV NETWORKED ROOM CONTROLLER A48110 W3A DVD RECORDER / VCR W / DIGITAL TUNER A21340 (OFCI) TO CATV NETWORK (OFCI) IR NETWORKED ROOM CONTROL PUCK SERIAL A48120 SP-BUS LM CV LL LR ASSISTED LISTENING TRANSMITTER A16110 WIRELESS MICROPHONE RECEIVER A11265 MIC [ 2A1 ] RF ASSISTIVE LISTENING ANTENNA A16110.2 RF RF ASSISTIVE LISTENING RECEIVER A16120.1 LL&LR LL+LR CV CV CV LL LL LL LR LR LR VIDEO DISPLAY A27242 IF FB1B REMOTE CONTROL WALL IR MODULE A48160 IR PWR AUDIO FOLLOW VIDEO PREAMP LM SWITCHER A48150 WALL BOX PASS THRU CPV AUDIO AMPLIFIER A14340 RF RF RGB COMPUTER INTERFACE A22030 IF CABLE CUBBY A63250 SERIAL SP-BUS RGB LL+LR RF AUX (OFCI) CONTROL MODULE A48100 RGB CAMERA (OFOI) SPKR W3A 70V 8W 70V SERIAL 8W LM LL+LR CEILING SPEAKER TILE A15130 (OFCI) MICROPHONE (OFOI) CEILING SPEAKER TILE A15130 (OFCI) MIC VIDEO CONFERENCING DVI CODEC A29060 (OFOI) TO CATV NETWORK (OFCI) AUDIOVISUAL ONE-LINE DIAGRAMS WALL RACK A48320 6 TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - SMALL CONFERENCE ROOM A171H T-401 3 T-401 TYPICAL AUDIOVISUAL ONE-LINE DIAGRAM - COMPUTER LAB/TEACHING B115 T-401 HDMI CAT5 LAPTOP OR PC (BY OWNER) LOCAL USE ONLY RGB RGB HDMI HDMI LL+LR LL+LR UTP AUDIOVISUAL RECEIVER A25510 CAT5 PROJECTOR A28033 TO OWNER PROVIDED NETWORK LAN CV IF C1B AUX (BY OWNER) LL LL LR LR HDMI LL CAT5 RGB HDMI HDMI LL+LR LL+LR UTP AUDIOVISUAL TRANSMITTER A25510 RGB LR [ 4A14 ] IF C1A UTP AUDIOVISUAL RECEIVER A25522 PROJECTOR A28033 SERIAL [ 4V2 ] HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 RGB UTP HDMI AUDIOVISUAL [ 4V2.5 ] TRANSMITTER LL+LR A25510 [ 4A15 ] 60 SEAT CLASSROOM 104 CAT5 RGB Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 HDMI DOCUMENT CAMERA (BY OWNER) A21240 CAT5 [ 4N1 ] RGB [ 4V3 ] UTP AUDIOVISUAL RECEIVER A25522 CV TO OWNER PROVIDED NETWORK LAN DESKTOP TOUCHPANEL A41160 [ 4C1 ] IR DVD/VCR PLAYER (OFCI) A21340 PROJECTOR A28033 LL+LR GOOSENECK MICROPHONE A11120 [ 4A1 ] HDMI [ 4V5.5 ] LL+LR [ 4A18 ] UTP AUDIOVISUAL TRANSMITTER A25510 LL LL LR LR IF C1A CAT5 SERIAL RGB CAT5 RGB [ 4V6 ] CV UTP PATCH PANEL PROJECTOR A28033 SERIAL HDMI RGB HDMI HDMI LL +LR LL+LR LAN RGB RGB UTP AUDIOVISUAL RECEIVER A25522 UTP AUDIOVISUAL TRANSMITTER A25510 TO OWNER PROVIDED NETWORK MIC MIC MIC B ALL POWER REQUIREMENTS INCLUDING BUT NOT LIMITED TO POWER SUPPLIES, POWER DISTRIBUTION AND POWER CORDS ARE TO BE PROVIDED BY CONTRACTOR UNLESS NOTED OTHERWISE C ALL AUDIOVISUAL CABLES SHALL BE ENCASED IN 1 1/4-INCH CONDUIT UNLESS OTHERWISE NOTED HDMI CV [ 4A3 ] IR DVD/VCR PLAYER (OFCI) A21340 LECTURE CAPTURE (BY OWNER) (FOR 110 SEAT CLASSROOM) LM SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT [ 4A9 ] LM LL+LR [ 4A10 ] LM IF FB6E [ 4A11 ] LM CPV HD CAMERA CCU A21040.1 CAT5 CAT5 RGB [ 4A12 ] CAT5 HD CAMERA A21040 EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL SYSTEM(S) SERIAL [ 4C2 ] TYPICAL OF THREE A CAT5 UTP AUDIOVISUAL RECEIVER A25522 [ 4A2 ] MIC GENERAL NOTES (FOR 60 SEAT CLASSROOM) TO OWNER PROVIDED NETWORK LAN LECTURE CAPTURE (BY OWNER) SERIAL UTP AUDIOVISUAL MATRIX SWITCHER A25103 CAT5 PROJECTOR LENS A28033.1 110 SEAT CLASSROOM 108 CAT5 RGB PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com LR IF FB6D CV Empowered Business - Quiet Technology RGB [ 4V5 ] MOVABLE PODIUM (OFCI) UTP AUDIOVISUAL RECEIVER A25522 CAT5 LL [ 4A17 ] IF CABLE CUBBY A63250 IF C1B UTP AUDIOVISUAL RECEIVER A25522 CV [ 4A16 ] MIC RIMROCK GROUP PROJECTOR LENS A28033.1 RGB [ 4V4 ] MIC PROJECTOR LENS A28033.1 CAT5 TO OWNER PROVIDED NETWORK LAN SERIAL S T E RN [ 4A13 ] LAPTOP OR PC (BY OWNER) UTP AUDIOVISUAL RECEIVER A25522 CV [ 4V1 ] RGB PROJECTOR LENS A28033.1 HDMI CAT5 CV UTP AUDIOVISUAL RECEIVER A25522 CAT5 SERIAL UTP AUDIOVISUAL RECEIVER A25522 UTP AUDIOVISUAL RECEIVER A24180 LL + LR UTP AUDIOVISUAL RECEIVER A24440 CAT5 CV WIRELESS LAVALIER MICROPHONE A11235 WIRELESS LAVALIER MICROPHONE TRANSMITTER A11235.1 MIC RF RF WIRELESS MICROPHONE RECEIVER A11265 LM [ 4A14 ] MIC FUTURE DISTANCE LEARNING (BY OWNER) RGB CAT5 [ 4A7 ] UTP AUDIOVISUAL RECEIVER A25522 UTP AUDIOVISUAL RECEIVER A24180 LL + LR CAT5 TIE LINES TO EXISTING SWITCHER IN 200 SEAT CLASS ROOM #A115C 60 SEAT CLASSROOM 104 RGB CPV CAT5 TYPICAL OF THREE HD CAMERA A21040 HD CAMERA CCU A21040.1 CAT5 CAT5 CAT5 SERIAL CV WIRELESS LAVALIER MICROPHONE A11235 WIRELESS LAVALIER MICROPHONE TRANSMITTER A11235.1 MIC LM RF RF WIRELESS MICROPHONE RECEIVER A11265 FUTURE DISTANCE LEARNING (BY OWNER) LL + LR CAT5 SERIAL [ 4C4 ] [ 4A8 ] UTP AUDIOVISUAL RECEIVER A24080 SERIAL [ 4C3 ] SERIAL [ 4C5 ] MIC UTP AUDIOVISUAL RECEIVER A25420 RGB SERIAL [ 4C6 ] CAT5 SERIAL [ 4C7 ] UTP AUDIOVISUAL RECEIVER A25420 UTP AUDIOVISUAL RECEIVER A24080 LL + LR CAT5 SERIAL [ 4C8 ] HDMI LAPTOP OR PC (BY OWNER) LOCAL USE ONLY RGB CAT5 LL+LR [ 4N1 ] TO OWNER PROVIDED NETWORK LAN UTP AUDIOVISUAL RECEIVER A25510 LM [ 4A1 ] [ 4A2 ] [ 4A3 ] AUX (BY OWNER) CV CV LL LL LR LR [ 4A4 ] [ 4V1 ] [ 4A5 ] [ 4A13 ] [ 4A6 ] [ 4A14 ] [ 4A7 ] LAPTOP OR PC (BY OWNER) RGB RGB HDMI HDMI LL+LR LL+LR [ 4A8 ] [ 4V2 ] [ 4A9 ] [ 4V2.5 ] [ 4A10 ] [ 4A15 ] TO OWNER PROVIDED NETWORK LAN [ 4A11 ] [ 4A12 ] MIC LM MIC LM MIC LM [ 4A14 ] ASSISTED LISTENING TRANSMITTER A16110 [ 4A13 ] RGB RGB MIC LM MIC LM MIC LM MIC LM LM DIGITAL SIGNAL PROCESSOR A13340 AUDIO AMPLIFIER A14610 LM LM SPKR LM LM AUDIO AMPLIFIER A14610 70V 70V SPKR 70V IR SERIAL MIC [ 4A4 ] SERIAL IF CABLE CUBBY A63250 SERIAL SERIAL IF FB6D MOVABLE PODIUM (OFCI) CV CV LL LL LR LR RGB RGB HDMI HDMI LL +LR LL+LR SERIAL [ 4C7 ] RGB RGB MIC MIC MIC MIC IF FB6E 110 SEAT CLASSROOM 108 [ 4C1 ] ASSISTED LISTENING ANTENNA A16110.2 RF [ 4C2 ] RF CC [ 4V5.5 ] CC LOUDSPEAKER A15481 RF 70V 30W 70V 30W LOUDSPEAKER A15481 LOUDSPEAKER A15481 CEILING LOUDSPEAKER A15150 30W 30W CEILING LOUDSPEAKER A15150 CEILING LOUDSPEAKER A15150 2 1 MARK CEILING LOUDSPEAKER A15150 10/28/2013 09/24/2013 DATE DESCRIPTION 30W CEILING LOUDSPEAKER A15150 CEILING LOUDSPEAKER A15150 CEILING LOUDSPEAKER A15150 ASSISTED LISTENING RECIEVER A16120.1 2 [ 4C4 ] [ 4C5 ] [ 4C6 ] SCREEN SWITCH A33399.3 [ 4C7 ] [ 4C8 ] CC LOW VOLTAGE OPERATOR A33399.1 CC 2 CEILING PROJECTION SCREEN 87" X 139" A33355 SCREEN SWITCH A33399.3 CC LOW VOLTAGE OPERATOR A33399.1 CC CEILING PROJECTION SCREEN 87" X 139" A33355 2 [ 4A18 ] [ 4V6 ] 70V 70V [ 4C3 ] CC [ 4V5 ] TO OWNER PROVIDED NETWORK LAN CONTROL PROCESSOR A42625 30W 30W ASSISTED LISTENING TRANSMITTER A16110 CC [ 4A16 ] TO OWNER PROVIDED NETWORK LAN SERIAL [ 4V4 ] [ 4A17 ] CEILING LOUDSPEAKER A15150 LM SERIAL 30W SPKR TO OWNER PROVIDED NETWORK MIC ASSISTED LISTENING RECIEVER A16120.1 SPKR SPKR IR GOOSENECK MICROPHONE A11120 RF 70V SPKR LM [ 4V3 ] [ 4C7 ] RF SPKR LOUDSPEAKER A15481 LAN ASSISTED LISTENING ANTENNA A16110.2 SPKR LM SERIAL DESKTOP TOUCHPANEL A41160 FLOOR RACK IN ROOM A107 A51120 RF MIC LM DOCUMENT CAMERA (BY OWNER) A21240 LM [ 4A13 ] LIGHTING CONTROL (BY OTHERS) CC SHADE CONTROL (BY OTHERS) CC LAN CC TO OWNER PROVIDED NETWORK SCREEN SWITCH A33399.3 CC CC LOW VOLTAGE OPERATOR A33399.1 60 SEAT CLASSROOM 104 [ 4A5 ] CC 2 CEILING PROJECTION SCREEN 87" X 139" A33355 SCREEN SWITCH A33399.3 [ 4A6 ] CC CC LOW VOLTAGE OPERATOR A33399.1 CC AUDIOVISUAL ONE-LINE DIAGRAM CEILING PROJECTION SCREEN 87" X 139" A33355 CC CC 1 FLOOR RACK IN ROOM A107 A51120 T-404 AUDIOVISUAL ONE-LINE DIAGRAM FOR 60 SEAT A104 AND 110 SEAT A108 CLASSROOMS LIGHTING CONTROL (BY OTHERS) T-404 110 SEAT CLASSROOM 108 GENERAL NOTES A DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD B THE WORK DETAILED ON THIS SHEET MAY BE DEPENDENT UPON AND/OR MAY AFFECT THE WORK OF THE OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING COORDINATION ISSUES AND DEPENDENCIES BEFORE THEY ARISE. CHANGES NECESSITATED BY THE FAILURE OF THE CONTRACTOR TO COORDINATE WITH OTHER TRADES SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER TO CEILING TO CEILING THREADED ROD THREADED ROD ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EC EC 4"X4" DEVICE BOX EC EC 4" x 4" DEVICE EC EC BOX WITH 2 GANG MUD RING 1" CONDUIT HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 EC EC 1" CONDUIT WALL MOUNT EC EC SC SC EC EC Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 INSULATED THROAT BUSHING 12" MINIMUM BEND RADIUS 1 1/2" PIPE 1" CONDUIT SC SC EC EC 1" CONDUIT ACCESSIBLE CEILING FIXED DOME CAMERA 1" CONDUIT STATION CABLES EXIT CONDUIT DIRECTLY INTO CABLE TRAY. NO ADDITIONAL SUPPORT REQUIRED 6" x 6" x 4" ELECTRICAL BOX MOUNTED WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EC EC EC EC ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL 1" CONDUIT EC EC 6" x 6" x 4" ELECTRICAL BOX MOUNTED WITHIN ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED S T E RN GROUNDING CONDUCTOR EC EC SC SC SC SC 1/4" FIXED DOME CAMERA EC EC SURGE PROTECTION DEVICE 1/2" CONDUIT GROUNDING CONDUCTOR SC SC RIMROCK GROUP BOND CONDUIT TO CABLE TRAY PENDANT MOUNTING BRACKET EC EC 1/2" CONDUIT Empowered Business - Quiet Technology 1" CONDUIT (MINIMUM) "TRAPEZE" TYPE SUPPORT BRACKET SC SC EC EC PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com EC EC EC EC 4" x 4" DEVICE BOX WITH 2 GANG MUD RING SC SC SURGE PROTECTION DEVICE "BASKET" TYPE CABLE TRAY SHOWN FOR ILLUSTRATION ONLY. SEE SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS FIXED DOME CAMERA SC SC CEILING LEVEL WALL WALL WALL WALL STRUCTURE EXTERIOR WALL MOUNTED CAMERA - TYPE F2 WALL MOUNTED CAMERA - TYPE F1 EXTERIOR WALL MOUNTED CAMERA - TYPE P 4" x 4" OUTLET BOX SUBSCRIPT SUBSCRIPT DEFINITION MOUNTING NOTES F1 FLUSH MOUNTED WALL -- F2 FLUSH MOUNTED EXTERIOR WALL -- P PENDANT MOUNTED EXTERIOR WALL -- EXTENSION RING MUDRING 4 ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL TYPICAL TELECOM RACEWAY AND OUTLET - DIRECT TO TRAY 1 SCALE: NONE TYPICAL FACEPLATE (SIX PORT SHOWN) SCALE: NONE J-HOOK TYPE SUPPORT MAY BE HUNG FROM CEILING AND/OR WALL MOUNTED. SEE SPECIFICATIONS TO TELECOM ROOM ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT TO CEILING TO CEILING THREADED ROD THREADED ROD EC EC 4"X4" DEVICE BOX EC EC 1" CONDUIT EC EC STATION CABLES EXIT CONDUIT DIRECTLY INTO CABLE TRAY 4"X4" DEVICE BOX EC EC TO OUTLET BOX SPACE CONSECUTIVE J-HOOKS PER SPECIFICATIONS STRUCTURE J-HOOK PATHWAY MOUNTING BASE EC EC 1" CONDUIT EXTENSION RING WITH EC EC 2 GANG MUD RING EC EC THREADED ROD ALL CABLE AND PATHWAYS ARE TO BE CONCEALED. EXTEND CONDUIT TO SECURITY ROOM SERVICING THIS LEVEL EXTENSION RING WITH EC EC 2 GANG MUD RING EC EC ACCESSIBLE CEILING 1" CONDUIT NON-ACCESSIBLE CEILING INSULATED THROAT BUSHING EC EC MINIMUM BEND RADIUS = 6 x INTERNAL DIAMETER POLE SC SC TO CEILING SUPPORT FIXED DOME SC SC CAMERA FIXED DOME SC SC CAMERA PENDANT MOUNTING SC SC BRACKET THREADED ROD FIXED DOME SC SC CAMERA ACCESSIBLE CEILING MOUNTED CAMERA - TYPE A NON-ACCESSIBLE CEILING MOUNTED CAMERA - TYPE N SURFACE MOUNT HOUSING "TRAPEZE" TYPE SUPPORT BRACKET CONDUIT TO CABLE TRAY (1" MIN) EXPOSED CEILING MOUNTED CAMERA - TYPE S "BASKET" TYPE CABLE TRAY SHOWN FOR ILLUSTRATION ONLY. SEE SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS DEVICE BOX CEILING GRID CABLE SUPPORT/STRAP 2 J-HOOK PATHWAY AND CABLE SUPPORT/STRAP (AV ONLY) SCALE: NONE 1 3/4" MODULAR FURNITURE PANEL 4" MINIMUM CLEARANCE BETWEEN BOX AND CEILING TO DEVICE SUBSCRIPT SUBSCRIPT DEFINITION MOUNTING NOTES A FLUSH MOUNTED ACCESSIBLE CEILING -- N FLUSH MOUNTED NON-ACCESSIBLE CEILING -- S SURFACE MOUNTED EXPOSED CEILING -- PATCH CORD TO JACK 1/2" LOCK RING 1/2" CHASE NIPPLE 2 1 MARK STATION CABLE 10/28/2013 09/24/2013 DATE DESCRIPTION 2 7/8" HUBBELL FACEPLATE HUBBELL BOX 5748IV SECURITY CAMERA DETAILS 7 5 SCALE: NONE WALL STRUCTURE HOLE FOR ANTENNA CEILING TILE TYPICAL PATHWAY/FIRESTOP DEVICE MOUNTING PLATE SHOWN WITH DOOR OPEN FOR CLARITY 3 SCALE: NONE FLEXIBLE CONDUIT TO SYSTEM FURNITURE (1 1/4" MINIMUM) (TELECOM) STUB TO CABLE TRAY CABLE PATHWAY FIRESTOP DEVICE(S). PROVIDE DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USABLE VOLUME OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THE VOLUME OF CABLE TRAY TO BE SERVED ABOVE CEILING OUTLET/RACEWAY - DIRECT TO CABLE TRAY STUB TO CABLE TRAY 1 1/4" CONDUIT FOR AV TO CEILING SPACE ABOVE/BELOW NON-METALLIC RISER RADIUS DROP GUIDE 1 1/4" CONDUIT (DATA) 1 1/4" CONDUIT FOR AV TO CEILING SPACE ABOVE/BELOW WALL WALL WALL 1" CONDUIT TO CABLE TRAY SCALE: NONE 3/4" CONDUIT FOR POWER STUB TO CABLE TRAY FURNITURE FEED COVER JUNCTION BOX - MODULAR FURNITURE FLEXIBLE CONDUIT TO SYSTEM FURNITURE (1 1/4" MINIMUM) (TELECOM) 1 1/4" CONDUIT (AV) 1" CONDUIT (DATA) 3/4" CONDUIT (POWER) 1 1/4" CONDUIT (AV) RADIUS DROP GUIDE FLOOR BOX (SEE ENLARGED VIEW) NOTES: 1. SCREW CEILING BOX INTO CEILING GRID. REFER TO SPECIFICATIONS AND UCB STANDARDS FOR MOUNTING INSTRUCTIONS 2. ELECTRICAL TELECOM CONTRACTOR AND TELECOM CONTRACTOR SHALL COORDINATE TELECOM OUTLET PLACEMENT AND ENCLOSURE ORIENTATION WITH EACH OTHER AND OWNER PRIOR TO INSTALLATION OF WAP ENCLOSURE AND ASSOCIATED CONDUIT 3. TELECOM CONTRACTOR SHALL INSTALL CABLING, TERMINATE, TEST AND DOCUMENT PER SPECIFICATIONS 10 WIRELESS ACCESS ENCLOSURE - CEILING MOUNT SCALE: NONE CABLE TRAY FLOOR BOX (SEE ENLARGED VIEW) 1 1/4" CONDUIT TO CABLE TRAY (DATA) CABLE TRAY TECHNOLOGY DETAILS 1" CONDUIT FOR DATA TO CABLE TRAY FLOOR BOX ENLARGED VIEW FACING VIEW 9 TYPICAL CABLE PATHWAY FIRESTOP DEVICE FOR CABLE TRAY JUNCTION SCALE: NONE FLOOR BOX ENLARGED VIEW SIDE VIEW 8 FLOOR BOX - FLEXIBLE CONDUIT (FC) SCALE: NONE 6 FLOOR BOX - 4 GANG SCALE: NONE 2 T-501 3/4" CONDUIT FOR DATA TO ACCESSIBLE CEILING MINIMUM BEND RADIUS = 6x INTERNAL DIAMETER INSULATED THROAT BUSHING 4 11/16" x 4 11/16" DEVICE BOX WITH 2 GANG MUD RING (AV) AUDIOVISUAL CABLES STUB CONDUIT 6-INCHES INTO ACCESSIBLE CEILING 'C' 4 11/16" x 4 11/16" OUTLET BOX WITH 1 GANG MUD RING (TELECOM) (1) 1 1/4" CONDUIT PROJECTOR POLE MOUNT TO CABLE TRAY GENERAL NOTES 4 11/16" x 4 11/16" DEVICE BOX WITH 2 GANG MUD RING (AV) 4 11/16" x 4 11/16" OUTLET BOX WITH 1 GANG MUD RING (TELECOM) (1) 1 1/4" CONDUIT PROJECTOR POLE MOUNT TO CABLE TRAY FRONT (1) 1" CONDUIT CEILING LEVEL 1 1/4" CONDUIT FOR AV TO ACCESSIBLE CEILING A DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING OR ARE TO BE PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH THE OTHER TRADES AND/OR THE OWNER IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD B THE WORK DETAILED ON THIS SHEET MAY BE DEPENDENT UPON AND/OR MAY AFFECT THE WORK OF THE OTHER TRADES. THE CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING COORDINATION ISSUES AND DEPENDENCIES BEFORE THEY ARISE. CHANGES NECESSITATED BY THE FAILURE OF THE CONTRACTOR TO COORDINATE WITH OTHER TRADES SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER FRONT S T E RN HDR Architecture 303 E 17th Avenue, Suite 1000 Denver, CO 80203-1256 (1) 1" CONDUIT DUPLEX POWER OUTLET DUPLEX POWER OUTLET Robert A.M. Stern Architects LLP 460 West 34th Street New York, NY 10001 WALL STRUCTURE 1/2" CONDUIT FOR POWER ELECTRICAL CONDUIT ELECTRICAL CONDUIT TOP VIEW 'A' DEVICE TOP VIEW ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR PROJECTORS. COORDINATE WITH AV CONTRACTOR FOR LOCATION ELECTRICAL CONTRACTOR TO PROVIDE STRUCTURAL SUPPORT FOR PROJECTORS. COORDINATE WITH AV CONTRACTOR FOR LOCATION 3' 1. 1 3' ATTACH TO STRUCTURE EXTENSION RING NOTES: ATTACH TO STRUCTURE ATTACH TO STRUCTURE RECONFIGURE BASED ON SPECIFIC LOCATION REQUIREMENTS RIMROCK GROUP 1 1/4" CONDUIT FOR AV TO DEVICE BOX Empowered Business - Quiet Technology PO Box 63149 Colorado Springs, CO 80962-3149 Voice: (719) 533-1112 - Fax: (719) 533-1113 info@rimrockgroup.com - www.rimrockgroup.com TYPICAL WALL BOX DETAIL SCALE: NONE ATTACH TO STRUCTURE THREADED ROD THREADED ROD UNISTRUT UNISTRUT 'B' ELECTRICAL CONTRACTOR TO PROVIDE 2' x 3' UNISTRUT RECTANGLE CONDUITS SUBSCRIPT A B C DEFAULT 4 11/16" x 4 11/16" 2 GANG (2) 1 1/4" W1x 4 11/16" x 4 11/16" 1 GANG (1) 1 1/4" W2x 4 11/16" x 4 11/16" 2 GANG (2) 1 1/4" W3x 3 GANG -- (3) 1" W4x 4 GANG -- (4) 1" W6x 6 GANG -- (6) 1" ELECTRICAL CONTRACTOR TO PROVIDE 2' x 3' UNISTRUT RECTANGLE CONDUITS DEVICE BOXES DEVICE BOXES NON ACCESSIBLE CEILING ACCESSIBLE CEILING TO DECK POLE POLE NOTES: 1. 8 WORKING CLEARANCE FOR FACEPLATE DETAILS, REFERENCE: 1/T-505 PROJECTOR MOUNT TYPICAL AUDIOVISUAL RACEWAY AND OUTLET TO DECK 12" THREADED ROD (TYPICAL) PROJECTOR MOUNT SYSTEMS BIOTECHNOLOGY BUILDING - ACADEMIC CLASSROOM BUILD-OUT WORKING 12" CLEARANCE CABLE TRAY H SCALE: NONE 6" W TRAPEZE HANGER (TYPICAL) TOP OF CEILING OR EQUIPMENT FRONT VIEW FRONT VIEW NOTES: "BASKET" TYPE CABLE TRAY SHOWN IS FOR ILLUSTRATION ONLY. REFER TO SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS 9 TOUCH PANEL DETAIL - CP TYPE B 6 SCALE: NONE WIDTH (W) OF CABLE WILL VARY. REFER TO DRAWINGS FOR SPECIFIC WIDTHS. PROVIDE TRAPEZE HANGERS IN WIDTHS TO FIT THE APPLICATION NOTES: NOTES: 1. COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR FOR PROJECTOR PLACEMENT PRIOR TO INSTALLING PROJECTOR STRUCTURAL SUPPORT 1. 2. COORDINATE PROJECTOR THROW WITH OWNER PRIOR TO INSTALLATION 2. COORDINATE PROJECTOR THROW WITH OWNER PRIOR TO INSTALLATION 3. ELECTRICAL CONTRACTOR SHALL ROUTE FLEX CONDUIT FROM PROJECTOR TO JUNCTION BOX LOCATED ABOVE STRUCTURAL SUPPORT. USE RIGID CONDUIT FOR ALL OTHER PROJECTOR CONDUIT REQUIREMENTS 3. ELECTRICAL CONTRACTOR SHALL ROUTE FLEX CONDUIT FROM PROJECTOR TO JUNCTION BOX LOCATED ABOVE STRUCTURAL SUPPORT. USE RIGID CONDUIT FOR ALL OTHER PROJECTOR CONDUIT REQUIREMENTS 4. MOUNT PROJECTOR IN SUCH A WAY AS NOT TO BE OBSTRUCTED BY LIGHT FIXTURES, SPRINKLER HEADS, ETC. 4. MOUNT PROJECTOR IN SUCH A WAY AS NOT TO BE OBSTRUCTED BY LIGHT FIXTURES, SPRINKLER HEADS, ETC. PROJECTOR MOUNT DETAIL - NON ACCESSIBLE CEILING 4 SCALE: NONE COORDINATE WITH OWNER AND AUDIOVISUAL CONTRACTOR FOR PROJECTOR PLACEMENT PRIOR TO INSTALLING PROJECTOR STRUCTURAL SUPPORT HEIGHT (H) OF CABLE TRAY IS CALLED OUT IN THE SPECIFICATIONS PROVIDE CABLE TRAY COMPLETE WITH ALL MATERIALS AND INCIDENTAL HARDWARE NECESSARY FOR A COMPLETE AND FULLY FUNCTIONAL CABLE TRAY SYSTEM, INCLUDING BUT NOT LIMITED TO STRAIGHT SECTIONS, T-JUNCTIONS AND RADIUS (ROUNDED) CORNERS CONFORMING TO TIA/EIA 569 BEND RADIUS REQUIREMENTS, EXPANSION JOINTS, SUPPORT HANGERS, CONNECTOR AND CLAMP ASSEMBLIES, CONNECTOR AND SPLICE PLATES, ETC. INSTALL IN ACCORDANCE WITH NEMA VE 2 (LATEST EDITION), TIA/EIA 569, AND MANUFACTURERS RECOMMENDATION AND INSTRUCTIONS PROJECTOR MOUNT DETAIL - ACCESSIBLE CEILING 2 SCALE: NONE TO ACCESSIBLE CEILING SPACE POWER CABLE TRAY - SINGLE TIER SCALE: NONE WOOD STUDS FINISHED CEILING (1) 3/4" CONDUIT FOR DATA ROUTE CONDUITS FOR DATA AND AV TO CABLE TRAY OR J-HOOK PATHWAY ABOVE ACCESSIBLE CEILING TO WALL 1 1/4" C (AV) TO WALL 2 1 MARK 1 T-503 FLAT PANEL DISPLAY WALL MOUNT CL DESCRIPTION VARIES 6 GANG 1 1/4" C (AV) 10/28/2013 09/24/2013 DATE FLAT PANEL DISPLAY TO WALL 1 1/4" C (AV) WALL (2) 1 1/4" CONDUITS FOR AV FLAT PANEL DISPLAY WALL BOX ROUTE CONDUIT FOR POWER PER ELECTRICAL DRAWINGS WALL CL HORIZONTAL TEE 10" LONG RADIUS BEND 12 3 GANG # 1 GANG VARIES 1 GANG T-502 NOT USED (2) 1 1/4" CONDUITS SCALE: NONE FLOOR BOX (SEE ENLARGED VIEW) TO WALL TO WALL 1 1/4" C (AV) (2) 1 1/4" CONDUITS 3/4" C (POWER) 8" 50" AFF 1" C (DATA) CONCRETE FLOOR 4 11/16" X 4 11/16" BOX WITH 1 GANG MUD RING FLUSH MOUNTED INTO WALL 16" OC 36" AFF TO WALL T.B.D. 4 11/16" X 4 11/16" BOX WITH 2 GANG MUD RING FLUSH MOUNTED INTO WALL POWER OUTLET FLUSH MOUNTED INTO WALL FLOOR BOX ENLARGED VIEW FINISHED FLOOR HORIZONTAL CROSS NOTES: NOTES: 1. 2. 3. # NOT USED SCALE: NONE 7 MAINTAIN CONDUIT SEPARATION AS REQUIRED BY STRUCTURAL ENGIINEER. COORDINATE CONDUIT REQUIREMENT WITH STRUCTURAL ENGINEER/ARCHITECT PRIOR TO INSTALLATION PREFERRED FLOOR BOX AND CONDUIT INSTALLATION IS AS SHOWN. IF FIELD CONDITIONS DICTATE ALTERNATE INSTALLATION, CONDUITS CAN BE ROUTED FROM BOTTOM OF FLOOR BOX AND STUBBED INTO ACCESSIBLE CEILING SPACE BELOW. PATHWAY MUST BE PROVIDED WITHIN INTERSTITIAL WALL SPACE IN QUANTITIES SHOWN AND ROUTED INTO ACCESSIBLE CEILING SPACE ABOVE ROOM SERVICED BY FLOOR BOX. IF FIELD CONDITIONS DO NOT ALLOW FOR ALTERNATE INSTALLATION METHOD, THEN ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ENGINEER PRIOR TO INSTALLATION SCALE: NONE CEILING HEIGHTS MAY VARY. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS 2. WOOD STUDS LOCATED WITHIN INTERSTITIAL WALL SPACE. CENTER WOOD STUDS ON DISPLAY LOCATION. WOOD STUDS SHALL BE IN ADDITION TO OTHER WALL STRUCTURES AND/OR CONSTRUCTION METHODS NOTES: 3. MOUNTING HEIGHT OF DISPLAYS MAY VARY. REFER TO PLAN DRAWINGS FOR MOUNTING HEIGHTS 1. "BASKET" TYPE CABLE TRAY SHOWN IS FOR ILLUSTRATION ONLY. REFER TO SPECIFICATIONS FOR ACTUAL TRAY REQUIREMENTS 4. DEVICE BOX AND CONDUIT LOCATIONS MAY VARY DUE TO FIELD CONDITIONS 2. ALL BENDS SHALL BE LONG RADIUS. 90-DEGREE OR ABRUPT BENDS ARE NOT ACCEPTABLE 3. ELECTRICAL GROUNDING AND BONDING: ALL CONNECTION HARDWARE SHALL BE CHECKED TO ENSURE THAT THEY ARE TIGHTENED AND THAT ALL CABLE TRAY SECTIONS ARE ELECTRICALLY CONTINUOUS AND/OR ELECTRICALLY GROUNDED TO ADJACENT TRAY SECTIONS AND BUILDING EARTH GROUND IN ACCORDANCE WITH GOVERNING REQUIREMENTS DRAWING NOTES: 1. ALL FLOOR BOX INSTALLS THAT PENETRATE ENTIRELY THROUGH THE FLOOR STRUCTURE SHALL HAVE FIRE TREATMENT TO MEET OR EXCEED FIRE RATING OF FLOOR STRUCTURE FLOOR BOX - 11 GANG 1. 5 CENTER LINE IS DENOTED FOR DEVICE BOXES AND NOT VIDEO DISPLAY MOUNT. CONTRACTOR SHALL LOCATE MOUNT AS REQUIRED TO PROVIDE BOTTOM OF SCREEN HEIGHT TYPICAL SMALL CONFERENCE ROOM DISPLAY WALL MOUNT DETAIL SCALE: NONE 3 TECHNOLOGY DETAILS CABLE TRAY BENDS AND JUNCTIONS SCALE: NONE 2 T-503