ELECTRICAL SYMBOL SCHEDULE
SYMBOL
DESCRIPTION
SYMBOL
GENERAL ELECTRICAL SYMBOLS
A.
A
ALL MOUNTING HEIGHTS INDICATED ARE FROM THE
FINISH FLOOR TO THE CENTER OF THE BOX.
C.
ITEMS SHOWN DOTTED ARE TO BE REMOVED, ITEMS
SHOWN WITH A LIGHT SCREENED LINE ARE EXISTING TO
REMAIN.
D.
MN
MOUNTING
HEIGHT
DESCRIPTION
SYMBOL
LIGHTING
DEVICES SHALL BE MOUNTD AT THE HEIGHT INDICATED,
UNLESS NOTED OTHERWISE. DEVICES MOUNTED IN
BLOCK/BRICK WALLS SHALL CORRESPOND WITH
BLOCK/BRICK COURSING. SEE MASONRY BACKBOX
MOUNTING HEIGHT DETAIL.
B.
DESCRIPTION
MOUNTING
HEIGHT
SYMBOL
SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE (TYPE
DENOTED)
MOTOR RATED SWITCH AND PILOT.
46"
MS
MOTOR RATED SWITCH.
46"
MOTOR STARTER SWITCH WITH MOTOR RUNNING PROTECTION
(ADD RELAY IF CONTROL CONTACTS ARE REQUIRED).
DISCONNECT SWITCH - NON FUSED.
6'-0"
LIGHT FIXTURE ON 24/7 (NIGHT LIGHT)
DISCONNECT SWITCH - FUSED.
6'-0"
RECESSED LIGHT FIXTURE (TYPE DENOTED)
'DEMOLITION' EXAMPLES:
MOTOR STARTER.
6'-0"
COMBINATION STARTER/DISCONNECT SWITCH.
6'-0"
T
THERMOSTAT - WALL MOUNTED.
FLUORESCENT STRIP LIGHTING FIXTURE; FOR SUSPENDED
MOUNTING HEIGHTS, SEE DRAWINGS.
PUSHBUTTON - SINGLE BUTTON, WALL MOUNTED.
R
WALL MOUNTED LIGHTING FIXTURE; SEE REFLECTED CEILING
PLAN FOR MOUNTING HEIGHT.
SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND
SPECIFIED (FLUSH OR SURFACE AS INDICATED); VERIFY
MOUNTING.
DATA
SYSTEMS CABLE DISTRIBUTION CABINET AS INDICATED AND
SPECIFIED (FLOOR OR WALL AS INDICATED).
LINEAR PENDANT LIGHTING FIXTURE; FOR SUSPENDED
MOUNTING HEIGHTS, SEE DRAWINGS.
KEYED NOTE
#
FEEDER OR EQUIPMENT DRAWING NOTE.
30" - 36"
PL
PB
3
PULLBOX
HH
J
SINGLE POLE LIGHT SWITCH WITH LIGHTED PILOT LIGHT
46"
SINGLE POLE LIGHT SWITCH
46"
#V
J #D
46"
OCCUPANCY SENSOR SWITCH
46"
J #
MCC
MOTOR CONTROL CENTER (W/CONCRETE PAD);
FLOOR MOUNTED.
K
KEYED LIGHT SWITCH (POLES AS INDICATED)
46"
PLUG-IN BUS DUCT SWITCH; SIZE AS INDICATED AND
SPECIFIED. VERIFY MOUNTING HEIGHT.
MC
MOMENTARY CONTACT LIGHT SWITCH
46"
D
DIMMER LIGHT SWITCH
46"
TS
TIME-SWITCH
46"
D
M
METER/SOCKET ASSEMBLY; MOUNT TOP AT 6'-0".
L
PC
L
OS
L
OS
BRANCH CIRCUIT, FEEDER, RACEWAY
LL-1
2,4
MOTOR NUMBER; REFER TO MOTOR SCHEDULE
S
S
V
CONTACTOR (ENCLOSURE MOUNTED)
(RATING, POLES AND MOUNTING AS INDICATED)
PANELBOARD NAME
M
A
V
-
FLOOR BOX, FULLY RECESSED IN FLOOR. REFER TO FLOOR
PLAN DRAWING FOR NUMBER OF RECEPTACLES AND VOICE
AND DATA CABLES/DEVICES.
SYSTEMS WALL BOX: #D INDICATES NO. OF DATA CABLES;
#V INDICATES NO. OF VOICE CABLES. FLEXIBLE CONDUIT
WHIP, CABLES AND DEVICES PROVIDED IN ELECTRIFIED
FURNITURE BY LOW-VOLTAGE CONTRACTOR.
P
PHOTOCELL - WALL, CEILING, OR ROOF MOUNTED; SEE
DRAWINGS.
90"
84"
OCCUPANCY DETECTOR - WALL OR CEILING CEILING MOUNT
#D,#V
BRANCH CIRCUITS (IN THE PANELBOARD)
ARROW INDICATES HOMERUN
CIRCUIT NUMBER, TYPICAL
P
18"
DUPLEX RECEPTACLE
#
RECEPTACLE (SINGLE)
18"
E
18"
DOUBLE DUPLEX RECEPTACLE (QUAD)
INDICATES CONDUIT IS SURFACE MOUNTED
INDICATES CONDUIT ROUTED CONCEALED ABOVE FLOOR OR
GRADE (IN CEILING OR WALL)
(1) HIGH MOUNTED DUPLEX RECEPTACLE AND
(1) LOW MOUNTED DUPLEX RECEPTACLE
H/L
W
90"
(1) HIGH MOUNTED DUPLEX RECEPTACLE
H
90"/18"
#
INDICATES CONDUIT UP
INDICATES CONDUIT DOWN
DUPLEX RECEPTACLE W/ GROUND FAULT CIRCUIT INTERRUPTER
(GFI)
GFI
CONDUIT STUB - TERMINATION INDICATED BY NOTE
POWER WALL BOX: # INDICATES NUMBER OF POWER
CIRCUIT(S). POWER WHIP SUPPLIED BY FURNITURE VENDOR,
INSTALLED BY ELECTRICAL CONTRACTOR.
1"C,3#4,1#3G
F
18"
RECESSED CEILING MOUNTED DUPLEX RECEPTACLE W/
ADDITIONAL 10' FLEX CONDUIT SLACK (COILED) WITH GROUND
WIRE; FOR FUTURE DEVICE RELOCATION.
J
INDICATES 1" CONDUIT, (3) NO. 4 AWG CONDUCTORS AND (1)
NO. 3 GROUND WIRE
J
Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt
1/8/2016 4:34:09 PM
90"
F
D
F
MAGNETIC DOOR HOLD-OPEN (WALL MOUNTED); MOUNT
PER DWGS.
FL
F
SPRINKLER FLOW-SWITCH; MOUNT PER DWGS.
TS
F
SPRINKLER TAMPER-SWITCH; MOUNT PER DWGS.
18"
F S
SMOKE DETECTOR-CEILING MOUNTED.
AUXILIARY INPUT CONNECTOR.
(1/2"C. BUSHED EMT TO ACCESSIBLE CEILING).
18"
F H
HEAT DETECTOR (RATE-OF-RISE) - CEILING MOUNTED.
136°
F H
HEAT DETECTOR (FIXED TEMPERATURE)- CEILING MOUNTED.
H.
F
DUCT SMOKE DETECTOR; MOUNT PER DWGS.
I.
J.
K.
VOLUME CONTROL.
(1/2"C. BUSHED EMT TO ACCESSIBLE CEILING).
46"
CALL BACK SWITCH.
(1/2"C. BUSHED EMT TO ACCESSIBLE CEILING).
46"
CM
F
18"
CS
F
CHLORINE GAS SENSOR; CEILING MOUNTED.
N.
O.
P.
GS
F
GAS SHUT-OFF; MOUNT PER DWGS.
Q.
F/S
F
FIRE/SMOKE DAMPER; MOUNT PER DWGS.
TV
H
TV/VIDEO OUTLET MOUNTED HIGH.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
TV
H/L
(1) TV/VIDEO OUTLET MOUNTED HIGH AND
(1) TV/VIDEO OUTLET MOUNTED LOW. (3/4"C. BUSHED EMT TO
ACCESSIBLE CEILING).
SD
18"
L.
M.
FIRE ALARM CONTROL MODULE; MOUNT PER DWGS.
R.
DATA OUTLET:
(1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO
BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE.
DATA AND VOICE OUTLET:
(1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). #D,#V INDICATES NUMBER OF DEVICES AND
CABLES TO BE PROVIDED. #D REPRESENTS DATA; #V
REPRESENTS VOICE. IF NO NUMBERS ARE INDICATED,
PROVIDE ONE OF EACH.
18"
PUBLIC VOICE OUTLET (TELEPHONE):
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS
OTHERWISE NOTED.
WALL VOICE OUTLET (TELEPHONE):
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS
OTHERWISE NOTED.
VOICE OUTLET:
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). # INDICATES NUMBER OF DEVICES AND CABLES TO
BE PROVIDED. IF NO NUMBERS ARE INDICATED, PROVIDE ONE.
IC
A
JUNCTION BOX WITH REQUIRED COVERPLATE - WALL OR
CEILING MOUNT - PLAN INDICATES MOUNTING AND FUNCTION
18"
WIRELESS ACCESS POINT (DATA OUTLET):
(1"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). PROVIDE ONE CABLE AND DEVICE, UNLESS
OTHERWISE NOTED. MOUNT HIGH ON WALL OR ON CEILING AS
INDICATED ON DWG.
2500 East 80th Street
Inver Grove Heights, MN 55076
Minnesota State Colleges
& Universities
30 E 7th St #350,
St Paul, MN 55101
ONE LINE SYMBOLS
20A CIRCUIT CONDUCTORS SHALL
BE SIZED AS FOLLOWS
90"/18"
DISTRIBUTION PANEL
C
CLOCK OUTLET.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
90"
B
BELL/AUDIBLE DEVICE.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
90"
120V CCT LENGTH
277V CCT LENGTH
AWG
< 75'
< 75'
12
75' - 120'
75' - 280'
10
120' - 200'
280' - 450'
8
> 200'
> 450'
6
PANEL
18"
UPS OR INVERTER
UPS
SECURITY DEVICES
##
S
SECURITY DEVICE. ## INDICATES THE FOLLOWING:
CM
DC
EL
ES
GB
IR
ML
XP
XS
48"
48"
STANDARD BACKBOX MOUNTING HEIGHTS
CONTROL MODULE
DOOR CONTACTS (MONITORING)
ELECTRIC LOCK
ELECTRIC STRIKE
GLASS BREAK DETECTOR
INFARED DETECTOR
MAGNETIC LOCK
EXIT PUSHBUTTON, MOUNT AT ADA HT
EXIT SENSOR
CR S
CARD READER ROUGH-IN AT ADA HEIGHT
DR S
DOOR RELEASE; MOUNT PER DWGS.
N
E
TRANSFER SWITCH
L
100"
DRAW-OUT CIRCUIT BREAKER
46"
18"
TRANSFORMER
46"
92"
ELECTRIC EYE; MOUNT PER DWGS.
CIRCUIT BREAKER
86"
3
18"
KP S
KEYPAD; VERIFY MOUNTING HEIGHT WITH DWGS.
LA S
LOCAL ALARM
46"
MC S
MASTER CONTROL STATION
46"
MD
S
MD
S
GENERATOR
GEN
ELECTRICAL ABBREVIATIONS LIST
80"
72"
60"
62"
64"
52"
54"
2
46"
5
36"
12"
4
18"
46"
2
44"
56"
2
7
46"
48"
38"
40"
30"
32"
22"
14"
1
6"
6
20"
18"
1
1
24"
36"
29"
16"
FINISHED FLOOR
8"
GENERAL NOTES:
A.
SWITCH
NUMBER NOTES:
MOTION DETECTOR; ARROW INDICATES DIRECTION.
(WALL OR CEILING MOUNTED).
1.
2.
FUSE
SECURITY CAMERA, CLOSED CIRCUIT.
(WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO
ACCESSIBLE CEILING).
S
3
88"
70"
FUSED SWITCH
PHOTO-ELECTRIC TRANSMITTER; MOUNT PER DWGS.
S
3
68"
4"
PHOTO-ELECTRIC RECEIVER; MOUNT PER DWGS.
T P
88"
78"
20"
46"
90"
76"
28"
18"
96"
94"
90"
84"
44"
EE S
VOICE OUTLET, INTERCOM ONLY:
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING SPACE OR AS
INDICATED). PROVIDE ONE CABLE AND DEVICE UNLESS
OTHERWISE NOTED.
INSTALL CONCEALED CONDUIT WITH FLUSH J.B.'S IN WALLS AND CEILINGS
UNLESS NOTED OTHERWISE. IN FINISHED AREAS WITH INACCESSIBLE WALLS OR
CEILINGS, PROVIDE SURFACE (WIREMOLD) RACEWAY; PAINT TO MATCH COLOR
OF ADJACENT WALL OR CEILING.
RACEWAYS SHALL CONTAIN A GROUNDING CONDUCTOR.
CIRCUITS SUPPLYING LINE TO NEUTRAL LOADS SHALL HAVE DEDICATED
NEUTRALS, i.e. ONE NEUTRAL PER PHASE. NEUTRAL CONDUCTORS SHALL HAVE
TRACER STRIPE ALONG ENTIRE LENGTH INDICATING ASSOCIATED PHASE.
BUILDING CONDUCTORS SHALL BE THWN/THHN. CONDUCTORS IN UNDERGROUND
CONDUIT OUTSIDE OF BUILDINGS SHALL BE XHHW.
NUMBERS AT RECEPTACLES AND LUMINAIRES CORRESPOND DIRECTLY WITH
PANELBOARD CIRCUIT NUMBERS AS SCHEDULED. BRANCH CIRCUIT WIRING AND
HOMERUNS ARE NOT SHOWN FOR CLARITY. ACCURATE RECORD DRAWING
INFORMATION IS TO BE PROVIDED AT THE PROJECT COMPLETION. TYPICAL
THROUGHOUT. REFER TO SPECIFICATIONS FOR MATERIALS AND INSTALLATION
REQUIREMENTS.
REFER TO CONTRACT DOCUMENTS FOR SEQUENCE OF CONSTRUCTION AND
PHASING OF THE CONTRACT.
SWITCHES SHALL BE MOUNTED PER ADA REQUIREMENTS, 40" AFF. UNLESS
OTHERWISE NOTED, RECEPTACLES AND TELECOMMUNICATION OUTLETS IN
FINISHED AREAS SHALL BE MOUNTED 18" AFF. RECEPTACLES IN UN-FINISHED
SPACES SHALL BE MOUNTED AT 48" OR 4" ABOVE WORK SURFACE.
COORDINATE RECEPTACLE MOUNTING HEIGHTS WITH MILLWORK LOCATIONS,
ARCHITECTURAL ELEVATIONS, AND MASONRY COURSING.
CRITICAL DEVICES / EQUIPMENT, INCLUDING TELEPHONE, COMPUTER, SECURITY,
AND FIRE ALARM, AFFECT ASSOCIATED SYSTEMS BUILDING-WIDE. THESE
SYSTEMS MUST REMAIN OPERATIONAL DURING THE CONSTRUCTION. INDIVIDUAL
DEVICES MAY BE DISCONNECTED AND/OR RECONNECTED DURING
CONSTRUCTION. COORDINATE POWER OUTAGES WITH OWNER. PROVIDE
TEMPORARY PANEL(S) AND/OR CIRCUIT(S) AS/IF NECESSARY TO MAINTAIN
CONTINUITY. PROTECT FROM PHYSICAL AND DUST DAMAGE.
THE BUILDING SHALL MAINTAIN POWER THROUGHOUT THE CONSTRUCTION
PROCESS. COORDINATE ENERGIZATION OF NEW EQUIPMENT AND THE
CORRESPONDING RECONNECTION OF EXISTING AFFECTED ELECTRICAL
DISTRIBUTION EQUIPMENT.
SEE RELATED PLUMBING AND HVAC DRAWINGS FOR LOCATION OF EQUIPMENT
REQUIRING ELECTRICAL CONNECTIONS. COORDINATE INTERCONNECTION
REQUIREMENTS WITH EQUIPMENT SHOP DRAWINGS.
WIRING FOR MISCELLANEOUS HVAC DEVICES AND CONTROLLERS SUCH AS
DAMPER MOTORS, THERMOSTATS, DUCT SMOKE DETECTORS, FREEZESTATS,
DIFFERENTIAL PRESSURE SWITCHES, OCCUPIED AND UNOCCUPIED SELECTOR
SWITCHES, ALARM LIGHTS, ETC., NOT SHOWN ON ELECTRICAL DRAWINGS IS
DIVISION 23 WORK.
FIELD VERIFY EXISTING CONDITIONS. DISCREPANCIES BETWEEN THE DRAWING
AND ACTUAL FIELD CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER PRIOR TO BIDS.
MAINTAIN EXISTING CIRCUIT CONTINUITY ON ALL SYSTEMS ON THE SITE THAT ARE
EXISTING TO REMAIN.
PROVIDE ALL CONDUIT HOMERUNS AS 3/4"C. MIN.
COORDINATE ALL WORK WITH OTHER CONTRACTORS AND OWNER.
ALL CUTTING AND PATCHING FOR DIV. 26 WORK SHALL BE UNDER SUPERVISION
AND APPROVAL OF ARCHITECT.
REMOVE AND/OR REINSTALL ELECTRICAL DEVICES IN ALL AREAS OF WORK AS
REQUIRED AND REPLACE ANY ELECTRICAL DEVICES DAMAGED BY WORK. NOT
ALL DEVICES MAY BE SHOWN ON DRAWINGS.
PROVIDE ALL BOXES, FITTINGS, CONDUIT, WIRING, TERMINATIONS, EQUIPMENT,
ETC, FOR A COMPLETE INSTALLATION.
IHCC ACTIVITIES
BUILDING PHASE ll EXERCISE ROOM
ADDITION
90"
TV/VIDEO CAMERA, CLOSED CIRCUIT.
(WALL OR CEILING MOUNTED, 3/4"C. BUSHED EMT TO ACCESSIBLE
CEILING).
TV
TV
SURFACE RACEWAY ASSEMBLY. REFER TO ARCHITECTURAL
AND ELECTRICAL PLANS FOR MOUNTING HEIGHT. PROVIDE AS
SPECIFIED, UNLESS NOTED OTHERWISE.
C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt
FIRE ALARM BELL (WP FOR EXTERIOR MOUNTING).
MICROPHONE OUTLET ( WALL OR CEILLING).
(1/2"C. BUSHED EMT TO ACCESSIBLE CEILING).
TV
L
R P
3.
4.
5.
6.
7.
MOUNTING HEIGHT OF STANDARD BACKBOXES ONLY. REFER TO DRAWINGS AND
DETAILS FOR MOUNTING HEIGHT OF OTHER BACKBOXES.
MOUNTING HEIGHT FOR BACKBOXES MOUNT LOW IN WALL.
MOUNTING HEIGHT FOR BACKBOXES MOUNTED NEAR MIDDLE OF WALL, INCLUDING DEVICES SUCH
AS TOGGLE SWITCHES.
MOUNTING HEIGHT FOR BACKBOXES MOUNTED HIGH IN WALL.
STANDARD COUNTER TOP.
STANDARD COUNTER TOP BACK SPLASH HEIGHT.
STANDARD DESK TOP.
STANDARD DESK TOP BACK SPLASH HEIGHT.
I hereby certify that this plan, specification or report was prepared by
me or under my direct supervision and that I am a duly Licensed
PROFESSIONAL ENGINEER
MINNESOTA
under the laws of the State of
BRADLEY R. JOHANNSEN
Date 12/04/15
43936
Registration Number
ELECTRICAL SYMBOL NOTES
Revisions
1P
A
AC
G
ACLG
ADO
AFF
AFG
AFI
AHU
AL
ALT
AMP
AMPL
ANNUN
APPROX
AQ-STAT
ARCH
ATS
AUTO
AUX
AV
AWG
BATT
BD
BLDG
BMS
E
F.
18"
18"
SPECIAL PURPOSE OUTLET; WALL OR RECESSED CEILING
MOUNTED
CABLE TRAY
90"
90"
TV/VIDEO OUTLET MOUNTED LOW.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING)
POWER AND MOTOR DEVICES
INDICATES CONDUIT ROUTED BELOW OR IN FLOOR
STRUCTURE OR BELOW GRADE OR AS NOTED.
FIRE ALARM HORN/STROBE (COMBINATION) - 75Cd,
U.N.O. (WALL OR CEILING MOUNTED).
SPEAKER WITH BACKBOX (WALL OR CEILING); VERIFY MOUNTING
HEIGHT. PA = SPEAKER FOR P.A. SYSTEM; V = WITH INTEGRAL
VOLUME CONTROL KNOB.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
PROJECTOR OUTLET (WALL OR CEILING).
P
18"
VOICE AND DATA DEVICES
#
L
PC
90"
46"
FOUR-WAY LIGHT SWITCH
OS
HANDHOLE
90"
FIREMAN PHONE JACK; MOUNT TOP 54" AFF PLUS OR
MINUS 2".
LOUD SPEAKER HORN ASSEMBLY- PA OR SOUND SYSTEM AS
INDICATED; VERIFY MOUNTING HEIGHT.
(3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
S
POKE-THROUGH, FULLY RECESSED IN FLOOR. REFER TO
FLOOR PLAN DRAWING FOR NUMBER OF RECEPTACLES AND
VOICE AND DATA CABLES/DEVIVES.
THREE-WAY LIGHT SWITCH
4
F
H
LIGHTING CONTROL
TRANSFORMER, WITH SIZE AS NOTED. SEE RISER DIAGRAM,
SCHEDULE OR FLOOR PLANS; VERIFY.
T
POWER POLE (DEVICES AS INDICATED)
POKE-THRU'S, FLOOR BOXES,
& FURNITURE CONNECTIONS
POLE MOUNTED SITE LIGHTING FIXTURE - SINGLE SQUARE
HEAD. # OF HEADS AS SHOWN.
AUTOMATIC TRANSFER SWITCH;
WALL OR FLOOR MOUNTED.
ATS
C
EMERGENCY LIGHTING UNIT - TWO HEAD MOUNTING AS
INDICATED ON DRAWINGS.
PANELBOARD; WALL MOUNTED WITH TOP 6'-0".
F
F
PAGING/INTERCOM SPEAKER HORN ASSEMBLY- P.A. OR AS
INDICATED (3/4"C. BUSHED EMT TO ACCESSIBLE CEILING).
MOUNT 12" BELOW CEILING OR AS INDICATED.
S
MOTOR NAME; REFER TO MOTOR SCHEDULE (AHU-#)
EXIT LIGHT-FACE SHOWN SHADED; PLAN INDICATES CEILING
OR WALL MOUNTING AND DIRECTIONAL ARROWS.
RELAY/CONNECTION CABINET;
WALL MOUNTED, WITH TOP 6'-0".
E.
60" OR 62"
M
SWITCHBOARD WITH CONCRETE PAD:
FLOOR MOUNTED.
C
AHU
CIRCULAR PENDANT LIGHT FIXTURE; FOR SUSPENDED
MOUNTING HEIGHTS, SEE DRAWINGS.
POWER DISTRIBUTION AND EQUIPMENT
FIRE ALARM STROBE (VISUAL) DEVICE - 75 Cd, U.N.O.
(WALL OR CEILING MOUNTED).
F
MOTOR:
#
TRACK LIGHTING FIXTURE; LENGTH AND MOUNTING AS NOTED
ON DRAWINGS.
#
F
RELAY - VERIFY MOUNTING HEIGHT; SEE DRAWINGS.
PP
ON NEW WORK LIGHTING, POWER AND SYSTEMS
DRAWINGS, SCREENED ELECTRICAL ITEMS DENOTES
EXISTING ITEMS TO REMAIN; SOLID ELECTRICAL ITEMS
DENOTES NEW ITEMS, UNLESS NOTED OTHERWISE
FIRE ALARM HORN (AUDIBLE), WALL MOUNTED.
F
TV
D.
FIRE ALARM MANUAL PULL STATION; MOUNT TOP 46" AFF
PLUS OR MINUS 2".
F
TELEPHONE TERMINAL CABINET; VERIFY MOUNTING.
'EXISTING TO REMAIN' EXAMPLES:
E.
B.
C.
G.
F
F
A.
FIRE ALARM CONTROL PANEL (MASTER); MOUNT TOP
62" AFF PLUS OR MINUS 2".
EQUIPMENT RACK: ABBREVIATION FOR SYSTEM SERVED AND
SPECIFIED; VERIFY MOUNTING.
EQ
SURFACE MOUNTED LIGHT FIXTURE (TYPE DENOTED)
B
MOUNTING
HEIGHT
FIRE ALARM DEVICES
LOCAL DISTRIBUTED SOUND SYSTEM WALL OR FLOOR AMPLIFIER
ASSEMBLY; VERIFY MOUNTING.
AMP
46"
LIGHT FIXTURE ON EMERGENCY CIRCUIT
DESCRIPTION
FIRE ALARM ANNUNCIATOR PANEL; MOUNT TOP AT 54" AFF.
TEL
ON DEMOLITION DRAWINGS, DASHED ELECTRICAL
ITEMS DENOTES EXISTING ITEMS TO BE REMOVED;
SOLID SCREENED ELECTRICAL ITEMS DENOTES
EXISTING ITEMS TO REMAIN, UNLESS NOTED OTHERWISE
SYMBOL
COMMUNICATION DEVICES
MS&P
MSS
MOUNTING
HEIGHT
DESCRIPTION
POWER AND MOTOR DEVICES
RECESSED FLUORESCENT LIGHT FIXTURE (TYPE DENOTED)
GENERAL ELECTRICAL NOTES
H
C
CAB
CATV
CB
CCTV
CKT
CLG
COMB
1 POLE (2P, 3P, 4P, ETC.)
AMPERE
ABOVE COUNTER OR AIR
CONDITIONER
ABOVE CEILING
AUTOMATIC DOOR OPENER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC FAULT CIRCUIT
INTERRUPTER
AIR HANDLING UNIT
ALUMINUM
ALTERNATE
AMPERE
AMPLIFIER
ANNUNCIATOR
APPROXIMATELY
AQUASTAT
ARCHITECT, ARCHITECTURAL
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AUDIO VISUAL
AMERICAN WIRE GAUGE
BATTERY
BOARD
BUILDING
BUILDING MANAGEMENT
SYSTEM
CONDUIT
CABINET
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
COMBINATION
CMPR
CONN
CONST
CONT
CONTR
CONV
CP
CRT
CT
CTR
CU
DCP
COMPRESSOR
CONNECTION
CONSTRUCTION
CONTINUATION OR
CONTINUOUS
CONTRACTOR
CONVECTOR
CIRCULATING PUMP
CATHODE-RAY TUBE
CURRENT TRANSFORMER
CENTER
COPPER
DEPT
EX
HTR
HV
HWP
DOMESTIC WATER
CIRCULATING PUMP
DEPARTMENT
EXISTING TO REMAIN
HEATER
HIGH VOLTAGE
HYDRONIC WATER PUMP
IC
IG
IMC
INCAND
IR
I/W
INTERRUPTING CAPACITY
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INCANDESCENT
INFRARED
INTERLOCK WITH
J-BOX
JUNCTION BOX
KV
KVA
KVAR
KW
KWH
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
LOC
LT
LTG
LTNG
LV
LOCATE OR LOCATION
LIGHT
LIGHTING
LIGHTNING
LOW VOLTAGE
MAX
MAG.S
M/C
MC
MCB
MCC
MDC
MDP
MFR
MFS
MAXIMUM
MAGNETIC STARTER
MOMENTARY CONTACT
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION CENTER
MAIN DISTRIBUTION PANEL
MANUFACTURER
MAIN FUSED DISCONNECT
SWITCH
MANHOLE
MICROPHONE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MANUAL MOTOR STARTER
MULTIOUTLET ASSEMBLY
MOTOR STARTER PANELBOARD
MAIN SWITCHBOARD
MOUNT
EMPTY CONDUIT
MANUAL TRANSFER SWITCH
MOTOR, MOTORIZED
PA
PB
PE
PED
PF
PH
PNL
PP
PR
PRI
PROJ
PRV
PT
PVC
NIC
NL
N.O.
NPF
NTS
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NON-FUSED SAFETY
DISCONNECT SWITCH
NOT IN CONTRACT
NEW LOCATION
NORMALLY OPEN
NORMAL POWER FACTOR
NOT TO SCALE
OH
OL
OVERHEAD
OVERLOADS
MH
MIC
MIN
MISC
MLO
MMS
MOA
MSP
MSBD
MT
MT.C
MTS
MTR
N.C.
NEC
NEMA
NFDS
PWR
PUBLIC ADDRESS
PULL BOX OR PUSHBUTTON
PNEUMATIC ELECTRIC
PEDESTAL
POWER FACTOR
PHASE
PANEL
POWER POLE
PAIR
PRIMARY
PROJECTION
POWER ROOF VENTILATOR
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
(CONDUIT)
POWER
QUAN
QUANTITY
RCPT
REQD
RL
RSC
RTU
RECEPTACLE
REQUIRED
RELOCATED
RIGID STEEL CONDUIT
ROOF TOP UNIT
SC
SEC
SHT
SIM
S/N
SPEC
SPKR
SP
SR
SS
SSW
S/S
STA
STD
SURF
SURFACE CONDUIT
SECONDARY
SHEET
SIMILAR
SOLID NEUTRAL
SPECIFICATION
SPEAKER
SPARE
SURFACE RACEWAY
STAINLESS STEEL
SELECTOR SWITCH
STOP/START PUSHBUTTONS
STATION
STANDARD
SURFACE MOUNTED
SW
SWBD
SYM
SYS
TEL
TERM
TL
TR
T-STAT
TTC
TV
TVTC
TYP
UE
UG
UH
UT
UV
SWITCH
SWITCHBOARD
SYMMETRICAL
SYSTEM
TELEPHONE
TERMINAL
TWIST LOCK
TAMPER RESISTANT
THERMOSTAT
TELEPHONE TERMINAL
CABINET
TELEVISION
TELEVISION TERMINAL
CABINET
TYPICAL
@
'
"
#
Ø
C
P
ANGLE
AT
FEET
INCHES
NUMBER
PHASE
CENTER LINE
PLATE
A2
EXAMPLE 1: LIGHTING FIXTURE TYPE "A" IS CONNECTED TO CIRCUIT 12 AND CONTROLLED
BY SWITCH "b".
12b
* P2D/I *
2aba
UNDERGROUND ELECTRICAL
UNDERGROUND
UNIT HEATER
UNDERGROUND TELEPHONE
UNIT VENTILATOR OR
ULTRAVIOLET
E
14
16c
V
VA
VDT
VERT
VFD
VOL
VOLT
VOLT-AMPERES
VIDEO DISPLAY TERMINAL
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
W
W/
WG
WH
W/O
WP
WATT
WITH
WIRE GUARD
WATER HEATER
WITHOUT
WEATHERPROOF
XFMR
XFR
TRANSFORMER
TRANSFER
7,9
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER.
THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.
THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
d
D600
EXAMPLE 2: THE FIXTURE TYPE SHOWN AS A NUMERATOR INDICATES ALL LIGHTING
FIXTURES IN THE ROOM OR SPACE ARE THE SAME TYPE. THE CIRCUIT NUMBER AND
SWITCH DESIGNATION SHOWN AS A DENOMINATOR INDICATES ALL LIGHTING FIXTURES IN
THE ROOM OR SPACE ARE CONNECTED TO THE SAME CIRCUIT, CONTROLLED BY THE SAME
SWITCHES, CENTER/OUTBOARD MULTILEVEL SWITCHING.
DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH
DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX
RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH "c".
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE:
SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".
WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600 WATT WALL BOX
DIMMER TO CONTROL LIGHTING FIXTURES INDICATED BY "e". SEE SPECIFICATIONS FOR
WATTAGE IF NOT INDICATED.
1,3,5
SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEE
THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OF
CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO
THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5.
SF-1
2,4,6
LPN-102
EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING.
SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROW
ON ILLUMINATED FACE(S). THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.
EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E" WITH SINGLE FACE AND DIRECTIONAL
ARROW IS CONNECTED TO CIRCUIT 14.
e
1
T1
MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR
CHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE THE MOTOR AND EQUIPMENT
SCHEDULE FOR THE MOTOR DESCRIPTION AND ELECTRICAL REQUIREMENTS. THE
CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL.
EXAMPLE: MOTOR SF-1; 3 PHASE CONNECTION TO CIRCUITS 2, 4, 6.
1
#10
H1
ELECTRIC HEATER CONNECTIONS. THE HEATER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER "H". SEE THE HEATER SCHEDULE FOR
ELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A
NUMBER(S) ADJACENT TO THE HEATER. EXAMPLE: ELECTRIC BASEBOARD HEATER
TYPE "H1" CONNECTED TO CIRCUITS 7, 9.
TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING
THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE
DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE:
TRANSFORMER TYPE "T1".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF
RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION
CODES.
Date
ELECTRICAL DRAWINGS
E0.00
E0.01
E1.00
E2.00
ELECTRICAL SYMBOLS AND ABBREVIATIONS
ELECTRIC KEYPLAN
ELECTRIC PLAN
ELECTRICAL SCHEDULES
Comm:
152039
Date:
1/11/16
Drawn:
A. WELLENS
Check:
S. CHHUM
SPECIAL NOTE. SEE THE SPECIAL NOTES ON THAT SHEET FOR THE NOTE NUMBER
INDICATED IN THE HEXAGON.
CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4"
CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.
CONDUIT SHOWN WITH SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR PER SLASH
MARK IN 3/4" CONDUIT UNLESS A CONDUCTOR AND CONDUIT SIZE IS SHOWN ADJACENT
TO THE SLASH MARKS. SLASH MARK INDICATORS ARE: SHORT STRAIGHT=PHASE
CONDUCTOR, LONG STRAIGHT=NEUTRAL CONDUCTOR, SHORT BENT ENDED=SWITCH
LEGS, LONG STRAIGHT WITH A DOT=GROUND CONDUCTOR, CHEVRON=CATEGORY 6,
HALF CHEVRON=CATEGORY 3, TWIST=SHIELDED TWISTED PAIR, CONCENTRIC CIRCLE
AND DOT=COAX CABLE.
LPN-102
1,3,5
Description
ELECTRICAL
SYMBOLS AND
ABBREVIATIONS
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS
SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT
DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES
(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO
PANELBOARD LPN-102; CIRCUITS 1, 3, 5.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT
TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
Scale:
As indicated
E0.00
Num
1
2
3
4
5
6
7
8
9
10
GENERAL SHEET NOTES
A.
VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL OWNER
FURNISHED EQUIPMENT PRIOR TO ROUGH-IN.
B. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT OF
FIXTURES AND CONTROL OF DEVICES.
C. ALL WALLS AND FLOOR MOUNTED BACK BOXES AND JUNCTION
BOXES SHALL BE MOUNTED RECESSED.
D. GFCI RECEPTACLES SHALL BE WIRED TO PROTECT ONLY THE
DEVICES IN THAT OUTLET BOX. DOWNSTREAM DEVICES SHALL NOT
BE PROTECTED BY GFCI.
E. CIRCUIT NUMBERS SHOWN ARE FOR SCHEMATIC PURPOSES AND ARE
FOR DISTINGUISHING CIRCUITS. RECORD AS-BUILT CIRCUITING IN A
TYPED AND DATED PANELBOARD SCHEDULE. ROUTE CIRCUTING TO
SPARE 20A, 120V BREAKERS IN EITHER PANEL L1A OR L1B.
F. PROVIDE CONSTRUCTION LIGHTING AND POWER AS REQUIRED FOR
TEMPORARY ENCLOSURE. REFER TO DETAIL H7 ON SHEET A0.01
AND SECTION 1.11 OF SPECIFICATION 26 00 05 FOR MORE
INFORMATION.
G. WHEN CORE-DRILLING OF EXISTING FLOORS IS REQUIRED,
PERFORM XRAY SCAN AND COORDINATE EXACT LOCATION OF
HOLES WITH OWNER PRIOR TO START OF WORK.
H. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH
ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT
PRIOR TO START OF WORK.
A
E
E
D
CB
A
D
CB
A
1
1
2
2
MN
IH
G
F
G
F
1.
3
EX MSB
2 EX FACP
3
2.
3.
L1B L1A
6
4
4.
8
3 EX DATA RACK
7
PA2B
4
5
LA2A
LA2B
EX GYM
CONTROL BOX
G
1
5.
4
B
EX CARD READER
HEAD END
B
C
C
D
6.
7.
DF-5 6
DF-3 6
1
1
8.
5
2
3
9
5
2
3
C
D
MECHANICAL ROOM
2500 East 80th Street
Inver Grove Heights, MN 55076
Minnesota State Colleges
& Universities
30 E 7th St #350,
St Paul, MN 55101
KEYED SHEET NOTES
B
IH
IHCC ACTIVITIES
BUILDING PHASE ll EXERCISE ROOM
ADDITION
9.
EXISTING 120/208V, 225A SQUARE D NQ PANELS. CIRCUITING
ON THIS SHEET AND SHEET E1.00 REFER TO SPARE BREAKERS
IN PANEL LA2B UNLESS NOTED OTHERWISE. CORE DRILL FLOOR
AS REQUIRED TO FEED NEW LOADS ON LOWER LEVEL.
EXISTING HONEYWELL NOTIFIER FIRE ALARM CONTROL PANEL.
EXISTING DATA RACK AND FUTURE PA SYSTEM HEADEND. ROUTE
ALL CAT6 CABLING AND PA SPEAKER WIRING BACK TO THIS
LOCATION.
INSTALL GYMNASIUM DESTRATIFICATION FAN SPEED SWITCH
WITHIN EXISTING GYMNASIUM CONTROL PANEL. SPEED SWITCH
FURNISHED BY MECHANICAL. UTILIZE EXISTING LIVE VOLTAGE
CONDUIT FOR NEW WIRING.
EXISTING 120/208V, 225A SQUARE D NQ PANEL. PROVIDE
60A/3P AND 30A/30 BREAKER FOR NEW AIR HANDLER UNIT
(AHU-5). CORE DRILL FLOOR AS REQUIRED.
PROPOSED ROUTING FOR LOW VOLTAGE CABLING FROM
ADDITION TO DATA ROOM. PROVIDE FLOOR PROTECTION AND
REPLACE CEILING TILES WITH NEW TO REPLACE DAMAGED
TILES AS REQUIRED.
PROPOSED ROUTING FOR POWER FROM ADDITION TO PANELS
ABOVE. PROVIDE FLOOR PROTECTION AND REPLACE CEILING
TILES WITH NEW TO REPLACE DAMAGED TILES AS REQUIRED.
SURFACE MOUNT FIXTURE TO UNDERSIDE OF STAIRS. PAINT
CONDUIT AND BOX TO MATCH ADJACENT SURFACES. FIXTURE
TO BE ON 24/7. CONNECT TO NEAREST LIGHTING CIRCUIT
AHEAD OF SWITCHING.
PROVIDE PROTECTION OF GYM FLOORING TO ACOMMODATE
ELECTRICAL WORK. COORDINATE WITH OTHER TRADES.
4
4
REFER TO SHEET E1.00 FOR ADDITION
DF-4 8
D
5
6
DF-6 8
5
6
6
6
E6
A
LOWER LEVEL KEYPLAN
A
1/16" = 1'-0"
E
E2
UPPER LEVEL KEYPLAN
1/16" = 1'-0"
Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt
1/8/2016 4:34:12 PM
C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt
F
I hereby certify that this plan, specification or report was prepared by
me or under my direct supervision and that I am a duly Licensed
PROFESSIONAL ENGINEER
MINNESOTA
under the laws of the State of
BRADLEY R. JOHANNSEN
Date 12/04/15
43936
Registration Number
Revisions
Description
Date
Num
1
G
Comm:
152039
Date:
1/11/16
Drawn:
A. WELLENS
Check:
S. CHHUM
North
ELECTRIC KEYPLAN
E
H
Scale:
As indicated
E0.01
C
1
2
C
A
3
B B
4
5
C
C
A
6
B B
B
7
C
A
A
8
9
B
D
10
C
IHCC ACTIVITIES
BUILDING PHASE ll EXERCISE ROOM
ADDITION
D
2500 East 80th Street
Inver Grove Heights, MN 55076
D F
11
11
1
6
2
D
3
D
4
6
L
OS
3
B
7
D
4
4
CORRIDOR
A127
B
4
6
4
7
F
D
L
OS
MECH
A130B
L
OS
5
F
4
12
F
F
4
Da
Db
Dc 3
2
L
OS
4
5
A
2
a
a
4
L
OS
5
A
a
CORRIDOR
A127
D F
4
10 S
TYP
A
A
A
b
F
48"
15
13
36"AFF
48"
25
MECH
A130B
15
15
6
TYP
17
EM1
EM1
SD
S
2
EXERCISE
ROOM
A130
1
4
5
1
S
5
F
abc
11
B
SD
CP-1
A S PA
3
abc
15
2
E3
A
STORAGE
A130A
J
2
4
4
4
2
WEIGHT ROOM
A125
13
14
4
30 E 7th St #350,
St Paul, MN 55101
AHU-3
AHU-3
(SUPPLY) (RETURN)
2
A
2
b
b
15
7
9'-0"AFF
TYP
DF-1
PA
DF-2
19
19
8
TYP
2
17
9'-0"AFF
S
5
4
STORAGE
A130A
F
3
B
4
1
2
F
S S S
PT ES DC
MN
4
WEIGHT ROOM
A125
F
S
5
F
F D
WEIGHT ROOM
A125
D F
48"
1
CR
S
1
Minnesota State Colleges
& Universities
4
J
EXERCISE
ROOM
A130
F
D F
11
6
L
OS
7
C
9'-0"AFF
abc
L
OS
5
D
4
7
D
HA
5
S
L
OS
D
4
A
c
2
A
2
c
c
9
2
23
EM1
5
S
ES
D1
A.
E
Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt
1/8/2016 4:34:13 PM
C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt
F
SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
PHASES OF DEMOLITION AND CONSTRUCTION. COORDINATE
WITH GENERAL CONSTRUCTION.
B. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND
LIGHTING FIXTURES IN DEMOLITION AREAS UNLESS NOTED
OTHERWISE.
C. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES IN
WALLS TO BE DEMOLISHED. WALLS TO BE DEMOLISHED ARE
SHOWN DASHED. DISCONNECT AND REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO LAST REMAINING DEVICE.
FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO
REMAIN. COORDINATE AND VERIFY REQUIREMENTS WITH NEW
WORK IN AREA.
D. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS
ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES
ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER
DEMOLITION. MODIFY OR REPLACE AS REQUIRED.
E. FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/
DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY WIRING
ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES
ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO
REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS
REQUIRED.
F. DISCONNECT AND REMOVE LIGHT SWITCHES IN DEMOLITION
AREAS AS NECESSARY TO ACCOMMODATE NEW DOOR
CONFIGURATIONS.
G DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL
DEVICES AND BACK BOXES AS NECESSARY WHERE NEW WALL
CONSTRUCTION WILL INTERSECT AN EXISTING WALL.
FURNISH AND INSTALL CONDUIT AND WIRE AS REQUIRED FOR
CONTINUITY OF CIRCUIT(S).
H. FURNISH AND INSTALL BLANK COVER PLATES OVER ALL
EXISTING UNUSED OPENINGS.
I. COORDINATE ALL OUTAGES (POWER, TELEPHONE, FIRE ALARM,
ETC) WITH OWNER AT LEAST THREE WEEKS IN ADVANCE.
2.
3.
4.
5.
EXISTING 13.8 KV MEDIUM VOLTAGE BOX TO REMAIN. DEMOLISH
EXISTING FEEDER AND PROVIDE NEW FEEDER TO CHILLER
BUILDING TRANSFORMER TO ACCOMODATE BUILDING
ADDITION. PROVIDE (1) 3.5" CONDUIT WITH (3) 1/C#2, COPPER
15KV MV-105 CABLE WITH EPR 133% INSULATION, TAPE SHIELD
AND 1#2 GROUND CABLE AND (1) SPARE 3.5" CONDUIT. FIELD
VERIFY EXACT ROUTING AND DEPTH. BURY MINIMUM OF 36"
BELOW FINISHED GRADE. PROVIDE DETECTABLE 6" WIDE
ORANGE WARNING TAPE 12" BELOW GRADE. APPROXIMATELY
160' RUN TO TRANSFORMER LOCATED BEHIND CHILLER
BUILDING, FIELD VERIFY EXACT LENGTH.
DEMOLISH EXISTING 1" TELEPHONE AND 1" FIRE ALARM CIRCUITS
FROM ACTIVITIES BUILDING TO CHILLER BUILDING TO
ACCOMODATE BUILDING ADDITION. PROVIDE 1" CONDUIT WITH
CABLING TO MATCH EXISTING FOR BOTH. BURY MINIMUM OF
36" BELOW FINISHED GRADE. PROVIDE DETECTABLE 6" WIDE
ORANGE WARNING TAPE 12" BELOW GRADE. APPROXIMATELY
160' RUN TO CHILLER BUILDING, FIELD VERIFY EXACT LENGTH.
DEMOLISH EXISTING EXTERIOR LIGHT FIXTURE. EXTEND EXISTING
CIRCUIT AND SWITCHING AS REQUIRED FOR NEW EXTERIOR
DOWNLIGHTS.
BASE BID: INTERCEPT AND REROUTE TELEPHONE AND FIRE
ALARM CONDUIT ON SOUTHERN WALL AS REQUIRED TO
ACCOMMODATE NEW DOOR INSTALLATION. PROVIDE NEW
WIRING SPLICED FROM NEAREST UPSTREAM DEVICE. DEDUCT
ALTERNATE #3: NO DOOR TO BE INSTALLED. EXISTING
TELEPHONE AND FIRE ALARM CONDUIT TO REMAIN AS IS.
DEMOLISH CONNECTION TO MOTORIZED HANDICAP DOOR
MOTOR AND ASSOCIATED PUSH PADDLES.
S
S
5
F
12'-0"AFF
WP
3
S S
PT DC
S
ES
6
HA
S
CR
A
LIGHTING PLAN
D7
1/8" = 1'-0"
GENERAL SHEET NOTES
KEYED SHEET NOTES
1.
12'-0"AFF
6
D4
GENERAL SHEET NOTES
9'-0"AFF
S
23
S S
PT DC
A
1/8" = 1'-0"
17
9
6
A
DEMOLITION PLAN
17
HA
6
D1
S
21
4
5
6
9'-0"AFF
CUH-1
2
D
44'' AFF 15
VESTIBULE HA
A128
4
6
D1
15
9'-0"AFF
17
A
J
VESTIBULE
A128
6
L
OS
5
4
E1
D
abc
S
4
S
17
B
A.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
WIRING ALL ELECTRICAL ITEMS SHOWN ON THIS DRAWING.
B. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE
BOTTOM OF THE FIXTURES UNLESS INDICATED OTHERWISE.
C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING
HEIGHTS OF EXTERIOR LIGHTING FIXTURES.
D. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR
SLAB UNLESS INDICATED ON PLAN BY DASHED CONDUIT.
E. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT
OF FIXTURES AND CONTROL OF DEVICES.
F. EXTEND EXISTING EXIT SIGN CIRCUIT TO NEW EXIT SIGNS.
G. ALL CIRCUITING SHOWN REFERS TO PANEL LA2B, SHOWN ON
SHEET E0.01.
H. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH
ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT
PRIOR TO START OF WORK.
POWER AND SYSTEMS PLAN
1/8" = 1'-0"
KEYED SHEET NOTES
1.
2.
3.
4.
5.
6.
7.
HIGH BAY LIGHT FIXTURES IN PERFORMANCE STUDIO TO BE
HUNG BY AIRCRAFT CABLE FROM UNISTRUT BETWEEN JOISTS.
DO NOT SUPPORT FIXTURE FROM ROOF DECK. LIGHTS TO BE
FLUSH WITH BOTTOM OF JOIST AND FOLLOW SLOPED CIELING,
RANGING FROM APPROXIMATELY 14'-0" AFF TO 23'-0" AFF.
EXTERIOR RECESSED DOWNLIGHTS TO BE MOUNTED IN SOFFIT.
CONNECT TO EXISTING EXTERIOR CIRCUITING AND CONTROLS.
PROVIDE 0-10V DIMMER SWITCHES WITH ASSOCIATED ROOM
CONTROLLERS (WATTSTOPPER DLM SYSTEM OR APPROVED
EQUAL). INTERFACE WITH OCCUPANCY SENSORS.
PROVIDE EMERGENCY INVERTER MOUNTED ON WALL TIGHT TO
CEILING FOR EXTERIOR EMERGENCY DOWNLIGHT. INVERTER
TO BE 100W MINIMUM, SELF DIAGNOSTICS, FUSED OUTPUT,
BROWN-OUT SENSING, LEAD CALCIUM BATTERY, MOMENTARY
TEST SWITCH (BODINE ELI-100 SERIES OR APPROVED EQUAL).
PROVIDE HIGH BAY TYPE OCCUPANCY SENSOR (SENSOR SWITCH
CM6 OR APPROVED EQUAL). SENSOR TO BE PIR, MANUAL
ON/AUTO OFF, WITH 30 MINUTE TIME DELAY. MOUNT TO
BOTTOM OF BAR JOISTS.
PROVIDE OCCUPANCY SENSOR (WATTSTOPPER DT-305 OR
APPROVED EQUAL). SENSOR TO BE DUAL TECHNOLOGY, AUTO
ON/AUTO OFF, WITH 30 MINUTE TIME DELAY.
INTERCONNECT SENSORS TOGETHER FOR CONTROL OF
CORRIDOR AND EXERCISE ROOM ENTRY WAY.
GENERAL SHEET NOTES
A.
VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL
OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH-IN.
B. CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING INTENT
OF FIXTURES AND CONTROL OF DEVICES.
C. ALL WALLS AND FLOOR MOUNTED BACK BOXES AND JUNCTION
BOXES SHALL BE MOUNTED RECESSED.
D. GFCI RECEPTACLES SHALL BE WIRED TO PROTECT ONLY THE
DEVICES IN THAT OUTLET BOX. DOWNSTREAM DEVICES SHALL
NOT BE PROTECTED BY GFCI.
E. CIRCUIT NUMBERS SHOWN ARE FOR SCHEMATIC PURPOSES AND
ARE FOR DISTINGUISHING CIRCUITS. RECORD AS-BUILT
CIRCUITING IN A TYPED AND DATED PANELBOARD SCHEDULE.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING
ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS, EXCEPT
WHERE NOTED OTHERWISE.
G. INSTALL CONDUIT WITH NO MORE THAN (2) 90° BENDS BETWEEN
PULL BOXES, AND NO MORE THAN 100'-0" BETWEEN PULL
BOXES. PULL BOXES SHALL BE INSTALLED FOR STRAIGHT THRU
PULLS ONLY.
H. ALL COMMUNICATIONS CABLES SHALL BE INSTALLED IN
CONDUIT, CABLE TRAY, OR SUPPORTED BY CABLE HOOKS.
PROVIDE BUSHINGS AT THE ENDS OF ALL CONDUIT WHERE
STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAY. PROVIDE CABLE HOOKS ABOVE
ACCESSIBLE CEILINGS FOR CABLE INSTALLATION WHERE NOT
INSTALLED IN CONDUIT OR CABLE TRAY.
I. PROVIDE AND INSTALL HONEYWELL H4D2F SECURITY CAMERAS
AT LOCATIONS SHOWN. VERIFY EXACT MOUNTING LOCATIONS
AND ORIENTATIONS WITH OWNER PRIOR TO INSTALLATION.
J. PROVIDE AND INSTALL THINLINE II HID CARD READERS AT
LOCATIONS SHOWN. CONNECT TO HONEYWELL PRO 2200 CARD
READER HEAD END LOCATED IN TECH CLOSET A114.
K. ALL CIRCUITING SHOWN REFERS TO PANEL LA2B, SHOWN ON
SHEET E0.01.
L. ALL EXPOSED CONDUIT AND BOXES TO BE PAINTED TO MATCH
ADJACENT SURFACES. VERIFY EXACT COLOR WITH ARCHITECT
PRIOR TO START OF WORK.
KEYED SHEET NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
FITNESS ROOM SOUND SYSTEM HEAD END RACK MOUNTED ON
WALL WITH AUXILIARY AND MICROPHONE INPUTS. REFER TO
DETAIL AND SPECIFICATIONS FOR MORE INFORMATION.
COORDINTATE EXACT LOCATION AND MOUNTING HEIGHT WITH
OWNER PRIOR TO INSTALLATION. PROVIDE DEDICATED 20A,
120V CIRCUIT. CONNECT TO EXISTING SOUND SYSTEM RACK.
(LOCATED IN GYMASIUM)
PROVIDE CONNECTION TO SPEED SWITCH FOR EXERCISE ROOM
FANS DF-1 AND DF-2. COORDINATE LOCATION WITH
MECHANICAL PRIOR TO INSTALLATION.
PROVIDE WEATHERPROOF APPLIANCE ABOVE FIRE
DEPARTMENT CONNECTION.
PROVIDE 120V CONNECTION TO EXTERIOR HEAT CHASE.
COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
MECHANICAL.
PROVIDE ROUGH-IN FOR DOOR SECURITY DEVICES AND 120V
CONNECTION. SEE DETAIL H8 ON SHEET E2.00 FOR DOOR
SECURITY DETAIL.
PROVIDE 1-GANG BOX WITH 3/4" CONDUIT AND (1) CATE5
CABLE TO DATA RACK FOR CAMERA. TYPICAL FOR ALL.
PROVIDE 1-GANG BOX WITH 1" CONDUIT AND SPEAKER WIRING
BACK TO AV RACK. VERIFY EXACT LOCATION AND MOUNTING
HEIGHT WITH OWNER PRIOR TO ROUGH-IN. TYPICAL FOR ALL.
PROVIDE 1-GANG BOX WITH 1" CONDUIT AND (1) CAT6 CABLE
TO DATA RACK FOR WIRELESS ACCESS POINT (WAP). WAP
PROVIDED BY OWNER. TYPICAL FOR ALL.
PROVIDE ELECTRICAL CONNECTIONS TO HANDICAP DOOR
MOTOR AND ASSOCIATED PUSH PADDLES.
PROVIDE PA SPEAKER TO MATCH EXISTING. PROVIDE WIRING
BACK TO PA SPEAKER AMPLIFER IN DATA RACK. TYPICAL FOR
ALL.
BASE BID: PROVIDE DOOR HOLDS. DEDUCT ALTERNATE #4:
DELETE DOOR HOLDS.
BASE BID: PROVIDE DOOR HOLD. DEDUCT ALTERNATE #3:
DELETE DOOR HOLD.
PROVIDE WIRING FOR EXISTING PA SPEAKERS IN WEIGHT ROOM
AND ROUTE TO FITNESS SOUND SYSTEM HEAD END RACK.
PROVIDE VOLUME CONTROL FOR SPEAKERS IN WEIGHT ROOM.
PROVIDE WALLPLATE WITH 3.5MM INPUT AUDIO JACK AND
VOLUME CONTROL FOR SPEAKERS IN EXERCISE ROOM.
CONNECT JACK TO SOUND SYSTEM HEAD END RACK.
I hereby certify that this plan, specification or report was prepared by
me or under my direct supervision and that I am a duly Licensed
PROFESSIONAL ENGINEER
under the laws of the State of
MINNESOTA
BRADLEY R. JOHANNSEN
Date 12/04/15
43936
Registration Number
Revisions
Description
Date
1
G
Comm:
152039
Date:
1/11/16
Drawn:
A. WELLENS
Check:
S. CHHUM
North
ELECTRIC PLAN
E
Num
H
Scale:
1/8" = 1'-0"
E1.00
1
2
3
4
5
6
7
8
9
10
LUMINAIRE SCHEDULE
LETTER
LUMINAIRE TYPE
LAMPS/WATTS
VOLT
MOUNTING
A
A
MICROPHONE INPUTS
A
2x4 LED HIGH BAY
M
LED, 85 CRI
4000K
MIN 19000 LUMENS
MVOLT
AIRCRAFT CABLE
LENS / LOUVER
LUMINAIRE DESCRIPTION
MANUFACTURER & SERIES
WIDE DISTRIBUTION
NO LENS
EXTERNAL WIREGUARD
FULL BODY CONSTRUCTION
0-10V DIMMING DRIVERS
WHITE FINISH
5 YEAR WARRANTY
DLC QUALIFIED
EQUAL OF LITHONIA
EQUAL OF COLUMBIA
EXERCISE ROOM
SPKR
DEVICE TO OVERWRITE
FITNESS SOUND SYSTEM
WHEN PA SYSTEM IS ACTIVE
SPKR
SPKR
SPKR
SPKR
2x4 VOLUMETRIC LED TROFFER
DIMMABLE
6 INCH ROUND LED DOWNLIGHT
LED, 85 CRI,
4000K
MIN 1000 LUMENS
MVOLT
RECESSED (GRID)
WHITE TRANSLUCENT ACRYLIC LENS
SPECULAR ALUMINUM REFLECTOR
0-10V DIMMING DRIVER
WHITE FINISH
5 YEAR WARRANTY
DLC QUALIFIED
SOFT SATIN REFLECTOR
MATCHING FLANGE
0-10V DIMMING DRIVER, 5%
5 YEAR WARRANTY
ENERGY STAR QUALIFIED
SPKR
2500 East 80th Street
Inver Grove Heights, MN 55076
OR APPROVED EQUAL
LITHONIA 2RTL4 SERIES
ALLOWANCE - $184/FIXTURE
Minnesota State Colleges
& Universities
38
30 E 7th St #350,
St Paul, MN 55101
JUNO L6 SERIES
D
MULTICHANNEL
AMPLIFIER
WIRELESS MIC
RECEIVERS
MN
B
LED, 85 CRI
4000K
4000 LUMENS
NOTES
152
METALUX HBLED SERIES
A
M
WATTS
MVOLT
RECESSED (GRID)
PRESCOLITE LF6LED SERIES
SPKR
SPKR
SPKR
SPKR
SPKR
18
LITHONIA LDN6 SERIES
ATLANTIC LED6 SERIES
WEIGHT ROOM
MIXER
IHCC ACTIVITIES
BUILDING PHASE ll EXERCISE ROOM
ADDITION
SPKR
D1
CD/MP3 PLAYER
6 INCH ROUND LED DOWNLIGHT
WET LISTED
LED, 80 CRI,
4000K
MIN 1000 LUMENS
MVOLT
RECESSED
(EXTERIOR
FLANGE)
GOTHAM EVO SERIES
0-10V DIMMING DRIVER, 5%
5 YEAR WARRANTY
ENERGY STAR QUALIFIED
WET LISTED
REGRESSED DEAD FRONT ACRYLIC LENS
MATCHING FLANGE
PRESCOLITE LF6LED SERIES
18
ATLANTIC LED7 SERIES
OR APPROVED EQUAL
COLUMBIA CSR4 SERIES
B
F
CONTROL
PANEL
VOLUME
CONTROL
VOLUME
CONTROL
C3
ETHERNET
CONNECTION
Rack-Mounted Equipment Shall Include:
(1) Shure ULXS 124/85 wireless combo system.
(1) Shure UA 507 antenna.
(1) Shure UA 221.
(1) Shure SM58 CN wired mic.
(1) Middle Atlantic EWR 10-22 wall rack.
(1) BSS Blu-100 DSP.
(1) Crown DCI 2/600 power amplifier
(2) Rapco/Horizon Blox 2 computer/MP3 interface.
FITNESS ROOM SOUND SYSTEM DETAIL
4 FOOT INDUSTRIAL STRIP
(2) F32T8/841
MVOLT
CHAIN HUNG
WHITE FINISH
SYMMETRIC REFLECTOR
WIREGUARD
NO LENS
10% UPLIGHT
LITHONIA LA SERIES
62
COOPER IAF SERIES
OR APPROVED EQUAL
E1
E3
EM1
EXIT SIGN
SINGLE FACE
EXIT SIGN
SINGLE FACE
EMERGENCY HEADS
EMERGENCY BUGEYE
LED
LED
LED
MVOLT
MVOLT
MVOLT
UNIVERSAL MOUNT
UNIVERSAL MOUNT
SURFACE
STENCIL FACE
RED LETTERS
STENCIL FACE
RED LETTERS
LITHONIA LE SERIES
NICKEL CADMIUM BATTERY
SELF DIAGNOSTICS
WHITE CAST ALUMINUM HOUSING
INVISIBLE CHEVRON ARROW
DUAL-LITE SE SERIES
SURE-LITES CX SERIES
1
10
1
3
1
OR APPROVED EQUAL
SURE-LITES APC SERIES
NICKEL CADMIUM BATTERY
SELF DIAGNOSTICS
WHITE CAST ALUMINUM HOUSING
INVISIBLE CHEVRON ARROW
OR APPROVED EQUAL
LITHONIA ELM2-LED SERIES
NICKEL CADMIUM BATTERY
SELF DIAGNOSTICS
ADJUSTABLE HEADS
10
SURE LITES LED SERIES
DUAL LITE LZ SERIES
NTS
OR APPROVED EQUAL
G
4 FOOT LED WALL BRACKET
C
LED, 85 CRI,
4000K
MIN 4000 LUMENS
MVOLT
SURFACE
LITHONIA WL4 SERIES
WHITE FINISH
SURFACE CONDUIT
PROVISIONS
IMPACT RESISTANT LENS
40
OR APPROVED EQUAL
LUMINAIRE SCHEDULE GENERAL NOTES
A. FLUORESCENT BALLASTS SHALL BE ELECTRONIC PROGRAMMED START UNLESS NOTED OTHERWISE.
B. FOR LINEAR FLUORESCENT LAMPS PROVIDE ROTARY LOCKING LAMP SOCKETS.
C. WHEN DIMMING IS NOT INDICATED ON PLANS FOR LUMINAIRES WITH 0-10V DIMMING, LEAVE 0-10V WIRING DISCONNECTED AND CAPPED FOR FUTURE USE.
D. MOUNTING HEIGHT IS TO BOTTOM OF FIXTURE.
E. IN ADDITION TO THE LUMINAIRES AND CONTROLS SHOWN ON DRAWINGS, THE FOLLOWING LUMINAIRES SHALL BE PROVIDED (FURNISH AND INSTALL) WHERE DIRECTED BY
ENGINEER DURING CONSTRUCTION. INSTALLATION OF LUMINAIRES SHALL INCLUDE 25’ OF WIRING AND ASSOCIATED RACEWAY AS REQUIRED. FOR EACH LUMINAIRE NOT
INSTALLED TURN LUMINAIRE OVER TO THE OWNER FOR SPARE MATERIALS AND PROVIDE A LABOR CREDIT OF $100 PER UNINSTALLED FIXTURE.
TYPE E1: (2) SPARES.
LUMINAIRE SCHEDULE NUMBERED NOTES
1. PROVIDE WIREGUARD (WG) WHERE INDICATED ON PLANS
D
E
Central: \\heasrvr.hea.office\HEA\COL-IHCC\152039-Activities Bldg Ph 2\06_ELEC\Revit\152039 Electric (Central) 2014.rvt
1/8/2016 4:34:13 PM
C:\Users\jmcdonald\Documents\152039 - Electric (Central) 2014_jmcdonald.rvt
F
I hereby certify that this plan, specification or report was prepared by
me or under my direct supervision and that I am a duly Licensed
PROFESSIONAL ENGINEER
under the laws of the State of
MINNESOTA
BRADLEY R. JOHANNSEN
Date 12/04/15
43936
Registration Number
Revisions
Description
PROVIDE 120V
CONNECTION
1/2"C FOR DOOR
CONTACT
Date
1
G
DOUBLE GANG BOX WITH
COVER PLATE, LOCATED
ABOVE ACCESSIBLE
CEILING.
1/2"C FOR POWER
TRANSFER HINGE.
1/2"C TO CARD READER
S
DC
PROVIDE REMOVABLE
FOAM IN DOOR FRAME
TO ALLOW FUTURE
DEVICE INSTALLATION
AND ACCESS TO
CONDUIT AFTER GROUT
INSTALLED INTO DOOR
FRAME.
S
PT
S
ES
42"
SINGLE GANG BOX FOR CARD
READER
S
CR
Comm:
152039
Date:
1/11/16
Drawn:
A. WELLENS
Check:
S. CHHUM
ELECTRICAL
SCHEDULES
NOTE:
E
A.
PROVIDE BLANK STAINLESS
COVERPLATE ON ALL UNUSED
BACKBOXES.
B.
BUSH ALL CONDUIT ENDS.
H
Scale:
H9
SECURITY RACEWAY DETAIL
NTS
Num
NTS