LEDAPS Series Steel LED Exit Signs

advertisement
JOB NAME:
TYPE NO.:
CATALOG NO.:
LEDAPS Series Steel LED Exit Signs
ORDERING INFORMATION
Catalog Number: Example: BNLEDAPS2GBTD1
MODEL
NUMBER OF EXIT LETTER
COLOR
NUMBER
FACES
LEDAPS - AC-Only
1 -Single Face R - Red
BNLEDAPS - Emergency No Canopy G - Green
Nickel Cadmium Battery.
2 -Single Face
No Remote Capacity.
With Canopy
HBPLEDAPS -Emergency 3 -Double Face
Lead Calcium Battery. 20W With Canopy
Remote Capacity.
HBPNLEDAPS - Emerg.
Special
Wording Available!
HOUSING
OPTIONS
COLOR
Blank - White
see below
B - Black
BS - Black with
Silver Stencil
Nickel Cadmium Battery.
20W Remote Capacity.
NOTE: HBPLEDAPS and HBPNLEDAPS models require an externally mounted power pack. (See Dimensions)
OPTIONS (1)(2)
DEH362-Par 36 Side Mounted Heads (3)
220 220VAC, 50Hz. Input
SW Special Wording (4)
DL Damp Location Application
TCI1 Two Circuit Input - 120V
TCI2 Two Circuit Input - 277V
TD1 15-Min. Retransfer Delay- 120V
TD2 15-Min. Retransfer Delay- 120V
SX Self-diagnostic Operation (5)
IA Audible Intermittent Alarm (5)
IV
Visual Intermittent Alarm (5)
FA Fire Alarm Panel Interface
TP Tamper-Proof Screws With Bit
ACCESSORIES
HSK18W 18” Stem Kit (White)
HSK18B 18” Stem Kit (Black)
PG-8
Wire Guard (Wall Mount Models)
PG11
Wire Guard (Ceiling/End Mount Models)
- Exits without Lighting Heads
Wire Guard (Ceiling/End Mount Models)
- Exits with Lighting Heads
VERS
Vandal/Environmental Shield
VERS4X Vandal/Environmental Shield with
Gasket
PG10
(1) Other options available.
(2) Some options may impact UL listing.
(3) 5.4W lamps. Heads may be front mounted (HBP models only).
(4) Specify special wording when ordering.
(5) For use with emergency models only.
Battery
Code Compliance
Warranty
Housing: Exits are constructed of heavy duty steel finished in baked-on powder paint providing scratch and corrosion resistance.
Wall Mounting: Knockouts in the exit housing’s back plate are provided for
attachment to wall surfaces and standard 31/2” and 4” electrical boxes.
Ceiling/End Mounting: Mounting canopies are provided with all models for
attachment to standard 31/2” and 4” electrical boxes in ceiling or end applications.
Letter Size: 6” letters with 3/4” stroke
Directional Arrows: Removable chevron arrows meet UL visibility requirements.
Normal AC and emergency exit face illumination is provided by a special high
intensity direct view red or green LED panel. Letter brightness and illumination uniformity exceed UL requirements.
• Dual input 120/277VAC, 60 Hz
• AC Lockout protection
• AC-On indicator light and test switch • Low voltage battery disconnect
• Automatic charger and transfer circuit Normal Input Power: (Regardless of AC input voltage) Single Face 3.9W (max).
Double Face 7.4W (max. )
Emergency models will draw up to 15W (max.) during charge cycles.
BN and HBPN: Sealed nickel cadmium longest life maintenance free battery.
HBP: Sealed lead calcium long life maintenance free battery.
Optimum operating temperature range: 32ºF to 104ºF (0ºC to 40ºC).
Damp Location temperature range: 50ºF to 104ºF (10ºC to 40ºC).
Provides a minimum of 90 minutes of full output emergency illumination
Emergency models are UL924 listed. Meets NFPA Life Safety Code 101.
Complies with NEC and OSHA.
Limited 3-year warranty. 5-year sealed nickel cadmium or 3-year lead calcium
pro-rata battery warranty
Specifications are subject to change without notice. Consult website for latest version of this spec sheet.
Crescent/Stonco • 200 Franklin Square Drive • Somerset, NJ 08873 •
Crescent is a Philips company
All Models
• Rugged steel construction
• Single or double face models
• Wall, ceiling or end mount models
• Red or green exit letters
• Universal directional knockout chevrons
• Choice of three scratch and corrosion resistant finishes
• Low power consumption
• High output, direct view LED illumination
• Universal 120/277VAC field selectable input
Emergency Models
• 90 minutes of emergency illumination
• Solid-state charging and switching circuits
• Maintenance free nickel cadmium or lead calcium battery
depending on model
• Low voltage disconnect protects battery
• AC Lockout feature reduces installation time
• Momentary test switch
• LED AC Ready indicator light
• Optional self-diagnostic circuit available
• UL operating range 68ºF to 86ºF (20ºC to 30ºC)
• Meets NFPA Life Safety Code 101, NEC and OSHA
• UL924 listed
DIMENSIONS
SPECIFICATIONS
Construction
Installation
Exit Face
Illumination
Electronics
Power
Consumption
PRODUCT FEATURES
• www.crescentlighting.com
AC-Only and
BNLEDAPS
Models
45/8”
11.7cm
67/8”
11.7cm
91/16”
23cm
73/4”
19.7cm
121/4”
31.1cm
21/4”
139/16”
5.7cm
34.5cm
HBPLEDAPS and HBPNLEDAPS Models
43/4”
12.1cm
1313/16”
121/2”
35.1cm
31.8cm
24”
61cm
NOTE: Dimensions and specifications subject to change without notice.
Form 1136A 04/12 © 2006 Philips group