IESO Expedited System Impact Assessment T1 Replacement at Richmond South DS 2014-EX720 Final Report Summary Conditional Approval for Connection Hydro Ottawa Ltd. (the “connection applicant”) is proposing to replace T1 at Richmond South DS with a replacement unit due to failure (“the project”). The connection applicant will install the failed unit that was removed under expedited SIA report 2012-EX601. This transformer will be operated without the under load tap changer (ULTC). This assessment concluded that the proposed changes are expected to have no material adverse impact on the reliability of the IESO-controlled grid. Therefore, the IESO recommends that a Notification of Conditional Approval for Connection be issued for the proposed project, subject to implementation of the requirements outlined in this report. Requirements The connection applicant shall satisfy all applicable requirements and standards specified in the Market Rules and the Transmission System Code. The following requirements summarize some of the general requirements that are applicable to the proposed project. 1. The connection applicant shall ensure that the 115 kV equipment is capable of continuously operating between 113 kV and 127 kV, as specified in Appendix 4.1 of the Market Rules. Protective relaying must be set to ensure that transmission equipment remains in-service for voltages up to 5% above the maximum continuous value. 2. If revenue metering equipment is being installed as part of this project, the connection applicant should be aware that revenue metering installations must comply with Chapter 6 of the IESO Market Rules. For more details the connection applicant is encouraged to seek advice from their Metering Service Provider (MSP) or from the IESO metering group 3. The connection applicant must complete the IESO Facility Registration/Market Entry process for the project in a timely manner before the IESO final approval for connection is granted. Final Report Public Page 1 of 3 T1 Replacement at Richmond South DS 2014-EX720 1 Project Description The applicant is proposing to replace T1 at Richmond South DS with a new unit due to failure. The connection applicant will install the failed unit that was removed under expedited SIA report 2012EX601. This transformer will be operated without the under load tap changer (ULTC). Richmond South DS is connected to the 115 kV circuit S7M and C7BM. The expected in-service date for the replacement transformer is June 18, 2014. The technical specifications of the existing and replacement transformers are given in Table 1. Richmond South DS All values for replacement equipment are specified at the time of order. Actual values to be provided prior to inservice dates. Transformer Failed T1 Replacement T1 Configuration Transformation (kV) Winding Configuration Impedance to Ground Three phase 110.0/8.32 Three phase 110.0/8.32 Delta/Wye HV – ungrounded LV – solidly grounded Delta/Wye HV – ungrounded LV – solidly grounded Thermal Rating Continuous Thermal Rating 6.0 MVA ONAN 6.0 MVA ONAN 10.0 MVA 6.0 MVA 10-DAY Thermal Rating 15-MIN Thermal Rating Positive Sequence Impedance (H-L) Under-load tap-changer Off-load tap-changer In Service OLTC position Not applicable. The transformer will be off loaded if required. R = not known X = 8.95% on 6 MVA base R = not known X = 8.5% on 6 MVA base LV ± 10%, 16 steps Tap 1: 118.25 kV Tap 2: 115.5 kV Tap 3: 112.75 kV Tap 4: 110.0 kV Tap 5: 107.25 kV Tap 2: 115.5 kV Not operable Tap 1: 118.25 kV Tap 2: 115.5 kV Tap 3: 112.75 kV Tap 4: 110.0 kV Tap 5: 107.25 kV To be advised Table 1 – Comparison of Transformer Parameters at Richmond South DS Final Report Public Page 2 of 3 T1 Replacement at Richmond South DS 2014-EX720 2 Assessments See the expedited SIA report 2012-EX601 for an assessment of load peaks and load projects and load angle assessment. The continuous rating of the replacement transformer is 6.0 MVA and therefore, there is a deficiency when compared to the 2012 peak load of 7.1 MVA. Hydro Ottawa Ltd. has advised that they would allow the transformer to be loaded slightly higher until they were able to off load to another transformer. 2.1 Conclusions It can be concluded that the replacement of T2 at Richmond South DS with a new transformer will not result in a material adverse impact on the reliability of the IESO-controlled grid provided that all requirements in this report are met. --End of Document-- Final Report Public Page 3 of 3