1 2 3 4 5 6 7 8 9 10 ELECTRICAL SYMBOL SCHEDULE SYMBOL DESCRIPTION SYMBOL GENERAL ELECTRICAL SYMBOLS A. A ALL MOUNTING HEIGHTS INDICATED ARE FROM THE FINISH FLOOR TO THE CENTER OF THE BOX. C. ITEMS SHOWN DOTTED ARE TO BE REMOVED, ITEMS SHOWN WITH A LIGHT SCREENED LINE ARE EXISTING TO REMAIN. D. MN MOUNTING HEIGHT DESCRIPTION SYMBOL LIGHTING DEVICES SHALL BE MOUNTD AT THE HEIGHT INDICATED, UNLESS NOTED OTHERWISE. DEVICES MOUNTED IN BLOCK/BRICK WALLS SHALL CORRESPOND WITH BLOCK/BRICK COURSING. SEE MASONRY BACKBOX MOUNTING HEIGHT DETAIL. B. DESCRIPTION MOUNTING HEIGHT SYMBOL SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE (TYPE DENOTED) MOTOR RATED SWITCH AND PILOT. 46" MS MOTOR RATED SWITCH. 46" MOTOR STARTER SWITCH WITH MOTOR RUNNING PROTECTION (ADD RELAY IF CONTROL CONTACTS ARE REQUIRED). DISCONNECT SWITCH - NON FUSED. 6'-0" LIGHT FIXTURE ON 24/7 (NIGHT LIGHT) DISCONNECT SWITCH - FUSED. 6'-0" RECESSED LIGHT FIXTURE (TYPE DENOTED) 'DEMOLITION' EXAMPLES: MOTOR STARTER. 6'-0" COMBINATION STARTER/DISCONNECT SWITCH. 6'-0" T THERMOSTAT - WALL MOUNTED. FLUORESCENT STRIP LIGHTING FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. PUSHBUTTON - SINGLE BUTTON, WALL MOUNTED. R WALL MOUNTED LIGHTING FIXTURE; SEE REFLECTED CEILING PLAN FOR MOUNTING HEIGHT. SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND SPECIFIED (FLUSH OR SURFACE AS INDICATED); VERIFY MOUNTING. DATA SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND SPECIFIED (FLOOR OR WALL AS INDICATED). LINEAR PENDANT LIGHTING FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. KEYED NOTE # FEEDER OR EQUIPMENT DRAWING NOTE. 30" - 36" PL PB 3 PULLBOX HH J SINGLE POLE LIGHT SWITCH WITH LIGHTED PILOT LIGHT 46" SINGLE POLE LIGHT SWITCH 46" #V J #D 46" OCCUPANCY SENSOR SWITCH 46" J # MCC MOTOR CONTROL CENTER (W/CONCRETE PAD); FLOOR MOUNTED. K KEYED LIGHT SWITCH (POLES AS INDICATED) 46" PLUG-IN BUS DUCT SWITCH; SIZE AS INDICATED AND SPECIFIED. VERIFY MOUNTING HEIGHT. MC MOMENTARY CONTACT LIGHT SWITCH 46" D DIMMER LIGHT SWITCH 46" TS TIME-SWITCH 46" D M METER/SOCKET ASSEMBLY; MOUNT TOP AT 6'-0". L PC L OS L OS BRANCH CIRCUIT, FEEDER, RACEWAY LL-1 2,4 MOTOR NUMBER; REFER TO MOTOR SCHEDULE S S V CONTACTOR (ENCLOSURE MOUNTED) (RATING, POLES AND MOUNTING AS INDICATED) PANELBOARD NAME M A V - FLOOR BOX, FULLY RECESSED IN FLOOR. REFER TO FLOOR PLAN DRAWING FOR NUMBER OF RECEPTACLES AND VOICE AND DATA CABLES/DEVICES. SYSTEMS WALL BOX: #D INDICATES NO. OF DATA CABLES; #V INDICATES NO. OF VOICE CABLES. FLEXIBLE CONDUIT WHIP, CABLES AND DEVICES PROVIDED IN ELECTRIFIED FURNITURE BY LOW-VOLTAGE CONTRACTOR. P PHOTOCELL - WALL, CEILING, OR ROOF MOUNTED; SEE DRAWINGS. 90" 84" OCCUPANCY DETECTOR - WALL OR CEILING CEILING MOUNT #D,#V BRANCH CIRCUITS (IN THE PANELBOARD) ARROW INDICATES HOMERUN CIRCUIT NUMBER, TYPICAL P 18" DUPLEX RECEPTACLE # RECEPTACLE (SINGLE) 18" E 18" DOUBLE DUPLEX RECEPTACLE (QUAD) INDICATES CONDUIT IS SURFACE MOUNTED INDICATES CONDUIT ROUTED CONCEALED ABOVE FLOOR OR GRADE (IN CEILING OR WALL) (1) HIGH MOUNTED DUPLEX RECEPTACLE AND (1) LOW MOUNTED DUPLEX RECEPTACLE H/L W 90" (1) HIGH MOUNTED DUPLEX RECEPTACLE H 90"/18" # INDICATES CONDUIT UP INDICATES CONDUIT DOWN DUPLEX RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER (GFI) GFI CONDUIT STUB - TERMINATION INDICATED BY NOTE POWER WALL BOX: # INDICATES NUMBER OF POWER CIRCUIT(S). POWER WHIP SUPPLIED BY FURNITURE VENDOR, INSTALLED BY ELECTRICAL CONTRACTOR. 1"C,3#4,1#3G F 18" RECESSED CEILING MOUNTED DUPLEX RECEPTACLE W/ ADDITIONAL 10' FLEX CONDUIT SLACK (COILED) WITH GROUND WIRE; FOR FUTURE DEVICE RELOCATION. J INDICATES 1" CONDUIT, (3) NO. 4 AWG CONDUCTORS AND (1) NO. 3 GROUND WIRE J Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt 1/8/2016 4:34:09 PM 90" F D F MAGNETIC DOOR HOLD-OPEN (WALL MOUNTED); MOUNT PER DWGS. FL F SPRINKLER FLOW-SWITCH; MOUNT PER DWGS. TS F SPRINKLER TAMPER-SWITCH; MOUNT PER DWGS. 18" F S SMOKE DETECTOR-CEILING MOUNTED. AUXILIARY INPUT CONNECTOR. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). 18" F H HEAT DETECTOR (RATE-OF-RISE) - CEILING MOUNTED. 136° F H HEAT DETECTOR (FIXED TEMPERATURE)- CEILING MOUNTED. H. F DUCT SMOKE DETECTOR; MOUNT PER DWGS. I. J. K. VOLUME CONTROL. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). 46" CALL BACK SWITCH. (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). 46" CM F 18" CS F CHLORINE GAS SENSOR; CEILING MOUNTED. N. O. P. GS F GAS SHUT-OFF; MOUNT PER DWGS. Q. F/S F FIRE/SMOKE DAMPER; MOUNT PER DWGS. TV H TV/VIDEO OUTLET MOUNTED HIGH. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). TV H/L (1) TV/VIDEO OUTLET MOUNTED HIGH AND (1) TV/VIDEO OUTLET MOUNTED LOW. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). SD 18" L. M. FIRE ALARM CONTROL MODULE; MOUNT PER DWGS. R. DATA OUTLET: (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE. DATA AND VOICE OUTLET: (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). #D,#V INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. #D REPRESENTS DATA; #V REPRESENTS VOICE. IF NO NUMBERS ARE INDICATED, PROVIDE ONE OF EACH. 18" PUBLIC VOICE OUTLET (TELEPHONE): (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS OTHERWISE NOTED. WALL VOICE OUTLET (TELEPHONE): (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS OTHERWISE NOTED. VOICE OUTLET: (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE. IC A JUNCTION BOX WITH REQUIRED COVERPLATE - WALL OR CEILING MOUNT - PLAN INDICATES MOUNTING AND FUNCTION 18" WIRELESS ACCESS POINT (DATA OUTLET): (1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE, UNLESS OTHERWISE NOTED. MOUNT HIGH ON WALL OR ON CEILING AS INDICATED ON DWG. 2500 East 80th Street Inver Grove Heights, MN 55076 Minnesota State Colleges & Universities 30 E 7th St #350, St Paul, MN 55101 ONE LINE SYMBOLS 20A CIRCUIT CONDUCTORS SHALL BE SIZED AS FOLLOWS 90"/18" DISTRIBUTION PANEL C CLOCK OUTLET. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). 90" B BELL/AUDIBLE DEVICE. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). 90" 120V CCT LENGTH 277V CCT LENGTH AWG < 75' < 75' 12 75' - 120' 75' - 280' 10 120' - 200' 280' - 450' 8 > 200' > 450' 6 PANEL 18" UPS OR INVERTER UPS SECURITY DEVICES ## S SECURITY DEVICE. ## INDICATES THE FOLLOWING: CM DC EL ES GB IR ML XP XS 48" 48" STANDARD BACKBOX MOUNTING HEIGHTS CONTROL MODULE DOOR CONTACTS (MONITORING) ELECTRIC LOCK ELECTRIC STRIKE GLASS BREAK DETECTOR INFARED DETECTOR MAGNETIC LOCK EXIT PUSHBUTTON, MOUNT AT ADA HT EXIT SENSOR CR S CARD READER ROUGH-IN AT ADA HEIGHT DR S DOOR RELEASE; MOUNT PER DWGS. N E TRANSFER SWITCH L 100" DRAW-OUT CIRCUIT BREAKER 46" 18" TRANSFORMER 46" 92" ELECTRIC EYE; MOUNT PER DWGS. CIRCUIT BREAKER 86" 3 18" KP S KEYPAD; VERIFY MOUNTING HEIGHT WITH DWGS. LA S LOCAL ALARM 46" MC S MASTER CONTROL STATION 46" MD S MD S GENERATOR GEN ELECTRICAL ABBREVIATIONS LIST 80" 72" 60" 62" 64" 52" 54" 2 46" 5 36" 12" 4 18" 46" 2 44" 56" 2 7 46" 48" 38" 40" 30" 32" 22" 14" 1 6" 6 20" 18" 1 1 24" 36" 29" 16" FINISHED FLOOR 8" GENERAL NOTES: A. SWITCH NUMBER NOTES: MOTION DETECTOR; ARROW INDICATES DIRECTION. (WALL OR CEILING MOUNTED). 1. 2. FUSE SECURITY CAMERA, CLOSED CIRCUIT. (WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). S 3 88" 70" FUSED SWITCH PHOTO-ELECTRIC TRANSMITTER; MOUNT PER DWGS. S 3 68" 4" PHOTO-ELECTRIC RECEIVER; MOUNT PER DWGS. T P 88" 78" 20" 46" 90" 76" 28" 18" 96" 94" 90" 84" 44" EE S VOICE OUTLET, INTERCOM ONLY: (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS OTHERWISE NOTED. INSTALL CONCEALED CONDUIT WITH FLUSH J.B.'S IN WALLS AND CEILINGS UNLESS NOTED OTHERWISE. IN FINISHED AREAS WITH INACCESSIBLE WALLS OR CEILINGS, PROVIDE SURFACE (WIREMOLD) RACEWAY; PAINT TO MATCH COLOR OF ADJACENT WALL OR CEILING. RACEWAYS SHALL CONTAIN A GROUNDING CONDUCTOR. CIRCUITS SUPPLYING LINE TO NEUTRAL LOADS SHALL HAVE DEDICATED NEUTRALS, i.e. ONE NEUTRAL PER PHASE. NEUTRAL CONDUCTORS SHALL HAVE TRACER STRIPE ALONG ENTIRE LENGTH INDICATING ASSOCIATED PHASE. BUILDING CONDUCTORS SHALL BE THWN/THHN. CONDUCTORS IN UNDERGROUND CONDUIT OUTSIDE OF BUILDINGS SHALL BE XHHW. NUMBERS AT RECEPTACLES AND LUMINAIRES CORRESPOND DIRECTLY WITH PANELBOARD CIRCUIT NUMBERS AS SCHEDULED. BRANCH CIRCUIT WIRING AND HOMERUNS ARE NOT SHOWN FOR CLARITY. ACCURATE RECORD DRAWING INFORMATION IS TO BE PROVIDED AT THE PROJECT COMPLETION. TYPICAL THROUGHOUT. REFER TO SPECIFICATIONS FOR MATERIALS AND INSTALLATION REQUIREMENTS. REFER TO CONTRACT DOCUMENTS FOR SEQUENCE OF CONSTRUCTION AND PHASING OF THE CONTRACT. SWITCHES SHALL BE MOUNTED PER ADA REQUIREMENTS, 40" AFF. UNLESS OTHERWISE NOTED, RECEPTACLES AND TELECOMMUNICATION OUTLETS IN FINISHED AREAS SHALL BE MOUNTED 18" AFF. RECEPTACLES IN UN-FINISHED SPACES SHALL BE MOUNTED AT 48" OR 4" ABOVE WORK SURFACE. COORDINATE RECEPTACLE MOUNTING HEIGHTS WITH MILLWORK LOCATIONS, ARCHITECTURAL ELEVATIONS, AND MASONRY COURSING. CRITICAL DEVICES / EQUIPMENT, INCLUDING TELEPHONE, COMPUTER, SECURITY, AND FIRE ALARM, AFFECT ASSOCIATED SYSTEMS BUILDING-WIDE. THESE SYSTEMS MUST REMAIN OPERATIONAL DURING THE CONSTRUCTION. INDIVIDUAL DEVICES MAY BE DISCONNECTED AND/OR RECONNECTED DURING CONSTRUCTION. COORDINATE POWER OUTAGES WITH OWNER. PROVIDE TEMPORARY PANEL(S) AND/OR CIRCUIT(S) AS/IF NECESSARY TO MAINTAIN CONTINUITY. PROTECT FROM PHYSICAL AND DUST DAMAGE. THE BUILDING SHALL MAINTAIN POWER THROUGHOUT THE CONSTRUCTION PROCESS. COORDINATE ENERGIZATION OF NEW EQUIPMENT AND THE CORRESPONDING RECONNECTION OF EXISTING AFFECTED ELECTRICAL DISTRIBUTION EQUIPMENT. SEE RELATED PLUMBING AND HVAC DRAWINGS FOR LOCATION OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. COORDINATE INTERCONNECTION REQUIREMENTS WITH EQUIPMENT SHOP DRAWINGS. WIRING FOR MISCELLANEOUS HVAC DEVICES AND CONTROLLERS SUCH AS DAMPER MOTORS, THERMOSTATS, DUCT SMOKE DETECTORS, FREEZESTATS, DIFFERENTIAL PRESSURE SWITCHES, OCCUPIED AND UNOCCUPIED SELECTOR SWITCHES, ALARM LIGHTS, ETC., NOT SHOWN ON ELECTRICAL DRAWINGS IS DIVISION 23 WORK. FIELD VERIFY EXISTING CONDITIONS. DISCREPANCIES BETWEEN THE DRAWING AND ACTUAL FIELD CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BIDS. MAINTAIN EXISTING CIRCUIT CONTINUITY ON ALL SYSTEMS ON THE SITE THAT ARE EXISTING TO REMAIN. PROVIDE ALL CONDUIT HOMERUNS AS 3/4"C. MIN. COORDINATE ALL WORK WITH OTHER CONTRACTORS AND OWNER. ALL CUTTING AND PATCHING FOR DIV. 26 WORK SHALL BE UNDER SUPERVISION AND APPROVAL OF ARCHITECT. REMOVE AND/OR REINSTALL ELECTRICAL DEVICES IN ALL AREAS OF WORK AS REQUIRED AND REPLACE ANY ELECTRICAL DEVICES DAMAGED BY WORK. NOT ALL DEVICES MAY BE SHOWN ON DRAWINGS. PROVIDE ALL BOXES, FITTINGS, CONDUIT, WIRING, TERMINATIONS, EQUIPMENT, ETC, FOR A COMPLETE INSTALLATION. IHCC ACTIVITIES BUILDING PHASE ll EXERCISE ROOM ADDITION 90" TV/VIDEO CAMERA, CLOSED CIRCUIT. (WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). TV TV SURFACE RACEWAY ASSEMBLY. REFER TO ARCHITECTURAL AND ELECTRICAL PLANS FOR MOUNTING HEIGHT. PROVIDE AS SPECIFIED, UNLESS NOTED OTHERWISE. C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt FIRE ALARM BELL (WP FOR EXTERIOR MOUNTING). MICROPHONE OUTLET ( WALL OR CEILLING). (1/2"C. BUSHED EMT TO ACCESSIBLE CEILING). TV L R P 3. 4. 5. 6. 7. MOUNTING HEIGHT OF STANDARD BACKBOXES ONLY. REFER TO DRAWINGS AND DETAILS FOR MOUNTING HEIGHT OF OTHER BACKBOXES. MOUNTING HEIGHT FOR BACKBOXES MOUNT LOW IN WALL. MOUNTING HEIGHT FOR BACKBOXES MOUNTED NEAR MIDDLE OF WALL, INCLUDING DEVICES SUCH AS TOGGLE SWITCHES. MOUNTING HEIGHT FOR BACKBOXES MOUNTED HIGH IN WALL. STANDARD COUNTER TOP. STANDARD COUNTER TOP BACK SPLASH HEIGHT. STANDARD DESK TOP. STANDARD DESK TOP BACK SPLASH HEIGHT. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed PROFESSIONAL ENGINEER MINNESOTA under the laws of the State of BRADLEY R. JOHANNSEN Date 12/04/15 43936 Registration Number ELECTRICAL SYMBOL NOTES Revisions 1P A AC G ACLG ADO AFF AFG AFI AHU AL ALT AMP AMPL ANNUN APPROX AQ-STAT ARCH ATS AUTO AUX AV AWG BATT BD BLDG BMS E F. 18" 18" SPECIAL PURPOSE OUTLET; WALL OR RECESSED CEILING MOUNTED CABLE TRAY 90" 90" TV/VIDEO OUTLET MOUNTED LOW. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING) POWER AND MOTOR DEVICES INDICATES CONDUIT ROUTED BELOW OR IN FLOOR STRUCTURE OR BELOW GRADE OR AS NOTED. FIRE ALARM HORN/STROBE (COMBINATION) - 75Cd, U.N.O. (WALL OR CEILING MOUNTED). SPEAKER WITH BACKBOX (WALL OR CEILING); VERIFY MOUNTING HEIGHT. PA = SPEAKER FOR P.A. SYSTEM; V = WITH INTEGRAL VOLUME CONTROL KNOB. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). PROJECTOR OUTLET (WALL OR CEILING). P 18" VOICE AND DATA DEVICES # L PC 90" 46" FOUR-WAY LIGHT SWITCH OS HANDHOLE 90" FIREMAN PHONE JACK; MOUNT TOP 54" AFF PLUS OR MINUS 2". LOUD SPEAKER HORN ASSEMBLY- PA OR SOUND SYSTEM AS INDICATED; VERIFY MOUNTING HEIGHT. (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). S POKE-THROUGH, FULLY RECESSED IN FLOOR. REFER TO FLOOR PLAN DRAWING FOR NUMBER OF RECEPTACLES AND VOICE AND DATA CABLES/DEVIVES. THREE-WAY LIGHT SWITCH 4 F H LIGHTING CONTROL TRANSFORMER, WITH SIZE AS NOTED. SEE RISER DIAGRAM, SCHEDULE OR FLOOR PLANS; VERIFY. T POWER POLE (DEVICES AS INDICATED) POKE-THRU'S, FLOOR BOXES, & FURNITURE CONNECTIONS POLE MOUNTED SITE LIGHTING FIXTURE - SINGLE SQUARE HEAD. # OF HEADS AS SHOWN. AUTOMATIC TRANSFER SWITCH; WALL OR FLOOR MOUNTED. ATS C EMERGENCY LIGHTING UNIT - TWO HEAD MOUNTING AS INDICATED ON DRAWINGS. PANELBOARD; WALL MOUNTED WITH TOP 6'-0". F F PAGING/INTERCOM SPEAKER HORN ASSEMBLY- P.A. OR AS INDICATED (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING). MOUNT 12" BELOW CEILING OR AS INDICATED. S MOTOR NAME; REFER TO MOTOR SCHEDULE (AHU-#) EXIT LIGHT-FACE SHOWN SHADED; PLAN INDICATES CEILING OR WALL MOUNTING AND DIRECTIONAL ARROWS. RELAY/CONNECTION CABINET; WALL MOUNTED, WITH TOP 6'-0". E. 60" OR 62" M SWITCHBOARD WITH CONCRETE PAD: FLOOR MOUNTED. C AHU CIRCULAR PENDANT LIGHT FIXTURE; FOR SUSPENDED MOUNTING HEIGHTS, SEE DRAWINGS. POWER DISTRIBUTION AND EQUIPMENT FIRE ALARM STROBE (VISUAL) DEVICE - 75 Cd, U.N.O. (WALL OR CEILING MOUNTED). F MOTOR: # TRACK LIGHTING FIXTURE; LENGTH AND MOUNTING AS NOTED ON DRAWINGS. # F RELAY - VERIFY MOUNTING HEIGHT; SEE DRAWINGS. PP ON NEW WORK LIGHTING, POWER AND SYSTEMS DRAWINGS, SCREENED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO REMAIN; SOLID ELECTRICAL ITEMS DENOTES NEW ITEMS, UNLESS NOTED OTHERWISE FIRE ALARM HORN (AUDIBLE), WALL MOUNTED. F TV D. FIRE ALARM MANUAL PULL STATION; MOUNT TOP 46" AFF PLUS OR MINUS 2". F TELEPHONE TERMINAL CABINET; VERIFY MOUNTING. 'EXISTING TO REMAIN' EXAMPLES: E. B. C. G. F F A. FIRE ALARM CONTROL PANEL (MASTER); MOUNT TOP 62" AFF PLUS OR MINUS 2". EQUIPMENT RACK: ABBREVIATION FOR SYSTEM SERVED AND SPECIFIED; VERIFY MOUNTING. EQ SURFACE MOUNTED LIGHT FIXTURE (TYPE DENOTED) B MOUNTING HEIGHT FIRE ALARM DEVICES LOCAL DISTRIBUTED SOUND SYSTEM WALL OR FLOOR AMPLIFIER ASSEMBLY; VERIFY MOUNTING. AMP 46" LIGHT FIXTURE ON EMERGENCY CIRCUIT DESCRIPTION FIRE ALARM ANNUNCIATOR PANEL; MOUNT TOP AT 54" AFF. TEL ON DEMOLITION DRAWINGS, DASHED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO BE REMOVED; SOLID SCREENED ELECTRICAL ITEMS DENOTES EXISTING ITEMS TO REMAIN, UNLESS NOTED OTHERWISE SYMBOL COMMUNICATION DEVICES MS&P MSS MOUNTING HEIGHT DESCRIPTION POWER AND MOTOR DEVICES RECESSED FLUORESCENT LIGHT FIXTURE (TYPE DENOTED) GENERAL ELECTRICAL NOTES H C CAB CATV CB CCTV CKT CLG COMB 1 POLE (2P, 3P, 4P, ETC.) AMPERE ABOVE COUNTER OR AIR CONDITIONER ABOVE CEILING AUTOMATIC DOOR OPENER ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ARC FAULT CIRCUIT INTERRUPTER AIR HANDLING UNIT ALUMINUM ALTERNATE AMPERE AMPLIFIER ANNUNCIATOR APPROXIMATELY AQUASTAT ARCHITECT, ARCHITECTURAL AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AUDIO VISUAL AMERICAN WIRE GAUGE BATTERY BOARD BUILDING BUILDING MANAGEMENT SYSTEM CONDUIT CABINET CABLE TELEVISION CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CEILING COMBINATION CMPR CONN CONST CONT CONTR CONV CP CRT CT CTR CU DCP COMPRESSOR CONNECTION CONSTRUCTION CONTINUATION OR CONTINUOUS CONTRACTOR CONVECTOR CIRCULATING PUMP CATHODE-RAY TUBE CURRENT TRANSFORMER CENTER COPPER DEPT EX HTR HV HWP DOMESTIC WATER CIRCULATING PUMP DEPARTMENT EXISTING TO REMAIN HEATER HIGH VOLTAGE HYDRONIC WATER PUMP IC IG IMC INCAND IR I/W INTERRUPTING CAPACITY ISOLATED GROUND INTERMEDIATE METAL CONDUIT INCANDESCENT INFRARED INTERLOCK WITH J-BOX JUNCTION BOX KV KVA KVAR KW KWH KILOVOLT KILOVOLT-AMPERE KILOVOLT-AMPERE REACTIVE KILOWATT KILOWATT HOUR LOC LT LTG LTNG LV LOCATE OR LOCATION LIGHT LIGHTING LIGHTNING LOW VOLTAGE MAX MAG.S M/C MC MCB MCC MDC MDP MFR MFS MAXIMUM MAGNETIC STARTER MOMENTARY CONTACT MECHANICAL CONTRACTOR MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION CENTER MAIN DISTRIBUTION PANEL MANUFACTURER MAIN FUSED DISCONNECT SWITCH MANHOLE MICROPHONE MINIMUM MISCELLANEOUS MAIN LUGS ONLY MANUAL MOTOR STARTER MULTIOUTLET ASSEMBLY MOTOR STARTER PANELBOARD MAIN SWITCHBOARD MOUNT EMPTY CONDUIT MANUAL TRANSFER SWITCH MOTOR, MOTORIZED PA PB PE PED PF PH PNL PP PR PRI PROJ PRV PT PVC NIC NL N.O. NPF NTS NORMALLY CLOSED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION NON-FUSED SAFETY DISCONNECT SWITCH NOT IN CONTRACT NEW LOCATION NORMALLY OPEN NORMAL POWER FACTOR NOT TO SCALE OH OL OVERHEAD OVERLOADS MH MIC MIN MISC MLO MMS MOA MSP MSBD MT MT.C MTS MTR N.C. NEC NEMA NFDS PWR PUBLIC ADDRESS PULL BOX OR PUSHBUTTON PNEUMATIC ELECTRIC PEDESTAL POWER FACTOR PHASE PANEL POWER POLE PAIR PRIMARY PROJECTION POWER ROOF VENTILATOR POTENTIAL TRANSFORMER POLYVINYL CHLORIDE (CONDUIT) POWER QUAN QUANTITY RCPT REQD RL RSC RTU RECEPTACLE REQUIRED RELOCATED RIGID STEEL CONDUIT ROOF TOP UNIT SC SEC SHT SIM S/N SPEC SPKR SP SR SS SSW S/S STA STD SURF SURFACE CONDUIT SECONDARY SHEET SIMILAR SOLID NEUTRAL SPECIFICATION SPEAKER SPARE SURFACE RACEWAY STAINLESS STEEL SELECTOR SWITCH STOP/START PUSHBUTTONS STATION STANDARD SURFACE MOUNTED SW SWBD SYM SYS TEL TERM TL TR T-STAT TTC TV TVTC TYP UE UG UH UT UV SWITCH SWITCHBOARD SYMMETRICAL SYSTEM TELEPHONE TERMINAL TWIST LOCK TAMPER RESISTANT THERMOSTAT TELEPHONE TERMINAL CABINET TELEVISION TELEVISION TERMINAL CABINET TYPICAL @ ' " # Ø C P ANGLE AT FEET INCHES NUMBER PHASE CENTER LINE PLATE A2 EXAMPLE 1: LIGHTING FIXTURE TYPE "A" IS CONNECTED TO CIRCUIT 12 AND CONTROLLED BY SWITCH "b". 12b * P2D/I * 2aba UNDERGROUND ELECTRICAL UNDERGROUND UNIT HEATER UNDERGROUND TELEPHONE UNIT VENTILATOR OR ULTRAVIOLET E 14 16c V VA VDT VERT VFD VOL VOLT VOLT-AMPERES VIDEO DISPLAY TERMINAL VERTICAL VARIABLE FREQUENCY DRIVE VOLUME W W/ WG WH W/O WP WATT WITH WIRE GUARD WATER HEATER WITHOUT WEATHERPROOF XFMR XFR TRANSFORMER TRANSFER 7,9 THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER. d D600 EXAMPLE 2: THE FIXTURE TYPE SHOWN AS A NUMERATOR INDICATES ALL LIGHTING FIXTURES IN THE ROOM OR SPACE ARE THE SAME TYPE. THE CIRCUIT NUMBER AND SWITCH DESIGNATION SHOWN AS A DENOMINATOR INDICATES ALL LIGHTING FIXTURES IN THE ROOM OR SPACE ARE CONNECTED TO THE SAME CIRCUIT, CONTROLLED BY THE SAME SWITCHES, CENTER/OUTBOARD MULTILEVEL SWITCHING. DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS CONTROLLED BY SWITCH "c". THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d". WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600 WATT WALL BOX DIMMER TO CONTROL LIGHTING FIXTURES INDICATED BY "e". SEE SPECIFICATIONS FOR WATTAGE IF NOT INDICATED. 1,3,5 SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OF CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5. SF-1 2,4,6 LPN-102 EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E" WITH SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 14. e 1 T1 MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR CHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE MOTOR DESCRIPTION AND ELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: MOTOR SF-1; 3 PHASE CONNECTION TO CIRCUITS 2, 4, 6. 1 #10 H1 ELECTRIC HEATER CONNECTIONS. THE HEATER TYPE IS INDICATED BY A NUMBER FOLLOWING THE UPPER CASE LETTER "H". SEE THE HEATER SCHEDULE FOR ELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE HEATER. EXAMPLE: ELECTRIC BASEBOARD HEATER TYPE "H1" CONNECTED TO CIRCUITS 7, 9. TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1". PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION CODES. Date ELECTRICAL DRAWINGS E0.00 E0.01 E1.00 E2.00 ELECTRICAL SYMBOLS AND ABBREVIATIONS ELECTRIC KEYPLAN ELECTRIC PLAN ELECTRICAL SCHEDULES Comm: 152039 Date: 1/11/16 Drawn: A. WELLENS Check: S. CHHUM SPECIAL NOTE. SEE THE SPECIAL NOTES ON THAT SHEET FOR THE NOTE NUMBER INDICATED IN THE HEXAGON. CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4" CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE. CONDUIT SHOWN WITH SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR PER SLASH MARK IN 3/4" CONDUIT UNLESS A CONDUCTOR AND CONDUIT SIZE IS SHOWN ADJACENT TO THE SLASH MARKS. SLASH MARK INDICATORS ARE: SHORT STRAIGHT=PHASE CONDUCTOR, LONG STRAIGHT=NEUTRAL CONDUCTOR, SHORT BENT ENDED=SWITCH LEGS, LONG STRAIGHT WITH A DOT=GROUND CONDUCTOR, CHEVRON=CATEGORY 6, HALF CHEVRON=CATEGORY 3, TWIST=SHIELDED TWISTED PAIR, CONCENTRIC CIRCLE AND DOT=COAX CABLE. LPN-102 1,3,5 Description ELECTRICAL SYMBOLS AND ABBREVIATIONS HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO PANELBOARD LPN-102; CIRCUITS 1, 3, 5. SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS. Scale: As indicated E0.00 Num 1 2 3 4 5 6 7 8 9 10 GENERAL SHEET NOTES A. VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH-IN. B. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT OF FIXTURES AND CONTROL OF DEVICES. C. ALL WALLS AND FLOOR MOUNTED BACK BOXES AND JUNCTION BOXES SHALL BE MOUNTED RECESSED. D. GFCI RECEPTACLES SHALL BE WIRED TO PROTECT ONLY THE DEVICES IN THAT OUTLET BOX. DOWNSTREAM DEVICES SHALL NOT BE PROTECTED BY GFCI. E. CIRCUIT NUMBERS SHOWN ARE FOR SCHEMATIC PURPOSES AND ARE FOR DISTINGUISHING CIRCUITS. RECORD AS-BUILT CIRCUITING IN A TYPED AND DATED PANELBOARD SCHEDULE. ROUTE CIRCUTING TO SPARE 20A, 120V BREAKERS IN EITHER PANEL L1A OR L1B. F. PROVIDE CONSTRUCTION LIGHTING AND POWER AS REQUIRED FOR TEMPORARY ENCLOSURE. REFER TO DETAIL H7 ON SHEET A0.01 AND SECTION 1.11 OF SPECIFICATION 26 00 05 FOR MORE INFORMATION. G. WHEN CORE-DRILLING OF EXISTING FLOORS IS REQUIRED, PERFORM XRAY SCAN AND COORDINATE EXACT LOCATION OF HOLES WITH OWNER PRIOR TO START OF WORK. H. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT PRIOR TO START OF WORK. A E E D CB A D CB A 1 1 2 2 MN IH G F G F 1. 3 EX MSB 2 EX FACP 3 2. 3. L1B L1A 6 4 4. 8 3 EX DATA RACK 7 PA2B 4 5 LA2A LA2B EX GYM CONTROL BOX G 1 5. 4 B EX CARD READER HEAD END B C C D 6. 7. DF-5 6 DF-3 6 1 1 8. 5 2 3 9 5 2 3 C D MECHANICAL ROOM 2500 East 80th Street Inver Grove Heights, MN 55076 Minnesota State Colleges & Universities 30 E 7th St #350, St Paul, MN 55101 KEYED SHEET NOTES B IH IHCC ACTIVITIES BUILDING PHASE ll EXERCISE ROOM ADDITION 9. EXISTING 120/208V, 225A SQUARE D NQ PANELS. CIRCUITING ON THIS SHEET AND SHEET E1.00 REFER TO SPARE BREAKERS IN PANEL LA2B UNLESS NOTED OTHERWISE. CORE DRILL FLOOR AS REQUIRED TO FEED NEW LOADS ON LOWER LEVEL. EXISTING HONEYWELL NOTIFIER FIRE ALARM CONTROL PANEL. EXISTING DATA RACK AND FUTURE PA SYSTEM HEADEND. ROUTE ALL CAT6 CABLING AND PA SPEAKER WIRING BACK TO THIS LOCATION. INSTALL GYMNASIUM DESTRATIFICATION FAN SPEED SWITCH WITHIN EXISTING GYMNASIUM CONTROL PANEL. SPEED SWITCH FURNISHED BY MECHANICAL. UTILIZE EXISTING LIVE VOLTAGE CONDUIT FOR NEW WIRING. EXISTING 120/208V, 225A SQUARE D NQ PANEL. PROVIDE 60A/3P AND 30A/30 BREAKER FOR NEW AIR HANDLER UNIT (AHU-5). CORE DRILL FLOOR AS REQUIRED. PROPOSED ROUTING FOR LOW VOLTAGE CABLING FROM ADDITION TO DATA ROOM. PROVIDE FLOOR PROTECTION AND REPLACE CEILING TILES WITH NEW TO REPLACE DAMAGED TILES AS REQUIRED. PROPOSED ROUTING FOR POWER FROM ADDITION TO PANELS ABOVE. PROVIDE FLOOR PROTECTION AND REPLACE CEILING TILES WITH NEW TO REPLACE DAMAGED TILES AS REQUIRED. SURFACE MOUNT FIXTURE TO UNDERSIDE OF STAIRS. PAINT CONDUIT AND BOX TO MATCH ADJACENT SURFACES. FIXTURE TO BE ON 24/7. CONNECT TO NEAREST LIGHTING CIRCUIT AHEAD OF SWITCHING. PROVIDE PROTECTION OF GYM FLOORING TO ACOMMODATE ELECTRICAL WORK. COORDINATE WITH OTHER TRADES. 4 4 REFER TO SHEET E1.00 FOR ADDITION DF-4 8 D 5 6 DF-6 8 5 6 6 6 E6 A LOWER LEVEL KEYPLAN A 1/16" = 1'-0" E E2 UPPER LEVEL KEYPLAN 1/16" = 1'-0" Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt 1/8/2016 4:34:12 PM C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt F I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed PROFESSIONAL ENGINEER MINNESOTA under the laws of the State of BRADLEY R. JOHANNSEN Date 12/04/15 43936 Registration Number Revisions Description Date Num 1 G Comm: 152039 Date: 1/11/16 Drawn: A. WELLENS Check: S. CHHUM North ELECTRIC KEYPLAN E H Scale: As indicated E0.01 C 1 2 C A 3 B B 4 5 C C A 6 B B B 7 C A A 8 9 B D 10 C IHCC ACTIVITIES BUILDING PHASE ll EXERCISE ROOM ADDITION D 2500 East 80th Street Inver Grove Heights, MN 55076 D F 11 11 1 6 2 D 3 D 4 6 L OS 3 B 7 D 4 4 CORRIDOR A127 B 4 6 4 7 F D L OS MECH A130B L OS 5 F 4 12 F F 4 Da Db Dc 3 2 L OS 4 5 A 2 a a 4 L OS 5 A a CORRIDOR A127 D F 4 10 S TYP A A A b F 48" 15 13 36"AFF 48" 25 MECH A130B 15 15 6 TYP 17 EM1 EM1 SD S 2 EXERCISE ROOM A130 1 4 5 1 S 5 F abc 11 B SD CP-1 A S PA 3 abc 15 2 E3 A STORAGE A130A J 2 4 4 4 2 WEIGHT ROOM A125 13 14 4 30 E 7th St #350, St Paul, MN 55101 AHU-3 AHU-3 (SUPPLY) (RETURN) 2 A 2 b b 15 7 9'-0"AFF TYP DF-1 PA DF-2 19 19 8 TYP 2 17 9'-0"AFF S 5 4 STORAGE A130A F 3 B 4 1 2 F S S S PT ES DC MN 4 WEIGHT ROOM A125 F S 5 F F D WEIGHT ROOM A125 D F 48" 1 CR S 1 Minnesota State Colleges & Universities 4 J EXERCISE ROOM A130 F D F 11 6 L OS 7 C 9'-0"AFF abc L OS 5 D 4 7 D HA 5 S L OS D 4 A c 2 A 2 c c 9 2 23 EM1 5 S ES D1 A. E Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt 1/8/2016 4:34:13 PM C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt F SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONSTRUCTION. B. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHTING FIXTURES IN DEMOLITION AREAS UNLESS NOTED OTHERWISE. C. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES IN WALLS TO BE DEMOLISHED. WALLS TO BE DEMOLISHED ARE SHOWN DASHED. DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN. COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA. D. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED. E. FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/ DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY WIRING ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED. F. DISCONNECT AND REMOVE LIGHT SWITCHES IN DEMOLITION AREAS AS NECESSARY TO ACCOMMODATE NEW DOOR CONFIGURATIONS. G DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES AND BACK BOXES AS NECESSARY WHERE NEW WALL CONSTRUCTION WILL INTERSECT AN EXISTING WALL. FURNISH AND INSTALL CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY OF CIRCUIT(S). H. FURNISH AND INSTALL BLANK COVER PLATES OVER ALL EXISTING UNUSED OPENINGS. I. COORDINATE ALL OUTAGES (POWER, TELEPHONE, FIRE ALARM, ETC) WITH OWNER AT LEAST THREE WEEKS IN ADVANCE. 2. 3. 4. 5. EXISTING 13.8 KV MEDIUM VOLTAGE BOX TO REMAIN. DEMOLISH EXISTING FEEDER AND PROVIDE NEW FEEDER TO CHILLER BUILDING TRANSFORMER TO ACCOMODATE BUILDING ADDITION. PROVIDE (1) 3.5" CONDUIT WITH (3) 1/C#2, COPPER 15KV MV-105 CABLE WITH EPR 133% INSULATION, TAPE SHIELD AND 1#2 GROUND CABLE AND (1) SPARE 3.5" CONDUIT. FIELD VERIFY EXACT ROUTING AND DEPTH. BURY MINIMUM OF 36" BELOW FINISHED GRADE. PROVIDE DETECTABLE 6" WIDE ORANGE WARNING TAPE 12" BELOW GRADE. APPROXIMATELY 160' RUN TO TRANSFORMER LOCATED BEHIND CHILLER BUILDING, FIELD VERIFY EXACT LENGTH. DEMOLISH EXISTING 1" TELEPHONE AND 1" FIRE ALARM CIRCUITS FROM ACTIVITIES BUILDING TO CHILLER BUILDING TO ACCOMODATE BUILDING ADDITION. PROVIDE 1" CONDUIT WITH CABLING TO MATCH EXISTING FOR BOTH. BURY MINIMUM OF 36" BELOW FINISHED GRADE. PROVIDE DETECTABLE 6" WIDE ORANGE WARNING TAPE 12" BELOW GRADE. APPROXIMATELY 160' RUN TO CHILLER BUILDING, FIELD VERIFY EXACT LENGTH. DEMOLISH EXISTING EXTERIOR LIGHT FIXTURE. EXTEND EXISTING CIRCUIT AND SWITCHING AS REQUIRED FOR NEW EXTERIOR DOWNLIGHTS. BASE BID: INTERCEPT AND REROUTE TELEPHONE AND FIRE ALARM CONDUIT ON SOUTHERN WALL AS REQUIRED TO ACCOMMODATE NEW DOOR INSTALLATION. PROVIDE NEW WIRING SPLICED FROM NEAREST UPSTREAM DEVICE. DEDUCT ALTERNATE #3: NO DOOR TO BE INSTALLED. EXISTING TELEPHONE AND FIRE ALARM CONDUIT TO REMAIN AS IS. DEMOLISH CONNECTION TO MOTORIZED HANDICAP DOOR MOTOR AND ASSOCIATED PUSH PADDLES. S S 5 F 12'-0"AFF WP 3 S S PT DC S ES 6 HA S CR A LIGHTING PLAN D7 1/8" = 1'-0" GENERAL SHEET NOTES KEYED SHEET NOTES 1. 12'-0"AFF 6 D4 GENERAL SHEET NOTES 9'-0"AFF S 23 S S PT DC A 1/8" = 1'-0" 17 9 6 A DEMOLITION PLAN 17 HA 6 D1 S 21 4 5 6 9'-0"AFF CUH-1 2 D 44'' AFF 15 VESTIBULE HA A128 4 6 D1 15 9'-0"AFF 17 A J VESTIBULE A128 6 L OS 5 4 E1 D abc S 4 S 17 B A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THIS DRAWING. B. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE FIXTURES UNLESS INDICATED OTHERWISE. C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR LIGHTING FIXTURES. D. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS INDICATED ON PLAN BY DASHED CONDUIT. E. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT OF FIXTURES AND CONTROL OF DEVICES. F. EXTEND EXISTING EXIT SIGN CIRCUIT TO NEW EXIT SIGNS. G. ALL CIRCUITING SHOWN REFERS TO PANEL LA2B, SHOWN ON SHEET E0.01. H. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT PRIOR TO START OF WORK. POWER AND SYSTEMS PLAN 1/8" = 1'-0" KEYED SHEET NOTES 1. 2. 3. 4. 5. 6. 7. HIGH BAY LIGHT FIXTURES IN PERFORMANCE STUDIO TO BE HUNG BY AIRCRAFT CABLE FROM UNISTRUT BETWEEN JOISTS. DO NOT SUPPORT FIXTURE FROM ROOF DECK. LIGHTS TO BE FLUSH WITH BOTTOM OF JOIST AND FOLLOW SLOPED CIELING, RANGING FROM APPROXIMATELY 14'-0" AFF TO 23'-0" AFF. EXTERIOR RECESSED DOWNLIGHTS TO BE MOUNTED IN SOFFIT. CONNECT TO EXISTING EXTERIOR CIRCUITING AND CONTROLS. PROVIDE 0-10V DIMMER SWITCHES WITH ASSOCIATED ROOM CONTROLLERS (WATTSTOPPER DLM SYSTEM OR APPROVED EQUAL). INTERFACE WITH OCCUPANCY SENSORS. PROVIDE EMERGENCY INVERTER MOUNTED ON WALL TIGHT TO CEILING FOR EXTERIOR EMERGENCY DOWNLIGHT. INVERTER TO BE 100W MINIMUM, SELF DIAGNOSTICS, FUSED OUTPUT, BROWN-OUT SENSING, LEAD CALCIUM BATTERY, MOMENTARY TEST SWITCH (BODINE ELI-100 SERIES OR APPROVED EQUAL). PROVIDE HIGH BAY TYPE OCCUPANCY SENSOR (SENSOR SWITCH CM6 OR APPROVED EQUAL). SENSOR TO BE PIR, MANUAL ON/AUTO OFF, WITH 30 MINUTE TIME DELAY. MOUNT TO BOTTOM OF BAR JOISTS. PROVIDE OCCUPANCY SENSOR (WATTSTOPPER DT-305 OR APPROVED EQUAL). SENSOR TO BE DUAL TECHNOLOGY, AUTO ON/AUTO OFF, WITH 30 MINUTE TIME DELAY. INTERCONNECT SENSORS TOGETHER FOR CONTROL OF CORRIDOR AND EXERCISE ROOM ENTRY WAY. GENERAL SHEET NOTES A. VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH-IN. B. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT OF FIXTURES AND CONTROL OF DEVICES. C. ALL WALLS AND FLOOR MOUNTED BACK BOXES AND JUNCTION BOXES SHALL BE MOUNTED RECESSED. D. GFCI RECEPTACLES SHALL BE WIRED TO PROTECT ONLY THE DEVICES IN THAT OUTLET BOX. DOWNSTREAM DEVICES SHALL NOT BE PROTECTED BY GFCI. E. CIRCUIT NUMBERS SHOWN ARE FOR SCHEMATIC PURPOSES AND ARE FOR DISTINGUISHING CIRCUITS. RECORD AS-BUILT CIRCUITING IN A TYPED AND DATED PANELBOARD SCHEDULE. F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS, EXCEPT WHERE NOTED OTHERWISE. G. INSTALL CONDUIT WITH NO MORE THAN (2) 90° BENDS BETWEEN PULL BOXES, AND NO MORE THAN 100'-0" BETWEEN PULL BOXES. PULL BOXES SHALL BE INSTALLED FOR STRAIGHT THRU PULLS ONLY. H. ALL COMMUNICATIONS CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL CONDUIT WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED INTO CABLE TRAY. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR CABLE INSTALLATION WHERE NOT INSTALLED IN CONDUIT OR CABLE TRAY. I. PROVIDE AND INSTALL HONEYWELL H4D2F SECURITY CAMERAS AT LOCATIONS SHOWN. VERIFY EXACT MOUNTING LOCATIONS AND ORIENTATIONS WITH OWNER PRIOR TO INSTALLATION. J. PROVIDE AND INSTALL THINLINE II HID CARD READERS AT LOCATIONS SHOWN. CONNECT TO HONEYWELL PRO 2200 CARD READER HEAD END LOCATED IN TECH CLOSET A114. K. ALL CIRCUITING SHOWN REFERS TO PANEL LA2B, SHOWN ON SHEET E0.01. L. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT PRIOR TO START OF WORK. KEYED SHEET NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. FITNESS ROOM SOUND SYSTEM HEAD END RACK MOUNTED ON WALL WITH AUXILIARY AND MICROPHONE INPUTS. REFER TO DETAIL AND SPECIFICATIONS FOR MORE INFORMATION. COORDINTATE EXACT LOCATION AND MOUNTING HEIGHT WITH OWNER PRIOR TO INSTALLATION. PROVIDE DEDICATED 20A, 120V CIRCUIT. CONNECT TO EXISTING SOUND SYSTEM RACK. (LOCATED IN GYMASIUM) PROVIDE CONNECTION TO SPEED SWITCH FOR EXERCISE ROOM FANS DF-1 AND DF-2. COORDINATE LOCATION WITH MECHANICAL PRIOR TO INSTALLATION. PROVIDE WEATHERPROOF APPLIANCE ABOVE FIRE DEPARTMENT CONNECTION. PROVIDE 120V CONNECTION TO EXTERIOR HEAT CHASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH MECHANICAL. PROVIDE ROUGH-IN FOR DOOR SECURITY DEVICES AND 120V CONNECTION. SEE DETAIL H8 ON SHEET E2.00 FOR DOOR SECURITY DETAIL. PROVIDE 1-GANG BOX WITH 3/4" CONDUIT AND (1) CATE5 CABLE TO DATA RACK FOR CAMERA. TYPICAL FOR ALL. PROVIDE 1-GANG BOX WITH 1" CONDUIT AND SPEAKER WIRING BACK TO AV RACK. VERIFY EXACT LOCATION AND MOUNTING HEIGHT WITH OWNER PRIOR TO ROUGH-IN. TYPICAL FOR ALL. PROVIDE 1-GANG BOX WITH 1" CONDUIT AND (1) CAT6 CABLE TO DATA RACK FOR WIRELESS ACCESS POINT (WAP). WAP PROVIDED BY OWNER. TYPICAL FOR ALL. PROVIDE ELECTRICAL CONNECTIONS TO HANDICAP DOOR MOTOR AND ASSOCIATED PUSH PADDLES. PROVIDE PA SPEAKER TO MATCH EXISTING. PROVIDE WIRING BACK TO PA SPEAKER AMPLIFER IN DATA RACK. TYPICAL FOR ALL. BASE BID: PROVIDE DOOR HOLDS. DEDUCT ALTERNATE #4: DELETE DOOR HOLDS. BASE BID: PROVIDE DOOR HOLD. DEDUCT ALTERNATE #3: DELETE DOOR HOLD. PROVIDE WIRING FOR EXISTING PA SPEAKERS IN WEIGHT ROOM AND ROUTE TO FITNESS SOUND SYSTEM HEAD END RACK. PROVIDE VOLUME CONTROL FOR SPEAKERS IN WEIGHT ROOM. PROVIDE WALLPLATE WITH 3.5MM INPUT AUDIO JACK AND VOLUME CONTROL FOR SPEAKERS IN EXERCISE ROOM. CONNECT JACK TO SOUND SYSTEM HEAD END RACK. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed PROFESSIONAL ENGINEER under the laws of the State of MINNESOTA BRADLEY R. JOHANNSEN Date 12/04/15 43936 Registration Number Revisions Description Date 1 G Comm: 152039 Date: 1/11/16 Drawn: A. WELLENS Check: S. CHHUM North ELECTRIC PLAN E Num H Scale: 1/8" = 1'-0" E1.00 1 2 3 4 5 6 7 8 9 10 LUMINAIRE SCHEDULE LETTER LUMINAIRE TYPE LAMPS/WATTS VOLT MOUNTING A A MICROPHONE INPUTS A 2x4 LED HIGH BAY M LED, 85 CRI 4000K MIN 19000 LUMENS MVOLT AIRCRAFT CABLE LENS / LOUVER LUMINAIRE DESCRIPTION MANUFACTURER & SERIES WIDE DISTRIBUTION NO LENS EXTERNAL WIREGUARD FULL BODY CONSTRUCTION 0-10V DIMMING DRIVERS WHITE FINISH 5 YEAR WARRANTY DLC QUALIFIED EQUAL OF LITHONIA EQUAL OF COLUMBIA EXERCISE ROOM SPKR DEVICE TO OVERWRITE FITNESS SOUND SYSTEM WHEN PA SYSTEM IS ACTIVE SPKR SPKR SPKR SPKR 2x4 VOLUMETRIC LED TROFFER DIMMABLE 6 INCH ROUND LED DOWNLIGHT LED, 85 CRI, 4000K MIN 1000 LUMENS MVOLT RECESSED (GRID) WHITE TRANSLUCENT ACRYLIC LENS SPECULAR ALUMINUM REFLECTOR 0-10V DIMMING DRIVER WHITE FINISH 5 YEAR WARRANTY DLC QUALIFIED SOFT SATIN REFLECTOR MATCHING FLANGE 0-10V DIMMING DRIVER, 5% 5 YEAR WARRANTY ENERGY STAR QUALIFIED SPKR 2500 East 80th Street Inver Grove Heights, MN 55076 OR APPROVED EQUAL LITHONIA 2RTL4 SERIES ALLOWANCE - $184/FIXTURE Minnesota State Colleges & Universities 38 30 E 7th St #350, St Paul, MN 55101 JUNO L6 SERIES D MULTICHANNEL AMPLIFIER WIRELESS MIC RECEIVERS MN B LED, 85 CRI 4000K 4000 LUMENS NOTES 152 METALUX HBLED SERIES A M WATTS MVOLT RECESSED (GRID) PRESCOLITE LF6LED SERIES SPKR SPKR SPKR SPKR SPKR 18 LITHONIA LDN6 SERIES ATLANTIC LED6 SERIES WEIGHT ROOM MIXER IHCC ACTIVITIES BUILDING PHASE ll EXERCISE ROOM ADDITION SPKR D1 CD/MP3 PLAYER 6 INCH ROUND LED DOWNLIGHT WET LISTED LED, 80 CRI, 4000K MIN 1000 LUMENS MVOLT RECESSED (EXTERIOR FLANGE) GOTHAM EVO SERIES 0-10V DIMMING DRIVER, 5% 5 YEAR WARRANTY ENERGY STAR QUALIFIED WET LISTED REGRESSED DEAD FRONT ACRYLIC LENS MATCHING FLANGE PRESCOLITE LF6LED SERIES 18 ATLANTIC LED7 SERIES OR APPROVED EQUAL COLUMBIA CSR4 SERIES B F CONTROL PANEL VOLUME CONTROL VOLUME CONTROL C3 ETHERNET CONNECTION Rack-Mounted Equipment Shall Include: (1) Shure ULXS 124/85 wireless combo system. (1) Shure UA 507 antenna. (1) Shure UA 221. (1) Shure SM58 CN wired mic. (1) Middle Atlantic EWR 10-22 wall rack. (1) BSS Blu-100 DSP. (1) Crown DCI 2/600 power amplifier (2) Rapco/Horizon Blox 2 computer/MP3 interface. FITNESS ROOM SOUND SYSTEM DETAIL 4 FOOT INDUSTRIAL STRIP (2) F32T8/841 MVOLT CHAIN HUNG WHITE FINISH SYMMETRIC REFLECTOR WIREGUARD NO LENS 10% UPLIGHT LITHONIA LA SERIES 62 COOPER IAF SERIES OR APPROVED EQUAL E1 E3 EM1 EXIT SIGN SINGLE FACE EXIT SIGN SINGLE FACE EMERGENCY HEADS EMERGENCY BUGEYE LED LED LED MVOLT MVOLT MVOLT UNIVERSAL MOUNT UNIVERSAL MOUNT SURFACE STENCIL FACE RED LETTERS STENCIL FACE RED LETTERS LITHONIA LE SERIES NICKEL CADMIUM BATTERY SELF DIAGNOSTICS WHITE CAST ALUMINUM HOUSING INVISIBLE CHEVRON ARROW DUAL-LITE SE SERIES SURE-LITES CX SERIES 1 10 1 3 1 OR APPROVED EQUAL SURE-LITES APC SERIES NICKEL CADMIUM BATTERY SELF DIAGNOSTICS WHITE CAST ALUMINUM HOUSING INVISIBLE CHEVRON ARROW OR APPROVED EQUAL LITHONIA ELM2-LED SERIES NICKEL CADMIUM BATTERY SELF DIAGNOSTICS ADJUSTABLE HEADS 10 SURE LITES LED SERIES DUAL LITE LZ SERIES NTS OR APPROVED EQUAL G 4 FOOT LED WALL BRACKET C LED, 85 CRI, 4000K MIN 4000 LUMENS MVOLT SURFACE LITHONIA WL4 SERIES WHITE FINISH SURFACE CONDUIT PROVISIONS IMPACT RESISTANT LENS 40 OR APPROVED EQUAL LUMINAIRE SCHEDULE GENERAL NOTES A. FLUORESCENT BALLASTS SHALL BE ELECTRONIC PROGRAMMED START UNLESS NOTED OTHERWISE. B. FOR LINEAR FLUORESCENT LAMPS PROVIDE ROTARY LOCKING LAMP SOCKETS. C. WHEN DIMMING IS NOT INDICATED ON PLANS FOR LUMINAIRES WITH 0-10V DIMMING, LEAVE 0-10V WIRING DISCONNECTED AND CAPPED FOR FUTURE USE. D. MOUNTING HEIGHT IS TO BOTTOM OF FIXTURE. E. IN ADDITION TO THE LUMINAIRES AND CONTROLS SHOWN ON DRAWINGS, THE FOLLOWING LUMINAIRES SHALL BE PROVIDED (FURNISH AND INSTALL) WHERE DIRECTED BY ENGINEER DURING CONSTRUCTION. INSTALLATION OF LUMINAIRES SHALL INCLUDE 25’ OF WIRING AND ASSOCIATED RACEWAY AS REQUIRED. FOR EACH LUMINAIRE NOT INSTALLED TURN LUMINAIRE OVER TO THE OWNER FOR SPARE MATERIALS AND PROVIDE A LABOR CREDIT OF $100 PER UNINSTALLED FIXTURE. TYPE E1: (2) SPARES. LUMINAIRE SCHEDULE NUMBERED NOTES 1. PROVIDE WIREGUARD (WG) WHERE INDICATED ON PLANS D E Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt 1/8/2016 4:34:13 PM C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt F I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed PROFESSIONAL ENGINEER under the laws of the State of MINNESOTA BRADLEY R. JOHANNSEN Date 12/04/15 43936 Registration Number Revisions Description PROVIDE 120V CONNECTION 1/2"C FOR DOOR CONTACT Date 1 G DOUBLE GANG BOX WITH COVER PLATE, LOCATED ABOVE ACCESSIBLE CEILING. 1/2"C FOR POWER TRANSFER HINGE. 1/2"C TO CARD READER S DC PROVIDE REMOVABLE FOAM IN DOOR FRAME TO ALLOW FUTURE DEVICE INSTALLATION AND ACCESS TO CONDUIT AFTER GROUT INSTALLED INTO DOOR FRAME. S PT S ES 42" SINGLE GANG BOX FOR CARD READER S CR Comm: 152039 Date: 1/11/16 Drawn: A. WELLENS Check: S. CHHUM ELECTRICAL SCHEDULES NOTE: E A. PROVIDE BLANK STAINLESS COVERPLATE ON ALL UNUSED BACKBOXES. B. BUSH ALL CONDUIT ENDS. H Scale: H9 SECURITY RACEWAY DETAIL NTS Num NTS E2.00