Risk Management Guidelines Residual Current Devices (RCDs) The Purpose of RCD’s Where to Use RCD’s Residual Current Devices (RCD) or Earth Leakage Circuit Breakers (ELCB) are electro-mechanical devices designed to switch off electric current in the event of an electrical fault. They can detect very small faults before they become dangerous and are an excellent additional protection against electric shock and from fires of an electrical nature. RCD’s work by measuring, indirectly, the leakage current from the live conductors to earth. They are not designed to detect overcurrent and are not replacements for fuses or other overcurrent-tripping devices. General Availability Outdoor Equipment RCD’s are available in many forms and ratings. If the tripping current of an RCD is 30 milliamperes, (30 mA), (0.03 Amps) or less then the RCD will give some protection from fatal electric shock and protection from fires generated from electrical faults. If set at above 30 milliamperes they will still provide a lesser degree of protection from electric shock but will still give protection from fires generated from electrical faults. All electrical outlets likely to be used to supply outdoor equipment must be RCD protected in new and existing installations. Any equipment likely to be used in damp environments must be designed for the purpose and be RCD protected in new and existing installations. Examples are in greenhouses, garages, supplies for lawnmowers etc. RMG 38 v7 01/11 When considering electrical safety and fire from electrical fault, all electrical circuits in new installations should be RCD protected. However, other aspects of safety have to be considered, other than that of protection against electrical issues. All power circuits in new installations should be RCD protected unless there is an overriding consideration such as high integrity supplies, freezer supplies, lighting etc. (modern UK practice is not to use RCD to protect lighting circuits). 1 2011 Royal & Sun Alliance Insurance plc Risk Management Guidelines Special Cases Every piece of electrical apparatus has a small leakage to earth due to the laws of nature. If too many loads are connected in parallel then the combined earth leakage current may be enough to trip an RCD even though each of the loads individually has no excessive earth leakage. Special cases such as laboratory test supplies, supplies in school laboratories and work areas, must be RCD protected in new and existing installations. Agricultural & Horticultural Premises For the purposes of protection against fire, RCD’s with a rated residual operating current not exceeding 0.5 Amps should be installed for the supply of all equipment other than that essential to the welfare of livestock. Testing An RCD is essentially a mechanical device and there is no way of knowing if it will work if it develops a fault. For this reason an RCD must be regularly tested using the test button. A notice should be fixed in a prominent position at or near the main distribution board. The notice should be in indelible characters not smaller than the illustration in section 514-12-02 of the 17th Edition of the IEE Wiring Regulations as reproduced below: All socket outlets should be protected by an RCD with a rated residual operating current not exceeding 0.03 Amps. In view of the special nature of farms and horticultural premises, this advice applies to both new and existing premises. Spurious Tripping "This installation, or part of it, is protected by a device which automatically switches off the supply if an earth fault develops. Test quarterly by pressing the button marked “T” or “Test”. The device should switch off the supply and should then be switched on to restore the supply. If the device does not switch off the supply when the button is pressed, seek expert advice." RCD’s have in some cases gained a reputation for unreliability due to so called spurious tripping. In most cases the tripping is not spurious but due to an incipient fault in the protected system or due to inappropriate use of RCD’s. The most common fault is to try to protect too many circuits with one RCD to reduce costs. In an ideal world all socket outlets would have individual RCD protection, thus a fault on any one protected load would not trip out any other circuit. RMG 38 v7 01/11 2 2011 Royal & Sun Alliance Insurance plc Risk Management Guidelines These and other Risk Management Guidelines addressing a wide variety of risk control issues are freely available from: www.rsabroker.com/risk-management The information set out in this document constitutes a set of general guidelines and should not be construed or relied upon as specialist advice. RSA does not guarantee that all hazards and exposures relating to the subject matter of this document are covered. Therefore RSA accepts no responsibility towards any person relying upon these Risk Management Guidelines nor accepts any liability whatsoever for the accuracy of data supplied by another party or the consequences of reliance upon it. Royal & Sun Alliance Insurance plc (No. 93792) Registered in England and Wales at: St Mark’s Court, Chart Way, Horsham, West Sussex, RH12 1XL Authorised & Regulated by the Financial Services Authority