PTM Installation Instructions

advertisement
The
Commander™
Series
PTM
Section 1
Section 2
General Description
The PTM is a timing module that allows users to control
an automatic door operator for a room where privacy is a
concern, such as a washroom, restroom, clean room, or
photo development room. From the outside of the room,
users are able to activate the door. Once inside, users
are able to lock the door which prevents access from the
outside “push to open” button. When egress is desired,
the user presses an inside “push to open” button which
deactivates the lock and activates the door. A keyswitch
override is present on the exterior, as well as LEDs to
indicate if the room is occupied. Green indicates
available while red indicates occupied.
The delay time between deactivating the lock and
activating the door, as well as the “on time” for door
activation are fully programmable.
!
INSTALLATION INSTRUCTIONS
Privacy Timing Module
WARNING: Devices to be controlled by the PTM
must be low voltage (12-24V) but can be
inductive loads. Surge suppressors are standard
on the PTM.
OPTIONS:
PTM = Privacy Timing Module
PTM-HDWE = Prewired Harness to Terminal Block &
Magnetic Door Position Switch
PTM-KIT = Turnkey Kit Includes PTM, PTM-HDWE &
Switches (830B-59J-PTM, 59V-PTM)
WET/DRY CONTACT OPTION:
The PTM has the option to supply power to Relay Output
1 contacts. This is known as having a "Wet" contact
instead of the conventional "Dry" contact closure. To use
output 1 as a "Wet" contact, change the jumper setting
(see Figure 1). The voltage supplied to Output 1 will be
the same as the voltage supplied to the input power wires
of the PTM.
!
WARNING: Changing jumper settings to enable
the “Wet” Contact option will apply a voltage to
the Output 1 relay contact. Please ensure that
any device connected to this output is capable of
accepting voltage. Failure to do so may result in
damage to the device.
!
WARNING: If the “Wet” Contact Option is to be
used, please ensure that no more than a
maximum of 3A current is to be supplied by the
PTM. Failure to do so may result in damage to
the PTM.
Basic Installation
1. Mount the PTM in desired location.
2. With power off, make all necessary wiring
connections to the wiring harnesses (Fig. 1) or
Pre-wired Terminal Block (Fig. 2).
Figure 1: PTM Layout and Wiring Connections
!
NOTICE: These instructions are provided for your
convenience. Please verify your installation is in
compliance with all applicable standards upon
completing installation of this device.
Section 3
Technical Data
Model.................................... PTM
Input Power........................... 12-24V AC or DC
Power Consumption............. 2W Maximum
Output Contacts................... Form C, Rated at 3 Amps
Relay Contact Rating............3A:120V AC; 3A:60V DC
Temperature Rating............. -22°F to 158°F
(-30°C to 70°C)
Weight................................... <0.25 lbs.
Physical Size......................... 4.75"L x 2.125"W x 0.75"H
Section 4
Warranty
MS SEDCO guarantees this product to be free from manufacturing
defects for 1 year from date of installation. Unless MS SEDCO is
notified of the date of installation, the warranty will be in effect for
1 year from the date of shipment from our factory. If, during the
first year, this device fails to operate and has not been tampered
with or abused, the unit can be returned prepaid to factory and it
will be repaired free of charge. After 1 year, the unit will be
repaired for a nominal service charge. This limited warranty is in
lieu of all other warranties expressed or implied, including any
implied warranty of merchantability, and no representative or
person is authorized to assume for MS SEDCO any other liability
in connection with the sale of our products. All warranties are
limited to the duration of this written warranty. In no event
shall MS SEDCO be liable for any special, incidental,
consequential or other damages arising from any claimed
breach of warranty as to its products or services.
Questions? Call us toll-free at 1-317-842-2545 or
visit us online at www.mssedco.com.
8701 Castle Park Drive  Indianapolis, Indiana 46256
Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com
Page 1
(82A044) PTMv0315
The
Commander ™
Series
PTM
INSTALLATION INSTRUCTIONS
Privacy Timing Module
FIGURE 1—PTM Layout & Wiring Connections
Input Actions
Input Connections
Green
Green
Blue
Input 1—Deactivates Output 1, then activates Output 2.
Input 2—Deactivates Output 1.
Input 3—Activates Output 1. Locks out Input 4.
Input 4—Activates Output 2.
Input Power 12-24V
(AC or DC)
Wht/Blue
Wht/Red
Wht/Grn
Wht/Vio
Wht/Gra
Output
Connections
Yellow
N.O.
Brown
Orange
COM
N.C.
Green
Green
Wht/Blue
Blue
Wht/Grn
Wht/Red
Wht/Vio
N.C.
CO M
N.O.
01= dry
01= wet
N.C.
CO M
N.O.
In series with electric lock
Output
#1
Output
#2
N.O.
COM
N.C.
N.O.
COM
N.C.
Output #1
RED LED &
Electric Lock
White
LED Connections
Gray
COM
N.C.
Output #1
Violet
Violet
N.O.
Output #2
Brown
Yellow
Gray
LED DISPLAY KEY
d1 = delay output 1 to 2
d2 = output 2 on time
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
o2 = output 2 (n.o. / n.c.)
DISPLAY
ADJUSTMENT
Orange
White
12-24V AC/DC
PROGRAM
MODE BUTTON
INPUT1
INPUT1
PTM
INPUT4
CO M
INPUT3
INPUT2
CO M
Wht/Brown
Wht/Gray
Wht/Brown
Switch Input #1 Inside Push to Open Switch
Switch Input #2 Outside Key Switch and Latchbolt
or Inside Lever Monitor (if used)
Switch Input # 3 Inside Push to Lock Switch
Switch Input #4 Outside Push to Open Switch
Wet/Dry
Contact Option
(Factory Setting = Dry Contact)
Output #1
GREEN LED
8701 Castle Park Drive  Indianapolis, Indiana 46256
Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com
Page 2
(82A044) PTMv0315
The
Commander ™
Series
INSTALLATION INSTRUCTIONS
Privacy Timing Module
FIGURE 2—PTM Kit Wiring Diagram
!
NOTE:
1. All LEDs provided have
built-in resistors.
Auto
Door
Control
Activation
Circuit
Green
Green
12-24V AC/DC
INPUT1
INPUT1
LED DISPLAY KEY
d1 = delay output 1 to 2
d2 = output 2 on time
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
o2 = output 2 (n.o. / n.c.)
Output #2
Output #1
01= dry
01= wet
DISPLAY
ADJUSTMENT
N.C.
CO M
N.O.
PROGRAM
MODE BUTTON
2. Strike shown is wired
fail-safe. Door can be
opened if power fails.
3. Strike and power voltages
must match.
N.C.
CO M
N.O.
PTM
Wht/Blue
Blue
Wht/Brn
Wht/Gray
Wht/Vio
Wht/Grn
Wht/Red
PTM Wire Harness is Prewired to Terminal Block
INPUT4
CO M
INPUT3
INPUT2
CO M
PTM
Green
LED
Strike
8701 Castle Park Drive  Indianapolis, Indiana 46256
Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com
Vcc +
24V -
Red
LED
Page 3
(82A044) PTMv0315
The
Commander ™
Series
PTM
INSTALLATION INSTRUCTIONS
Privacy Timing Module
FIGURE 3—LOCK AND RUN DETERRANT DIAGRAM
NOTE: Additional Red LED’s are
connected in parallel with
the one shown.
Green
LED
Door
Activation
1
2
3
4
12-24V AC or DC
Inside
Unlock & Open
6
Unlock
Lock
7
Open
5
8
Vcc +
24V -
Strike
Outside
OU
PN
E L
NO
C
K
NC
NO
COM
L
O
C
K
Red Green
Key
9
Red
LED
O
P
E
N
Guard
Magnetic
Switch on Door
Bypass Switch