XXIV Symposium Electromagnetic Phenomena in Nonlinear Circuits June 28 - July 1, 2016 Helsinki, FINLAND ______________________________________________________________________________________________________ MODIFICATION OF THE OPERATING POINT OF RESIDUAL CURRENT TRANSFORMERS FOR HIGH FREQUENCY EARTH FAULT CURRENTS DETECTION Stanislaw Czapp, Krzysztof Dobrzynski, Jacek Klucznik, Zbigniew Lubosny, Robert Kowalak Gdańsk University of Technology, Faculty of Electrical and Control Engineering ul. Narutowicza 11/12, 80-233 Gdańsk, Poland, e-mail: stanislaw.czapp@pg.gda.pl 500 RCD1 400 tripping current (mA) Abstract - For protection against electric shock in low voltage systems residual current devices are commonly used. However, their proper operation can be interfered when earth fault current with high frequency components occurs. Serious hazard of electrocution exists then. One of the most important element of residual current devices is a residual current transformer with iron core. Tripping characteristic of residual current devices strictly depends on the operating point and properties of the current transformer. This paper presents problems of the operation of the residual current transformer in presence of high frequency current components. 300 200 RCD2 100 30 0 50 100 200 300 400 500 600 700 800 900 1000 frequency (Hz) I. INTRODUCTION Protection against electric shock in low voltage systems is very often realized with the use of residual current devices (RCDs) [1]. They are applied in various types of electrical circuits also in circuits where there is earth fault current with high frequency components. It leads to the problem of RCDs compatibility with such a type of current [2-5]. Voltage and current harmonics are mainly produced by power electronics converters [6]. An example oscillogram of earth fault current from circuit with frequency converter is presented in Fig. 1. 10 ms 10 ms i (t)(t) EE 0.5 A 50 Hz 150 Hz 0.1 A 0 2.5 3 kHz 5 6 kHz 7.5 10 12 kHz 12.5 (kHz) 15 17.5 20 22.5 25 Fig.1. Oscillogram of earth fault current in the case of fault in the output terminals of the frequency converter, and spectrum of this current The waveform presented in Fig. 1 comprises harmonics, especially high-order harmonics. The order of harmonics corresponds with the applied PWM frequency of the converter. Typical residual current devices are not compatible for the detection of earth (residual) current comprising high frequency components. For such earth fault currents, tripping current of residual current devices can be very high [2]. This negatively influences the effectiveness of protection against electric shock. Figure 2 presents tripping current of the example RCDs as a function of earth fault current frequency. Tripping current of these RCDs rises with frequency rising. In case of RCD1 there is no tripping if the frequency exceeds 400 Hz. Fig.2. Tripping current of the selected RCDs (In = 30 mA) as a function of earth fault current frequency It is important to perform analysis of the operation of main components of RCDs, especially their current transformer, when high frequency residual current flows. II. ANALYSIS OF THE OPERATION OF RESIDUAL CURRENT TRANSFORMERS Residual current devices comprise an iron core current transformer (CT) and an electromechanical relay (ER) with a permanent magnet (Fig. 3). The secondary current is(t), transformed by the current transformer, in the one half-wave amplifies the magnetic flux of the permanent magnet but in the second half-wave that flux is reduced. If the current is(t) reaches a predetermined level, the magnetic flux derived from that current is high enough to reduce the magnetic flux of the permanent magnet, and RCD opens the main circuit. In order to ensure sufficient value of secondary current is(t), sufficient value of secondary voltage es(t), especially peak value, should be induced. Secondary voltage (rms value) is defined by the following formula: Es 4.44 f Ns Φ 4.44 f Ns B sFe (1) where: f – earth fault current frequency, Ns – number of turns of the secondary winding, – magnetic field strength, B – magnetic induction, sFe – current transformer core crosssection. Unfortunately, in some cases this voltage does not rise to frequency proportionally (Fig. 4). For primary current equal to the rated residual current In of a RCD, induced voltage es(t) rises only slightly. If frequency rises 20 times (from 50 to 1000 Hz) the peak value of es(t) rises about 1.35 (instead ______________________________________________________________________________________________________ 137 of 20). It means that the tripping threshold of a RCD rises rapidly and protection against electric shock may not be effective. PE L1 L2 L3 N RCD is (t) CT ER es (t) test RT i(t) = ip (t) load In the case of this iron core, the proper operation of a RCD (for various frequencies) can be achieved when the operating point of the current transformer (i.e. iron core) is situated close to the saturation point for the highest expected frequency (for example fs1000 if the highest frequency is equal to 1000 Hz). A process of designing of residual current devices for circuits of high frequency residual current should take into account the properties of an iron core of residual current transformers in presence of high frequency waveforms. Operating point of current transformers should be modified then. Figure 6 presents induced secondary voltage obtained for the proposed modified operating point of the current transformer. The expected rise in voltage occurs for primary current equal to 5In. It is observed that the most important value of the induced secondary voltage – peak value – significantly rises with frequency rising. This result may be achieved by modification of the windings of the current transformer. Fig.3. Simplified diagram of a RCD: CT – current transformer, ER – electromechanical relay, RT – test resistance, i(t) – residual (earth fault) current, ip(t) – primary current of the current transformer, is(t) – secondary current of the current transformer, es(t) – induced secondary voltage of the current transformer Fig.6. Measured (for example residual current device) secondary voltage es(t) for primary current ip(t) equal to the residual current 5In; frequency: 50, 150, 1000 Hz III. CONCLUSIONS Fig.4. Measured (for example residual current device) secondary voltage es(t) for primary current ip(t) equal to the rated residual current In; frequency: 50, 150, 1000 Hz One of the main sources of the results presented in Fig. 4 is a very wide hysteresis loop of the iron core of the current transformer for high frequency (Fig. 5). To achieve the same level of induction in the current transformer core for higher frequencies, a higher value of earth fault current is necessary. 50 Hz induction required level of induction 150 Hz 1000 Hz fs50 fs150 fs1000 field strength Fig.5. Hysteresis loops of the selected current transformer for various frequency primary current. Required magnetic field strength: fs50 for 50 Hz, fs150 for 150 Hz, fs1000 for 1000 Hz Proper operation of RCDs for earth fault current with high frequency components strictly depends on the properties of residual current transformer to be applied in the RCDs. Process of selection of this transformer and its coordination with other elements of RCDs should take into account the frequency range of the earth fault current to be detected. REFERENCES [1] HD 60364-4-41:2007, “Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against electric shock”. [2] S. Czapp, “Comparison of residual current devices tripping characteristics for selected residual current waveforms”, Elektronika ir Elektrotechnika, No. 4, pp. 7-10, 2010. [3] F. Freschi, “High-frequency behavior of residual current devices”, IEEE Trans. on Power Deliv., vol. 27, No. 3, pp. 1629-1635, 2012. [4] T. M. Lee, T. W. Chan, “The effects of harmonics on the operational characteristics of residual current circuit breakers”, Int. Conf. on Energy Management and Power Delivery, Proc. of EMPD’95, vol. 2, pp. 715719, Nov. 1995. [5] X. Luo, Y. Du, X. H. Wang et al., “Tripping characteristics of residual current devices under nonsinusoidal currents”, IEEE Trans. on Ind. Appl., vol. 47, No. 3, pp. 1515-1521, 2011. [6] J. Schoneck, Y. Nebon, “LV protection devices and variable speed drives”, Cahier technique No. 204, Schneider Electric, 2002. ______________________________________________________________________________________________________ 138 Proceedings of EPNC 2016, June 28 - July 1, 2016 Helsinki, FINLAND