Megger Cable Fault Location PFL40 series

advertisement
Megger
Cable Fault Location
PFL40 series
1
Megger’s new PFL40-1500/2000
Power Fault Locator.
Fault Identification
LV Pre-Location
Fault Diagnosis
HV Pre-Location
Fault Located
Pinpoint
Fault Location
Fault Located
Fault Located
Fault
Conditioning
PFL40 =
Restoration
2
Megger’s new PFL40-1500/2000
Power Fault Locator.
The PFL40-1500/2000 really is the
“Complete Solution”
3
Megger’s new PFL40-1500/2000
Power Fault Locator.
•
•
•
•
•
•
•
•
•
What we “offer”
Ease of use
9
Cable and fault diagnosis
Fault conditioning
Fault prelocation
Pinpoint fault location
9
Easy to deploy
Rapid , accurate and safe
Tough, field proven equipment
Fully integrated system
9
9
9
9
9
9
9
The PFL40-1500/2000 ticks all the boxes
4
Megger’s new PFL40-1500/2000
Power Fault Locator.
What we “offer”
•
•
•
•
•
•
•
•
•
•
•
•
Fully integrated system
Auto ranging, colour display TDR.
d.c. testing up to 40kV
Leakage current
25mA constant test current
Proof/burn up to 34kV
34kV arc reflection method
Impulse Current
Voltage Decay (optional)
34kV 3-range surge generator (4kV option)
1500joule (optional 2000j)
Safety ground monitor (optional)
5
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
F. The PFL series are portable, stand-alone CFL & HV
system. All CFL & HV testing features in one field
proven case
B. No need to invest in expensive customized test vans
A. No other manufacturer has the same feature set in
one enclosure/case
F. Analogue metering of the voltage and current
B Analogue metering is preferred as fault breakdown,
and ticking faults can be easily identified
A. Analogue metering assists in identifying and
diagnosis the type of fault, essential when deciding
which fault location method to use.
6
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
F. Easy to use PLC control., selects testing methods
B. Selection of HV operations is via this easy to use
PLC control.
A. There has been a trend in recent years to combine all
controls with the TDR. This creates confusion and a
difficult to use instrument
F. 40kV dc testing & 34kV dc proof / burn features.
B. This combination allows d.c. testing (diagnosis) and
high voltage fault conditioning.
A. No other manufacturer offer both these features in
the same unit, they normally offer one or the other.
d.c. testing is used for diagnosis & the proof/burn
mode is used to stabilise difficult to find faults.
7
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
F. 34kV Surge Voltage
B. The 34kV Surge allows the prelocation and pinpoint
location of more difficult faults easier.
A. This a unique feature that no other manufacturer has
in a mobile portable unit.
F. 1500 standard and 2000 joule Surge Energy on all
ranges.
B. The high surge energy enables the creation of a
flashover at the point of fault, in difficult situation.
A. No other manufacturer offers a 3-range 2000joule
surge capability in a single portable unit.
8
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
F. Integrated large colour display TDR.
B. The large colour display, makes fault analysis
easier, and encompasses pulse echo, arc
reflection and impulse current methods of fault
prelocation..
A. The large, uncluttered graphical display enables
quick and accurate fault location. On-board
memory for trace (with parameters) storage and
recall, report generation assists with asset
management.
9
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
F. Developed, manufactured by
Megger.
B. Megger has over 100 years of
experience of supplying test and
measurement equipment
worldwide. Several CFL patents
are also held dating back sever
decades.
A. The customer can be assured that
he is supported by an International
Company, with extensive
experience and an experienced
world-wide network of distributors
and authorised repair agents.
10
Megger’s new PFL40-1500/2000
Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
Patents from the same stable.
1957: Bechtel:
Fault Location in Electrical Cables
1974: Ironside: Multiple Null Bridges
1992: Steiner:
DART (Differential Arc Reflection Techniques
We are Strong !
11
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
SebaKMT: Trading
company of Seba
Dynatronic &
Hagenuk KMT
SFX 40-25
Specification
d.c. Testing
Current trips
Surge
-Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
SFX 40-25
40kV @ 15mA
NO
12.5kV -25kV or
16kv – 32kV
4kV or 8kV
1000joules
2000j (2nd box)
5 – 20 secs
ARM
Impulse Current
Voltage Decay
20kV @ 100mA
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
12
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
SebaKMT: Trading
company of Seba
Dynatronic &
Hagenuk KMT
SFX32
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
SFX 32
32kV @ 15mA
NO
8-16-32kV
-1000joules
1750j
3 - 10 secs
Arc Reflection
Impulse Current
Voltage Decay
32kV @ 160mA
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
13
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
SebaKMT: Trading
company of Seba
Dynatronic &
Hagenuk KMT
SFX 25
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
SFX 25
25kV @ 5mA
NO
12.5 - 25kV
-1120joules
-3 - 9 secs
Arc Reflection
----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
14
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
BAUR
Can be configured
with
SSG1100/1500/2100
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
Syscompact 3000
32kV (850mA max?)
NO
8 – 16 – 32kV
1100–1500–2100j
10 – 30secs
SIM
DC SIM / MIM
Impulse Current
32kV (850mA max?)
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
15
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
BAUR
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
Syscompact 2000
16kV @
NO
8 – 16kV
1024joules
10 – 20secs
SIM
Impulse Current
---
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
16
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
Hiptronics
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
5100-FC
15kV
NO
7.5 or 15kV
-480joules
-6 secs
ARC Reflection
----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
17
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
Hipotronics
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
CF 70 Series
70kV
NO
25kV
-3750joules
7500joules
3 – 30seconds
TDR only
--70kV @ 100mA
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
18
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
VON
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
XF16-1280
16kV
NO
8 – 16kV
-1280joules
2560joules
15 secs
Arc Reflection
----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
19
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
VON
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
--Proof/Burn
XF25-1563
25kV
NO
12-5 – 25kV
-1563joules
3126 joules
15 secs
Arc Reflection
----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
20
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
VON
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
---Proof/Burn
XF28-1960
28kV
NO
14 – 28kV
-1960joules
3920joules
15 secs
Arc Reflection
-----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
21
Megger’s new PFL40-1500/2000
Power Fault Locator.
Competitor (Other Manufacturers!)
VON
2-piece
Specification
d.c. Testing
Current trips
Surge
Optional
Energy
Optional
Surge Rate
Modes
---Proof/Burn
XF32-5120
32kV
NO
8 – 16 – 32kV
-5120joules
-15 secs
Arc Reflection
-----
PFL40-1500/2000
40kV @ 25mA
Selectable
8 – 16 – 34kV
4kV
1500joules
2000j (integrated)
2 – 10sec
Arc Reflection
Impulse Current
Voltage Decay
14kV @ 120mA
34kV @ 60mA
22