PRODUCT DESCRIPTION

The Luminoso LED E mergency Battery Back-up work s with all 120V AC input voltage , powering the AC driver of the led lights. The LED EMB I from Luminoso is a UL Recognized

LED Emergency Back-up that allows the same LED fixture to be used for both normal and emergency operation. In the event of a power failure, the EMBI switches to the emergency mode and operates the existing fixture for 90 minutes. The unit contains a battery, charger, and converter circuit in and is available in different mounting configurations for individual fixture requirements.

1.

The EMBI-18W-Y is for use with an LED Fixture load up to 18W at a rated voltage of 170VDC

2.

The EMBI-25W-Y is for use with an LED Fixture load up to 25W at a rated voltage of 170VDC

FEATURES

1.

R ecyclable Ni-Cad battery.

2.Includes test switch and charge indicator accessory kit.

3.For use with switched or unswitched fixtures

4.Meets or exceeds all National Electrical Code and Life Safety Code

Emergency Lighting

Dimensions

TECHNICAL SPECIFICATIONS :

Model(UL)

Output Power

Input Power

Output Voltage

Emergency Operation

Operating Temp

Input Voltage

Battery

UL Conditions of

Acceptability

EMBI-18W-Y EMBI-25W-Y

18W(Max)

6 Watts(Max)

170VDC( Equivalent 120VAC)

≥ 90 minutes

0 ℃ to 50 ℃

25W(Max)

6 Watts(Max)

100-277 VAC, 50-60Hz

High Temp Nickel-Cadmium 24 Hour Recharge 7-10

Year Life Expectancy

Must be factory wired Battery temperature must not exceed 50 ℃

Model

A

B

C

D

E

TYPICAL WIRING DIAGRAM

HOT A.C.LINE

NEUTRAL

WALL SWITCH

BROWN

BLACK

WHITE

Flex (B)

Led

Emergency Lamp

Flex (A)

PURPLE

(AC DRIVER HOT LINE)

BLUE

(AC DRIVER NEUTRAL)

AC DRIVER

WITH LAMP

(2)TEST SWITCH

RED(+)

CHARGE INDICATOR

GRAY(-)

Equipment

WHITE

WHITE UNIT CONNECTOR

C

EMBI-18W-Y

69mm

71mm

377mm

69mm

22.2mm

EMBI-25W-Y

69mm

71mm

377mm

69mm

22.2mm

D

( ) DO NOT MATE CONNECTOR UNTIL

INSTALLATION IS COMPLETE AND

AC POWER IS SUPPLIED.

(2) ) TEST ACCESSORY LEADS-

OBSERVE PROPER POLARITY

WIRING.

The WALL SWITCH control the on and off of the AC DRIVER when the urban voltage is normal.

Order Information

Product Category Source

Example: EMB I 1 8W-Y

Base

EMBI 18W

25 W

Y = 120-277V

T: (305) 364-8099  9800 NW 78 th

Ave, Miami, FL 33016 

Instruction Manual

LED Lamp Emergency Equipment

IMPORTANT SAFEGUARDS

When using electrical equipment,basic safety precautions should always be followed,including the following:

READ AND FOLLOW ALL SAFETY

INSTRUCTIONS

1.

To prevent high voltage from being present on the purple and blue output leads prior to installation, The

LED Lamp Emergency Backup connector must be open. Join the connector after the LED Lamp

Emergency Backup has been installed and before the AC power is supplied.

2.

The LED Lamp Emergency Backup work with all the led lights which the input voltage is AC100-277V or 100-135V powering the AC driver of the led lights.

The output voltage of emergency backup is 170V DC which equals to 120VAC.EH-18170-XXU/EH-18170-XXG

Maxium18W ,EH-25170-XXU/EH-25170-XXG Maxium

25W Emergency time: Min 90 minutes.Please do not use this production in any other application.

3 . Make sure all connections are in accordance with the National Electrical Code or any local regulations.

4 . To reduce the risk of electric shock, disconnect both normal and auxiliary power supplies and connector of the LED Lamp Emergency Backup before servicing.

5 . The AC power source (100-277VAC/120-250VAC) ahead of any wall switch is required to provide battery charging current.

6 . Do not install near gas or electric heaters.

7 . This product is for use with indoor or damp locations where ambient temperature is ( 0 ℃ to 50 ℃ ).

Not suitable for wet or hazardous locations.

8 . This is a sealed unit. Integral battery is not replaceable. Replace entire unit when necessary.

9 .The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

10 .Servicing should be performed by qualifed service personnel.

11 .Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.

12.

Do not use this equiment for other than its intended use.

SAVE THESE INSTRUCTIONS

Production Information

AC Input Model

100-277VAC

(UL)

EMBI-18W

EMBI-25W

LED Lamp

18W

25W

INSTALLING THE LAMP EMERGENCY

EQUIPMENT

1 .THE LED Lamp Emergency Backup will be ocated between the AC power sources and the AC driver as shown in wiring diagram section of instructions.

2 .NOTE: THE LED Lamp Emergency Backup may be installed in close proximity to the fxture or remote from the fxture.

3 .The maximum remote distance using 16 AWG wire is

250 ft. Contact the factory for more information.

4 .The AC power is fed to THE LED Lamp Emergency

Backup.

5 .The AC driver receives power from the LED Lamp

Emergency Backup.Identify the output wires of the

LED Lamp Emergency Backup by the presence of the purple and blue leads.

STEP 1: DISCONNET AC POWER FROM

FIXTURE

1 .Disconnect all power sources from lighting fxture and ensure they are locked out during installation or maintenance.

2 .Disconnect power leads from the AC driver.

3 .Select a suitable location for the LED Lamp Emergency

Backup and install such that its output leads can connect to the input leads of the AC driver.

4 .See Illustration 1, for typical installation and select appropriate mounting method.

STEP 2: WIRING THE LED Lamp Emergency

Backup

1 .Use the wiring diagram found on page 4 as reference.

2 .Connect the AC power source leads to the input of the EMERGENCY EQUIPMENT.

3 .Connect the output leads of The LED Lamp

Emergency Backup to the AC driver.

4 .Wire the AC driver with the lamp in accordance with manufactures installation instructions.

5 .Make sure all connections are in accordance with the

National Electrical Code,and any local regulations.

CAUTION :

THE LED Lamp Emergency Backup unit connector is disconnected.

NOTE:Make sure that the necessary branch circuit wiring is available.

An unswitched source of power is required. The unswitched and switched power source must be fed from the same branch circuit.

Instruction Manual

LED Lamp Emergency Equipment

6 .Connect the indicator LED by matching red and gray leads.

7 .In a readily visible location, attach the label

"CAUTION-This Unit Has More than one power connection point. To reduce the risk of electric shock, Disconnect both the branch circuitbreakers or fuses and the LED Lamp Emergency

Backup connector supply before servicing."

STEP 3: JOIN THE LED Lamp Emergency

Backup CONNECTOR & APPLY POWER

1 .After installation is complete, join the LED Lamp

Emergency Backup connector and apply AC power.

2 .At this point,power shoule be connected to both the AC driver and the LED Lamp Emergency

Backup and the Charging Indicator Light should illuminate indicating the battery is charging.

3 .A short-term discharge test may be conducted after the LED Lamp Emergency Backup has been charging for 1 hour, Charge for 24 hours before conducting a longterm dis-charge test.Refer to

OPERATTION.

Illsutration1

OPERATION

During normal operation, AC power is supplied to the AC driver through the LED Lamp Emergency

Backup and charges the battery.The LED Lamp

Emergency Backup detects AC input line voltage

(100-277AC/120-250VAC)and automatically sets the output voltage during emergency mode.When

AC power fails, The LED Lamp Emergency Backup automatically switches to emergency mode,keeping the load illuminated for a minimum of 90 minutes.

When AC power is restored, The LED Lamp

Emergency Backup returns to charging mode. The

LED Lamp Emergency Backup consists of a lowbattery voltage disconnect which is reset when AC power is restored.

MAINTENANCE

Although no routine maintenance is required to keep

The LED Lamp Emergency Backup functional,it should be checked periodically to ensure that it is working. The following schedule is recommended:

1 .Visually inspect the charging indicator light monthly. It should be illuminated.

2 .Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. The lamp should operate at full illumination.

3 .Conduct a 90-minute discharge test once a year. The lamp should operate at full illumi-nation for at least

90 minutes.

IN

C

R

E

R

O

T

E

R

The T-BAR mounting bracket assembly is sold separately and is available from the factory as an accessory kit(T-BAR-MB).call your local distributor or the factory for complete information.

EMERGENCY EQUIPMENT

No Shading -Equipment supplied by others

1

2

3

4

-Flexible conduit (supplied) to connect

AC driver wires.

-Existing conduit to run existing wires

to lamp holder.

-AC line in.

-Conduit and junction box (not supplied).

REFER ANY SERVIVING INDICATED BY

THESE CHECKS TO QUALIFIED PERSONNEL!

THE LED LAMP EMERGENCY BACKUP AND

AC DRIVER MUST BE FED FROM THE SAME

BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY.CONSULT

THE FACTORY FOR OTHER WIRING DIAGRAMS.

WIRING DIAGRAM

HOT A.C.LINE

NEUTRAL

WALL SWITCH

BROWN

BLACK

WHITE

(2)TEST SWITCH Flex (B)

LED Lamp

Emergency

Equipment

Flex (A)

BLUE

(AC DRIVER NEUTRAL)

WHITE

RED(+)

PURPLE

(AC DRIVER HOT LINE)

WHITE

UNIT CONNECTOR

CHARGE INDICATOR

GRAY(-)

AC DRIVER

WITH LAMP

Note: Make sure the necessary branch circuit wiring is available.An unswitched source of power is required.

The unswitched and switched power sources must be fed from the same branch circuit.