PG28 17.3:pocketguide 8 new 24/03/2015 14:04 Page 1 POCKET GUIDE 28 Application of residual current devices (RCDs) This Guide gives information on typical applications of RCDs, according to their rated residual operating current (I⌬n). See NICEIC and ELECSA Pocket Guide 29 for information on the classification of RCDs according to whether or not they incorporate a time delay and according to their ability to give protection where current includes a d.c. component. See NICEIC and ELECSA Pocket Guide 25 for information on the operating times of RCDs. The ‘preferred’ values of I⌬n given in product standards for RCDs used in electrical installations are 10 mA, 30 mA, 100 mA, 300 mA and 500 mA. For most of these values of I⌬n, Table 1 summarises some typical applications for RCDs, and the main requirements of BS 7671. Table 1 – Application and use of RCDs I⌬n 30 mA (Note 2) Typical application(Note 1) Socket-outlets rated at up to 20 A (Notes 4 and mobile equipment up to 32 A for use outdoors Cables concealed in walls and partitions in certain circumstances (Note 6) Lighting in places such as telephone kiosks, bus shelters, advertising panels and town plans All low voltage circuits (e.g. 230 V) of a location containing a bath or shower either serving the location or passing through zones 1 and/or 2 but not serving the location All low voltage circuits of a sauna location, except sauna heater unless recommended by manufacturer Final circuits supplying socket-outlets rated at up to 32 A in agricultural and horticultural premises Caravan pitch socket-outlets. Each socket-outlet to be individually protected by an RCD(Note 7) Circuits supplying floor and ceiling heating systems BS 7671 Regulation Additional protection & 5) 411.3.3 522.6.202 522.6.203 714.411.3.3 701.411.3.3 703.411.3.3 705.411.1 708.533.1.13 753.415.1 Continued overleaf Amd 3: 2015 Based on information as at January 2015 © Certsure LLP Pocket Guide 28 rev 1 01/15 PG28 17.3:pocketguide 8 new 24/03/2015 14:04 Page 2 POCKET GUIDE 28 Application of residual current devices (RCDs) Table 1 – Application and use of RCDs (continued) I⌬n Typical application(Note 1) BS 7671 Regulation Certain circuits of a location containing a swimming or paddling pool Socket-outlets for boats, and circuits to supply houseboats, at marinas and similar. Each to be individually protected by an RCD(Note 7) The installation of a caravan or motor caravan(Note 7) Charging points for electric vehicles (Note 7) Circuits supplying floor and ceiling heating systems See regulations Installations generally (if a sufficiently low listed opposite earth fault loop impedance (Zs) for (Note 3) overcurrent device cannot be achieved) Fault protection 30 mA (Note 2) 702.410.3.4.1 702.410.3.4.2 709.531.2 721.411.1 722.531.2.101 753.411.3.2 411.4.5 (TN system), 411.5.3 Fault protection Protection against fire (TT system) Not exceeding Final circuits supplying socket-outlets rated at more than 32 A in agricultural 100 mA 705.411.1 and horticultural premises Not exceeding Wiring systems except mineral insulated 300 mA (Note 8) cable, busbar trunking and Powertrack, in locations with risk of fire due to 422.3.9 processed or stored materials. Agricultural and horticultural premises (Note 7) 705.422.7 Circuits in agricultural and horticultural premises, except socket-outlet circuits 705.411.1 (covered earlier) Not exceeding Final circuits supplying socket-outlets 500 mA rated at more than 32 A on construction and demolition sites, where the protective measure is automatic disconnection of 704.411.3.2.1 supply Notes. 1 The applications in Table 1 are not exhaustive. For example, RCDs required by Part 7 of BS 7671 in Sections 710 (Medical locations), 711 (Exhibitions, shows and stands), 717 (Mobile or transportable units) and 740 (Temporary installations for fairgrounds etc) are not included. 2 RCD must be of general (non-delay) type. 3 Except for a special installation or location for which Part 7 of BS 7671 gives a different requirement. 4 Where, other than for an installation in a dwelling, a documented risk assessment determines that the RCD protection is not necessary. 5 Except a labelled or otherwise identified socket-outlet for a particular item of equipment. 6 Cables without earthed metallic covering or earthed metallic enclosure or forming part of a SELV or PELV circuit, at a depth of less than 50 mm from surface of wall or partition, or irrespective of depth if the wall or partition has internal metal parts (except screws or nails etc). 7 RCD must disconnect all live (line and neutral) conductors. 8 I⌬n must be not more than 30 mA where a resistive fault may cause a fire (see Regulation 422.3.9 for details). www.niceic.com www.elecsa.co.uk www.eca.co.uk For further copies of this guide telephone 0870 013 0382 or e-mail enquiries@certsure.com © Certsure LLP Pocket Guide 28 rev 1 01/15