R Electrical Part 1

advertisement
SOME OF THESE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECT
V
DOWNLIGHT/INDUSTRIAL FIXTURE, SURFACE OR PENDANT MOUNTED.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
SINGLE DIRECTIONAL, WALLWASH LIGHT FIXTURE, RECESSED IN CEILING.
DENOTES WALL MOUNTED OVER COUNTER, 6" ABOVE BACK SPLASH UON.
DUAL DIRECTIONAL, WALLWASH LIGHT FIXTURE, RECESSED IN CEILING.
INDOOR FAN POWERED VAV BOX MOTOR, SINGLE PHASE, MOUNTED FROM STRUCTURE
ABOVE, NIEC. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTED
MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO VAV BOX WITH 2 #12
CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR.
'G' DENOTES GROUND FAULT CURRENT INTERRUPTER (GFCI), 'A' DENOTES ARC FAULT
CURRENT INTERRUPTER (AFCI).
SINGLE DIRECTIONAL, WALLWASH LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
AF
A
PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS.
SHADING DENOTES DEVICE CONNECTED TO EMERGENCY POWER CIRCUIT.
SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE
WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS:
A: 30A, NON-FUSED
AF: 30A, FUSED
B: 60A, NON-FUSED
BF: 60A, FUSED
C: 100A, NON-FUSED
CF: 100A, FUSED
D: 200A, NON-FUSED
DF: 200A, FUSED
E: 400A, NON-FUSED
EF: 400A, FUSED
F: 600A, NON-FUSED
FF: 600A, FUSED
G: 800A, NON-FUSED
GF: 800A, FUSED
SHADING DENOTES DEVICE WITH ISOLATED GROUND.
1
MAGNETIC MOTOR STARTER. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER.
1
COMBINATION MAGNETIC MOTOR STARTER/SAFETY DISCONNECT SWITCH. ADJACENT
NUMBER INDICATES NEMA SIZE OF STARTER.
DUAL DIRECTIONAL, WALLWASH LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
SHADING DENOTES SPLIT WIRED DEVICE.
T
VFD
VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT FURNISHED AND INSTALLED
UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS
DIVISION AS NOTED ON PLANS.
SHADING DENOTES SPECIALTY DEVICE, TYPE AS NOTED ON PLANS.
LINEAR WALLWASH LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
LINEAR, MULTI-HEAD, ADJUSTABLE ACCENT LIGHT FIXTURES, RECESSED IN CEILING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
SCONCE LIGHT FIXTURE, WALL MOUNTED.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR
FITTING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED
POKE-THRU FLOOR FITTING.
T
J
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION FLOOR
PENETRATION, +12" UON.
P T
P
S
T
S
FLOODLIGHT FIXTURE, STANCHION MOUNTED ABOVE GRADE.
SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON.
SM
CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING.
FLEXIBLE METALLIC CONDUIT.
LIGHTING CONTROL OCCUPANCY SENSOR WITH SINGLE LEVEL SWITCHING, WALL
MOUNTED, +42" UON.
M
LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED FOR AREA COVERAGE.
D
PRESET SCENE CONTROL LIGHTING STATION WITH DIMMING CAPABILITIES, WALL MOUNTED,
+42" UON. REFER TO PLANS AND SCHEDULES FOR CONTROL.
CONDUIT TURNED DOWN.
EGRESS LIGHTING TRANSFER DEVICE
PC
PHOTOELECTRIC CELL
DS
DAYLIGHT SENSOR, SUBSCRIPTS ARE SWITCH LEGS CONTROLLED
a,b
BID ALTERNATES
BATTERIES.
NEUTRAL SERVICE DISCONNECT LINK.
NO.
C:\Users\jleite\Documents\Center St_jleite.rvt
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E0.1 SYMBOLS LIST AND DRAWING INDEX.DWG
Last Plotted: 2016-04-01
Last saved by: PAUL(2016-03-23)
DIGITAL METERING UNIT.
WHM
WATT HOUR METER.
GND
GROUND BUS.
NEU
NEUTRAL BUS.
BELOW FINISHED CEILING
NC
NORMALLY CLOSED
BOC
BACK OF CURB
NF
NON-FUSED
BPS
BOLTED PRESSURE CONTACT SWITCH
NIEC
NOT IN ELECTRICAL CONTRACT
C
CONDUIT
NO
NORMALLY OPEN
CCTV
CLOSED CIRCUIT TELEVISION
NTS
NOT TO SCALE
CL
CURRENT LIMITING CIRCUIT BREAKER
OR FUSE
OC
ON CENTER
OFCI
CP
CIRCULATION PUMP
OWNER FURNISHED CONTRACTOR
INSTALLED
CKT
CIRCUIT
PDU
POWER DISTRIBUTION UNIT
CT
CURRENT TRANSFORMER
PIV
POST INDICATING VALVE
CU
COPPER
PNL
PANEL
DF
DRINKING FOUNTAIN
PT
POTENTIAL TRANSFORMER
DW
DISH WASHER
PVC
POLYVINYL CHLORIDE
(E)
EXISTING TO REMAIN
RF
REFRIGERATOR
EC
ELECTRICAL CONTRACTOR
(R)
EXISTING TO BE REMOVED
EF
EXHAUST FAN
(RL)
RELOCATED
EP
EXPLOSION PROOF
(RR)
REMOVE AND RELOCATE
EPO
EMERGENCY POWER OFF
RSC
RIGID STEEL CONDUIT
EMCS
ENERGY MANAGEMENT CONTROL
SYSTEM
SAD
SEE ARCHITECTURAL DRAWINGS
SPD
SURGE PROTECTION DEVICE
EMT
ELECTRICAL METALLIC TUBING
TC
TIME CLOCK
ETD
EMERGENCY TRANSFER DEVICE
TGB
TELECOMMUNICATIONS GROUND BUS
EVCS
ELECTRIC VEHICLE CHARGING STATION
TP
TWISTED-PAIR
EWH
ELECTRIC WATER HEATER
TX
TRANSFORMER
F
FUSED
TYP
TYPICAL
(F)
FUTURE
UON
UNLESS OTHERWISE NOTED
UPS
UNINTERRUPTIBLE POWER SUPPLY
UR
UNDERCOUNTER REFRIGERATOR
V
VOLTS
VA
VOLTS-AMPS
VAV
VARIABLE AIR VOLUME
DESCRIPTION
A: Priority Items to be Included in Total Bid Price
A1
HIGH SPEED ROLL-UP DOORS AT VEHICLE ENTRIES
A2
VISION LIGHT AT ELEVATORS
A3
ADDISON ST. & CENTER ST. GROUND FLOOR LOBBY WALL FINISH - DURAROCK
A4
ADDISON ST. & CENTER ST. GROUND FLOOR LOBBY WALL FINISH - CERAMIC
TILE
B: Bid Alternates
B1
Lighting:
a. ACCENT LIGHTING AT ROOF CANOPY - TYPE F5
b. ACCENT COLOR BLAST UPLIGHT ON BOTTOM OF SLABS
c. GUARDRAIL LIGHTING AT 2ND FLOOR WALKWAYS INSTEAD OF
d. STAIR DOWNLIGHTS AT SUPPORT BEAMS
B2
B3
PHOTOVOLTAIC SYSTEM:
a. INCREASE THE PV ARRAY TO MAXIMUM COVERAGE.
b. BATTERY STORAGE FOR SMART PV ARRAY - BASED ON MAXIMUM SIZE
c. DEDUCT FOR SWITCHGEAR REDUCTION FOR INITIAL PV ARRAY
MICROGRID SYSTEM (ENTIRE)
FLA
FULL LOAD AMPERES
FMC
FLEXIBLE METAL CONDUIT
FSD
FIRE/SMOKE DAMPER
HEAT DETECTOR INITIATING DEVICE, STRUCTURE MOUNTED ABOVE SUSPENDED CEILING TO
SURFACE JUNCTION BOX.
VFD
VARIABLE FREQUENCY DRIVE
FSEC
FOOD SERVICE EQUIPMENT
CONTRACTOR
VM
VENDING MACHINE
MANUAL PULL STATION INITIATING DEVICE, WALL MOUNTED AT +48" UON.
FRAP
FIREMAN'S REMOTE ANNUNCIATOR
PANEL
W
WATTS
MOTOR OPERATED FIRE/SMOKE DAMPER 'FSD', NIEC. SYMBOL DENOTES INTERFACE
FOR POWER, CONTROL AND POSSIBLY MONITORING CONNECTIONS FROM FIRE ALARM
SYSTEM. ALSO, INCLUDES LOCAL POWER DISCONNECT MEANS. 'ES' BY FSD INDICATES END
SWITCH CONNECTIONS FOR MONITORING BOTH 'OPEN' AND 'CLOSED POSITIONS.
ADJACENT NUMBER INDICATES QUANTITY OF ACTUATORS AND END SWITCH GROUPS
REQUIRING CONNECTION PER FSD, IF MORE THAN 1.
WAP
WIRELESS ACCESS POINT
G
GROUND
WH
WATER HEATER
GB
GROUND BUS
WP
WEATHERPROOF
GD
GARBAGE DISPOSAL
2SP
TWO SPEED
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
1Ø
1 PHASE
SPRINKLER SYSTEM WATER FLOW SWITCH, NIEC. SYMBOL DENOTES INTERFACE FOR
MONITORING CONNECTION FROM FIRE ALARM SYSTEM.
GND
GROUND
3Ø
3 PHASE
GRAP
GENERATOR REMOTE ANNUNCIATOR
PANEL
1P
1 POLE
GWH
GAS WATER HEATER
2P
2 POLE
HPC
HIGH PRESSURE CONTACT SWITCH
3P
3 POLE
HVAC
HEATING,VENTING AND AIR
CONDITIONING
3W
3 WIRE
4W
4 WIRE
IMC
INTERMEDIATE METAL CONDUIT
IWH
INSTANTANEOUS OR POINT OF USE
WATER HEATER
JB
JUNCTION BOX
END-OF-LINE RESISTOR.
CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF
CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT
SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS):
MAGNETIC TYPE DOOR HOLD OPEN/RELEASE DEVICE, WALL MOUNTED, NIEC. SYMBOL
DENOTES INTERFACE FOR POWER AND CONTROL CONNECTIONS FROM FIRE ALARM
SYSTEM.
AUDIBLE NOTIFICATION APPLIANCE, WALL MOUNTED, 6" BELOW CEILING OR +80" AFF,
WHICHEVER IS LOWER.
E0.2
ELECTRICAL SCHEDULES
E0.3
TITLE 24
E0.4
TITLE 24
E0.5
TITLE 24
E2.1
GROUND LEVEL POWER AND SIGNAL PLAN
E2.2
SECOND LEVEL POWER AND SIGNAL PLAN
E2.3
THIRD LEVEL POWER AND SIGNAL PLAN
VISIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED IN FLUSH BACK BOX. NUMBER
ASSOCIATED WITH 'cd' REPRESENTS CANDELA RATING OF STROBE.
E2.4
FOURTH LEVEL POWER AND SIGNAL PLAN
E2.5
FIFTH LEVEL POWER AND SIGNAL PLAN
AUDIBLE/VISIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED IN FLUSH BACK BOX.
NUMBER ASSOCIATED WITH 'cd' REPRESENTS CANDELA RATING OF STROBE.
E2.6
SIXTH LEVEL POWER AND SIGNAL PLAN
E2.7
SEVENTH LEVEL POWER AND SIGNAL PLAN
E2.8
ROOF POWER AND SIGNAL PLAN
E3.1
GROUND LEVEL LIGHTING PLAN
E3.2
SECOND LEVEL LIGHTING PLAN
E3.3
THIRD LEVEL LIGHTING PLAN
E3.4
FOURTH LEVEL LIGHTING PLAN
E3.5
FIFTH LEVEL LIGHTING PLAN
E3.6
SIXTH LEVEL LIGHTING PLAN
E3.7
SEVENTH LEVEL LIGHTING PLAN
E3.8
ROOF LIGHTING PLAN
E4.1
ENLARGED PLANS
E5.1
SINGLE LINE DIAGRAMS
E5.2
PANEL SCHEDULES
E5.3
SINGLE LINE LOW VOLTAGE DIAGRAMS
E6.1
ELECTRICAL DETAILS
E6.2
ELECTRICAL DETAILS
E6.3
ELECTRICAL DETAILS
E6.4
ELECTRICAL DETAILS
VISIBLE NOTIFICATION APPLIANCE, WALL MOUNTED, 6" BELOW CEILING OR +80" AFF,
WHICHEVER IS LOWER. NUMBER ASSOCIATED WITH 'cd' REPRESENTS CANDELA RATING
OF STROBE.
TWO PIECE SURFACE METAL RACEWAY, MOUNTED AS NOTED IN PLANS.
CABLE TRAY, CABLE RUNWAY OR LADDER RACK SUSPENDED FROM STRUCTURE
ABOVE. REFER TO PLANS FOR SIZE AND MOUNTING.
AUDIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED IN FLUSH BACK BOX.
NAME
2004
NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY.
EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER ANOTHER
SECTION AND WIRED UNDER THIS SECTION.
A
2-F3
A
ALARM MONITORING CONTACT, MOUNTED AS NOTED ON PLANS.
EL
ELECTRIC MORTISE DOOR LOCK, NIEC, BUT WIRED UNDER THIS DIVISION.
ES
ELECTRIC DOOR STRIKE, NIEC, BUT WIRED UNDER THIS DIVISION.
ML
ELECTROMAGNETIC DOOR LOCK, NIEC, BUT WIRED UNDER THIS DIVISION.
EP
ELECTRIFIED PANIC HARDWARE, NIEC, BUT WIRED UNDER THIS DIVISION.
MP
MECHANICAL PANIC HARDWARE, NIEC, BUT WIRED UNDER THIS DIVISION.
RX
REQUEST-TO-EXIT SWITCH, NIEC, FURNISH WITH DOOR HARDWARE AND WIRED UNDER
THIS DIVISION.
P
POWER TRANSFER HINGE, NIEC.
R
DOOR RELEASE MOTION SENSOR, WALL OR CEILING MOUNTED ABOVE DOOR, UON.
D
DURESS STATION, MOUNTED AS NOTED ON PLANS.
M
AREA MOTION SENSOR, CEILING MOUNTED, UON.
M
AREA MOTION SENSOR, WALL MOUNTED, +84" UON.
GB
GLASS BREAK DETECTOR, CEILING MOUNTED, UON.
CR
CARD READER CONTROLLER, WALL MOUNTED, +36" UON.
K
KEY PAD CONTROLLER, WALL MOUNTED, +42" UON.
PS
REMOTE MOUNTED POWER SUPPLY FOR LOW-VOLTAGE EQUIPMENT CONNECTIONS.
FEEDER SIZE. REFER TO FEEDER SCHEDULE.
DETAIL REFERENCE:
FIXTURE IDENTIFICATION TAG:
FIXTURE TYPE
QUANTITY
DRAWING
TITLE
SYMBOLS LIST AND DRAWING INDEX
FIREMAN'S TELEPHONE JACK, WALL MOUNTED, +42" UON.
1
DRAWING
NUMBER
E0.1
AUDIBLE/VISIBLE NOTIFICATION APPLIANCE, WALL MOUNTED, 6" BELOW CEILING OR
+80" AFF, WHICHEVER IS LOWER. NUMBER ASSOCIATED WITH 'cd' REPRESENTS
CANDELA RATING OF STROBE.
E2.1, E4.1
E2.1, E3.1
E2.1
E2.1, E3.1
FIREMAN'S FAN CONTROL PANEL
CONDUIT SLEEVE, WITH INSULATING BUSHINGS.
SHEET NUMBER
DETAIL DESIGNATION
INCLUDE IN TOTAL BID PRICE, PROVIDE BREAKOUT COST
1A
TENANT IMPROVEMENTS FOR ART DISPLAY
1B
AUDIO VISUAL FOR ART DISPLAY
2
TENANT IMPROVEMENTS FOR BIKE STATION, CAFÉ AND BIKE LINK
FFCP
EOL
N/A
N/A
N/A
N/A
E2.8
E2.1, E4.1
E5.1
FIRE ALARM JUNCTION BOX
DIFFERENTIAL PRESSURE SWITCH, NIEC. SYMBOLS DENOTES INTERFACE FOR
MONITORING CONNECTION FROM FIRE ALARM SYSTEM TO ANNUNCIATE FAN OPERATION.
INCLUDE A REMOTE MOUNTED ADDRESSABLE MONITORING MODULE AT EACH LOCATION.
ELECTRICAL
DOCUMENT
LOCATION
E3.8
E3 SERIES
E3.2
E3 SERIES
FAJB
REMOTE MOUNTED SINGLE INPUT, ADDRESSABLE, MONITORING MODULE FOR INITIATING
CIRCUIT CONNECTION.
ONE CATEGORY 6 CABLE, FIXED POSITION IP CAMERA, MOUNTED AS NOTED ON PLANS.
Architecture / Engineering / Consulting
560 - 14th Street Suite 300
Telephone 510 473 0300
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
Revision
Date
Date
Project No.
Drawn By
Checked By
Scale
Drawing Title:
SYMBOL LIST AND
DRAWING INDEX
ONE CATEGORY 6 CABLE, PAN/TILT/ZOOM (PTZ) IP CAMERA, MOUNTED AS NOTED ON
PLANS.
SECURITY SYSTEM MONITOR/S.
NVR
NETWORK VIDEO RECORDER/SERVER.
Oakland, CA 94612
Fax 510 473 0310
ISSUE KEY:
ISSUED AS PART OF A SET
ALLOWANCES:
PARKING ACCESS CONTROL & EQUIPMENT WILL BE NOTED AS AN
ALLOWANCE FOR THE CONTRACTOR TO CARRY IN THE BID. INSTALLTAION BY
CONTRACTOR.
CA 94704
Oakland
Irvine
Los Angeles
FIRE ALARM CONTROL PANEL
DPS
PS
BERKELEY,
FACP
REMOTE MOUNTED PROGRAMMABLE CONTROL RELAY MODULE FOR ADDRESSABLE
CONTROL.
MULTI-OUTLET TWO PIECE SURFACE RACEWAY; TYPE, DEVICE SPACING AND
MOUNTING AS NOTED ON PLANS.
EMERGENCY GENERATOR.
DMU
BFC
CR
1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON.
2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG
CONDUCTORS, UON.
3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10 AWG
CONDUCTORS, UON.
AUTOMATIC TRANSFER/BY-PASS ISOLATION SWITCH.
NORMALLY CLOSED CONTACT.
NEW
AIR PRESSURE SWITCH FOR PRE ACTION SPRINKLER SYSTEMS, NIEC. SYMBOL
DENOTES INTERFACE FOR MONITORING CONNECTION FROM FIRE ALARM SYSTEM.
INCLUDE A REMOTE MOUNTED ADDRESSABLE MONITORING MODULE AT EACH LOCATION.
CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS.
LIGHTING CONTROL OCCUPANCY SENSOR WITH SINGLE DIMMER, WALL MOUNTED, +42"
UON.
NORMALLY OPEN CONTACT.
(N)
REMOTE MOUNTED DUAL INPUT, ADDRESSABLE, MONITORING MODULE FOR INITIATING
CIRCUIT CONNECTION.
CONDUIT TURNED UP
CONTROL STATION, WALL MOUNTED, +42" UON.
CONTROL CONTACTOR.
BUILDING AUTOMATION SYSTEM
DM
CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET.
LIGHTING CONTROL OCCUPANCY SENSOR WITH DUAL LEVEL SWITCHING, WALL MOUNTED,
+42" UON.
ETD
SURGE PROTECTION DEVICE, 'SPD'.
BAS
CONDUIT RUN EXPOSED ON WALL OR CEILING.
LOW-VOLTAGE LIGHTING CONTROL SWITCHING STATION, WALL MOUNTED, +42" UON. REFER
TO PLANS AND SCHEDULES FOR DEVICE QUANTITIES AND RELAYS CONTROLLED
EM.
SPD
MICROWAVE
SPRINKLER SYSTEM POST INDICATING VALVE 'PIV', NIEC. SYMBOL DENOTES INTERFACE
FOR MONITORING CONNECTION FROM FIRE ALARM SYSTEM. INCLUDE A REMOTE
MOUNTED ADDRESSABLE MONITORING MODULE AT PIV.
CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.
CURRENT TRANSFORMERS.
NORM.
MW
SPRINKLER SYSTEM TAMPER SWITCH, NIEC. SYMBOL DENOTES INTERFACE FOR
MONITORING CONNECTION FROM FIRE ALARM SYSTEM.
WALL BOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND
FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DE-RATING WHEN INSTALLED
GANGED LOCATIONS.
LINE-VOLTAGE MULTIPLE GANG SWITCHING STATION, WALL MOUNTED, 42" UON. REFER TO
PLANS FOR DEVICE QUANTITIES AND TYPES.
M
2
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD ELEMENT, MOUNTED
ADJACENT TO MOTOR.
S
L
F
STEPLIGHT FIXTURE, WALL MOUNTED.
SINGLE-POLE, SINGLE-THROW, EXPLOSION PROOF SWITCH, WALL MOUNTED, +42" UON.
GROUND FAULT ALARM, NO SHUNT TRIP.
AUTOMATIC OR MANUAL TRANSFER SWITCH.
AUTOMATIC TRANSFER SWITCH
HEAT DETECTOR INITIATING DEVICE, CEILING MOUNTED ON FLUSH OR SURFACE JUNCTION
BOX.
PILOT LIGHT, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
EP
S
M1
POTENTIAL TRANSFORMERS.
ATS
PROJECTED BEAM SMOKE DETECTOR INITIATING DEVICES TO INCLUDE TRANSMITTER,
BR RECEIVER AND REMOTE INDICATOR STATION, WALL OR PENDANT MOUNTED IN FLUSH
OR SURFACE JUNCTION BOX AS NOTED ON PLANS. BT=BEAM TRANSMITTER, BR=BEAM
RECEIVER.
BT
LINEAR SIGN LIGHT FIXTURE, STANCHION MOUNTED ABOVE GRADE.
INDICATES ELECTRICALLY OPERATED WHEN ASSOCIATED WITH CIRCUIT BREAKER.
CONNECTION TO GROUND.
TWO CATEGORY 6 CABLES U.O.N.,TELECOMMUNICATION DEVICE, MOUNTED ABOVE
ACCESSIBLE CEILING IN SURFACE MOUNT BOX.
SINGLE-HEAD AREA POST-TOP LIGHT FIXTURE WITH POLE, MOUNTED TO CONCRETE BASE.
KEY-OPERATED, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER THIS
DIVISION, WALL MOUNTED, +42" UON.
TC
S
TRANSFORMER.
MANUAL TRANSFER SWITCH
SMOKE DETECTOR INITIATING DEVICE, IN-DUCT MOUNTED TYPE AT, DUCTED FSD'S.
GROUND WELL MOUNTED FLUSH IN FINISHED GRADE.
F
S
MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER.
UTILITY METER.
MTS
SMOKE DETECTOR INITIATING DEVICE, STRUCTURE MOUNTED ABOVE SUSPENDED
CEILING TO SURFACE JUNCTION BOX.
LIGHT FIXTURE BOLLARD, MOUNTED TO CONCRETE BASE.
MANUAL MOTOR STARTER/DISCONNECT SWITCH, MOUNTED ADJACENT TO MOTOR.
D
S
GROUND FAULT RELAY WITH SHUNT TRIP.
MAIN TELECOM GROUND BUS
AMPERE OVERCURRENT TRIP (WHEN
APPLIED TO CIRCUIT BREAKERS)
SMOKE DETECTOR INITIATING DEVICE, CEILING MOUNTED ON FLUSH OR SURFACE JUNCTION
BOX.
AREA LIGHT FIXTURE, SURFACE OR RECESSED MOUNTED TO WALL.
M
S
INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
INDICATES KIRK-KEY INTERLOCK WHEN ASSOCIATES WITH OVERCURRENT PROTECTION
DEVICES. ADJACENT NUMBER CORRESPONDS WITH DEVICE INTERLOCK.
MTGB
AT
SMOKE DETECTOR INITIATING DEVICE, DUCT-MOUNTED TYPE WITH SAMPLING TUBE,
LOCATED AT SUPPLY AIR FANS 2000cfm AND LARGER.
TWO-HEAD AREA LIGHT FIXTURES WITH BRACKET ARMS AND POLE, MOUNTED TO
CONCRETE BASE.
SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
K
S
INDICATES SHUNT TRIP WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES.
TWO CATEGORY 6 CABLES U.O.N.,TELECOMMUNICATION DEVICE, MOUNTED IN FLOOR
MONUMENT.
QUANTITY OF DATA AND/OR VOICE TELECOMMUNICATIONS DEVICES.
#D/#V
SINGLE-HEAD AREA LIGHT FIXTURE WITH BRACKET ARM AND POLE, MOUNTED TO
CONCRETE BASE.
ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE-THRU
FLOOR FITTING WITH KO IN COVER TO ACCEPT FURNITURE WHIP.
P
FOUR-WAY SWITCH, WALL MOUNTED, +42" UON.
INDICATES COMMUNICATION NETWORK WIRING WHEN ASSOCIATED WITH CIRCUIT
BREAKER.
ALUMINUM
ONE CATEGORY 6 CABLE U.O.N., EMERGENCY TELEPHONE WITH BLUE LIGHT.
EXTERIOR:
ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION FEEDS,
MOUNTED IN FLUSH FLOOR BOX WITH KO'S IN COVER TO ACCEPT FURNITURE WHIPS
BOLTED PRESSURE OR HIGH PRESSURE CONTACT SWITCH.
C
EMPTY CONDUIT
AL
EXIT SIGN LIGHT FIXTURE, CEILING OR WALL MOUNTED WITH DIRECTIONAL ARROWS AS
NOTED ON PLANS. WORD 'EXIT' TO BE LOCATED IN SHADED FACE(S).
ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON. CONSISTS
OF 4 11/16" SQ. X 2 1/8" DEEP. JUNCTION BOX, SINGLE GANG RING, AND STAINLESS STEEL
COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP.
P
THREE-WAY SWITCH, WALL MOUNTED, +42" UON.
INDICATES INTEGRAL GROUND FAULT RELAY WHEN ASSOCIATED WITH CIRCUIT BREAKER.
MTC
ASYMMETRIC INTERRUPTING CURRENT
TWO CATEGORY 6A CABLES, WIRELESS ACCESS POINT, CEILING MOUNTED.
FULL SHADING OF ANY FIXTURE INDICATES STANDBY/CRITICAL LIGHTING.
INDICATES CABLE TERMINATION LUGS AT EQUIPMENT BUS.
G
EMPTY
AIC
TWO CATEGORY 6A CABLES, WIRELESS ACCESS POINT, WALL MOUNTED, 8" BFC UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE
ABOVE. TYPE AS NOTED ON PLANS.
POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING. TYPE
AS NOTED ON PLANS.
INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
MT
TWO CATEGORY 6 CABLES U.O.N.,TELECOMMUNICATION DEVICE, MOUNTED IN
FIRE-RATED POKE-THRU FLOOR FITTING.
EMERGENCY SELF-POWERED BATTERY PACK WITH LIGHT FIXTURE HEADS AS NOTED ON
PLANS OR IN FIXTURE SCHEDULE.
COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX.
TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.
DEVICE BRANCH CIRCUIT POWER DISTRIBUTION BOX FOR INTERFACE BETWEEN
MULTI-CIRCUIT HOMERUN AND MC CABLE BRANCH CIRCUITING. MINIMUM BOX SIZE IS
10"X10"X4" DEEP. BOX MOUNTED FROM STRUCTURE ABOVE IN ACCESSIBLE CEILING
SPACE. ADJACENT NUMBERS INDICATE CIRCUITS AVAILABLE AT BOX.
GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER.
MAIN LUGS ONLY
ABOVE FINISHED FLOOR
LINEAR TRACK SYSTEM WITH PLUG-IN ADJUSTABLE LIGHT FIXTURE HEADS. TRACK SHALL
BE EITHER RECESSED, SURFACE OR PENDANT MOUNTED TO CEILING AS NOTED IN FIXTURE
SCHEDULE.
COMBO EXIT SIGN AND EGRESS LIGHTING FIXTURE, CEILING OR WALL MOUNTED WITH
ARROWS AS NOTED ON PLANS OR IN FIXTURE SCHEDULE.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLOOR MONUMENT.
ELECTRICAL VEHICLE CHARGING STATION, PEDESTAL MOUNTED.
MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH.
MLO
AFF
ELECTRIFIED FURNITURE PARTITION TELECOMMUNICATION CABLE FEEDS, MOUNTED
IN FIRE-RATED POKE-THRU THRU FLOOR FITTING WITH 1 1/4" KO'S IN COVER TO
ACCEPT FURNITURE WHIPS.
DECORATIVE CHANDELIER OR BOWL TYPE FIXTURE, PENDANT MOUNTED.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
DRIVEN GROUND ROD IN GROUND WELL WITH COVER.
FUSED SWITCH.
MOTOR CONTROL CENTER
ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION
FEEDS, MOUNTED IN FLUSH FLOOR BOX WITH KO'S IN COVERS TO ACCEPT FURNITURE
WHIPS. TELECOMMUNICATIONS WHIP SHALL BE 1 1/4" MINIMUM.
P T
HALF SHADING OF ANY FIXTURE INDICATES LIFE SAFETY/EGRESS LIGHTING.
BRANCH CIRCUIT POWER DISTRIBUTION BOX OF MANUFACTURED WIRING SYSTEM WITH
MODULAR CONNECTORS FOR INTERFACE TO BRANCH CIRCUIT MODULAR CABLE SETS
AND CABLE OR CONDUIT HOMERUN. BOX MOUNTED FROM STRUCTURE ABOVE IN
ACCESSIBLE CEILING SPACE. ADJACENT NUMBERS INDICATE CIRCUITS AVAILABLE AT
BOX.
MCC
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
DRIVEN GROUND ROD.
ELECTRICAL VEHICLE CHARGING STATION, WALL MOUNTED.
MAIN CIRCUIT BREAKER
ELECTRIFIED FURNITURE PARTITION TELECOMMUNICATION CABLE FEED, WALL
MOUNTED, +18" UON. CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP. JUNCTION BOX, SINGLE
GANG RING, AND STAINLESS STEEL COVERPLATE WITH 1 1/4" KO AND GROMMET.
WRAP EXPOSED CABLE WITH SPIRAL WRAP.
LINEAR WALLWASH LIGHT FIXTURE, RECESSED IN CEILING.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
VARIABLE FREQUENCY DRIVE FURNISHED AND INSTALLED UNDER ANOTHER DIVISION.
PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
MCB
COMBINATION POWER/TELECOMMUNICATION DEVICES, MOUNTED IN FIRE-RATED
POKE-THRU FLOOR FITTINGS. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.
ADJUSTABLE ACCENT LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDER
ANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER
SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
VFD
AMPERE OVERCURRENT FRAME SIZE
(WHEN APPLIED TO CIRCUIT BREAKERS)
OR AMPERE FUSE SIZE (WHEN APPLIED
TO FUSES)
TWO CATEGORY 6 CABLES U.O.N.,COMBINATION POWER/TELECOMMUNICATION
DEVICES, MOUNTED IN FLUSH FLOOR BOX. TYPE AS NOTED ON PLANS OR IN
SPECIFICATIONS.
ADJUSTABLE ACCENT LIGHT FIXTURE, RECESSED IN CEILING.
P
AF
TWO CATEGORY 6 CABLES U.O.N.,TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH
FLOOR BOX.
DOWNLIGHT FIXTURE, RECESSED IN CEILING.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
INDOOR EXHAUST FAN MOTOR, SINGLE PHASE. MAKE POWER CONNECTIONS TO INCLUDE
JUNCTION BOX MOUNTED MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO
FAN WITH 2 #12 CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN
STARTER AND MOTOR.
F
TWO CATEGORY 6 CABLES U.O.N., TELECOMMUNICATION DEVICE, WALL MOUNTED
OVER COUNTER, 6" ABOVE BACK SPLASH, UON.
STRIP LIGHT FIXTURE, SURFACE MOUNTED VERTICALLY ON WALL OR IN COVE.
SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
ELECTRIC MOTOR, NIEC. MAKE POWER CONNECTIONS ONLY AS NOTED ON PLANS.
MAIN BUILDING GROUND BUS
BID ADDENDUM 3
DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 3Ø,480-120/208V, UON.
MBGB
04.01.2016
JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.
ARC FAULT CIRCUIT INTERRUPTER
BID ADDENDUM 2
J
AFI
03.25.2016
PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL.
STRIP LIGHT FIXTURE, SURFACE MOUNTED IN ARCHITECTURAL CEILING COVE.
LIGHTING CONTROL PANEL
PERMIT RESUBMITTAL
PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL.
LCP
BID
STRIP LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
ABOVE FINISHED CEILING
02.26.2016
JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO STRUCTURE IN ACCESSIBLE CEILING
SPACE.
AFC
02.26.2016
J
PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL.
TWO CATEGORY 6CABLES U.O.N., TELECOMMUNICATION DEVICE, WALL MOUNTED, +18"
UON.
PERMIT
LIGHT FIXTURE, WALL MOUNTED.
LIFE SAFETY CONTROL PANEL
11.20.2015
JUNCTION BOX, MOUNTED FLUSH IN CEILING.
LSCP
65% CD SET
J
AMPERES
100% DD SET
LIGHT FIXTURE, SURFACE OR PENDANT MOUNTED.
A
10.15.2015
JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX.
PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL.
ONE CATEGORY 6 CABLES, TELECOMMUNICATION DEVICE, WALL MOUNTED AT +42".
07.15.2015
J
W
50% DD SET
LIGHT FIXTURE, RECESSED IN CEILING.
06.26.2015
JUNCTION BOX, WALL MOUNTED, +18" UON.
ISSUE TITLE
J
DATE
SWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL CENTER,
FLOOR MOUNTED.
Drawing No.
E0.1
ARCHITECTURAL LIGHTING FIXTURE SCHEDULE
FEEDER
CONDUIT
CONDUCTORS
9004
900 AMP,3 PHASE,4 WIRE
3-3.00"
3 SETS OF 4 #350 KCMIL
1 #2/0 PER SET
-
9003
900 AMP,3 PHASE,3 WIRE
3-3.00"
3 SETS OF 3 #350 KCMIL
1 #2/0 PER SET
-
TYPE
AF1
MFR. / CAT. NO.
Ecosense # WWEA-12-30-120-6
Mounting Brackets - EXT-A-MNT-ADJ
Jumper Cables - EXT3P-A-JMP-120-1
LAMP QTY / TYPE WATTS
LED
5 W/LF
380 lm/LF
3000 K
80+ CRI
VOLTS
DESCRIPTION
120 LED linear wallwash, 6°x6°, IP66
AF2
Ecosense - Trov # L50-E-12-06-40-80MULT-15x35
Mounting Brackets - MNT-L-TRK-12
Mounting Clips - MNT-L-CLIP
Jumper Cables - CBL-3P-L-UNV-01
LED
492 lm/LF
4000 K
80 CRI
6 W/LF
120
we-ef # 663-2621
LED
246 lm
3000 K
12 W
LIGHTING FIXTURE SCHEDULE
LOCATION
Front of Screen
LED linear wallwash, 15°x35°, multi-volt, IP66.
8004
800 AMP,3 PHASE,4 WIRE
3-3.00"
3 SETS OF 4 #300 KCMIL
1 #1/0 PER SET
-
8003
800 AMP,3 PHASE,3 WIRE
2-3.00"
2 SETS OF 3 #500 KCMIL
1 #1/0 PER SET
-
7004
700 AMP,3 PHASE,4 WIRE
2-3.50"
2 SETS OF 4 #500 KCMIL
1 #1/0 PER SET
-
7003
700 AMP,3 PHASE,3 WIRE
2-3.00"
2 SETS OF 3 #400 KCMIL
1 #1/0 PER SET
-
6004
600 AMP,3 PHASE,4 WIRE
2-3.00"
2 SETS OF 4 #350 KCMIL
1 #1 PER SET
-
6003
600 AMP,3 PHASE,3 WIRE
2-2.50"
2 SETS OF 3 #350 KCMIL
1 #1 PER SET
-
5004
500 AMP,3 PHASE,4 WIRE
2-2.50"
2 SETS OF 4 #250 KCMIL
1 #2 PER SET
-
5003
500 AMP,3 PHASE,3 WIRE
2-2.00"
2 SETS OF 3 #250 KCMIL
1 #2 PER SET
-
4504
450 AMP,3 PHASE,4 WIRE
2-2.50"
2 SETS OF 4 #4/0
1 #2 PER SET
-
4503
450 AMP,3 PHASE,3 WIRE
2-2.00"
2 SETS OF 3 #4/0
1 #2 PER SET
-
4004
400 AMP,3 PHASE,4 WIRE
1-3.50"
4 #500 KCMIL
1 #2
-
4003
400 AMP,3 PHASE,3 WIRE
1-3.00"
3 #500 KCMIL
1 #2
-
3504
350 AMP,3 PHASE,4 WIRE
1-3.50"
4 #500 KCMIL
1 #2
-
3503
350 AMP,3 PHASE,3 WIRE
1-2.50"
3 #400 KCMIL
1 #2
-
3004
300 AMP,3 PHASE,4 WIRE
1-3.00"
4 #350 KCMIL
1 #4
-
3003
300 AMP,3 PHASE,3 WIRE
1-2.50"
3 #350 KCMIL
1 #4
-
2754
275 AMP,3 PHASE,4 WIRE
1-3.00"
4 #300 KCMIL
1 #4
-
2753
275 AMP,3 PHASE,3 WIRE
1-2.50"
3 #300 KCMIL
1 #4
-
2504
250 AMP,3 PHASE,4 WIRE
1-2.50"
4 #250 KCMIL
1 #4
-
2503
250 AMP,3 PHASE,3 WIRE
1-2.00"
3 #250 KCMIL
1 #4
-
2254
225 AMP,3 PHASE,4 WIRE
1-2.50"
4 #4/0
1 #4
-
2253
225 AMP,3 PHASE,3 WIRE
1-2.00"
3 #4/0
1 #4
-
2004
200 AMP,3 PHASE,4 WIRE
1-2.00"
4 #3/0
1 #6
-
2003
200 AMP,3 PHASE,3 WIRE
1-2.00"
3 #3/0
1 #6
-
1754
175 AMP,3 PHASE,4 WIRE
1-2.00"
4 #2/0
1 #6
-
1753
175 AMP,3 PHASE,3 WIRE
1-1.50"
3 #2/0
1 #6
-
1504
150 AMP,3 PHASE,4 WIRE
1-1.50"
4 #1/0
1 #6
-
1503
150 AMP,3 PHASE,3 WIRE
1-1.50"
3 #1/0
1 #6
-
1254
125 AMP,3 PHASE,4 WIRE
1-1.50"
4 #1
1 #6
-
1253
125 AMP,3 PHASE,3 WIRE
1-1.25"
3 #1
1 #6
-
1004
100 AMP,3 PHASE,4 WIRE
1-1.25"
4 #2
1 #8
-
1003
100 AMP,3 PHASE,3 WIRE
1-1.25"
3 #2
1 #8
-
904
90 AMP,3 PHASE,4 WIRE
1-1.25"
4 #2
1 #8
-
903
90 AMP,3 PHASE,3 WIRE
1-1.25"
3 #2
1 #8
-
804
80 AMP,3 PHASE,4 WIRE
1-1.25"
4 #4
1 #8
-
803
80 AMP,3 PHASE,3 WIRE
1-1.00"
3 #4
1 #8
-
1 LIGHTING CONTROLS: To be determined. Provide appropriate dimming, power supply, and electronic ballast interfaces, coordinated with voltage.
704
70 AMP,3 PHASE,4 WIRE
1-1.25"
4 #4
1 #8
-
2 Contractor shall verify fixture mounting & coordination with final specified ceiling system.
703
70 AMP,3 PHASE,3 WIRE
1-1.00"
3 #4
1 #8
-
3 All fixtures shall be U.L. or ETL listed.
-
4 Architect to verify all specified finishes.
604
60 AMP,3 PHASE,4 WIRE
1-1.25"
4 #6
1 #10
603
60 AMP,3 PHASE,3 WIRE
1-1.00"
3 #6
1 #10
-
504
50 AMP,3 PHASE,4 WIRE
1-1.00"
4 #8
1 #10
-
503
50 AMP,3 PHASE,3 WIRE
1-0.75"
3 #8
1 #10
-
404
40 AMP,3 PHASE,4 WIRE
1-0.75"
4 #8
1 #10
-
403
40 AMP,3 PHASE,3 WIRE
1-0.75"
3 #8
1 #10
-
304
30 AMP,3 PHASE,4 WIRE
1-0.75"
4 #10
1 #10
-
303
30 AMP,3 PHASE,3 WIRE
1-0.75"
3 #10
1 #10
-
204
20 AMP,3 PHASE,4 WIRE
1-0.50"
4 #12
1 #12
-
203
20 AMP,3 PHASE,3 WIRE
1-0.50"
3 #12
1 #12
-
154
15 AMP,3 PHASE,4 WIRE
1-0.50"
4 #12
1 #12
-
153
15 AMP,3 PHASE,3 WIRE
1-0.50"
3 #12
1 #12
-
FEEDER SCHEDULE GENERAL NOTES:
1.
CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE BASED ON COPPER CONDUCTORS WITH THHN/THWN
INSULATION.
2.
FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED
SIZE GROUND CONDUCTOR IN EACH CONDUIT.
AF3
Philips ColorBlast Powercore #
123-000021-06
LED
1471 lm
50W
120
LED RGB surface mounted wall wash, 86° beam spread,
white housing, directed at bottom of slabs, multi-volt, IP66
Remarks: Controls--iPlayer 3. Coordinate with general
building controls.
Back of screen
on structure levels 02-07
AF5
Philips eW Blast Powercore #
523-000069-14
LED
2398 lm
4000 K
82 CRI
50W
120
White LED surface mounted wall wash, 83° beam spread,
white housing, multi-volt, dimmable, IP66.
Top of
crashwall on
level 08
AF6
Amerlux Hornet High Power
HORNET # HP-A14-18-LED-WT-TN120-FL-3000-9
Track - GES204-3
LED
1369 lm
3000K
97CRI
18W
120
LED track head, 28° beam spread, white finish,
ELVdimming.
Art Display
AF7
Prudential Lighting # P4000
P4030-LED3-LO-FWA-TMW-D1-SCUNIV-MPCA-X1-DMD
LED
5800 lm
3000 K
83 CRI
56W
120
LED pendant, 3" diameter, white finish, multi-volt, 0.1%
dimming .
Art Display
Ecosense Trov # L50-E-48-06-40-90MULT-15x15
LED
492lm/LF
4000 K
90CRI
6 W/LF
LED
492lm/LF
4000 K
90CRI
6 W/LF
AF8
Ecosense Trov #L50-E-48-06-40-90MULT-ASYM
AF8A
LED linear graze, 15°x15°, multi-volt, IP66.
120
FINELITE # 619 WS-32 & 9-SO-3500-120-SCSF-2 CUSTOM CORNERS
OR
PRUDENTIAL P83-LEDREG4-LED4-LOR*=RGW-LP-SC-UNIV-X3B-2 CUSTOM
CORNER
OR
NEORAY S123 DRP LO-35-TBD-XX-SC-120-
LED 3500K/80CRI 9.3 WATTS/FT 120
60,000 HOURS
DESCRIPTION
LOCATION
SURFACE OR MOUNTED LED STRIP. WITH FROSTED ACRYLIC
UTILITY ROOMS
LENS. 22 GAUGE DIE FORMED C.R.S.HOUSING. 92% REFLECTIVE
WHITE POLYESTER POWDER COAT PAINT BONDED TO PHOSPHATE
FREE MULTI STAGE PRETREATED METAL. ALL PARTS PAINTED
AFTER FABRICATION TO INHIBIT CORROSION. CONSTANT
CURRENT , CLASS 2 DRIVER. CONFORMS TO UL STD 1598.
SUITABLE FOR DAMP LOCATIONS. 5 YEAR WARRANTEE.
4" WIDE BY 5" HIGH PERIMETER SLOT. REFLECTORS ARE DIE
FORMED 24 GAUGE COLD ROLLED STEEL FINISHED IN A HIGH
REFLECTANCE MATTE WHITE POWDER COAT PAINT.
CASHIER
OFFICES
47
120
1X4 X 3" SURFACE MOUNTED DIMMABLE TROFFER WITH FROSTED
ACRYLIC LENS . 19 GAUGE HOUSING PAINTED 92% WHITE
POLYESTER POWDER COATED WHITE PAINT. LED BARDS ARE
ACCESSIBLE BELOW CEILING AND RATED AT 50,000 HOURS LIFE.
F4
HE WILLIAMS # LLMS-41-L34/835-RD-DIM LED 80CRI/4000K 42
4100 LUMENS
OR
METALUX#4SNLED-L4-44SL-LW-UNIV-L8XXCD1-U
OR
PRUDENTIAL#R1-LED40-4-SAL-TMW-UNIVSUR-DM10
120
F5
LED
HE WILLIAMS #96-4-L62/840DIM-120
OR
METALUX# 4VT2-LD4-6-XX-UNIV-L840-CD1WL
OR
LITHONIA#VAP-6000LM-FST-WD-120-GZ1040K-80CRI
73
120
NARROW LED LED LENSED STRIP SERIES. 20 GAUGE DIE
BIKE STORAGE
FORMED HOUSING. FROSTED ROUND EXTRUDED MATTE ACRYLIC
LENS. TEXTURED MATTE WHITE POLYESTER POWDER COATED
PAINT BONDED TO PHOSPHATE-FREE MULTI-STAGE PRETREATED
METAL. ALL PARTS PAINTED AFTER FABRICATIONTO INHIBIT
CORROSION. CONSTANT CURRENT , CLASS 2 DRIVER.
CONFORMS TO UL STD 1598. SUITABLE FOR DAMP LOCATIONS. 5
YEAR WARRANTEE.
VAPORTIGHT LINEAR LED FIXTURE SURFACE MOUNTED.
ELEVATOR SHAFT
AND PIT
F6/8'
HE WILLIAMS # LLMS-68-L34/835-SQ-DIM LED 80CRI/4000K 64
6800 LUMENS
OR
PRUDENTIAL#S1-LED40-4-SAL-TMW-UNIVSUR-DM10
OR
EUREKA FLARE # 3550
120
SIMILAR TO F4 BUT SQUARE AND 8'-0"
LARGER
RESTROOMS
F6/4'
LED 80CRI/4000K 42
HE WILLIAMS # LLMS-41-L/835-SQ-DIM
4100 LUMENS
OR
EUREKA FLARE # 3550
OR
PRUDENTIAL#S1-LED40-4-SAL-TMW-UNIVSUR-DM10
120
SIMILAR TO F4 BUT SQUARE AND 4'-0"
SMALLER
RESTROOMS
Bike Sign
F7
NOT USED
F8
KENALL TD17HO-DTS-5S-TP-GW-47L-40K8- LED 80CRI/4000K 54
6,671 LUMENS
DCC-120-TL1000
OR
McGRAW-EDISON TT-B4-LED-E1-WQ-8030
OR
LITHONIA PGX LED-P3-T5R-120-SRM-TBDMOD 80CRI
BERKELEY,
CA 94704
Oakland
Irvine
Los Angeles
Architecture / Engineering / Consulting
560 - 14th Street Suite 300
Telephone 510 473 0300
120
Oakland, CA 94612
Fax 510 473 0310
GARAGE
SURFACE MOUNTED LED GARAGE FIXTURE. MARINE GRADE DIE
CAST ALUMINUM HOUSING AND UV-STABLIZED POLYCARBONATE
LENS. POLYESTER POWDER COAT FINISH ON ALL ALUMINUM
COMPONENTS WITH FIVE-STEP PRE-TREATMENT TO WITHSTAND
1,000 HOUR SALT SPRAY TEST PER ASTM B117. DIRECT TO
SURFACE MOUNTING MOUNTING OVER RECESSED JUNCTION BOX.
10 YEAR WARRANTEE.
Consulting Engineers
F8A
KENALL TD17HO-DTS-5S-TP-GW-30L-40K8- LED 80CRI/4000K 34
6,271 LUMENS
DCC-120-TL1000
OR
McGRAW-EDISON TT-B3-LED-E1-WQ-803
OR
LITHONIA PGX LED-P2-T5R-120-SRM-TBDMOD 80CRI
120
SIMILAR TO F8 BUT LOWER OUTPUT SURFACE MOUNTED LED
GARAGE FIXTURE. NOTE FIXTUES MATCH PICTURES ABOVE
F9
LED 80CRI/4000K 8W/LF
AION# HOUSING:AT845 AS-F-W96"
LIGHT ENGINE# 3450 D100 DC DRIVER
OR
CELESTIAL SERPENS GX SERIES # SERFX-277-300
OR
APPROVED EQUAL BY INTER-LUX
120
RECESSED LINEAR FIXTURE WASHING INTERIOR WALLS. FIXTURE PUBLIC
SHALL BE IN CONTINUOUS ROWS, IN ARCHITECTURAL SLOT. WITH CORRIDORS AND
AT ELEVATOR
REMOTE DRIVERS TBD.
LOBBIES.
F10
LED 3500K/80CRI 33W
PHILIPS LIGHTOLIER #C6X6L-30-N-1-VB60,000 HOURS
Z10V C6X6-3000-DL-4000-WH-WH-WRATED LIFE
CA6X6FMR-VB
OR
LITHONIA GOTHAM #ICO-SQ-40-30-4WRFLLD-50D-120
OR
COOPER IRIS P406TAT-EDC4X41-E4DCMW
120
6" SQUARE APERTURE WHITE LED WALL WASHER, RECESS DEPTH ELEVATOR
6-1/2" INCLUDING LIGHT ENGINE DO NOT INSTALL INSULATION
LOBBY
ABOVE OR WITHIN 3" OF LUMINAIRE. 0.09" CLEAR BOROSILICATE
GLASS. SELF FLANGE WHITE REFLECTOR UL LISTED FOR WET
LOCATIONS
F11
LED 80CRI/4000K 8W/LF
AION# HOUSING:AT402 AS-F-W96"
LIGHT ENGINE# 3450 D100 DC DRIVER
DRIVER
OR
CELESTIAL SERPENS GX SERIES # SERFX-277-300
OR
APPROVED EQUAL BY INTER-LUX
120
FIXTURE MOUNTED WITHIN CUSTOM ENCLOSURE WITHIN STAIR
RAIL ASSEMBLY. REMOTE DRIVER LOCATION IN STAIR. EXACT
LOCATION TO BE DETERMINED
F12
KENALL #N548-C-1-45L40K-DCC-1-120-SA LED 4000K
OR
INDATECH#HXPF4-90-U-35-BCK
OR
BEGHELLI-BX910LED-4-HT-50W0WT40-120PM
120
SURFACE MOUNTED ENCLOSED AND GASKETED FIXTURE WITH
ROOF UNDER
SURFACE MOUNT ADAPTER. MOUNT TO THE BOTTOM WEB OF THE TRUSS
ROOF TRUSS SYSTEM. PROVIDE SHEET METAL SHROUD ABOVE
FIXTURE TO ALLOW WET LISTING, PAINTED PER ARCHITECT'S
DIRECTION. FEED CONDUIT FROM ENDS. ONE-PIECE SEAM
WRAPAROUND POLYCARBONATE LENS.
F13
LED 80CRI/4000K 8W/LF
AION# HOUSING:AT845 AS-F-W96"
LIGHT ENGINE# 3450 D100 DC DRIVER
OR
CELESTIAL SERPENS GX SERIES # SERFX-277-300
OR
APPROVED EQUAL BY INTER-LUX
120
7'-0" & 12'-0" SURFACE MOUNTED LED FIXTURE TO WASH MURALS. ELEVATOR
MURAL WALLS
F14
METEOR # CCS-50-40K-U-V-100-B-SU-OUT- LED 80CRI/4000K 55
DF
OR
LITHONIA GOTHAM EVO-CYL-50-30-6ARWD-LD
OR
WE-EF# DAC220-LED-630-1253 MOD WIDE
SPREAD LENS
120
SURFACE LED 6" X 13" CYLINDER. SURFACE MOUNTED . 100
DEGREE BEAM, DIE CAST ALUMINUM BODY, MACHINED ALUMINUM
MOUNTING PLATE, STAINLESS STEEL SCREWS, CLEAR GLASS. 5
YEAR WARRANTY. IP65, IK 08 LISTED.
CANOPY AT ROOF
ELEVATOR
F15
METEOR # CCS-50-40K-U-V-60-B-SU-OUT
OR
LITHONIA GOTHAM EVO-CYL-50-30-6ARWD-LD
OR
WE-EF# DAC220-LED-630-1253 MOD
SPREAD LENS
LED 80CRI/4000K 55
120
SIMILAR TO F14 BUT 60 DEGREE BEAM SPREAD.
CANOPY AT
LOWER LEVEL
SFX
PHILIPS LIGHTOLIER #EEXSSCOR EQUAL BY LITHONIA OR COOPER
LED
3
120
SURFACE OR PENDANT MOUNTED EXIT SIGN, DIE-CAST ALUMINUM EXIT PATHS
HOUSING.
SFX2
PHILIPS ER60MLD-3-R-WA-PM
OR EQUAL BY LITHONIA OR COOPER
LED
8
120
SURFACE MOUNTED WEATHERPROOF LED EXIT SIGN
EXTERIOR
LOCATIONS
FEX
EMERGI-LITE #W-12SV224M-2-LJ-D
OR EQUAL BY LITHONIA OR COOPER
LED
6
120
UNIT EMERGENCY BATTERY LIGHT WITH LED LAMPS. 12VOLT, 24
WATTS LEAD CALCIUM BATTERY, NEMA 4X.
ELECTRICAL,
GENERATOR
ROOMS
7 See architectural drawings for mounting dimensions and/or details
SUBMITTALS: as part of this work the Contractor shall, within 15 days after award of the Contract, sumbit a complete material list of all lighting fixtures, miscellaneous materials,
8 and controls proposed to be furnished and installed. This submittal shall include manufacturer’s specifications, cut sheets, and other data required to demonstrate compliance with
specified requirements. Submittals shall be in PDF format.
No substitution of specified fixture, lamp or controls manufacturer will be acceptable without specific prior approval of the Architect. If Contractor makes a substitution without said
prior approval, he shall replace the substituted item with the specified item and to the Architect's labor costs involved in re-aiming fixtures, traveling to the site, etc.) without any
9
additional shall bear all associated costs (including but not limited to the Architect's labor costs involved in re-aiming fixtures, traveling to the site, etc.) without any additional charge
to the Owner.
10 Any fluorescent lamp on dimming ballast must be operated at full output for a minimum of 100 hours before being dimmed.
Any non-fluorescent lamp or non-LED used during the course of construction shall be replaced and re-lamped prior to project turnover to owner. The cost of lamp replacement
shall be incurred by Contractor.
12 Remote transformers, power supplies, and ballasts to be located in well ventilated location as required.
Remote transformers shall be UL listed with re-settable secondary side circuit breaker protection per NEC.
Transformer size and secondary breaker capacity shall be determined by Electrical Contractor for each condition. At remote transformers, minimum secondary wire size shall be
#10 stranded THHN unless noted otherwise. Maximum secondary run shall be less than wire size to be acceptable. 20LF for 150VA load. For greater load or longer run, indicates a
smaller provide voltage drop calculation and proposed wire size unless voltage drop calculation wire size to be acceptable.
END OF SECTION
FIRE ALARM SEQUENCE OF OPERATION MATRIX
FIRE/SMOKE DAMPER FAULT
CLOSE FIRE/SMOKE DAMPERS ON A
PER FLOOR BASIS
SHUTDOWN ASSOCIATED HVAC UNIT
SHUNT-TRIP ASSOCIATED POWER
ELEVATOR RECALL TO ALTERNATE
FLOOR
ELEVATOR RECALL TO 1ST FLOOR
UNLOCK EXIT DOORS
ROLL-DOWN DOORS, SHUTTERS AND
SMOKE-GUARD CLOSURE
DOOR HOLD/OPEN RELEASE
RECORD ALL SYSTEM ACTIVITIES AT
PRINTER
EQUIPMENT CONTROLLED
TRANSMIT SUPERVISORY SIGNAL TO
MONITORING COMPANY
TRANSMIT TROUBLE SIGNAL TO
MONITORING COMPANY
TRANSMIT ALARM SIGNAL TO
MONITORING COMPANY
TRANSMIT SUPERVISORY SIGNAL TO
REMOTE ANNUNCIATOR
TRANSMIT TROUBLE SIGNAL TO
REMOTE ANNUNCIATOR
TRANSMIT ALARM SIGNAL TO REMOTE
ANNUNCIATOR
ACTIVATE AUDIBLE & VISUAL
EVACUATION FOR BUILDING
NOTIFICATION
INDICATE INPUT SIGNAL ON LCD
DISPLAY
ACTUATE SUPERVISORY SIGNAL
AUDIBLE (BUZZER)
ACTUATE SUPERVISORY SIGNAL
INDICATOR (AMBER LED)
ACTUATE TROUBLE SIGNAL
AUDIBLE(BUZZER)
ACTUATE TROUBLE SIGNAL
INDICATOR (AMBER LED)
ACTUATE ALARM SIGNAL AUDIBLE
(BUZZER)
ACTUATE ALARM SIGNAL INDICATOR
(RED LED)
SYSTEM OUTPUTS
FACP ANNUNCIATION
SYSTEM INPUTS
120
LED 80 CRI-40W
PHILIPS DAYBRITE# 1-SDL-41L-840-4-D4,500
UNIV-DIM
OR
LITHONIA #RTLX4-40L-MVOLT-EZ1-LP840
OR
CORELIGHT # R2-W-L-2-L35-1-D-120-14-SU
6 Fixtures to be mounted with lamps oriented as indicated on drawings.
SYSTEM OPERATION INPUT
SIGNALS AND OUTPUT
FUNCTIONS
VOLTS
F3
5 All track and low voltage strip lights to be furnished with all necessary feeds, splices, connections, etc.as required for a complete installation.
11
WATTS
F2
Bike Sign
LED linear graze asymetrical, 15°x15°, multi-volt, IP66.
120
LAM P QTY / TYPE
F1
Level 02
walkway
AF4
MFR. / CAT. NO.
HE WILLIAMS # 75L-4-LED*PH50/835-DMA LED 80CRI/4000K 52 W
5000 LUMENS
OR
COOPER 4SWLED-LD4-56HL-LWUNIV-L8XXCD2-SVPD2-U
OR
LITHONIA ZL1F-L48-6000LM-MDD-120-40K80CRI-WH
Front of Screen
LED surface mounted downlight, 50° beam spread, black
finish, 0-10V dimming, IP55.
Mounted to horizontal screen structure.
120
TYPE
MANUAL PULL STATION
AREA SMOKE DETECTOR
AREA HEAT DETECTOR
ELEVATOR INTERFACE INPUTS:
45
GARAGE
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
STAIR
Revision
Date
LOBBY SMOKE DETECTOR, EXCEPT 1ST FLR
LOBBY SMOKE DETECTOR @ 1ST FLR
MACHINE ROOM SMOKE DETECTOR
ELEVATOR SHAFT SMOKE DETECTOR
MACHINE ROOM HEAT DETECTOR
DUCT-MTD SMOKE DETECTOR @ HVAC UNIT
IN-DUCT DETECTOR @ FSD
SURFACE PLENUM SMOKE DETECTOR @ FSD
WATERFLOW SWITCH
VALVE TAMPER SWITCH
POST INDICATING VALVE
EMERGENCY GENERATOR MONITORING:
C:\Users\jleite\Documents\Center St_jleite.rvt
GENERATOR RUNNING
GENERATOR TROUBLE
LOW FUEL TANK
OUTPUT BREAKER OPEN
INITIATING CIRCUIT:
OPEN WIRE
Date
Project No.
Drawn By
Checked By
Scale
GROUNDED WIRE
SHORTED WIRES
NOTIFICATION CIRCUIT:
OPEN WIRE
GROUNDED WIRE
SHORTED WIRES
SIGNALING LINE CIRCUIT:
OPEN WIRE
GROUNDED WIRE
WIRE TO WIRE SHORT & OPEN
WIRE TO WIRE SHORT & GROUND
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E0.2 LIGHTING FIXTURES AND PANEL SCHEDLULES.DWG
Last saved by: PAUL(2016-04-01)
Last Plotted: 2016-04-01
ELEVATOR SHAFT HEAT DETECTOR
Drawing Title:
ELECTRICAL
SCHEDULES
OPEN & GROUND
LOSS OF CARRIER
POWER DISCONNECT SUPERVISION
Drawing No.
FIRE ALARM SYSTEM LOW BATTERY
E0.2
BERKELEY,
CA 94704
J
Oakland
Irvine
Los Angeles
7
18
S
18
J
17
J
J J J
J
5
J
10
AF
J
S
CR
6
2D/1V
J
8
J
6
Architecture / Engineering / Consulting
J
T
17
2
A
ES
RX
15
J
S
S
6
T
560 - 14th Street Suite 300
Telephone 510 473 0300
T
6
12
J
2D/1V
2D/1V
J
2D/1V
Consulting Engineers
WAP
1
2D/1V
T
W
2V T
S
3
2D/1V
3
J
J J
3
ES
1V/1D
J
2D
2D/1V
2D
J
T
S
3
6
3
14
2D/1V
2D
2D
2D
13
J
J
J
J
J
CR
A ES
CR
8
2D
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
15
J
ES J
CR
15
Oakland, CA 94612
Fax 510 473 0310
T
2D/1V
S
9
E
17
S
T
3
16
17
2
J
J
6
J
CENTER STREET
J
T
S
17
J
J
J
8
J
17
J
Revision
Date
AF
S
10
T
5
J
E
J J J J
17
8
11
18
18
C:\Users\jleite\Documents\Center St_jleite.rvt
#
1
11
2
12
3
4
5
6
7
13
14
Date
Project No.
Drawn By
Checked By
Scale
15
16
8
17
9
Drawing Title:
10
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.1 GROUND LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-04-01)
Last Plotted: 2016-04-01
project
N true
N
7
18
GROUND LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.1
BERKELEY,
CA 94704
5.5
Oakland
Irvine
Los Angeles
Architecture / Engineering / Consulting
6
J
S
E
1
T
10
UP
560 - 14th Street Suite 300
Telephone 510 473 0300
8
DN
Oakland, CA 94612
Fax 510 473 0310
8
8
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
This one
5
A.9
J
J
2
3
4
2
J
J 3
3
J
3
J J
J
3
J J
3
J J
2
3
2
3
J
J 2
J
J
J
J
2
3
J
5
J
2
2
J
J
2
3
J
2
J
3
2
2
4
J
Revision
Date
7
7
ST
UP
ST
7
DN
E
ST
ST
7
9
C:\Users\jleite\Documents\Center St_jleite.rvt
#
1
2
10
Date
Project No.
Drawn By
Checked By
Scale
3
4
5
6
Drawing Title:
7
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.2 SECOND LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-03-24)
Last Plotted: 2016-03-24
6
8
9
SECOND LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.2
BERKELEY,
CA 94704
Oakland
Irvine
Los Angeles
7
Architecture / Engineering / Consulting
DN
2
J
E
6
1
560 - 14th Street Suite 300
Telephone 510 473 0300
4
UP
Oakland, CA 94612
Fax 510 473 0310
4
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
2 J J
2
3
2
J J
3
2
J
J 3
J
J
3
2
2
J
J
3
J 3
3
J 3
2
J J
J J
3 J J
3
2
J
2
3
2
3
J
J
J 2
J
J 2
Revision
3
Date
UP
3
1
E
J
5
DN
2
C:\Users\jleite\Documents\Center St_jleite.rvt
#
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.3 THIRD LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-03-23)
Last Plotted: 2016-03-23
7
1
5
2
6
Date
Project No.
Drawn By
Checked By
Scale
3
4
7
Drawing Title:
THIRD LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.3
BERKELEY,
CA 94704
A
Oakland
Irvine
Los Angeles
T
S
DN
T
Architecture / Engineering / Consulting
2
E
J
6
1
560 - 14th Street Suite 300
Telephone 510 473 0300
4
Oakland, CA 94612
Fax 510 473 0310
4
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
Revision
Date
3
UP
1
3
E
J
5
T
T
S
DN
A
C:\Users\jleite\Documents\Center St_jleite.rvt
#
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.4 FOURTH LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-03-23)
Last Plotted: 2016-03-23
2
1
5
2
6
Date
Project No.
Drawn By
Checked By
Scale
3
4
Drawing Title:
FOURTH LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.4
BERKELEY,
CA 94704
CONVERSION MANAGEMENT ASSOCIATES, INC.
1620 Montgomery Street Suite 320, San Francisco, CA 94111
415.597.8414
Oakland
Irvine
Los Angeles
Architecture / Engineering / Consulting
2
J
E
6
1
560 - 14th Street Suite 300
Telephone 510 473 0300
4
Oakland, CA 94612
Fax 510 473 0310
UP
4
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
Revision
Date
3
1
3
E
J
5
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.5 FIFTH LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: LIZ(2016-03-03)
Last Plotted: 2016-03-08
2
#
1
5
2
6
Date
Project No.
Drawn By
Checked By
Scale
11/19/2015
14877
3
4
PERMIT SET
11/19/2015
Drawing Title:
FIFTH LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.5
BERKELEY,
CA 94704
CONVERSION MANAGEMENT ASSOCIATES, INC.
1620 Montgomery Street Suite 320, San Francisco, CA 94111
415.597.8414
Oakland
Irvine
Los Angeles
DN
Architecture / Engineering / Consulting
2
J
E
6
1
560 - 14th Street Suite 300
Telephone 510 473 0300
4
Oakland, CA 94612
Fax 510 473 0310
UP
4
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
Revision
Date
3
UP
1
3
E
J
5
DN
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.6 SIXTH LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-03-08)
Last Plotted: 2016-03-08
2
#
1
5
2
6
Date
Project No.
Drawn By
Checked By
Scale
11/19/2015
14877
3
4
PERMIT SET
11/19/2015
Drawing Title:
SIXTH LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.6
BERKELEY,
CA 94704
CONVERSION MANAGEMENT ASSOCIATES, INC.
1620 Montgomery Street Suite 320, San Francisco, CA 94111
415.597.8414
Oakland
Irvine
Los Angeles
DN
Architecture / Engineering / Consulting
2
J
E
6
1
560 - 14th Street Suite 300
Telephone 510 473 0300
4
UP
Oakland, CA 94612
Fax 510 473 0310
4
Consulting Engineers
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
Revision
3
Date
UP
3
1
E
J
5
DN
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.7 SEVENTH LEVEL POWER AND SIGNAL PLAN.DWG
Last saved by: LIZ(2016-03-03)
Last Plotted: 2016-03-08
2
#
1
5
2
6
Date
Project No.
Drawn By
Checked By
Scale
11/19/2015
14877
3
4
PERMIT SET
11/19/2015
Drawing Title:
SEVENTH LEVEL
POWER AND SIGNAL
PLAN
Drawing No.
E2.7
BERKELEY,
CA 94704
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
Oakland
Irvine
Los Angeles
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
2
1
DN
18
18
J
2
E
WP
WP
7
1
Architecture / Engineering / Consulting
G
6
560 - 14th Street Suite 300
Telephone 510 473 0300
4
Oakland, CA 94612
Fax 510 473 0310
4
7
Consulting Engineers
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
THE POWER HOUSE
1305 MARINA VILLAGE PARKWAY
ALAMEDA, CA. 94501
(510) 769-7600
JOB #14073
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
7
Revision
Date
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
3
1
3
G
(2) 2" CONDUIT RISER FOR
PHOTOVOLTAIC PANELS
7
MOUNT ON CANOPY
SUPPORT AT +80" AFF,
TYP.
WP
E
J
5
43
DN
WP
WP
43
18
18
C:\Users\jleite\Documents\Center St_jleite.rvt
#
3/25/2015 7:59:25 AM
Filename: \\TAU\DATA\CADFILES\14073_BERKELEY CENTER STREET GARAGE\CAD\BPS-E2.8-ROOF POWER AND SIGNAL PLAN.DWG
Last saved by: PAUL(2016-04-01)
Last Plotted: 2016-04-01
project
N true
N
2
SMART INVERTER TYPE PHOTOVOLTAIC SYSTEM SHALL INCLUDE THE
FOLLOWING FEATURES:
BASE DESIGN SHALL BE PRICED BASED ON 11,174 SQUARE FEET OF AVAILABLE ROOF TRUSS SPACE. ESTIMATED
AT 15W/SF, THIS IS ROUGHLY A 168 KW SYSTEM. GRID CONNECTED, NET-METERING.
MUST BE ABLE TO OFFER LOW VOLTAGE RID-THROUGH.
BID ALTERNATE DESIGN B2(a) SHALL BE PRICED FOR THE MAXIMUM CAPACITY OF THE ROOF TRUSS AT 21,200
SQUARE FEET . AT 15W/SF, THIS IS ROUGHLY A 318 KW SYSTEM. GRID-CONNECTED, NET METERING.
MUST BE ABLE TO RECEIVE ACTIVE AND REACTIVE POWER (P&Q) SET
POINTS.
SYSTEM MUST BE IN COMPLIANCE WITH
IEEE 1547.4
Guide for Design, Operation, and Integration of
Distributed Resource Island Systems with Electric Power Systems
BID ALTERNATE DESIGN B2 (b) SHALL INCLUDE (FOR BOTH OF THE ABOVE SIZES) A SMART INVERTER PV
STORAGE TYPE SYSTEM. FOR BID PURPOSES ONLY, USE A BATTERY SIZED AT 100KWH, BUT EXCLUDE THE
BATTERY STORAGE. THE SYSTEM SHALL HAVE THE CAPABILITY OF RUNNING AS A STANDARD GRID-CONNECTED
SETUP, AND CONVERT TO UTILIZING STORAGE AT A FUTURE DATE WITH MINIMAL RE-WORK.
BID ALTERNATE DESIGN B2 (c) SHALL BE PRICED AS THE DEDUCTIVE COST FOR LIMITING THE PV SYSTEM TO THE
BASE DESIGN, AND THE DOWNSIZING THE PV INFRASTRUCTURE TO MATCH. INCLUDE LINE ITEMS FOR THE
SWITCHGEAR BUS TO BE REDUCED BY 400 AMPS, THE CIRCUIT BREAKER AT THE MAIN SWITCHBOARD TO BE
REDUCED TO 600 AMPS, AND THE RISERS FOR THE PV SYSTEM REDUCED TO CODE MINIMUM.
1
2-WAY COMMUNICATION SYSTEM - PART OF FIRE ALARM/LIFESAFETY SYSTEM. ROUTE 3/4"C.O.
TO MAIN CONTROLLER IN ELECTRICAL ROOM #2.
2
12"WX12"HX4"D NEMA 3, SCREW COVER TELECOM J-BOX, WITH 2-2" RISER CONDUITS FROM
FLOOR BELOW AND TO FLOOR ABOVE.
3
ROUTE (1) 1" C. TO J-BOX. TERMINATE IN A FLUSH MOUNT 4" SQ. BOX IN CEILING. ROUTE DATA
CABLE TO MECHANICAL ROOM IDF ON LEVEL 1.
4
ROUTE (1) 1" C. TO TELECOM J-BOX. TERMINATE IN A FLUSH MOUNT 4" SQ. BOX IN CEILING.
ROUTE DATA CABLE TO IT/SVR ROOM IDF ON LEVEL 1.
5
6
WALL MOUNT A E-PHONE ON WALL AND ROUTE (1) 1" C. TO J-BOX. TERMINATE IN A FLUSH
MOUNT SINGLE
GANG BOX IN WALL AT 18" BELOW E-PHONE. PROVIDE A .75" LIQUID TIGHT CONDUIT FROM
OUTLET BOX TO BOTTOM OF E-PHONE. ROUTE TELEPHONE CABLE TO IT/SRV ROOM IDF ON
LEVEL 1 AND CROSS CONNECT TO 110 RISER.
7
RISER LOCATION FOR PHOTOVOLTAIC PANEL SYSTEM. PROVIDE (1) 3" SLEEVE TO FLOOR
BELOW. SEE PV SYSTEM DRAWINGS FOR FEEDER INFORMATION. ALSO REFER TO PV SYSTEM
BID ALTERNATES THIS SHEET.
8
MOUNT RECEPTACLE AT HEIGHT TO BE DETERMINED BY THE ELEVATOR INSTALLER OR
INSPECTOR.
Date
Project No.
Drawn By
Checked By
Scale
WALL MOUNT A E-PHONE ON WALL AND ROUTE (1) 1" C. TO J-BOX. TERMINATE IN A FLUSH
MOUNT SINGLE GANG BOX IN WALL AT 18" BELOW E-PHONE. PROVIDE A .75" LIQUID TIGHT
CONDUIT FROM OUTLET BOX TO BOTTOM OF E-PHONE. ROUTE TELEPHONE CABLE TO
MECHANICAL ROOM IDF ON LEVEL 1 AND CROSS CONNECT TO 110 RISER.
Drawing Title:
ROOF
POWER AND SIGNAL
PLAN
Drawing No.
E2.8
Download