Control transformers STN..., DTZ Multi-winding transformer UTI Multipurpose power supply units AING All transformers are constructed and tested according to IEC/EN 61558 guidelines. Depending on version, they can therefore be used in compliance with the safety norm IEC/EN 60204. Single-phase STN control transformers Complete safety for electrical controls → Page 15/4 Single/three-phase control, isolating, and STI, STZ, DTZ safety transformers With increased insulation for the production of low voltages → Page 15/6 Single-phase UTI multi-winding transformers Control, isolation and safety transformers according to IEC/EN 61558-2-2 +++ simple engineering as they are adapted to various worldwide control voltages → Page 15/9 Multipurpose power supply units AING Safety transformers to IEC/EN 61558-2-6 +++ All voltages from one device +++ allow simple engineering and low wiring costs → Page 15/9 2010 CA08103002Z-EN www.eaton.com Control transformers, multi-winding transformers, universal power supply units System overview Transformers, universal power supply units 15/2 Ordering Single-phase control transformers with STN standard voltages 15/4 Single-phase STN control transformers 15/5 Single-phase control, isolating and STI safety transformers 15/6 Single-phase control, isolating and STZ safety transformers 15/7 Three-phase control, isolating, and DTZ safety transformers 15/8 Single-phase UTI multi-winding transformers 15/9 Multipurpose power supply units AING 15/9 IP23 enclosures 15/10 Shielding winding 15/10 Inrush current limiters 15/10 Additional tappings 15/11 Additional windings 15/11 Engineering Size selection for control transformers 15/12 Protection of control transformers 15/12 Technical data Transformers 15/13 Multipurpose power supply units AING 15/13 Dimensions b f c g 1) e a Single-phase STN control transformers 15/15 Single-phase control, isolating, and STI, STZ safety transformers 15/16 Three-phase control, isolating, and DTZ safety transformers 15/17 Multipurpose power supply units AING 15/18 Single-phase UTI multi-winding transformers 15/18 IP23 enclosures for transformers 15/19 Further transformers can be obtained from: Trafomodern Transformatoren Ges.m.b.H. Industriestraße II/11 A-7053 Hornstein E-Mail: info@trafomodern.com Internet: www.trafomodern.com 15/2 Transformers System overview 1 2 6 7 3 4 8 5 2010 CA08103002Z-EN www.eaton.com Standard transformers Single-phase control transformers STZ safety transformers STZ isolating transformers STZ 1 Additional tappings 2010 CA08103002Z-EN www.eaton.com 6 Primary, secondary → Page 15/11 Shielding winding 7 → Page 15/10 Sheet-steel enclosure, degree of protection IP23 2 Primary tapping ± 5 % Built and tested to IEC/EN 61558-2-2/2-4/2-6, VDE 0570-2-2/2-4/2-6, UL 506, CSA 22.2 No. 66 → Page 15/8 Single-phase control transformers STI safety transformers STI isolating transformers STI 15/3 Transformer features Primary tapping ± 5 % Built and tested to IEC/EN 61558-2-2/2-4/2-6, VDE 0570-2-2/2-4/2-6, UL 506, CSA 22.2 No. 66 → Page 15/7 Three-phase control transformers DTZ safety transformers DTZ isolating transformers DTZ Transformers 8 Enclosure for enhanced degree of protection Selection of features → Ordering details of the respective transformer → Page 15/10 3 Primary tapping ± 5 % Built and tested to IEC/EN 61558-2-2/2-4/2-6, VDE 0570-2-2/2-4/2-6, UL 506, CSA 22.2 No. 66 → Page 15/6 Single-phase control transformers STN 3 Primary tapping ± 5 % Built and tested to IEC/EN 61558-2-2, VDE 0570-2-2 UL 506, CSA 22.2 No. 66 → Page 15/4 Single-phase multi-winding transformers UTI 4 Primary tapping 208 to 600 V Built and tested to IEC/EN 61558-2-2/2-4/2-6, VDE 0570-2-2/2-4/2-6, UL 506, CSA 22.2 No. 66 → Page 15/9 Universal power supply unit AING 5 Primary tapping ± 5 % Safety transformer to IEC/EN 61558-2-2/2-6, VDE 0570-2-2/2-6, For every output voltage • a fuse • an LED • a changeover contact → Page 15/9 15/4 Transformers Single-phase control transformers with standard voltages STN HPL15004EN Ordering Single-phase control transformers with standard voltages Rated output kVA Short-time rating kVA Preferred voltage 400/230 V Preferred voltage 400/24 V Preferred voltage 230/24 V Part no. Article no. Part no. Article no. Part no. Article no. Price See price list Price See price list Price See price list Std. pack Single-phase control transformers with standard voltages IEC/EN 61558-2-2 VDE 0570 Part 2-2 Rated input voltage 230 ± 5 % V , 400 ± 5 % V Rated output voltage 24 V , 230 V 0.06 0.095 0.1 0.16 0.16 0.32 0.2 0.38 0.25 0.44 0.315 0.6 0.4 0.62 0.5 0.88 0.63 1.51 0.8 2.25 1 3.28 1.3 4.8 1.6 3.98 2 5.75 2.5 7.24 3 8.36 4 12.2 STN0.06(400/230) 204936 STN0.1(400/230) 204942 STN0.16(400/230) 204948 STN0.2(400/230) 204977 STN0.25(400/230) 204980 STN0.315(400/230) 204982 STN0.4(400/230) 204984 STN0.5(400/230) 204986 STN0.63(400/230) 204988 STN0.8(400/230) 204990 STN1.0(400/230) 204992 STN1.3(400/230) 221523 STN1.6(400/230) 221524 STN2.0(400/230) 221525 STN2.5(400/230) 221526 STN3.0(400/230) 221527 STN4.0(400/230) 221528 STN0.06(400/24) 204937 STN0.1(400/24) 204943 STN0.16(400/24) 204949 STN0.2(400/24) 204978 STN0.25(400/24) 221509 STN0.315(400/24) 221511 STN0.4(400/24) 221514 STN0.5(400/24) 221516 STN0.63(400/24) 221518 STN0.8(400/24) 221520 STN1.0(400/24) 221522 STN0.06(230/24) 204935 STN0.1(230/24) 204941 STN0.16(230/24) 204947 STN0.2(230/24) 204976 STN0.25(230/24) 221508 STN0.315(230/24) 221510 STN0.4(230/24) 221513 STN0.5(230/24) 221515 STN0.63(230/24) 221517 STN0.8(230/24) 221519 STN1.0(230/24) 221521 1 off Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection 2010 CA08103002Z-EN www.eaton.com UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - Transformers 15/5 Single-phase control transformers STN HPL15005EN Single-phase control transformers Rated output Short-time rating kVA kVA Part no. Article no. Price See price list Std. pack Notes 1 off Ordering example When ordering, the part number must include the following details: STN0, 1(*/*) First asterisk ≙ rated input voltage Second asterisk ≙ rated output voltage • Desired part no. STN0, 1 • Desired rated input voltage 200 V • Desired rated output voltage 18.5 V The correct part no. is STN0. 1(200/18.5) Transformer-protective circuit-breakers PKZMO-…-T → Page 7/6 Single-phase control transformers IEC/EN 61558-2-2 VDE 0570 Part 2-2 Rated input voltage 100 – 690 ± 5 % V Rated output voltage 12 – 250 V 0.06 0.095 0.1 0.16 0.16 0.32 0.2 0.38 0.25 0.44 0.315 0.6 0.4 0.62 0.5 0.88 0.63 1.51 0.8 2.25 1 3.28 1.3 4.8 1.6 3.98 2 5.75 2.5 7.24 3 8.36 4 12.2 STN0.06(*/*) 204938 STN0.1(*/*) 204939 STN0.16(*/*) 204944 STN0.2(*/*) 204950 STN0.25(*/*) 204979 STN0.315(*/*) 204981 STN0.4(*/*) 204983 STN0.5(*/*) 204985 STN0.63(*/*) 204987 STN0.8(*/*) 204989 STN1.0(*/*) 204991 STN1.3(*/*) 204993 STN1.6(*/*) 204994 STN2.0(*/*) 204995 STN2.5(*/*) 204996 STN3.0(*/*) 204997 STN4.0(*/*) 204998 Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - 2010 CA08103002Z-EN www.eaton.com 15/6 Transformers Single-phase control, isolating and safety transformers HPL15006EN STI Single-phase control, isolating and safety transformers Rated output Short-time rating kVA kVA Standard voltage 400/230 V Standard voltage 400/24 V Standard voltage 230/230 V Standard voltage 230/24 V Price See price list Part no. Article no. Part no. Article no. Part no. Article no. Part no. Article no. Std. pack STI0.06(400/230) 029975 STI0.1(400/230) 046630 STI0.16(400/230) 046633 STI0.2(400/230) 046636 STI0.25(400/230) 046638 STI0.315(400/230) 046639 STI0.4(400/230) 046640 STI0.5(400/230) 046641 STI0.63(400/230) 046883 STI0.8(400/230) 046889 STI1.0(400/230) 046895 STI1.3(400/230) 046918 STI1.6(400/230) 046952 STI2.0(400/230) 035258 STI2.5(400/230) 035259 STI3.0(400/230) 035260 STI4.0(400/230) 035261 STI0.06(400/24) 029971 STI0.1(400/24) 046631 STI0.16(400/24) 046634 STI0.2(400/24) 046637 STI0.25(400/24) 035249 STI0.315(400/24) 035250 STI0.4(400/24) 035251 STI0.5(400/24) 035252 STI0.63(400/24) 035253 STI0.8(400/24) 035254 STI1.0(400/24) 035255 STI0.06(230/230) 029968 STI0.1(230/230) 029976 STI0.16(230/230) 035247 STI0.2(230/230) 035248 STI0.25(230/230) 036400 STI0.315(230/230) 040641 STI0.4(230/230) 040642 STI0.5(230/230) 040643 STI0.63(230/230) 040644 STI0.8(230/230) 026641 STI1.0(230/230) 026642 STI1.3(230/230) 035256 STI1.6(230/230) 035257 STI2.0(230/230) 036398 STI2.5(230/230) 036399 STI0.06(230/24) 029977 STI0.1(230/24) 046629 STI0.16(230/24) 046632 STI0.2(230/24) 046635 STI0.25(230/24) 035262 STI0.315(230/24) 036392 STI0.4(230/24) 036393 STI0.5(230/24) 036394 STI0.63(230/24) 036395 STI0.8(230/24) 036396 STI1.0(230/24) 036397 1 off Single-phase control, isolating and safety transformers with standard voltages IEC/EN 61558-2-2/2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) Rated input voltage 230 ± 5 % V, 400 ± 5 % V Rated output voltage 24 , 230 V 0.06 0.13 0.1 0.24 0.16 0.36 0.2 0.44 0.25 0.6 0.315 0.75 0.4 1.1 0.5 1.6 0.63 1.7 0.8 2 1 2.8 1.3 3.7 1.6 5.5 2 7 2.5 9 3 11.5 4 15 Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection 2010 CA08103002Z-EN www.eaton.com UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - Transformers 15/7 Single-phase control, isolating and safety transformers STZ HPL15007EN Single-phase control, isolating and safety transformers Rated output Short-time rating kVA kVA Part no. Article no. Price See price list Std. pack Notes 1 off • Transformers with rated output voltages ≦ 50 V can be used as safety transformers to IEC/EN 61558. Single-phase control, isolating and safety transformers IEC/EN 61558-2-2/2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) Rated input voltage 50 – 950 ± 5 % V Rated output voltage 12 – 1000 V 0.06 0.13 0.1 0.24 0.16 0.36 0.2 0.44 0.25 0.6 0.315 0.75 0.4 1.1 0.5 1.6 0.63 1.7 0.8 2 1 2.8 1.3 3.7 1.6 5.5 2 7 2.5 9 3 11.5 4 15 5.3 13 8.3 21 13.3 34 STZ0.06(*/*) 914761 STZ0.1(*/*) 914762 STZ0.16(*/*) 914763 STZ0.2(*/*) 914764 STZ0.25(*/*) 914765 STZ0.315(*/*) 914766 STZ0.4(*/*) 914767 STZ0.5(*/*) 914768 STZ0.63(*/*) 914769 STZ0.8(*/*) 914770 STZ1.0(*/*) 914771 STZ1.3(*/*) 914772 STZ1.6(*/*) 914773 STZ2.0(*/*) 914774 STZ2.5(*/*) 914775 STZ3.0(*/*) 914776 STZ4.0(*/*) 914777 STZ5.3(*/*) 201060 STZ8.3(*/*) 201062 STZ13.3(*/*) 201064 Ordering example When ordering, the part number must include the following details: STZ0.06(*/*) First asterisk ≙ rated input voltage Second asterisk ≙ rated output voltage • Desired part no. STZ0.06 • Desired rated input voltage 230 V • Desired rated output voltage 12 V The correct type reference is STZ0.06(230/12) Caution! Standard voltages 400/230 V, 400/24 V,230/230 V, 230/24 V are only supplied as STI → Page 15/6 if other suffixes, e.g. shield winding, are not ordered. Accessories → Page 15/10 Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - 2010 CA08103002Z-EN www.eaton.com 15/8 Transformers Three-phase control, isolating and safety transformers HPL15008EN DTZ Three-phase control, isolating and safety transformers Rated output Short-time rating kVA kVA Part no. Article no. Price See price list Std. pack Notes DTZ0.1(*/*)* 914799 DTZ0.16(*/*)* 914800 DTZ0.25(*/*)* 914801 DTZ0.4(*/*)* 914802 DTZ0.5(*/*)* 914803 DTZ0.63(*/*)* 914804 DTZ1.0(*/*)* 914805 DTZ1.6(*/*)* 914806 DTZ2.0(*/*)* 914807 DTZ2.5(*/*)* 914808 DTZ4.0(*/*)* 914809 DTZ6.3(*/*)* 914810 DTZ8.0(*/*)* 914811 DTZ10(*/*)* 914812 DTZ12.5(*/*)* 914813 DTZ16(*/*)* 914814 DTZ20(*/*)* 914815 1 off • Transformers with rated output voltages ≦ 50 V can be used as safety transformers in accordance with IEC/EN 61558. DTZ25(*/*)* 914816 1 off Three-phase control, isolating and safety transformers IEC/EN 61558-2-2/2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) Rated input voltage 50 – 950 ± 5 % V Rated output voltage 18.5 – 1000 V 0.1 0.2 0.16 0.32 0.25 0.5 0.4 0.8 0.5 1 0.63 1.38 1 2.2 1.6 3.5 2 4.4 2.5 5.5 4 6.2 6.3 15.7 8 20 10 25 12.5 31 16 40 20 50 25 62 Ordering example When ordering, the part number must include the following details: DTZ0.1(*/*)* First asterisk ≙ rated input voltage Second asterisk ≙ rated output voltage Third asterisk ≙ configuration • Desired part no. DTZ0.1 • Desired rated input voltage 200 V • Desired rated output voltage 18.5 V • Desired configuration Dy(n)5 The correct type reference is DTZ0.1(200/18.5)DY(N)5) Accessories → Page 15/10 Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection 2010 CA08103002Z-EN www.eaton.com UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - Transformers 15/9 Single-phase multi-winding transformers UTI, AING HPL15009EN Single-phase multi-winding transformers Rated output kVA Rated input voltage V Rated output voltage V Part no. Article no. Price See price list Std. pack Notes 1 off Transformer-protective circuit-breakers PKZM0-...-T → Page 7/6 Single-phase multi-winding transformers (Universal) control, isolating and safety transformers to VDE 0550, IEC/EN 61558-2-2/2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) 0.1 208 2 x 115 230 380 0.2 400 415 0.315 440 460 0.5 480 500 525 0.63 550 575 0.8 600 1 Rated output kVA Max. output current A UTI0.1-115 206923 UTI0.2-115 206924 UTI0.315-115 206925 UTI0.5-115 206926 UTI0.63-115 206927 UTI0.8-115 206928 UTI1.0-115 206929 Part no. Article no. Price See price list Std. pack Notes 1 off • Circuit diagram: Multipurpose power supply units AING Safety transformer to IEC/EN 61558-2-2/2-6 VDE 0570 Part 2-2/2-6 For every output voltage a fuse, an LED and a changeover contact for monitoring and annunciation. Non-standard voltages please enquire Rated input voltage 230 ± 5 % V Rated output voltage 24 AC, 10 DC, 24 DC V 0.1 4.2 1 3 0.192 8 1 3 AING4 269516 AING8 269517 +5 % 230 V 24 V AC –5 % 0 +10 V DC _ +24 V DC 0 _ Signal contacts Switching voltage max. 250 V AC/110 V DC max. 1 A Switching duty 62 VA/30 W LED indicators • Output voltage present: LED = green • Fuse fault/missing: LED = red Size/type FK2 fuses are used. Notes Information relevant for export to North America Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Suitable for Max. Voltage Rating Degree of Protection UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking E167225 XPTQ2, XPTQ8 UL report applies to both US and Canada – UL Recognized, certified by UL for use in Canada Branch circuits 600 V AC IEC: IP00, UL/CSA Type: - 2010 CA08103002Z-EN www.eaton.com 15/10 Transformers Accessories HPL15010EN +IP23..., +W..., EEB..., +EEB... Accessories For use with Part no. suffix Article no. for ordering only with basic unit STZ0.06 … STZ0.16 +IP23/01 200618 +IP23/02 200623 +IP23/03 200624 +IP23/04 226100 +IP23/05 200648 +IP23/06 200649 Price See price list Std. pack Notes Information relevant for export to North America 1 off Enclosure can be used with primary or secondary voltages >110 V. For lower voltages, please enquire. IP23 enclosures STZ0.2 … STZ0.5 STZ0.63 … STZ1.3 STZ1.6 … STZ2.0 STZ5.3 … STZ8.3 STZ13.3 STZ2.5 … STZ4.0 DTZ1.0 … DTZ2.0 DTZ0.1 … DTZ0.16 DTZ0.25 … DTZ0.63 DTZ2.5 … DTZ6.3 DTZ8.0 … DTZ25 +IP23/32A 200763 +IP23/30 200706 +IP23/31 200753 +IP23/33 200754 +IP23/34 200755 Enclosure can be used with primary or secondary voltages from 42 V to max. 1000 V incl. taps. Shielding winding STZ0.06 … STZ1.6 STZ2.0 … STZ13.3 DTZ0.1… DTZ6.3 DTZ8.0 … DTZ20 Primary current For use with IN A +W1.8 082270 +W4.0 082271 +W6.0 082274 +W20.0 082275 Type Article no. when ordered separately 1 off Price See price list Shielding winding means additional shielding between the primary and secondary winding. Type suffix Article no. for ordering only with basic unit Price See price list UL/CSA approval not required Std. pack Notes 1 off Primary current: from the transformer rating plate or by calculation Inrush current limiters For single-phase transformers 1 STI STZ 2 3 EEB1 226102 EEB2 226104 EEB3 226106 +EEB1 226101 +EEB2 226103 +EEB3 226105 Single-phase: IN = SN /(UNprim x η) Three-phase: IN = SN /(√3 UNprim x η) SN = rated transformer output UNprim = Transformer´s primary rated voltage η = efficiency (from the technical data table) 2010 CA08103002Z-EN www.eaton.com Transformers 15/11 Accessories +ZA..., +DZA..., +ZW... HPL15011EN Accessories Current range A Part no. suffix Article no. for ordering only with basic unit For use with Price See price list Std. pack Notes 1 off Selection of the correct tap. Ordering example for single-phase transformers: • Selected transformer STZ0.25(400/24) • Required voltage of additional tapping 22 V • The current for selection of the tapping is calculated as follows: Additional tappings For deviations in the rated input or output voltage of more than ± 10 %: • Ask about size of the transformer. • Also state distribution of rating in addition to the tapping. < 16 STZ Primary Single-phase side transformers < 16 STZ Secondary Single-phase transformers +ZA16P(*) 931897 +ZA16S(*) 931895 I = S/U I = current S = apparent power U = voltage of the tapping I = 250/22 = 11.4 A → +ZA16 For the secondary tapping, the correct suffix is: +ZA16S(22) A primary side additional tapping is determined in the same manner. < 16 DTZ Primary side Three-phase transformers +DZA16P(*) 930200 < 16 DTZ Secondary Three-phase transformers +DZA16S(*) 200406 Selection of the correct tap. Ordering example for three-phase transformers: • Selected transformer DTZ0.25(400/24) • Required voltage of additional tapping 22 V • The current for selection of the tapping is calculated as follows: I = S/(√3 x U) I = current S = apparent power U = voltage of the tapping I = 250/( √3 x 22) = 6.6 A → +DZA16 For the secondary tapping, the correct suffix is: +DZA16S(22) A primary side additional tapping is determined in the same manner. Additional windings For primary extra winding please enquire A maximum of 5 additional windings can be ordered for the primary and/or secondary side. < 16 STZ Second- Single-phase ary transformers +ZW16S(*V*VA) 279276 1 off Ordering example for single-phase transformers: Transformer STZ...(400 V/200 V) with 1000 VA and a secondary additional winding for 100 V and 200 VA, resulting in the required rating of 1200 VA. The correct part no. is: STZ1.3(400/200) For pricing of the additional winding, the current is calculated as follows.: I = S/U I = current S = apparent power of the additional winding U = voltage of the additional winding I = 200/100 = 2 A → +ZW16 For the secondary additional winding, the correct suffix is: +ZW16S(100V200VA) Notes Information relevant for export to North America UL/CSA approval not required 2010 CA08103002Z-EN www.eaton.com 15/12 Transformers Selection and protection of control transformers ST..., DT... Engineering Protection of control transformers Selection and protection of control transformers Size selection for control transformers Determination of the continuous rating The control transformer must be rated in size so that the voltage drop remains within the permissible tolerance range even under unfavorable conditions. The determination of the transformer rating is performed by the addition of all the sealing powers of all loads which are to be connected simultaneously as well as addition of the inrush power of the largest load, and multiplying the result by a factor of 0.8. If the ratings of the loads are very similar, the sum of all inrush powers of the simultaneously connected loads is added to the sum of all the sealing powers and the result is multiplied by a factor of 0.8. Determination of the short-time rating If the primary requirement is to switch large contactors, it is recommended that the control transformer is selected on the basis of the short-time rating. In most cases, this will mean that the transformer rating is reduced. It is important to ensure that the sealing power does not exceed the continuous rating. Operational conditions The protective device shown in the table below must be connected upstream of the primary. The overload release of the circuit-breaker must be set to the stated current. The current to be set must also be stated on the rating plate of the transformer. If a short-circuit release is present it must be set to the maximum value. The setting values of the circuitbreaker apply up to 1.06 times the rated voltage. For a higher mains voltage the +5 % terminal is to be used. In the case of transformers > 2.0 kVA (DT...> 4.0 kVA) the circuit-breaker may trip under certain mains supply conditions (Ik > 6 kA) and with unfavorable starting torque. In such cases we recommend the use of an inrush current limiter. The inrush current limiter can be ordered as an accessory. Ordering details → Accessories Setting range of the motor-protective circuit-breaker as a function of the STI, STZ and DTZ transformer rated power (VA) Part no. ST…0.06 ST…0.1 ST…0.16 ST…0.2 ST…0.25 ST…0.315 ST…0.4 ST…0.5 ST…0.63 ST…0.8 ST…1.0 ST…1.3 ST…1.6 ST…2.0 ST…2.5 ST…3.0 ST…4.0 DT…0.1 DT…0.16 DT…0.25 DT…0.4 DT…0.5 DT…0.63 DT…1.0 DT…1.6 DT…2.0 DT…2.5 DT…4.0 DT…6.3 Primary voltage 200 V Protective Setdevice ting A PKZM0-0.4 0.4 PKZM0-0.63 0.5 PKZM0-1 0.8 PKZM0-1.6 1.3 PKZM0-2.5 1.6 PKZM0-2.5 2.0 PKZM0-4 3.1 PKZM0-6.3 5.0 PKZM0-6.3 6.2 PKZM0-10 7.6 PKZM0-16 12.0 PKZ2/ZM-25 18.9 230 V Protective device PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZM0-10 PKZM0-10 PKZM0-16 PKZ2/ZM-16 PKZ2/ZM-25 PKZ2/ZM-25 PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-4 PKZM0-6.3 PKZM0-6.3 PKZM0-10 PKZM0-16 PKZ2/ZM-25 Setting A 0.3 0.5 0.8 1.0 1.3 1.5 2.0 2.4 3.0 3.8 4.7 6.3 7.4 10.0 11.5 16.0 18.1 0.3 0.5 0.7 1.1 1.4 1.8 2.7 4.3 5.4 6.7 10.4 16.4 400 V Protective device PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZM0-6.3 PKZ2/ZM-10 PKZ2/ZM-16 PKZ2/ZM-16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZ2/ZM-10 Setting A 0.2 0.3 0.5 0.6 0.7 0.9 1.1 1.4 1.7 2.2 2.7 3.5 4.2 5.3 6.6 10.0 10.4 0.2 0.3 0.4 0.7 0.8 1.0 1.6 2.5 3.1 3.8 6.0 9.5 415 V Protective device PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZM0-6.3 PKZ2/ZM-10 PKZ2/ZM-16 PKZ2/ZM-16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZ2/ZM-10 For all other transformers use transformer-protective circuit-breakers PKZM0-...-T. → Page 7/6 2010 CA08103002Z-EN www.eaton.com Setting A 0.2 0.3 0.5 0.6 0.7 0.9 1.1 1.3 1.7 2.1 2.6 3.4 4.1 5.1 6.4 10.0 10.0 0.2 0.3 0.4 0.6 0.8 1.0 1.5 2.4 3.0 3.7 5.8 9.1 440 V Protective device PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZ2/ZM-10 PKZ2/ZM-10 PKZ2/ZM-10 PKZM0-0.25 PKZM0-0.4 PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZ2/ZM-10 Setting A 0.2 0.3 0.4 0.5 0.7 0.8 1.0 1.2 1.6 2.0 2.5 3.2 4.0 4.8 6.0 7.1 10.0 0.2 0.3 0.4 0.6 0.7 0.9 1.4 2.3 2.8 3.5 5.5 8.6 500 V Protective device PKZM0-0.16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-4 PKZM0-6.3 PKZ2/ZM-6 PKZ2/ZM-10 PKZ2/ZM-10 PKZM0-0.16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-6.3 PKZ2/ZM-10 Setting A 0.2 0.2 0.4 0.5 0.6 0.7 0.9 1.1 1.4 1.7 2.2 2.8 3.4 4.2 5.3 6.2 8.3 0.1 0.2 0.3 0.5 0.6 0.8 1.3 2.0 2.5 3.1 4.8 7.6 690 V Protective device PKZM0-0.16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1 PKZM0-1.6 PKZM0-1.6 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZ2/ZM-4 PKZ2/ZM-6 PKZ2/ZM-6 PKZM0-0.16 PKZM0-0.25 PKZM0-0.4 PKZM0-0.63 PKZM0-0.63 PKZM0-0.63 PKZM0-1 PKZM0-1.6 PKZM0-2.5 PKZM0-2.5 PKZM0-4 PKZM0-6.3 Setting A 0.1 0.2 0.3 0.3 0.4 0.5 0.7 0.8 1.0 1.3 1.6 2.0 2.5 3.1 4.0 4.5 6.0 0.1 0.2 0.3 0.4 0.5 0.6 0.9 1.4 1.8 2.2 3.5 5.5 Transformers 15/13 Transformers, universal power supply units STI, STZ, DTZ, STN, UTI, AING Technical data Transformers, universal power supply units Control transformers General Standards Built and tested to Suitable for use to Ambient temperature Characteristics Terminals Connection lugs Insulation class Rated frequency Primary tapping Degree of protection Separate windings Completely vacuum-impregnated Reinforced insulation Rated duty factor °C Hz % DF Multi-winding transformers UTI Universal power supply units AING Safety transformer to IEC/EN 61558-2-2/ 2-6 VDE 0570 Part 2-2/ 2-6 ● – B 50 - 60 ±5% IP20 ● ● ● 100 STI, STZ DTZ STN IEC/EN 61558-2-2/ 2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) IEC/EN 61558-2-2/ 2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) IEC/EN 61558-2-2 VDE 0570 Part 2-2 IEC/EN 60204-1, ÖVE-EN 13 VDE 0113, VDE 0100 Part 410 -25 - +40 IEC/EN 60204-1, ÖVE-EN 13 VDE 0113, VDE 0100 Part 410 -25 - +40 IEC/EN 60204-1, ÖVE-EN 13 VDE 0113, VDE 0100 Part 410 -25 - +40 (Universal) control, isolating and safety transformers to VDE 0550, IEC/EN 61558-2-2/ 2-4/2-6 VDE 0570 Part 2-2, Part 2-6 (safety transformers), Part 2-4 (isolating transformers) IEC/EN 60204-1, ÖVE-EN 13 VDE 0113, VDE 0100 Part 410 -25 - +40 ● (< 115 A) ● (> 115 A) B 50 - 60 ±5% IP00 ● ● ● 100 ● (< 115 A) ● (> 115 A) B 50 - 60 ±5% IP00 ● ● ● 100 ● (< 115 A) ● (> 115 A) B 50 - 60 ±5% IP00 ● ● – 100 ● – B 50 - 60 ± 20 % IP00 ● ● ● 100 2010 CA08103002Z-EN IEC/EN 60204-1 VDE 0113 -25 - +40 www.eaton.com 15/14 Transformers Transformers STI, STZ, DTZ, UTI Transformers Total weight No-load losses kg W Shortcircuit losses W Shortcircuit voltage % Efficiency Single-phase control, isolating, and safety transformers1) ST…0.06 ST…0.1 ST…0.16 ST…0.2 ST…0.25 ST…0.315 ST…0.4 ST…0.5 ST…0.63 ST…0.8 ST…1.0 ST…1.3 ST…1.6 ST…2.0 ST…2.5 ST…3.0 ST…4.0 STZ5.3 STZ8.3 STZ13.3 1.5 2 2.3 3 3.8 4.3 5.2 6.8 7.7 9.6 13.4 14.9 17.4 21.5 21.5 26 35 40 55 80 6 7 9 11 13 10 17 15 15 17 27 32 21 27 39 30 38 40 65 95 1) 1 1.5 2.4 2.8 2.9 3.5 4.2 5.1 7.1 9.8 12.4 14.1 14.3 19.9 20 23 27 7 7 11 9 9 11 12 15 21 24 33 46 43 56 21 32 28 No-load losses kg W 5 8 12 17 14 18 18 24 27 25 29 35 37 33 43 55 88 165 200 265 7.8 6.9 6.6 6.6 5.1 5.5 4.4 3.9 4.1 3.2 2.9 3 2.4 2 2.4 2.1 2.2 4 4 3.5 0.85 0.87 0.88 0.88 0.9 0.92 0.92 0.93 0.94 0.95 0.95 0.95 0.96 0.97 0.97 0.97 0.97 0.96 0.97 0.97 10 15 16 19 21 21 27 27 32 24 26 33 44 42 145 94 143 11 10 6.7 6.8 6.3 5.3 5.3 4.1 3.8 2.5 2.2 2.1 2.5 2 2.4 2.4 2.4 0.79 0.84 0.87 0.88 0.9 0.91 0.92 0.93 0.93 0.94 0.94 0.94 0.95 0.95 0.95 0.96 0.96 DTZ0.1 DTZ0.16 DTZ0.25 DTZ0.4 DTZ0.5 DTZ0.63 DTZ1.0 DTZ1.6 DTZ2.0 DTZ2.5 DTZ4.0 DTZ6.3 DTZ8.0 DTZ10 DTZ12.5 DTZ16 DTZ20 DTZ25 1.9 2.5 3.6 5.1 6.1 8.9 12.9 18.5 22.4 29.3 39.6 50.2 55 70 80 95 125 160 5 8 11 15 20 25 35 55 60 80 60 66 60 80 95 100 140 180 Shortcircuit voltage % Efficiency 28 20 25 40 35 50 50 60 75 85 100 170 250 280 300 420 400 350 15 9.5 8.5 8 6 5.5 4 3 3.5 2.5 2 2 4 3.5 4 4.5 3.5 3 0.75 0.85 0.88 0.88 0.9 0.9 0.92 0.93 0.94 0.94 0.96 0.96 0.96 0.97 0.97 0.97 0.98 0.98 7.5 6.5 5 3.5 3.8 2.8 2.1 0.84 0.87 0.89 0.92 0.92 0.93 0.93 Single-phase multi-winding transformers UTI0.1 UTI0.2 UTI0.315 UTI0.5 UTI0.63 UTI0.8 UTI1.0 2 3 4.3 6.8 7.7 9.6 13.4 8 10 15 26 25 33 46 All no-load loss, short-circuit loss, short-circuit voltage and efficiency values apply at a temperature of 20 °C. 2010 CA08103002Z-EN Shortcircuit losses W Three-phase control, isolating, and safety transformers1) Single-phase control transformers1) STN0.06 STN0.1 STN0.16 STN0.2 STN0.25 STN0.315 STN0.4 STN0.5 STN0.63 STN0.8 STN1.0 STN1.3 STN1.6 STN2.0 STN2.5 STN3.0 STN4.0 Total weight www.eaton.com 11 19 23 23 32 29 30 Transformers 15/15 Single-phase control transformers STN Dimensions Single-phase control transformers Single-phase control transformers STN0.06...2.0 2) c±5 ① Connection lugs ② Maximum space requirement ③ With STN0,06-0.2 ground connection at bottom c1 3) 1) og e f 2) a b1 2) b±5 Part no. STN0.06 STN0.1 STN0.16 STN0.2 STN0.25 STN0.315 STN0.4 STN0.5 STN0.63 STN0.8 STN1.0 STN1.3 STN1.6 STN2.0 12 V b 79 75 97 83 103 111 108 120 121 124 150 138 183 213 a 66 85 85 106 106 106 121 121 151 151 151 175 175 175 c 78 91 91 112 121 121 133 133 157 196 196 213 170 170 24 V b 79 75 97 83 83 91 88 120 121 138 164 148 138 168 c 78 91 91 112 112 112 124 133 157 157 157 169 216 216 42 V b 79 75 97 83 83 91 88 100 107 124 164 148 148 178 c 78 91 91 112 112 112 124 124 145 145 157 169 169 169 110 V b 79 75 97 83 83 91 88 100 107 124 150 138 138 168 c 78 91 91 112 112 112 124 124 145 145 145 157 157 157 230 V b 79 75 97 83 83 91 88 100 107 124 150 138 138 168 c 78 91 91 112 112 112 124 124 145 145 145 157 157 157 e 50 64 64 80 80 80 90 90 122 122 122 135 135 135 f 56 47 70 61 61 70 68 80 82 99 125 110 110 141 ⌀g 4.8x8 4.8x8 4.8x8 5.8x9 5.8x9 5.8x9 5.8x12 5.8x12 7x15 7x15 7x15 7x15 7x15 7x15 b1 67 60 83 80 80 89 86 98 104 121 147 135 135 165 c1 60 76 76 97 97 97 106 106 132 132 132 152 152 152 STN2.5...4.0 ① Connection lugs ② Maximum space requirement 2) b1±5 2) c±5 c1 f ⭋g 1) e b 2) a Part no. STN2.5 STN3.0 STN4.0 a 230 230 230 b 130 155 170 c1 250 250 250 e 190 190 190 f 200 200 200 ⌀g 11 11 11 b1 12 V 185 210 225 c 12 V 260 260 260 b1 24V 185 230 245 c 24V 250 250 250 b1 42 V 205 230 245 c 42 V 255 255 255 b1 110 V 160 185 200 c 110 V 275 275 275 2010 CA08103002Z-EN b1 230 V 145 170 185 c 230 V 255 255 255 www.eaton.com 15/16 Transformers Single-phase control, isolating, and safety transformers STI, STZ Single-phase control, isolating, and safety transformers Single-phase control, isolating, and safety transformers ST...0.06...2.5 ① Connection lugs ② With STI/STZ0.06 … 0.16 ground connection at bottom c1 c±5 2) 1) g e f a b1 b±5 Part no. ST…0.06 ST…0.1 ST…0.16 ST…0.2 ST…0.25 ST…0.315 ST…0.4 ST…0.5 ST…0.63 ST…0.8 ST…1.0 ST…1.3 ST…1.6 ST…2.0 ST…2.5 a 85 85 85 106 106 121 121 121 151 151 151 175 195 195 195 12 V b 75 89 97 83 111 - c 91 91 91 112 124 - 24 V b 75 89 97 83 91 88 100 140 121 138 164 148 142 154 154 c 91 91 91 112 112 119 119 131 157 157 157 169 240 240 240 42 V b 75 89 97 83 91 88 100 120 107 124 164 148 149 161 154 110 V b 75 89 97 83 91 88 100 120 107 124 150 138 142 154 161 c 91 91 91 112 112 119 119 119 145 145 157 169 186 186 240 c 91 91 91 112 112 119 119 119 145 145 145 157 174 174 186 230 V b 75 89 97 83 91 88 100 120 107 124 150 138 142 154 154 c 91 91 91 112 112 119 119 119 145 145 145 157 174 174 174 b1 60 74 83 80 89 86 98 118 104 121 147 135 140 152 152 c1 76 76 76 97 97 106 106 106 132 132 132 152 166 166 166 e 64 64 64 80 80 90 90 90 122 122 122 135 150 150 150 ST...3.0...4.0 b f c g 1) e a Part no. ST…3.0 ST…4.0 a 230 230 2010 CA08103002Z-EN 12 V b - c - www.eaton.com 24 V b 210 235 c 250 250 42 V b 230 255 c 255 255 110 V b 185 210 c 275 275 230 V b 170 200 c 255 255 e 190 190 f 200 200 ⌀g 11 11 f 47 61 70 61 70 68 80 100 82 99 125 110 110 122 122 ⌀g 4.8x8 4.8x8 4.8x8 5.8x9 5.8x9 5.8x12 5.8x12 5.8x12 7x15 7x15 7x15 7x15 10x18 10x18 10x18 Transformers 15/17 Three-phase control, isolating, and safety transformers STZ, DTZ Three-phase control, isolating, and safety transformers c±5 STZ5.3...13.3 f e a b±5 g 12 V Part no. a b c STZ5.3 260 200 *) STZ8.3 260 STZ13.3 320 *) The higher rated voltage is valid 24 V b 200 230 240 42 V b 200 230 240 c *) *) *) c *) *) *) 110 V b 214 244 270 c 374 374 440 230 V b 214 244 270 c 360 374 440 e 230 230 270 f 126 156 172 ⌀g 10x18 10x18 13x20 Three-phase control, isolating, and safety transformers DTZ0.1...25 ① The higher rated operating voltage applies ② Terminals ≦ 25 A ③ Connection lugs > 63 A 2) c1 c 3) og e a f b1 b Part no. DTZ0.1 DTZ0.16 DTZ0.25 DTZ0.4 DTZ0.5 DTZ0.63 DTZ1.0 DTZ1.6 DTZ2.0 DTZ2.5 DTZ4.0 DTZ6.3 a 125 125 155 155 190 190 210 230 240 265 300 300 18.5 V b 65 75 77 92 82 102 137 144 117 132 166 193 DTZ8.0 DTZ10.0 DTZ12.5 DTZ16 DTZ20 DTZ25 390 390 390 450 450 450 200 - c 134 134 154 154 180 180 210 234 279 299 317 285 1) - 24 V b 65 75 77 92 112 132 137 114 117 132 166 210 200 216 231 221 251 281 c 134 134 154 154 191 191 210 269 279 299 333 285 1) 1) 1) 1) 1) 1) 42 V b 65 75 77 92 82 102 137 144 117 132 147 193 200 216 231 221 251 281 c 134 134 154 154 180 180 210 234 279 299 333 333 1) 1) 1) 1) 1) 1) 110 V b 65 75 77 92 82 102 117 114 141 152 157 173 184 199 214 204 234 264 c 134 134 154 154 180 180 199 223 244 264 296 333 374 374 374 434 1) 1) 230-690 V b c 65 134 75 134 77 154 92 154 82 180 102 180 117 199 114 223 117 233 132 253 157 296 173 296 e 100 100 130 130 170 170 175 176 185 200 224 224 f 45 55 57 72 58 78 97 95 95 102 119 145 ⌀g 8x5 8x5 8 x 12 8 x 12 8 x 12 8 x 12 8 x 12 7 x 13 10 x 18 10 x 18 10 x 18 10 x 18 b1 61 71 77 92 82 102 117 114 117 132 147 173 c1 102 102 128 128 155 155 174 198 208 228 260 260 184 199 214 204 234 264 350 350 350 400 400 400 126 141 156 142 172 202 10 x 18 10 x 18 10 x 18 13 x 20 13 x 20 13 x 20 152 167 182 172 202 232 310 310 310 360 360 360 374 374 374 434 434 434 2010 CA08103002Z-EN www.eaton.com 15/18 Transformers Single-phase multi-winding transformers, universal power supply units UTI, AING Single-phase multi-winding transformers, universal power supply units Universal power supply units AING4, AING8 a 62 70 5.8 155 Part no. AING4 AING8 14.5 80.5 a 110 90 Single-phase multi-winding transformers UTI... c1 c±5 2) og e f 1) a±5 b1 1) b±5 2010 CA08103002Z-EN www.eaton.com Us = 115 V Part no. a b c UTI0.1… 85 89 93 UTI0.2… 106 82 112 UTI0.315… 121 88 124 UTI0.5… 121 120 124 UTI0.63… 151 107 150 UTI0.8… 151 124 150 UTI1.0… 151 150 150 Us … Secondary voltage 1) 2) e 64 80 90 90 122 122 122 f 61 61 68 100 82 99 125 ⌀g 4.8x8 5.8x9 5.8x12 5.8x12 7x15 7x15 7x15 Maximum space requirement With type UTI0,1… ground connection at bottom b1 74 80 86 118 104 121 147 c1 76 97 106 106 132 132 132 Transformers 15/19 Enclosure for transformers IP23 Enclosure for transformers IP23 enclosures +IP23/01, +IP23/02 a Part no. +IP23/01 +IP23/02 +IP23/03 +IP23/04 +IP23/30 +IP23/31 +IP23/32A b c b 118 192 192 231 192 231 263 c 145 184 184 254 184 254 360 +IP23/04, +IP23/31, +IP 23/32A a a +IP23/03 a 122 160 203 203 160 203 315 c b c b a +IP23/30 b c +IP23/05, +IP23/06, +IP 23/33, +IP23/34 Part no. +IP23/05 +IP23/06 +IP23/33 +IP23/34 c a 570 690 520 620 b 390 500 410 560 c 390 480 340 440 c1 430 540 360 460 e 230 270 212 350 f 390 500 330 430 ⌀g 10 13 10 12 a b f e g c1 2010 CA08103002Z-EN www.eaton.com