FIRE PROTECTION for MUSEUM OF ISLAMIC ARTS Doha, Qatar A

advertisement
1 June 2004
Base Building — Issued for Construction
SECTION 15500 — FIRE PROTECTION
for
MUSEUM OF ISLAMIC ARTS
Doha, Qatar
Architect
I.M. Pei, Architects
88 Pine Street
New York, New York 10005 USA
Structural Consulting Engineers
Leslie E. Robertson Associates
30 Broad Street
New York, New York 10004 USA
Mechanical/Electrical/Vertical Transportation Consulting Engineers
Jaros, Baum & Bolles
80 Pine Street
New York, New York 10005 USA
SECTION 15500
FIRE PROTECTION
TABLE OF CONTENTS
Article
Title
Page
PART 1 - GENERAL
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19
1.20
1.21
1.22
1.23
1.24
1.25
1.26
1.27
General Requirements
Work of Other Sections
Description of Systems
Notice to Bidders
Subcontractor/Engineer
General
Coordination
Composite Drawings
General Construction Drawings
Shop Drawings and Consulting Fire Protection Engineer’s Review
Record Drawings
Codes and Permits
Protective Painting
Identification of Systems
Tools
Sleeves
Operating and Maintenance Instructions
Repair and Maintenance Parts
Subcontracts
Engineering Reference Points
Guarantee
Cutting and Patching
Rubbish Removal
Cleaning and Protection
Unit Prices
Submittals
Approved Manufacturers
1
1
1
3
3
3
4
5
7
7
12
13
13
13
14
14
15
15
16
16
16
17
17
17
18
18
19
PART 2 - PRODUCTS
2.01
2.02
2.03
2.04
2.05
2.06
2.07
Materials of Piping Systems
Hangers, Inserts and Pipe Supports
Seismic Restraints
Valves
Insulation
Sprinkler Heads
Alarm Devices
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
20
24
25
25
26
27
27
15500-TC-1
Fire Protection
Issued for Construction
1 June 2004
TABLE OF CONTENTS (Continued)
Article
2.08
2.09
2.10
2.11
2.12
2.13
2.14
2.15
2.16
Title
Sprinkler Drains
Signs
Fire Standpipe System/Sprinkler System Appurtenances
Fire Pump Installation
Fire Pump Controller
Jockey Pump Controller
Electric Motors
Preaction Sprinkler System
FM-200 Fire Suppression System
Page
28
29
29
30
31
34
35
35
45
PART 3 - EXECUTION
3.01
3.02
3.03
General Installation
Tests
Pipe and Material Finishes
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
52
53
55
15500-TC-2
Fire Protection
Issued for Construction
1 June 2004
SECTION 15500
FIRE PROTECTION
PART 1 - GENERAL
1.01
1.02
GENERAL REQUIREMENTS
A.
Work of this Section, as shown or specified, shall be in accordance with
the requirements of the Contract Documents.
B.
Drawings, general provisions of Contract, and General Conditions all
form a part of this Section of the Contract Documents.
C.
Where General Conditions clauses are repeated in these Specifications, it
is to call special attention to them, or as a further qualification. No
General Conditions clause referring to work of this Section shall be
considered waived unless specifically stated herein.
WORK OF OTHER SECTIONS
A.
1.03
The following items of work will be done under Specifications of other
Trades:
1.
Funnel drains for drain and test purposes.
2.
General cutting and patching of openings, except as called for in
detail hereinafter.
3.
All finished painting of exposed pipes and apparatus.
4.
All electrical wiring, including all wiring from the alarm
switches to alarm panels, central stations, and alarm devices.
5.
Concrete bases and supports for pumps, pneumatic tanks, gravity
tanks and compressors.
DESCRIPTION OF SYSTEMS
A.
Provide a combination fire standpipe-sprinkler system to provide fire
protection for the entire building, including but not limited to the
following:
1.
Extension from the exterior yard main, provided under another
Section of the Specifications, to the fire protection system.
2.
Provide a complete combination fire standpipe-sprinkler system
in accordance with the Building Code of Qatar, NFPA Standards
and the rules of all local authorities having jurisdiction.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-1
Fire Protection
Issued for Construction
1 June 2004
3.
4.
The fire standpipe portion of the system shall include:
a.
Cross-connections between water supply(ies), siamese
connections and fire pump suction and discharge
connections.
b.
Risers serving hose reels and sprinkler connections at
each floor and where indicated on the drawings.
c.
Fire pumps (one [1] electric and one [1] diesel driven)
and controls.
d.
Hose stations where indicated.
Sprinkler systems shall be supplied from the fire standpipe risers
or distribution mains. Systems shall include:
a.
A shutoff valve or shutoff valve and pressure reducing
valve as indicated on the drawings, flow switch and a
drain/test connection for each valved section.
b.
A vertical drain riser serving each floor control valve.
c.
Preaction alarm valves and piping supplying distribution
systems in the Gallery and other areas indicated on the
Contract Documents.
d.
FM-200 fire suppression system for the electric
substation, Transformer Room, Telephone Main Switch
Room, and museum display cabinets and as indicated on
the drawings, complete with FM-200 container,
detectors, piping, alarms, control panel and piping.
e.
The sprinkler systems shall be hydraulically calculated
to the following parameters:
1)
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Hazard Classification
a)
Museum/Office Areas: Light Hazard,
4.1 lpm/sq.m. over 140 sq.m.
b)
Storage, Mechanical Equipment Rooms,
Shops: Ordinary Hazard, 6.1 lpm/sq.m.
over 140 sq.m.
c)
Loading Dock and Parking Garage:
Ordinary Hazard, 6.1 lpm/sq.m. over
140 sq.m.
d)
Water Curtains: 0.3 lineal m.
15500-2
Fire Protection
Issued for Construction
1 June 2004
5.
1.04
1.05
1.06
Include all pipe, fittings, mains, risers, branches, valves, alarm
valves, alarm switches, ladders, signs, siamese connections,
protective painting, test connections, sprinkler heads, drains,
tests, alarm panels, automatic booster pumps, automatic fire
pumps, etc., in full accordance with Underwriters' and municipal
requirements.
NOTICE TO BIDDERS
A.
Before submittal of bid, examine all drawings, specifications, addenda,
alternates, special conditions, equipment furnished by others and
installed by this Subcontractor, and all other bidding documents of all
Sections of this project, verify all governing conditions at the site, and
become fully informed as to the extent and character of the work
required, as well as its relation to other work in the building. Submittal
of a bid is an agreement to all requirements of the Contract Documents,
and no consideration will be granted for any claimed misunderstanding
thereof.
B.
Submittal of a bid is deemed a representation by the bidder that it is
qualified in all respects properly to perform the work for which it is
bidding and has experience with similar work. Bidders are deemed to be
aware, on the basis of their background and experience, of materials
which may be required in the discharge of their responsibilities, even
though unspecified. For example, claims for extras for unspecified
shoring or supporting materials will not be considered if the need for
such materials would have been reasonably obvious to bidders skilled
and experienced in the work to be done, and the submittal of a bid shall
be deemed a waiver of any such claims.
SUBCONTRACTOR/ENGINEER
A.
Throughout these Specifications, the term “this Subcontractor” shall be
understood to mean the individual, partnership or corporation to whom
has been awarded the Contract for providing the Heating, Ventilating and
Air Conditioning Work.
B.
Throughout these Specifications, the term “Engineer” shall be
understood to mean the Assistant Director Building Engineer
Department, in the Ministry of Municipal Affairs and Agriculture, or any
other person approved by the government.
GENERAL
A.
Execute the work in the best and most thorough manner and to the
satisfaction of the Engineers and Consulting Engineers, who will jointly
interpret the meaning of the drawings and specifications and shall have
the power to reject any work and materials which, in their judgment, are
not in full accordance therewith.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-3
Fire Protection
Issued for Construction
1 June 2004
1.07
B.
Make every effort to furnish all equipment of any equipment type (such
as motors, motor controls, pumps, valves, etc.) from one manufacturer.
C.
Manufacturers of all equipment shall have representatives, a service
department, factory trained servicemen and spare parts stocked in Qatar.
Manufacturers not meeting this requirement will not be accepted or
approved.
D.
Any equipment or material substitution that is constructed to a different
national standard than that specified or implied shall be accompanied by
full supporting technical data confirming that the alternative standards
meet or exceed the specified standard. It is the intent of this
Specification to encourage bidding of acceptable equipment; however,
the burden of proof concerning acceptability is on the alternative product
or manufacturer.
E.
The drawings show the various piping and ductwork systems
schematically. No added compensation will be permitted for variations
due to field conditions, and final coordination by the various
Subcontractors.
F.
All information contained within this Specification is intended to set
forth the minimum requirements for this project. In the event local and
governmental Codes, technical references, ordinances, guidelines and
regulations (as hereinafter discussed) exceed the equipment and/or
products that are specified herein, this Subcontractor shall provide, at no
additional cost to the Owner, the better quality equipment and products
(and any associated labor) accordingly.
COORDINATION
A.
Certain materials will be furnished, installed, or furnished and installed,
under other Sections and Contracts. Examine the Contract Documents to
ascertain these requirements.
B.
Carefully check space requirements with other Trades to insure that all
material can be installed in the spaces allotted thereto. Finished
suspended ceiling elevations are indicated on the general construction
drawings.
C.
Transmit to Trades doing work of other Sections all information required
for work to be provided under their respective Sections (such as fresh
water connections, drains, compressed air outlets, foundations, electric
wiring, access doors, steam connections, and the like) in ample time for
installation.
D.
Wherever this Subcontractor's work interconnects with work of other
Subcontractors, this Subcontractor shall coordinate his work with these
Subcontractors to insure that all Subcontractors have the information
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-4
Fire Protection
Issued for Construction
1 June 2004
necessary so that they may properly install all the necessary connections
and equipment. Identify all work items (valves, flow detectors, etc.) in
an approved manner in order that the Ceiling Trade may know where to
install access doors and panels.
1.08
E.
Caution men both verbally and in writing as to the dangers involved in
doing work within or adjacent to electrical closets on various floors, the
Mechanical Rooms and the Switchboard Rooms, due to dangers caused
by presence of high voltages and currents present in these spaces.
F.
Furnish and set all sleeves for passage of pipes through structural
masonry and concrete walls and floors and elsewhere as will be required
for the proper protection of each pipe passing through building surfaces.
Coordinate this work with the Contractor in order to properly expedite
and perform this work.
G.
Provide required supports and hangers for piping and equipment, so that
loading will not exceed allowable loadings of structure. Submittal of a
bid shall be deemed a representation that the Subcontractor submitting
such bid has ascertained allowable loadings and has included in his
estimates the costs associated in furnishing required supports.
H.
Field drilling, cutting and/or reinforcing of holes in structural metal deck
required for work under this Section shall be coordinated through the
Contractor and approved by the Structural Consulting Engineer. All
such drilling, cutting and reinforcing costs shall be borne by this
Subcontractor.
I.
Due to the type of the installation, a fixed sequence of operation is
required to properly install the complete systems. It shall be the
responsibility of this Subcontractor to coordinate, protect and schedule
his work with other Trades in accordance with the construction sequence.
J.
Architectural drawings shall be checked for ceiling height requirements.
COMPOSITE DRAWINGS
A.
The coordination of the Mechanical and Electrical Trades (i.e., heating,
ventilating and air conditioning, plumbing, electrical, vertical
transportation and fire protection work) with each other and with the
interfaced Structural and Architectural Trades shall be accomplished by
an “overlay” process by which the final location of the various trades
work shall be overlaid onto reproducible Composite Drawings that
originate with the Heating, Ventilating and Air Conditioning
Subcontractor. This overlay process shall take place to meet the time
schedule of the project as set forth by the Owner or his designated
representatives.
B.
Coordination of work shall include, without additional cost to the Owner,
the preparations of the composite drawing by each Subcontractor, as
well as the necessary re-routing and minor relocation of work to
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-5
Fire Protection
Issued for Construction
1 June 2004
accommodate the detailed job requirement and to clear architectural
features and building structural elements. The Composite Drawings shall
be on mylar at a scale sufficient to clearly describe all conditions, but not
less than a scale of 1:50. The background mylar shall be prepared by the
Heating, Ventilating and Air Conditioning
Subcontractor at no
additional cost to the Owner. It shall be based on the erection drawings
as prepared by the Structural Steel and Concrete Subcontractors. The
base drawings, after being prepared by the Heating, Ventilating and Air
Conditioning Subcontractor, shall then sequentially have the work of the
Plumbing Contractor, Electrical Contractor and Fire Protection
Contractor added by the distribution of the drawings to these
Subcontractors, who will add their respective work.
C.
In preparing the Composite Drawings, minor changes in duct, pipe or
conduit routings that do not affect the intended function may be made as
required to avoid space conflicts, when mutually agreed, but items may
not be resized or exposed items relocated without the Consulting
Engineer’s approval. No changes shall be made in any wall or chase
locations, ceiling heights, door swings or locations, window or other
openings, or other features affecting the function or aesthetic effect of the
building. The drawing shall indicate all ductwork, grilles, registers,
diffusers, dampers, terminal units, coils, smoke detectors, piping, valves,
sprinkler heads, smoke detectors, light fixtures, access requirements,
access doors, etc. The drawing shall permit the installation of lights and
diffusers at any location on any office story without relocating of
horizontal duct runs or sprinkler piping. If conflicts or interference
require interpretations of the Contract Documents, the Engineer and the
Consulting Engineer’s clarifications shall be obtained. Each Trade shall
use a different color pencil for work on the coordination drawing.
D.
After any conflicts or interferences are resolved, the composite mylar
drawings shall then be signed and dated by each of the Subcontractors,
indicating their awareness of the agreement with the indicated routings
and layouts and their interrelationship with the adjoining or contiguous
work of all Contracts. The drawings shall be maintained in a current
state by the Subcontractors. Thereafter, no unauthorized deviations will
be permitted.
E.
The original composite mylar drawings signed by all Subcontractors
shall be retained by the Subcontractor and be available for examination
and reference by the Owner, Engineer and Consulting Fire Protection
Engineer at any time. Furthermore, copies of these originals shall be
provided at any time if requested by the Engineer.
F.
The Composite Drawings shall not substitute for a Subcontractor’s shop
drawings for the respective Trades which shall be submitted to the
Engineer. The shop drawings, required by Article 1.10, shall accurately
record the agreed Composite Drawings as detailed for the respective
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-6
Fire Protection
Issued for Construction
1 June 2004
Trade and shall only be submitted for approval after the completion of
these Composite Drawings.
1.09
1.10
GENERAL CONSTRUCTION DRAWINGS
A.
This Subcontractor shall produce General Construction Drawings
showing all bases, holes, openings, chases and other general construction
work requirements associated with the work of his Trade. The execution
of the general construction work will be by others.
B.
Any preliminary general construction work and structural information
already provided by the Consulting Fire Protection Engineer shall be
confirmed by this Subcontractor and incorporated into his own General
Construction Drawings.
C.
General Construction Work Drawings shall be fully detailed and
dimensioned and this Subcontractor shall be solely responsible for their
accuracy.
D.
The drawings shall be fully coordinated with all other services and the
structure. This Subcontractor shall work in conjunction with other
Subcontractors to ensure that the drawings are fully coordinated and that
other Subcontractors’ works have been taken fully into account.
E.
The submission of General Construction Drawings shall be carried out
strictly in accordance with a detailed project schedule prepared by the
Owner or the Owner’s Representative to eliminate any supplemental
work by the General Subcontractor.
F.
If in the event of any general construction work being omitted, carried
out incorrectly, or out of sequence, due to inaccuracies in the General
Construction Drawings or because they have not been provided in
accordance with the agreed project schedule, this Subcontractor shall be
held responsible for the cost of all necessary remedial works.
G.
General Construction Work Drawings shall be subject to the same
submission, commenting and issue procedures as detailed in this
Specification for the Shop Drawings.
H.
All General Construction Work Drawings used by site personnel shall
bear a Consultant’s review stamp.
SHOP DRAWINGS AND CONSULTING
FIRE PROTECTION ENGINEER’S REVIEW
A.
Before the installation of any equipment or material by this
Subcontractor, full Shop Drawings, as detailed hereinbelow, shall be
submitted for approval by the Consulting Fire Protection Engineer. All
Shop Drawings shall be submitted by the process approved by the
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-7
Fire Protection
Issued for Construction
1 June 2004
Owner. The Shop Drawings shall be submitted in sets: one in English,
and one in Arabic.
B.
The Consulting Fire Protection Engineer will review shop drawings and
samples for conformance with the design concept of the project and the
information contained in the Contract Documents. The Consulting Fire
Protection Engineer’s review of shop drawings and samples is only for
the convenience of the Owner in following the work and does not relieve
the Subcontractor of responsibility for deviations from the requirements
of the Contract Documents. The Consulting Fire Protection Engineer’s
review shall not be construed as a complete or detailed check of the work
submitted, nor shall it relieve the Subcontractor of responsibility for
errors of any sort in the shop drawings and samples, or from the
necessity of furnishing any work required by the Contract Documents
which may have been omitted from the shop drawing submittals. The
review of a separate item shall not indicate review of the complete
assembly in which it functions. Nothing in the Consulting Fire
Protection Engineer’s review of shop drawings and samples shall be
considered as authorizing 1) a departure from Contract Documents or
Specifications, or 2) additional cost to the Owner, or 3) increased time
for completion of the work.
C.
The Consulting Fire Protection Engineer will review shop drawings and
samples with reasonable promptness and will return them to the
Subcontractor stamped to indicate the appropriate action as follows:
1.
“NO EXCEPTIONS TAKEN” means that fabrication,
manufacture or construction may proceed providing the
submittal complies with the Contract Documents.
2.
“MAKE CORRECTIONS NOTED” means that fabrication,
manufacture or construction may proceed providing the
submittal complies with the Consulting Fire Protection
Engineer’s notations and the Contract Documents. A copy of the
corrected submittal shall be returned to the Consulting Fire
Protection Engineer for record.
If, for any reason, the
Subcontractor cannot comply with the notations, the
Subcontractor shall resubmit as described for submittals stamped
“REVISE AND RESUBMIT”.
3.
“REVISE AND RESUBMIT” means that the Subcontractor
must comply with the Consulting Fire Protection Engineer’s
notations and resubmit before fabrication, manufacture or
construction may proceed. Submittals stamped in this manner
are not permitted on the job site.
4.
“REJECTED” means that the submittal does not comply with the
Contract Documents and that fabrication, manufacture or
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-8
Fire Protection
Issued for Construction
1 June 2004
construction shall not proceed. Submittals stamped in this
manner are not permitted on the job site.
D.
All shop drawings and samples shall be identified as follows:
1.
Date of submittal.
2.
Title of project.
3.
Name of Subcontractor and date of his approval.
4.
Name of Sub-subcontractor or supplier and date of submittal to
Subcontractor.
5.
Number of submission.
6.
Any qualification, departure or deviation from the requirements
of the Contract.
7.
Reference Local and Governmental Departments and references
to specific standards, where required.
8.
Such additional information as may be required by the
Specifications for the particular material being furnished.
E.
Consulting Fire Protection Engineer’s review is for general compliance
with the design concept and Contract Documents. Markings or
comments or the lack thereof shall not be construed as relieving the
Subcontractor from compliance with the project plans and Specifications.
The Subcontractor remains solely responsible for details and accuracy,
for confirming and correlating all quantities and dimensions, for
selecting fabrication processes, for techniques of construction, for
performing his work in a safe manner, and for coordinating his work
with that of other Trades.
F.
The term “shop drawings” shall include layout, detail, and assembly
drawings, diagrams, schedules, catalogue sheets, printed descriptive
matter, and tabular and graphical presentations of operating and
performance data that describe work required by the Contract
Documents.
G.
No part of the work shall be started in the shop or in the field until the
Consulting Fire Protection Engineer has reviewed the shop drawings and
samples for that portion of the work. Thereafter, the work shall be
executed in accordance with the Contract Documents and the indicated
status of the reviewed shop drawing.
H.
Shop drawings and samples shall be submitted for review sufficiently in
advance of the scheduled start of the work in the shop or in the field to
allow ample time, in consideration of the number and complexity of the
drawings in the submittal, for the Consulting Fire Protection Engineer to
make an orderly review. No extension of the time to complete the work
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-9
Fire Protection
Issued for Construction
1 June 2004
will be granted to the Subcontractor by reason of his failure in this
respect.
I.
The Subcontractor shall carefully check shop drawings and samples,
including those received by him from Sub-subcontractors and material
men, for accuracy, completeness of required information and
conformance with the Contract Documents. Shop drawings found to be
inaccurate, incomplete or not in conformance with the Contract
Documents shall be corrected before being submitted to the Consulting
Fire Protection Engineer for review.
J.
Each submitted shop drawing shall bear the Subcontractor’s stamped
and signed certification that the work has been checked for all related job
conditions, for maintenance of architectural conditions, and coordinated
with the shop drawings of other affected trades for interrelated work, as
required for the proper and complete performance of the work. No shop
drawing submittal will be reviewed without this certification.
K.
Each shop drawing and sample submitted for review shall be
accompanied by a letter of transmittal, and shall be identified by the
project title, Subcontractor’s name, and a reference to the related part of
the Contract Documents.
L.
Shop drawings for manufactured material and equipment shall include
model numbers, dimension drawings, operating weights, material
specifications, operating features and controls, wiring diagrams,
performance characteristics, service procedures, including clearance
requirements for maintenance work, and conformance to specified codes
and code ratings. Note that in addition to these requirements, other
specific submittal data, and forms of data submission, are required by the
Contract Documents for particular items of equipment and material.
M.
Shop drawings for Equipment Rooms, and for piping and similar
distribution services shall show by dimension the exact size and location
of each element of the system in both the horizontal and vertical plane, as
well as relationship to the building structure, architectural construction,
equipment, and the work of other Trades. Shop drawings shall clearly
show where doors providing access to valves, cleanouts and other
devices will be will be required in finished construction. Pads,
foundations, anchorages, supports and attachments to the building
structure where required for the installation of the work shall be shown in
layout and detail with sizes, dimensions, materials and methods of
construction noted. The work described in any shop drawing submission
shall he carefully checked by this Subcontractor for all clearances
(including those required for maintenance and servicing), field
conditions, maintenance of architectural conditions and proper
coordination with all Trades on the job. Each submitted shop drawing
shall include a certification by the Fire Protection Subcontractor that all
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-10
Fire Protection
Issued for Construction
1 June 2004
related job conditions have been checked and that no conflict exists. No
shop drawing submission will be reviewed without such certification.
N.
Samples shall be identical in all respects to the material which is to be
installed or applied in the execution of the work, and shall be of
sufficient size or quantity to permit proper evaluation and review.
Manufacturer’s descriptive labels and printed application instructions
which are normally attached to the material or its packaging shall be
furnished with the sample. Samples shall be submitted for review when
requested by the Consulting Fire Protection Engineer.
O.
Within a period of time as specified by the Owner after award of the
Contract, the Subcontractor shall submit for the Consulting Fire
Protection Engineer’s review, a list of the manufacturers and Subsubcontractor whose products and services he proposes to use for the
work. Proposed substitutions for material and equipment required by the
Contract Documents shall be submitted to the Consulting Fire Protection
Engineer for review during this period. Submittals proposing or
requesting substitutions shall be expressly identified as such in a letter of
transmittal, with the reasons for requesting the substitution stated.
Submittals for this purpose shall be complete in every respect, shall
conform to all the information requirements for shop drawing and sample
submittals, and shall include, at no cost to the Owner, the necessary
revisions to other related work required by the Contract Documents. The
judgment of the Consulting Fire Protection Engineer with respect to the
adequacy and acceptability of a proposed substitution shall be final and
binding on the Subcontractor, and shall not be subject to question in any
other place. After the expiration of this period, substitutions for material
or equipment shall not be proposed or requested in shop drawing and
sample submittals, and the Subcontractor will be required to execute the
work in accordance with the provisions of the Contract Documents.
P.
After award of the Contract and before submittal of any shop drawings,
the Subcontractor shall submit a schedule listing all shop drawings and
samples with the projected date that each item will be submitted to the
Consulting Fire Protection Engineer for review.
Q.
Submit detailed shop layout drawings for each floor of the project,
including all the Mechanical Equipment Rooms, showing equipment and
piping work. All drawings shall be submitted at a scale of not less than
1:50, with Mechanical Equipment Rooms, core details and sections at
1:20 scale. Piping shop drawings shall also indicate the point loading
and spacing of each hanger and the method of support. Drawings shall
include full coordinated floor plans and risers. In addition, required
detail drawings, such as anchor and guide details, coil and equipment
connections, radiation piping within enclosures, fan coil units within
enclosures, built-up casing details, plenum details, etc., shall be
submitted.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-11
Fire Protection
Issued for Construction
1 June 2004
R.
Submit manufacturer’s data or shop drawings of the following:
Pumps
Pump Controls
Sprinkler Head Cabinet
S.
Tanks
Air Compressors
Submit names, sizes, catalogue numbers and/or samples of the following
materials:
Sprinkler Heads
Pipe
Strainers
Valve Tags
Fire Hose
Fire Hose Reel Cabinet
1.11
Fittings
Valves
Pressure Gauges
Sleeves and Escutcheons
Hangers
Flow Switches
T.
Submit copies of engineering calculations for hydraulically designed
systems.
U.
Shop drawings for hydraulically designed systems and calculations for
same shall be submitted as a package.
V.
Each shop drawing shall contain job title and reference to the applicable
drawing and/or specification article.
RECORD DRAWINGS
A.
During construction, keep an accurate record of all deviations between
the work as shown on drawings and that which is actually installed. This
record set of prints shall be kept at job site for inspection by the
Architects.
B.
Upon completion of the installation, furnish two (2) copies of the
drawing files in AutoCAD 2002 format on “Zip Drive” diskettes, and
obtain from the Architects a complete set of mylar transparencies on
heavy gauge film. Enter thereon, in a neat and accurate manner, a
complete record of all revisions of the original drawings, as actually
installed. The cost for transparencies and for making required changes
shall be borne by this Subcontractor. Submit one set of black and white
prints of these revised transparencies to Architects and Consulting
Engineers for review. After review by Engineers and Consulting
Engineers, make necessary changes to transparencies and then deliver
them to the Engineers for transmittal to the Owner, before final payment
is made.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-12
Fire Protection
Issued for Construction
1 June 2004
1.12
1.13
1.14
CODES AND PERMITS
A.
Install all work in full accordance with the requirements of all local and
governmental departments having jurisdiction over these matters, as well
as with any requirements of the NFPA, British standards and other
applicable Codes. Secure and pay for necessary approvals, permits,
inspections, carting, legal dumping, etc., and deliver the official records
of the granting of permits to the Engineer without additional cost to the
Owner.
B.
Provide signs required by the municipal authorities.
PROTECTIVE PAINTING
A.
Provide protective painting as herein specified. Finished painting will be
done by another Trade.
B.
Deliver all equipment with prime coat or prime and finish coat as
specified. Clean up all equipment and leave in condition for finish
painting before acceptance.
C.
Provide all pipe hangers in concealed locations with a heavy factory coat
of aluminum or black asphaltum paint unless hangers are galvanized or
cadmium plated.
D.
Provide a heavy field coat of black asphaltum paint on all steel pipe,
cradles, vibration isolating mounts, and the like, that will be encased or
partially encased in building construction, set in cement or fill, before
items are built into the general construction.
IDENTIFICATION OF SYSTEMS
A.
Provide a tag for each valve, 80 mm. diameter brass or aluminum tags
stamped with designating numbers 50 mm. high, painted with white
enamel; background painted with red enamel. Attach tag to valve handle
or spindle with brass chain.
B.
Provide diagrammatic charts of all piping systems. Provide schedules of
all valves. Provide two copies of charts and schedules in laminated form,
suitable for wall mounting. Provide three copies of charts and schedules,
printed on cloth and bound in booklets. Valve numbering system shall
indicate service and shall indicate floor level where valve is installed.
Valve charts and schedules must indicate valve sizes. Valve charts must
indicate type of valve.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-13
Fire Protection
Issued for Construction
1 June 2004
1.15
1.16
TOOLS
A.
All special tools needed for proper operation, adjustment and
maintenance of equipment shall be delivered to Owner's representative
and a receipt requested for same.
B.
Tools shall include one complete set of high grade wrenches for pumps,
compressors, and other equipment furnished in a suitable hardwood or
other approved container with lock and two (2) keys. Pasted on inside
cover shall be list of all tools provided in box.
C.
Furnish one pressure grease gun of approved design and size, complete
with necessary adaptor to fit all lubricating fittings on installed
equipment.
SLEEVES
A.
B.
C.
Provide sleeves for all pipes passing through floors, walls and concrete,
or concrete fireproofed beams.
1.
Sleeves in concrete beams, through concrete walls, and exposed
pipes penetrating floors: Schedule 40 steel pipe.
2.
Sleeves within furred out enclosures in floors, through partitions,
steel beams and walls: 1.24 mm. thick galvanized sheet metal.
3.
Provide sleeves in foundation walls and in concrete pits with
anchor flanges.
Provide sleeves with an i.d. at least 12.7 mm. greater than outside of pipe
served, including pipe insulation which must be continuous through
sleeve.
1.
Finish sleeves flush with underside of slab and 25.4 mm. above
finished floor.
2.
Caulk space between pipes and sleeves in exterior walls,
foundation walls and pits, with lead and oakum. Where piping
penetrates walls (other than foundation walls), partitions, floor
slabs, etc., space between piping and sleeve shall be packed with
mineral wool.
Set sleeves as construction progresses and secure in place during pouring
of concrete.
1.
Where cellular steel flooring is installed, furnish and locate
sleeves, cut holes through deck, reinforce deck, and set sleeves.
Coordinate sleeve locations with Flooring Subcontractor and
electrical distribution. Submit drawings showing location of
holes and proposed reinforcing and obtain Engineer's approval
before proceeding with installation.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-14
Fire Protection
Issued for Construction
1 June 2004
1.17
1.18
D.
Do not support pipes by resting clamps on sleeves. Clamps must extend
beyond sleeve and be supported outboard of sleeve as detailed on
drawings.
E.
Provide waterproof type pipe sleeves, Zurn Z-197 with galvanized
Schedule 40 pipe extensions where penetrating membrane waterproofed
floors.
F.
Wherever pipes are exposed and pass through walls, floors, partitions
ceilings, fit them with chromium plated cast brass escutcheons held
place with set screws. Fit escutcheons snug over insulation, secure
place. Take special care to protect the escutcheons during the course
construction.
G.
Where space for future pipe is required, provide sleeves and fill with
lightweight concrete.
or
in
in
of
OPERATING AND MAINTENANCE INSTRUCTIONS
A.
Three sets of operating and maintenance instruction manuals, covering
completely equipment starting sequences, operation, maintenance,
automatic controls, pumps and compressors, and listing of all spare parts,
shall be furnished to the Owner in Arabic only. Three sets of lubricating
charts and manuals for each item of equipment shall be furnished to
Owner. Two (2) additional sets of the above shall be furnished: one (1)
in English and one (1) in Arabic.
B.
Furnish a list of manufacturers (with names of local representatives) in
order to expedite ordering of replacement parts. All travel expenses and
accommodations shall be included for the manufacturer’s
representatives.
REPAIR AND MAINTENANCE PARTS
A.
Furnish each item listed below. List of parts included in manufacturer's
standard export kit shall be submitted for approval. Where no standard
export kit exists, the Subcontractor shall submit a suggested list of parts
for approval. List of parts shall include any manufacturer's model
numbers, serial numbers, parts numbers, or any other identification
required for the ordering of spare parts.
Equipment
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Parts Required
15500-15
Fire Protection
Issued for Construction
1 June 2004
B.
1.19
SUBCONTRACTS
A.
1.20
1.21
Approved kits and listed parts shall be turned over to the Owner in new
condition and a receipt obtained for same. A copy of the receipt shall be
submitted for record.
Where Contract Documents require manufacturers' services, and
wherever the staff of the Trade performing the work of this Section
cannot adequately perform such services, this Trade shall stipulate such
performance in its contracts with its Subcontractors or SubSubcontractors, vendors, manufacturers, and the like, or else
subsequently pay them any additional fees required therefor.
ENGINEERING REFERENCE POINTS
A.
The Contractor will provide bench marks, monuments, and other
reference points on the job which will be available for this
Subcontractor's use.
B.
Maintain all existing bench marks, monuments and other reference points
and perform all field engineering required to insure that work under this
Section shall conform with grades, elevations and lines required.
GUARANTEE
A.
Submit a single guarantee stating that all portions of the work are in
accordance with Contract requirements. Guarantee all work against
faulty and improper material and workmanship for a period of one year
from date of final acceptance by the Owner, except that where guarantees
or warranties for longer terms are specified herein, such longer term shall
apply. At no additional cost to Owner, within 24 hours after notification,
correct any deficiencies which occur during the guarantee period, all to
the satisfaction of the Owner and Engineers. This Subcontractor shall
require similar guarantees from his Sub-subcontractor.
B.
Be responsible for all leaks in all pipes for a period of one year from date
of acceptance of work under this Contract. Repair at no cost to Owner
all such leaks which occur within 24 hours notice thereof by the Owner.
Leaks which occur prior to the completion of this Contract shall be
repaired at once. Be responsible for any damage caused by such leaks
and repair thereof and reimburse Owner for all expense incurred thereby.
This
Subcontractor indemnifies the Owner, the
Engineer, the
Consulting Engineer and the Contractor against loss, liability, damage or
expense, including reasonable attorneys' fees, in connection with any
claim resulting from such leaks which may be asserted by tenants or any
other third person.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-16
Fire Protection
Issued for Construction
1 June 2004
1.22
1.23
1.24
CUTTING AND PATCHING
A.
In general, cutting and patching will be done under other Sections of the
Specifications.
B.
Furnish to the Contractor necessary information so that openings for this
work can be built into the floors and walls in time. Such cooperation is
required to keep cutting of walls and floors to a minimum.
C.
Set sleeves for pipes accurately before concrete floors are poured, or set
boxes on the forms to leave openings in the floors and subsequently set
required sleeves in the openings.
D.
Should Subcontractor neglect to perform preliminary work, and should
cutting be required in order to install equipment, the expense of this
cutting and restoring of surfaces to their original condition shall be borne
by this Subcontractor.
RUBBISH REMOVAL
A.
At conclusion of each day's work clean up and stockpile on site, at
location designated by the Contractor, all rubbish, debris and trash,
which may have accumulated during the day as a result of work of this
Subcontractor and of his presence on the job. Contractor will then
remove stockpiled rubbish.
B.
Sidewalks and streets adjoining the property shall be kept broom clean
and free of debris, rubbish, trash and obstructions of any kind caused by
work of this Subcontractor, which will affect the condition and safety of
streets, walks, utilities and property.
CLEANING AND PROTECTION
A.
Remove from entire installation of work all protecting materials, dirt,
dust, smears, stains, paint spots, and the like, and leave in a clean
condition.
B.
As soon as sprinkler heads are in place, cover each head with a small
paper bag of an approved type, and remove it only after all painting is
complete. After the bag is removed, clean and polish all heads.
C.
Cover and protect all openings left in floor for passage of pipes. Protect
pipes with suitable coverings as soon as set. Close all open ends of pipes
with a plug fitting to prevent obstruction and damage.
D.
Before final connections are made and before operation of equipment
and piping, thoroughly blow out, rod out, or wash out all piping, at least
twice in a manner as directed and/or approved by the Engineer, to
remove all accumulation of dirt, chips or other deleterious material.
Make all temporary connections and furnish all appliances required for
the purpose of cleaning at no extra expense to the Owner.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-17
Fire Protection
Issued for Construction
1 June 2004
1.25
UNIT PRICES
A.
State in proposal a unit price per head to be added or deducted if
additional or fewer heads or nozzles are required due to a change in
architectural design or scope of work. Submit the prices in the following
form:
1)
2)
3)
4)
5)
6)
7)
8)
1.26
Unit
Increase
Decrease
Brass Upright Head
Chrome Pendent Head
Brass Pendent Head
Chrome Flush Ceiling Head
Brass Sidewall Head in
Elevator Pit
Hose Station (No Cabinet)
Hose Station (With Cabinet)
Each Type
Cover Plate Flush Type Head
$------$------$------$------$-------
$------$------$------$------$-------
$------$-------
$------$-------
$-------
$-------
B.
Any deletion of heads or nozzles, interchange or substitution in the types
of heads or nozzles shall be made in accordance with the price
established for such changes.
C.
The prices shall include (on a unit basis per head) all necessary branch
piping, cross mains, fittings, hangers, etc., as required to make the
system complete, but shall not include bulk or feed mains or branch
piping in excess of 15 feet for a single head or nozzle.
SUBMITTALS
A.
Submit the following manufacturer's shop drawings and data:
Pumps
Pump Controls
Pneumatic Tank Controller
Carbon Dioxide Equipment
Sprinkler Head Cabinet
B.
Tanks
Air Compressors
Compressed Air Filter
Water Meter
Submit names, sizes, catalogue numbers and/or samples of the following
materials:
Sprinkler Heads
Pipe
Strainers
Pressure Gauges
Sleeves and Escutcheons
Hangers
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Fittings
Nozzles
Valves
Float Switches
Valve Tags
Insulation
15500-18
Fire Protection
Issued for Construction
1 June 2004
1.27
C.
Submit copies of engineering calculations for hydraulically designed
systems.
D.
Shop drawings for hydraulically designed systems and calculations for
same shall be submitted as a package and after final approval shall be
filed by the Subcontractor with the authorities.
E.
Each shop drawing shall contain job title and reference to the applicable
drawing and/or specification article.
APPROVED MANUFACTURERS
A.
Furnish all major items of equipment and materials as made by the
following manufacturers:
Fire Protection Equipment
Croker
Elkhart
Seco
Standard Fire Hose Co.
Fire Pumps
Aurora
Peerless
Fire Pump Controllers
Firetrol
Joslyn-Clark
Lexington Controls
Hangers
Fee & Mason
Grinnell
Motors
Continental Electric
General Electric
Siemens Allis
U. S. Electric Motors
Westinghouse
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-19
Fire Protection
Issued for Construction
1 June 2004
Sprinkler Heads
Central
Grinnell
Reliable
Star
Viking
Tamper Switches
Acme
Grinnell
Potter
Viking
Valves
Jenkins
Stockham
TA
Walworth
Water Flow Detectors
Acme
Grinnell
Potter
Reliable
Viking
PART 2 - PRODUCTS
2.01
MATERIALS OF PIPING SYSTEMS
A.
Piping
1.
Steel Pipe (Stl.): Pipe shall be manufactured in accordance with
the latest issue of ASTM Standard A-53 and meet B.5 1387.
Each length shall be legibly marked by the producer to show
name of manufacturer, kind of pipe, specification number and
pipe length. Each length shall be hydrostatically tested at the
mill and the producer's certification of said tests shall be
furnished. Pipe shall be black or galvanized for drain risers,
preaction systems and wet and dry rising mains, and of the
weight, fitting type and joining method as specified hereinafter
or indicated on the drawings.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-20
Fire Protection
Issued for Construction
1 June 2004
2.
B.
Ductile Iron Water Pipe (D.I.W.P.): Pipe shall be ductile iron
pipe, Class 52 bell and spigot pipe or mechanical joint pipe,
equal to ANSI Specification A21.51, each length marked with
manufacturer's name, weight and class. Pipe shall be as
manufactured by American Cast Iron Pipe Co., United States
Pipe and Foundry Company, National Cast Iron Pipe Company,
or as approved, coated on the outside with a bituminous seal coat
and lined on the inside with a hard smooth cement surface in
accordance with ANSI A21-4. Fittings shall be "push-on" type
or mechanical joint type in accordance with ANSI A21.10 and
ANSI A21.11, as specified or indicated on the drawings.
Variations in thickness class and joining methods shall be as
specified hereinafter, or indicated on the drawings.
System Requirements
1.
Buried Water Supply: Ductile iron pipe with mechanical joint
type fittings.
2.
Fire Standpipe Piping (Wet and Dry Rising Mains): Galvanized
wrought steel, B.S. 1387.
a.
3.
Schedule 40 and 80 pipe fittings shall be screwed,
malleable iron galvanized fittings, UL and FM approved
for this service. Mechanical groove couplings, Victaulic
Style 07 "Zero-Flex", or as approved, may be used in
lieu of screwed fittings. When used with Schedule 10
pipe, couplings shall be rolled groove. When used with
Schedule 80 pipe, couplings shall be cut groove. Either
roll or cut groove may be used with Schedule 40 pipe.
Welded joints and fittings may be used where permitted
by the authorities having jurisdiction provided safety
procedures described in NFPA-13 and 14 are followed.
Sprinkler System Piping: Galvanized steel, Schedule 40
a.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Schedule 40 and 80 pipe fittings shall be screwed,
standard weight, cast iron, UL and FM approved,
fittings. Mechanical groove couplings, Victaulic Style
75, or as approved, may be used in lieu of screwed
fittings. When used with Schedule 10 pipe, couplings
shall be rolled groove. When used with Schedule 80
pipe, couplings shall be cut groove. Either roll or cut
groove may be used with Schedule 40 pipe. Welded
joints and fittings may be used where permitted by the
authorities having jurisdiction provided safety
procedures described in NFPA-13 and 14 are followed.
15500-21
Fire Protection
Issued for Construction
1 June 2004
b.
4.
For piping 50 mm. and larger, Victaulic Style 920 or
Style 921 Mechanical-T with locating collar engaging
into the pipe may be used for less than full size branch
connections.
1)
Victaulic hole cutting tool with coupon retaining
pilot dual bit shall be used for all holes made
outside of a fabrication shop. The following
pipe preparation and installation procedures
shall be followed.
2)
Holes must be drilled on centerline of pipe.
Make certain the hole to receive the MechanicalT is the proper size. After hole has been
properly cut in pipe, check pipe surface within
16 mm. of hole to be certain it is clean, smooth
and free from indentations or projections which
would affect gasket sealing. The pipe around
the entire circumference within the MechanicalT fitting shall be free of any dirt, scale or
projection which might prevent the MechanicalT from seating fully on the pipe surface.
Remove any burrs, sharp or rough edges from
the hole which might affect assembly, proper
seating of the locating collar, or flow from the
outlet or gasket seating.
3)
To install, check gasket and apply a thin coat of
Victaulic lubricant or silicone lubricant to all
surfaces of the gasket. Reposition gasket into
housing using alignment tabs on sides for proper
positioning. Make sure that the locating collar is
in the outlet hole. Tighten bolt nuts uniformly
until the upper housing is in complete surface
contact in the gasket pocket area and the
assembly is rigid. Nuts must be tightened to 50
lb.-ft. with even gaps between the bolt pads for
Style 920 and 30 lb.-ft. for Style 921.
FM-200 Piping: Seamless black steel, ASTM A-106, Schedule
40
a.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Fittings for FM-200 Piping:
conforming to one of the following:
Black,
1)
Malleable iron 300 lb. - ASTM A-197.
2)
Ductile iron 300 lb. - ASTM A-395.
15500-22
screwed,
Fire Protection
Issued for Construction
1 June 2004
C.
3)
Forged steel - ASTM A-234.
4)
Ordinary cast iron fittings shall not be used.
Joining Methods
1.
Make screwed joints without the use of lampwick or filler,
except "utility compound" or teflon tape applied to male threads
only.
2.
Cut or rolled grooves in pipe for use with mechanical grooved
couplings shall be made with an approved machine
manufactured by the supplier of the couplings.
3.
Make welded joints (except for pipe welded end-to-end) with
forged one-piece welding flanges, caps, nozzles, elbows, branch
outlets and tees, of Tube-Turn, Taylor-Forge, Ladish, Grinnell,
or other approved make. Submit cut samples for approval if
directed. Use fittings of a type which maintains full wall
thickness at all points, ample radius and fillets, and proper bevels
or shoulders at ends. "Weld-o-lets" may be used where standard
fittings of required sizes are not available and elsewhere as
approved.
a.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
All job welding shall be done by the electric arc welding
process in accordance with the following:
1)
All joints shall be 45 degree bevel type. Pipe
mill-beveled or machine-beveled by this
Subcontractor.
2)
All scale and oxide removed with hammer,
chisel or file and bevel left smooth and clean.
3)
Pipe lengths lined up straight with abutting pipe
ends concentric.
4)
Both conductors from the welding machine shall
be extended to locations at which welding work
is being done. The leads from welding machine
to location of welding work shall be held
together with tape or other approved means so as
to prevent induced current in structural steel, in
piping or in other metals within the building.
The ground lead shall be connected to length of
pipe with suitable clamp in such manner that
welding current will not flow through joints in
pipe, structural steel of building or steel pipe
supports.
15500-23
Fire Protection
Issued for Construction
1 June 2004
5)
2.02
Weld metal thoroughly fused with base metal at
all sections. Welds shall be of sound metal, free
from laps, slag inclusion or other defects.
b.
All welders shall be certified for the service for which
they are employed and on which they work by the
National Certified Pipe Welding Bureau of the
Mechanical Contractors Association of America.
c.
Connections to equipment shall be made with weld neck
flanges of forged steel or stainless steel as required.
HANGERS, INSERTS AND PIPE SUPPORTS
A.
Provide suitable and substantial hangers and supports for all piping.
B.
Space supports so that there is at least one hanger for each length of pipe,
with one hanger within 750 mm. of the end sprinkler head. Where this
would require hangers closer than 1,830 mm. apart, hanger spacing may
be increased to 3,050 mm. between hangers for pipes up to and
including 50 mm. ips and 3,660 mm. between hangers for pipes 65
mm. ips and larger. Where possible, fasten hanger rods to structural steel
beams.
C.
Support hangers from approved concrete inserts where concrete slabs
exist. Use inserts with space for nuts of all sizes. On all inserts for pipes
75 mm. or larger in size, insert a reinforcing rod 16 mm. in diameter
through slot provided for this purpose, and maintain it in place when
concrete is poured. Place all inserts in forms for all pipes which are to be
hung, in ample time to allow the Concrete Work to be performed on
schedule. If any pipe has to be hung in space where no inserts have been
provided, drill a hole from below through stone concrete slabs, and
provide a rod and hanger attached to an approved fishplate, or for pipes
smaller than 75 mm. ips, install a Phillips red head stud concrete anchor
or other approved self-drilling type expansion shield. For pipes 75 mm.
ips and over, attach the rod and hanger to a 50 mm. x 50 mm. angle
fastened to the slab by two Phillips expansion shields. Do not use shields
smaller than 10 mm. size. The rods on all hangers shall be of adequate
size to support the loads which they carry.
D.
Support vertical risers from the building construction by means of pipe
clamps, Grinnell Fig. 261, at every floor, or as approved. Provide
channels of approved sizes where pipe clamps are too short to connect to
the building construction.
E.
Do not hang piping from ductwork or piping.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-24
Fire Protection
Issued for Construction
1 June 2004
F.
2.03
SEISMIC RESTRAINTS
A.
2.04
This Subcontractor may coordinate with the other Subcontractors to use
common means of support. Submit for approval all pertinent design data
relating to the support, as well as verification of the responsibility for the
support.
All seismic restraints shall be capable of safely accepting one-half "g"
external forces without failure and shall maintain all equipment, piping,
in a captive position. Seismic restraints shall not short circuit isolation
systems or transmit objectionable vibration or noise, and shall be
provided on all fire protection equipment. Calculations by registered
Civil or Structural Engineer shall be submitted to verify snubber
capacities for each piece of equipment and/or the requirements as
detailed in NFPA 13, 1999, Section 6-4 shall be maintained.
VALVES
A.
All FSP water control valves within the building shall be OS&Y wedge
gate valves with painted iron wheel handles, shall have gland followers
in stuffing boxes, constructed so that they may be repacked while open
and under pressure. All valves shall have the name of the manufacturer
and working pressure cast or stamped thereon.
1.
Ball Valves: Ball valves shall be all brass or bronze construction
with replaceable teflon seat ring, two-piece union or three-piece
bolted construction, with stuffing box; working pressure shall
not be less than 150 lbs. at 175° F. and shall conform with ANSI
standards. All valves shall be standard port unless full-ported
valves are indicated on plans. Threaded valves used in brazed or
soldered piping systems shall be fitted with adapters. When
brazed or soldered end valves are used, teflon seats must be
removed prior to soldering or brazing.
2.
Butterfly Valves: Wafer type butterfly valves (use screwed lug
type when valve has to perform dead-end service): Cast iron
body to 200 psi wwp, ductile iron for higher pressures, installed
between flanges of similar rating; stem to be monel or 416
stainless steel sized in accordance with AWWA-6504-70 Class
150; stem seal shall not rely on compression between seating
material and disc, but shall be accomplished by O-rings; disc
shall be bronze, fastened to shaft by means of dowels or
locknuts; bushings at each end of valve stem shall be teflon;
seating material shall be Buna-N one piece, of groove or ledge
design, to prevent dislocation during closure; seating material
must simultaneously act as flange gasket; valve must be factory
tested and certified to seat bubbletight; actuators shall be manual
gear type with handwheel; valve shall incorporate a visible
indication of open or closed position and tamper switch.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-25
Fire Protection
Issued for Construction
1 June 2004
2.05
B.
Wet system alarm valves shall be Reliable Type "E" with full trim,
including retard and electric switch, or as approved.
C.
Deluge valves shall be Reliable Model "A" "B" valve.
D.
Pressure regulating valves (PRV) where installed shall be 400 psi wwp
bronze body with balanced piston and capped bonnet. Valve shall be
Zurn Series Z3004 "Pressure-Tru" or Potter Roemer Series PRV-400-2.5
"Reg-U-Matic" or as approved. Provide pressure gauges upstream and
downstream of PRV.
E.
Provide ladders to all valves located more than 2 m. above floor.
INSULATION
A.
All insulation shall be done by an approved Sub-subcontractor
specializing in this type of work. Insulation shall be Owens-Corning
Fiberglas, or as approved.
B.
Fiberglas Density: All glass fiber pipe insulation in Equipment Rooms
shall be of one-piece type with at least 4 pound density.
C.
Insulation Jackets: White fire retardant vapor barrier, factory applied,
with self-sealing laps and self-sealing end strips. Ends of pipe insulation
shall be sealed off at valves, fittings, flanges and 21 feet of continuous
runs with BF 30-35.
1.
D.
It is the intent of these Specifications that all vapor barriers be
sealed and continuous through hangers, sleeves, etc.
Fittings, Valves and Flanges
1.
Where manufactured, use factory premolded glass fiber covers
on all fittings and valves. Insulate flanges with glass fiber
insulation to a thickness equal to the adjoining covering.
2.
Where premolded covers are not available for fittings and valves,
use mitered sections of 7 pound Fiberglas pipe covering, or build
up the insulation with 1 pound Fiberglas Aerocor double
wrapped to a thickness equal to the adjoining insulation.
E.
Insulation Exposed to Weather: Cover all piping with weatherproof
jacket of corrugated aluminum with a 75 mm. lap that will shed water.
Fittings, valves and flanges weatherproofed with a weatherproof mastic
reinforced with a glass cloth membrane and further coated with mastic.
F.
Fastening of Insulation: Aluminum bands on approximately
centers and at all fittings and valves.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-26
305 mm.
Fire Protection
Issued for Construction
1 June 2004
G.
2.06
2.07
Insulation shall be protected from hangers by a 180 degree galvanized
steel saddle on the outside of the insulation and vapor barrier. A half
section of waterproof, calcium silicate, high density insulation of the
same thickness as the pipe insulation, and full length of the saddle, shall
be used to support the weight of the pipe at the saddle. Saddles shall be
of sufficient length to allow for the hanger load at the specified hanger
spacing.
SPRINKLER HEADS
A.
Provide automatic sprinkler heads of finish as approved by the
Architects. All flush type sprinkler heads shall be Viking Model D;
cover plate flush type sprinkler heads shall be Reliable Model "G4FR" 8
mm. plate diameter, finish as selected by Engineer; all other sprinkler
heads shall be Reliable Model "G" automatic water spray heads, or as
approved.
B.
All heads shall be as approved by the Engineers, the municipal
authorities and by the insuring agencies having jurisdiction.
C.
All heads shall be "Standard" 12 mm. diameter orifice, quick response,
upright, pendent, flush type pendent, cover plate flush type, or dry type
pendent, to fit the conditions in which they are installed.
D.
All pendent heads and flush type pendent heads installed in ceilings shall
be chrome plated with chrome plated escutcheons.
E.
All upright heads, side wall heads and pendent heads connected to
exposed piping shall be rough brass construction, unless otherwise noted
on the drawings.
F.
All heads shall be of the proper temperature rating for the locations in
which they are installed. In general, temperature rating shall be 74°C.,
except for Mechanical Equipment Rooms and Kitchen areas, which shall
be 141°C.
G.
Furnish and install, where directed, one approved type sprinkler cabinet
containing not less than 24 extra sprinkler heads, of the various degrees
used in the work; also one sprinkler wrench for emergency use.
ALARM DEVICES
A.
All interconnecting electrical wiring will be furnished under the
Specifications of other Trades. Provide all switches directly connected
to equipment provided by this Trade, required for the transmission of
alarm impulses. Switches shall be open or closed type to conform with
the alarm system to which they are connected.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-27
Fire Protection
Issued for Construction
1 June 2004
B.
C.
Provide tamper switches for the following valves:
1.
All valves controlling the flow of water to sprinkler heads,
including floor control valves, pump control valves, meter
valves, etc.
2.
Switches shall give an alarm if the valves served are closed, the
switches are removed, or if the cover is opened. Valve stems
shall be notched to take the switches. Switches shall be Acme
Fire Alarm Co. Type OSYS-U, or as approved.
Provide the following flow alarm devices:
1.
Retard chamber and closed circuit electric switch for each alarm
valve.
2.
Paddle type water flow detectors, closed circuit type with an
adjustable retard or time delay to prevent false alarms due to
water pressure surges. Switches shall be Acme Fire Alarm Co.,
Type WFD, or as approved.
3.
Pressure type flow alarm switch for each deluge preaction and
dry pipe valve.
D.
Power failure, pump operating indication, phase reversal, automatic
transfer switch position for each fire pump and each sprinkler booster
pump.
E.
Provide the following level alarm switches:
1.
2.08
High and low water alarm switches for suction tank.
SPRINKLER DRAINS
A.
Provide all necessary drain valves, capped nipples, auxiliary piping, etc.,
as required to drain trapped portions of the system.
B.
Inspectors test connections shall be provided with a sight connection and
piped to waste.
C.
Main drain and test connection shall be piped to waste.
D.
Automatic ball drips from siamese connections, etc., shall be piped to
waste or connected to the waste connection from the FSP siamese.
E.
Provide all piping required to spill the drains and test connections to the
floor, funnel or other drainage connections provided under the Plumbing
Contract, or arrange with the Plumbing Subcontractor to provide
additional drainage facilities, in which case pay all charges related to the
additional Plumbing Work.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-28
Fire Protection
Issued for Construction
1 June 2004
2.09
SIGNS
A.
2.10
Provide all designating signs for curb valves, control valves, alarms,
hydraulically designed systems, etc., as required by the authorities
having jurisdiction.
FIRE STANDPIPE SYSTEM/SPRINKLER SYSTEM APPURTENANCES
A.
Provide the fire standpipe/sprinkler system appurtenances required to
provide fire protection for the entire building.
B.
Finish hose reels, hose valves, hose couplings, hose nozzles, spanner
wrenches and chains, siamese connections and hydrant connections as
specified under "Pipe and Material Finishes".
C.
Elkhart Brass Co. numbers have been used to designate the type of
material desired; equivalent material as made by other manufacturers
listed as "Approved Manufacturers" may be submitted for approval.
D.
Provide flush type, or free-standing type, siamese as indicated on the
drawings, cast bronze, complete with yellow cast iron caps and brass
chains. Install siamese at the outside walls of the building in the
locations indicated on drawings. Siamese shall be similar to Elkhart No.
166, No. 165, No. 15, or as approved. Siamese escutcheon shall be
modified to eliminate all manufacturer's identification marks and
lettering other than that required by the authorities.
E.
Hose reel stations indicated on the drawings shall consist of valve, reel,
hose, nozzle, spanner wrench and chain.
F.
Hose Reel Cabinets Where Indicated on the Drawings: All steel hose
cabinets, 1.214 mm. stainless steel with satin finish cabinet and custom
face. Minimum of 5 mm. plate doors with roller embossed finish, onepiece construction . Recess cabinet and door into wall flush with face
of stone. Furnish doors as detailed on the architectural drawings.
Hinges: Concealed continuous piano type hinge finished to match
exterior of cabinet, right or left as required. Do not use screws or bolt
heads on face of cabinets.
Provide custom lettering as directed by
Engineer on face, if required by Code.
G.
Roof Manifolds:
caps and chains.
H.
Use materials as scheduled for each of the FSP pressure zones.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Stainless steel with 65 mm. stainless angle valves,
15500-29
Fire Protection
Issued for Construction
1 June 2004
2.11
FIRE PUMP INSTALLATION
A.
Provide a complete fire pump installation, including fire pumps (one [1]
electric, one [1] diesel) and jockey pumps, as herein described and/or as
indicated on the plans. Installation shall be in accordance with NFPA-20
and Qatar Standards, complete with all accessories and controls and shall
meet the hereinafter specified construction requirements. Working
pressures, capacities and stages shall be as specified or indicated on the
drawings. Pumps shall be connected to horizontal a.c. squirrel cage
motors by means of flexible couplings of approved design. The pump
and motor combination shall be mounted on a fabricated steel base with
sufficient grout holes to permit grouting to a concrete base at least 0.3
meters high. Provide an approved shop drawing for base construction
and provide and set the required anchor bolts. The fire pumps shall be
horizontal split case design; jockey pumps shall be horizontal or vertical
split or diffuser type as required.
1.
B.
C.
Pumps shall be equal in construction to the pumps scheduled or
specified and shall have similar curves and efficiencies.
Pump Construction
1.
Pumps shall be constructed in accordance with local standards as
required by the authorities having jurisdiction.
2.
Where standard construction of the pumps submitted cannot
meet the suction and working pressure limits set by the above
standards, "heavy" construction pumps shall be used.
Supply and install for each fire pump the following accessories of proper
design and working pressure requirements:
11111112-
Discharge tee
Hose valve header with one 60 mm. tap for each 1,000 l./min. of
pump capacity
Set hose valves with (National Standard) threads
Main relief valve flanged 100 mm., steel
Automatic air release valve, high pressure
Set suction and discharge gauges with gauge savers
Splash partition
Sheet metal guards over shafts, one between splash plate and
motor, and one between splash plate and pump
1.
Pressure relief valve shall be constructed for discharge against
pressure (to suction connection).
2.
Provide spring-loaded bronze fitted check valves in each pump
discharge line.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-30
Fire Protection
Issued for Construction
1 June 2004
2.12
D.
Motors for automatic service shall be squirrel cage motors rated for
40°C. rise.
E.
The suppliers of fire pumps and the controls shall include in their base
price the services of at least one service man from the pump supplier and
one man from the control supplier for a minimum of two (2) working
days. This time shall be spent in instructing the operating personnel in
the proper procedure to be followed when operating the fire pump
system. Supervision of installation and startup is not to be considered as
a portion of these two (2) days.
FIRE PUMP CONTROLLER
A.
The fire pump control panel shall be completely assembled, wired and
tested at the manufacturer's plant, and shall be specifically approved for
fire pump service. The design of the controller shall conform to the
requirements outlined in Pamphlet No. 20 issued by the National Fire
Protection Association (NFPA). All equipment shall be approved by
Factory Mutual, Underwriters' Laboratories, and all authorities having
jurisdiction. The panel shall be enclosed in a driptight, free-standing
formed sheet steel cabinet arranged to permit installation with back
against the wall with all operating handles, wiring and components
accessible from the front. Entire assembly, including enclosure, shall
have a withstand rating of not less than 150,000 amperes at 380 volts.
B.
Controller shall be combined manual and automatic type, with automatic
transfer switch as hereinafter described for emergency power supply,
suitable for primary resistance reduced voltage starting of squirrel cage
motor, and shall consist of the following components:
1.
One isolating switch, 3 pole, nonfusible of approved capacity,
with latch-in device manually operated.
2.
One circuit breaker, manually operated, 3 pole, 600 volts, a.c.,
having a rating of at least 115% of the rated full load current of
the motor. Breaker shall permit normal starting without tripping
and shall provide stalled rotor protection and instantaneous short
circuit protection. Breaker of the inverse time delay type with a
time delay of not over 20 seconds on 600% (locked rotor
current) of the motor full load current. The magnetic trips shall
be calibrated at least up to and set at 300% of the motor full load
amperes.
3.
One motor starter, magnetic, reduced voltage type without
overload protection, designed to be energized automatically
through action of the pressure regulator, or manually by means
of a start button on the front of the enclosure. Under emergency
conditions it shall be possible to close the starter mechanically
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-31
Fire Protection
Issued for Construction
1 June 2004
through an externally operated handle provided with a latch-in
device.
4.
One pressure regulator switch of the Bourdon tube type with
mercury tube contact for controlling the running of the motor
automatically and provided with independent adjusting screws
for cut-in and cutout pressure points. Connection to the pressure
switch shall be separated from all electrical components by a
waterproof barrier.
5.
One running period timer to determine the minimum length of
time the motor will run when started automatically provided the
pressure regulator has reached the cutout setting at or before the
end of the timing interval. If not, the pressure regulator shall
govern the stopping of the motor.
6.
One control relay to operate in conjunction with the running
period timer with provision to bypass the timer to permit an
automatic start of the pump and continuous operation until
manually stopped.
7.
One deluge valve relay for remote starting.
8.
One power availability relay energized from the load side of the
circuit breaker so that it will drop out if the circuit breaker is
opened or the power fails. This relay shall be provided with one
normally closed and one normally open isolated contact for
remote alarm indication.
9.
One pilot light connected to load side of circuit breaker to
indicate power is available at the controller.
10.
One start button on front of enclosure.
11.
One manual release button on front of enclosure.
12.
Terminal blocks and red nameplates shall be provided as
required by the Underwriters.
13.
Transfer Switch for Emergency Power Supply
a.
The automatic transfer switch shall be housed in a
barriered compartment of the fire pump controller.
b.
The transfer switch and fire pump controller
combination shall be listed for fire pump service.
c.
Electrical ratings of automatically operated transfer
switches shall comply with NFPA requirements.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-32
Fire Protection
Issued for Construction
1 June 2004
d.
Transfer switches shall be mechanically held.
e.
Manual operation shall be by direct mechanical or
electrical remote manual control.
f.
Automatic transfer switches shall be capable of manual
(nonelectrical) operation.
g.
An isolating means, located within the automatic transfer
switch enclosure, shall be provided ahead of the
emergency input terminals of the transfer switch.
h.
The generator control circuit from the Fire Pump Room
shall be of closed circuit design, so arranged that the
opening of the circuit will start emergency generator.
i.
Auxiliary contacts, installed on the isolating means of
the emergency side of the transfer switch, shall be
arranged in the generator control circuit (from the Fire
Pump Room) to prevent starting of the generator from
this transfer switch signal when the controller or transfer
switch is being serviced.
j.
The position of the transfer switch emergency side
isolating means shall be supervised to indicate when it is
open. Supervision shall operate an audible and visual
signal in the Pump Room and at a remote point when
required.
k.
Indication of Switch Position: Two pilot lights, properly
identified, shall be provided to indicate transfer switch
position, with duplicate sets of such contacts for remote
indication of switch position.
l.
Voltage Sensing: Voltage sensing devices shall be
provided to monitor all ungrounded lines of the normal
and emergency sources of power.
m.
The transfer switch shall transfer and retransfer the load
automatically. Power to accomplish transferal shall be
supplied by the source to which the load is being
transferred.
n.
Time Delay on Starting of Alternate Power Source: An
adjustable .5-6 second time delay device shall be
provided to delay starting of the alternate source
generator in the event of momentary power dips and
interruptions of the normal source. Relays shall be set to
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-33
Fire Protection
Issued for Construction
1 June 2004
transfer to emergency at 70% normal voltage, and
retransfer at 90%.
2.13
o.
Transfer to Alternate Power: Transfer to the alternate
power source shall be delayed until proper alternate
source voltage and frequency are achieved.
p.
Time Delay of Retransfer to Normal Power: An
adjustable timer with a bypass shall be provided to delay
retransfer from the alternate source of power to the
normal until the normal source is stabilized.
q.
Means shall be provided to prevent higher than normal
starting currents when transferring the fire pump motor
from one source to the other by providing an in-phase
monitor to protect against abnormal inrush currents
which may result from out-of-phase transfer of motor
loads. The monitor shall initiate operation of the transfer
switch when the remote or local pushbutton is actuated
and the phase angle between both sources is approaching
zero phase angle. The motor currents upon reconnection
shall not exceed normal starting values. In-phase
transfer shall be provided in either direction whenever
both power sources are above 70% of nominal voltage.
r.
The fire pump controller-transfer switch assembly shall
be marked to indicate that the isolating means for both
the controller and transfer switch must be opened before
servicing the controller, transfer switch or motor.
C.
Control panel shall be Firetrol, Inc., Model FTA1500, or as approved.
D.
See Equipment Schedule for start-stop pressure settings.
JOCKEY PUMP CONTROLLER
A.
Pump controller shall consist of a NEMA Type 1 wall mounted formed
sheet steel enclosure with the following parts assembled and wired
therein:
1.
One externally operated fusible disconnecting switch.
2.
One across-the-line type magnetic starter with thermal overload
protection.
3.
One hand-off-automatic selector switch.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-34
Fire Protection
Issued for Construction
1 June 2004
2.14
2.15
4.
One running period timer to keep motor running for a
predetermined time after each automatic start to prevent too
frequent starting and stopping.
5.
One pressure regulator of the Bourdon tube type with adjustable
cut-in and cutout points.
B.
Controller shall meet requirements of NFPA, Underwriters Laboratories
and Factory Mutual, and shall be Firetrol, Inc., Model FTA500, or as
approved.
C.
See Equipment Schedule for start-stop pressure settings.
ELECTRIC MOTORS
A.
Provide electric motors for driving fire protection equipment of proper
type, power and speed to suit the specified equipment; if other equipment
is submitted, include the proper adjustment of motor speed and power
without additional cost to the Owner. Coordinate the NEMA type of
each motor with the torque and inertia load of the equipment served, the
inrush characteristics of the motor and the starter selection so that all
items furnished constitute a properly related package. Certify to the
coordination of the equipment at the time drawings are submitted for
approval.
B.
Motors shall comply in all respects with NFPA Standard No.
"Centrifugal Fire Pumps".
C.
All Motors: Quiet operating type, guaranteed to fulfill specified
requirements without producing any sound audible outside of Machine
Rooms. Supply motors made by one of the approved manufacturers.
D.
All motors are to have roller or ball bearing mounted shafts.
E.
All motors mounted in the vertical position shall have drip covers.
F.
Horsepower, rpm, voltage, hertz and phase shall be as scheduled.
G.
Wound rotor motors shall be open induction type with a rated operating
temperature of 40°C. higher than ambient.
20,
PREACTION SPRINKLER SYSTEM
A.
Provide preaction sprinkler systems for the areas designated on the
drawings, complete with central control panels, including outlying
detection devices, alarms, conduit and wires, preaction sprinkler valves
and trim, air compressor panel in preaction valve closet, and piping,
complete and ready for operation, all as shown on the drawings and as
hereinafter specified.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-35
Fire Protection
Issued for Construction
1 June 2004
B.
1.
The system shall be capable of signaling an alarm prior to the
development of visible smoke due to a fire condition. The
system shall provide audible and visual annunciation at its
central panel upon detection of a fire condition, visually
identifying the space associated with each of its individual
detection devices. The system shall be electrically supervised
against wiring derangement of all circuitry involved by zone in
the sensing of fire, and the response signal of alarm. The
occurrence of a wiring derangement shall cause an audible and
visual trouble indication to occur at the central panel.
2.
The entire preaction system shall be furnished and installed
under the responsibility of one Contract.
3.
All devices, combinations of devices and equipment constructed
and installed in conformity with this Specification shall be
approved by the applicable insurance agency for the purposes for
which they are installed and by all authorities having
jurisdiction.
4.
Any equipment proposed as equal to that herein specified must
be proven by the Section, who shall submit to the Engineer the
manufacturer's name and model numbers of substitute equipment
and material, together with three (3) copies of engineering data
sheets, and a list of twenty (20) installations of similar
equipment which have been satisfactorily installed and in
continuous operation on user's premises over a period of three
(3) years.
Smoke Detection System
1.
System Components
a.
Central Control Panel
1)
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Control panel shall be Notifier Model NFS 3030
“Series” addressable fire alarm control panel.
The control console shall contain a
microprocessor based central processing unit
(CPU). The CPU shall communicate with and
control the following types equipment used to
make up the system: intelligent addressable
smoke and thermal (heat) detectors, addressable
modules, panel modules, including initiating
circuits, control circuits, and notification
appliance circuits, local and remote operator
terminals, printers, annunciators, and other
system controlled devices.
15500-36
Fire Protection
Issued for Construction
1 June 2004
2)
3)
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
In conjunction with intelligent loop control
modules and loop expander modules, the main
FACP shall perform the following functions:
a)
Supervise and monitor all intelligent
addressable detectors and monitor
modules connected to the system for
normal, trouble and alarm conditions.
b)
Supervise all initiating signaling and
notification circuits throughout the
facility by way of connection to monitor
and control modules.
c)
Detect the activation of any initiating
device and the location of the alarm
condition.
Operate all notification
appliances and auxiliary devices as
programmed. In the event of CPU
failure, all SLC loop modules shall
fallback to degrade mode. Such degrade
mode shall treat the corresponding SLC
loop control modules and associated
detection devices as conventional twowire operation. Any activation of a
detector in this mode shall automatically
activate
associated
notification
appliance circuits.
d)
Visually and audibly annunciate any
trouble, supervisory, security or alarm
condition on operator’s terminals, panel
display, and annunciators.
When a fire alarm condition is detected and
reported by one of the system initiating devices
or appliances, the following functions shall
immediately occur:
a)
The system alarm LED shall flash.
b)
A local piezo-electric audible device in
the control panel shall sound a
distinctive signal.
c)
The 640-character backlit LCD display
shall indicate all information associated
with the fire alarm condition, including
15500-37
Fire Protection
Issued for Construction
1 June 2004
the type of alarm point and its location
within the protected premises.
4)
5)
d)
Printing and history equipment shall log
and print the event information along
with a time and date stamp.
e)
All system outputs assigned via
preprogrammed
equations
for
a
particular point in alarm shall be
executed, and the associated system
outputs (alarm notification appliances
and/or relays) shall be activated.
When a trouble condition is detected and
reported by one of the system initiating devices
or appliances, the following functions shall
immediately occur:
a)
The system trouble LED shall flash.
b)
A local piezo-electric audible device in
the control panel shall sound a
distinctive signal.
c)
The 640-character backlit LCD display
shall indicate all information associated
with the trouble condition, including the
type of trouble point and its location
within the protected premises.
d)
Printing and history storage equipment
shall log and print the event information
along with a time and date stamp.
e)
All system outputs assigned via
preprogrammed
equations
for
a
particular point in trouble shall be
executed, and the associated system
outputs (trouble notification appliances
and/or relays) shall be activated.
When a supervisory condition is detected and
reported by one of the system initiating devices
or appliances, the following functions shall
immediately occur:
a)
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
The system trouble LED shall flash.
15500-38
Fire Protection
Issued for Construction
1 June 2004
6)
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
b)
A local piezo-electric audible device in
the control panel shall sound a
distinctive signal.
c)
The 640-character backlit LCD display
shall indicate all information associated
with
the
supervisory
condition,
including the type of trouble point and
its location within the protected
premises.
d)
Printing and history storage equipment
shall log and print the event information
along with a time and date stamp.
e)
All system outputs assigned via
preprogrammed
equations
for
a
particular point in trouble shall be
executed, and the associated system
outputs (notification appliances and/or
relays) shall be activated.
When a security alarm condition is detected and
reported by one of the system initiating devices
or appliances, the following functions shall
immediately occur:
a)
The system security LED shall flash.
b)
A local piezo-electric audible device in
the control panel shall sound a
distinctive signal.
c)
The 640-character backlit LCD display
shall indicate all information associated
with the fire alarm condition, including
the type of alarm point its location
within the protected premises.
d)
Printing and history storage equipment
shall log and print the event information
along with a time and date stamp.
e)
All system outputs assigned via
preprogarmmed
equations
for
a
particular point in alarm shall be
executed, and the associated system
outputs (alarm notification appliances
and/or relays) shall be activated.
15500-39
Fire Protection
Issued for Construction
1 June 2004
7)
8)
9)
When a prealarm condition is detected and
reported by one of the system initiating devices
or appliances, the following functions shall
immediately occur:
a)
The system prealarm LED shall flash.
b)
A local piezo-electric audible device in
the control panel shall sound a
distinctive signal.
c)
The 640-character backlit LCD display
shall indicate all information associated
with the fire alarm condition, including
the type of alarm point and its location
within the protected premises.
d)
Printing and history storage equipment
shall log and print the event information
along with a time and date stamp.
e)
All system outputs assigned via
preprogrammed
equations
for
a
particular point in alarm shall be
executed, and the associated system
outputs (alarm nofitication appliances
and/or relays) shall be activated.
The power supply unit for the smoke detection
system shall be capable of providing power for
the following functions for the system:
a)
Furnish necessary d.c.
operation of detectors.
b)
Provide control of fire alarm and trouble
alarm signals.
c)
Provide control
equipment.
d)
Activate preaction sprinkler valves.
Z:\worldox\docs\122690\spc\00015628.DOC
for
supplementary
The unit shall perform the following functions:
a)
Museum of Islamic Art
Doha, Qatar
of
power
Provide visual indication of the zone in
which the alarm initiating detector is
located.
15500-40
Fire Protection
Issued for Construction
1 June 2004
10)
b.
c.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
b)
Provide visual indication of the zone in
which a trouble signal is initiated.
c)
Provide supplementary nonpowered
control circuits which shall be activated
independently for each zone.
This panel shall contain all logic circuitry to
provide for cross-zoning control functions, as
described
hereinbefore
under
"System
Operations".
Detection Devices
1)
Detectors shall be Notifier FSI-751.
The
detector shall operate on the ionization principle
to detect the presence of combustion gases, fire
and smoke. It shall be of the two (2) chamber
design. The first, or reference chamber, shall
compensate against sensitivity charges due to
temperature, barometric pressure and humidity
variations. The second, or sensing chamber,
shall be open to the outside elements through a
protective screening which will prevent insects
and foreign matter from entering and causing
false alarms. The detector shall contain no hot
filament tubes or moving parts, and shall plug
into a base having a neon alarm indicating lamp.
The detector shall not require replacement or
readjustment after a fire alarm has been given.
The detector sensitivity shall be individually
adjustable and set by the factory-trained
technician at installation and thereafter be fixed.
It shall be possible to measure the detector's
sensitivity with an appropriate instrument.
2)
Underfloor detectors shall be mounted on
mounting bracket and secured to structural slab.
Audible Signals: The system audible/visual signals shall
be die-cast, dustproof, 24 volts d.c., vibrating/strobe
type, designed to be mounted directly on a standard 100
mm. octagon outlet box, and shall be 250 mm. diameter
strobe/bells for alarm, 150 mm. diameter strobe for
trouble (common trouble).
15500-41
Fire Protection
Issued for Construction
1 June 2004
d.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
Graphic Annunciator
1)
Graphic annunciator shall be mounted in a 16
gauge sheet steel cabinet for recessed mounting,
where shown on the drawings. Cabinet shall be
primed and finished in red semigloss baked
enamel. Doors shall be provided with all
required cutouts for operating control
components, and shall be hinged and provided
with a tumbler type lock and key.
2)
Each panel shall contain a map type annunciator.
This annunciator shall contain one pilot light for
each smoke detector installed below the raised
floor of the area and one pilot light for each
ceiling zone (two lights). Pilot lights shall
illuminate when the smoke detectors are in
alarm condition. The annunciator shall be a map
of the area containing the general outline of the
walls, doors, etc., and shall be geographically
oriented to the area. The pilot lights shall be
arranged according to the locations shown on the
plans. The map shall show the location of the
panel and shall have the words "YOU ARE
HERE" imprinted on the face. The face of the
annunciator shall be constructed of plexiglas
plastic laminate with matte finish. The lines
representing the walls and doors of the area and
other information lettering shall be engraved in
the surface. Pilot lights shall be red and shall be
cylindrical type, with flat face of the smoke
detectors under the floor. Pilot lights shall
utilize LED lamps.
Provide lamp test
pushbutton, momentary type, so that, when
depressed, all the lamps will illuminate. Provide
10 spare lamps.
3)
All components of each area control panel shall
be prewired at the factory to terminal strips so
that no field wiring need be connected directly
to the components. Marker strips shall be
provided so that each terminal may be
designated with its respective wire number.
4)
All wiring connections within each panel shall
be accessible from the front when the doors are
open. Back wired panels will not be accepted.
Wiring between components on the doors and
15500-42
Fire Protection
Issued for Construction
1 June 2004
stationary components within the cabinet shall
be neatly bundled, harnessed and protected, and
installed with enough slack so that doors may be
opened and closed without damaging the wiring.
2.
Power Supply: Only one source of energy shall be connected to
the system. This service connection shall be 120/208 volt, single
phase, 3 wire, taken from the standby power system, through an
approved fuse cutout box.
3.
System Operations
a.
The smoke detection system shall consist of detectors
wired and cross-zoned in accordance with the schedule
listed herein, central control panel, power supply and
auxiliary functions as specified herein.
b.
The system shall function as follows when any single
detector operates within the protected area.
c.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
1)
Light proper zone indication and fire indication
on central control panel.
2)
Light proper ceiling zone indication on mimic
annunciator.
3)
Sound alarm strobe/bells (waterflow, smoke
detection or manual release).
4)
Initiate signal to building fire alarm system.
(Coordinate contact closure requirements.)
Subsequent operation of a "cross-zoned" detector within
the affected area shall:
1)
Sound combination strobe/horns.
2)
Silence alarm strobe/bells.
3)
Light proper zone indication and fire indication
on central control panel.
4)
Initiate second zone signal to the building fire
alarm system.
5)
Actuate circuits to close associated dampers and
shut down associated fans and air conditioning
units.
15500-43
Fire Protection
Issued for Construction
1 June 2004
d.
C.
D.
6)
Deactivate electrical supply (after adjustable 030 second time delay) to all computer units via
shunt trip circuit breakers on distribution panels.
7)
Actuate preaction sprinkler valve.
Common trouble alarm shall initiate signal to building
system, and sound local trouble strobe/bells.
4.
Wiring: The wiring arrangement for the system shall be as
shown on the drawings. Each wire shall be a single No. 14
AWG minimum conductor (smoke detectors, No. 16 AWG
minimum) with 1.2 mm. Type THWN insulation. All wiring for
the automatic fire detection system shall be installed in a rigid
iron, steel or aluminum conduit, except where required otherwise
by the Code, and shall generally be run concealed in finished
spaces, and exposed in unfinished spaces. Conduit containing
wires, identified as fire and detection system wires, will not be
permitted to contain any other wires. Conduit shall enter only at
the side or the bottom of cabinets.
5.
Installation
a.
The system shall be installed in a workmanlike manner,
and in accordance with Specifications and standards
approved by all authorities having jurisdiction.
b.
The system shall be provided complete with all outlet
boxes, junction boxes, cabinets, etc., regardless of
whether or not such items are furnished as integral parts
of the equipment.
Preaction sprinkler components shall be as manufactured by Reliable
Automatic Sprinkler Co. and shall include the major items listed herein:
1.
Water Control Valve: Model B deluge valve, complete with
basic trim and wet pilot line trim sets.
2.
Release Valve: Model LV2LBX25 Supertrol release valve.
3.
Air Supply: Model B air compressor panel, 406 mm. x 508 mm.
x 150 mm., complete with air compressor, pressure switch,
copper tubing, alarm horn and contacts for remote alarm.
Piping: Preaction sprinkler piping shall be galvanized steel, Schedule 40
or 10 as herein specified.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-44
Fire Protection
Issued for Construction
1 June 2004
2.16
FM-200 FIRE SUPPRESSION SYSTEM
A.
B.
Provide an FM-200 system for the Museum display cabinets, electrical
substation, Transformer Rooms and Telephone Main Switch Room or as
indicated on the drawings, complete with FM-200 storage containers and
piping, complete and ready for operation, all as shown on the drawings
and as hereinafter specified.
1.
The system shall be capable of signaling an alarm prior to the
development of visible smoke due to a fire condition. System
shall provide audible and visual annunciation at its central panel
upon detection of a fire condition, visually identifying the space
associated with each of its individual detection devices. The
system shall be electrically supervised against wiring
derangement of all circuitry involved by zone in the sensing of
fire, and the response signal of alarm. The occurrence of a
wiring derangement shall cause an audible and visual trouble
indication to occur at the central panel.
2.
The entire automatic fire and smoke detection system shall be
furnished and installed under the responsibility of our Contract
by the Electrical Subcontractor. The FM-200 extinguishing
system shall be furnished and installed under this Contract.
3.
All devices, combinations of devices and equipment constructed
and installed in conformity with this Specification shall be
approved by the Qatar Fire Department and by all authorities
having jurisdiction.
4.
Provide all wiring and controls to sequence the associated
heating, ventilating and air conditioning system dampers, air
conditioning units and fans. Refer to heating, ventilating and air
conditioning drawings for locations and description of
equipment and damper operations and "System Operations"
herein.
5.
Provide pressure-operated switches to shut down any electrically
operated equipment, such as fresh air and exhaust fan, etc.
Pressure switch and alarms to indicate operation of system and a
pressure switch for use in separate single circuit provided by
others.
System Components
1.
Central Control Panel
a.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
All components of the central control panel shall be
prewired to terminal strips, and shall be securely
fastened to steel rails mounted in a 14 gauge sheet steel
15500-45
Fire Protection
Issued for Construction
1 June 2004
housing, finished in scratch-resistant, baked red enamel.
The panel shall be complete with a continuous 1/4 barrel
hinge, and provided with an Eagle 903 lock and keys.
Separate illuminated signal indications shall be provided
for power, fire and trouble, in addition to one indication
per zone. Plastic nameplates, engraved and filled, shall
be provided for each indication, and shall be securely
fastened to the panel with machine screws. Control
housing shall be Notifier Model NFS 640 addressable
fire control panel. Provisions shall be made for
operation from a self-contained, 24 volts d.c. emergency
power supply. The units shall have built-in rechargeable
standby batteries of sufficient capacity to provide for a
minimum of four hours of continuous monitoring with a
full alarm and auxiliary control capability for five full
minutes at the end of the four hour period. All battery
recharging and power leads shall be designed for ease of
installation with no special tools required. Provide for a
local alarm indication on the control panel for “low
battery” condition. It shall be constructed to permit
maintenance by qualified electricians without special
tools or training. The central control panel shall contain
the following individual units of control equipment.
b.
c.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
The power supply unit for the smoke detection system
shall provide the following functions for the system:
1)
Furnish necessary d.c. power for operation of
detectors.
2)
Provide control of fire alarm and trouble alarm
signals.
3)
Provide control supplementary equipment.
The zone indicator units for the detection system shall
perform the following functions:
1)
Provide visual indication of the zone in which
the alarm initiating detector is located.
2)
Provide visual indication of the zone in which a
trouble signal is initiated.
3)
Provide supplementary nonpowered control
circuits which shall be activated independently
for each zone.
15500-46
Fire Protection
Issued for Construction
1 June 2004
d.
The supervised relay panel shall be closed circuit, made
up of multiple contact control relays, one (1) 6 ampere
fuse. Panel shall be of modular construction and shall be
installed in the central control panel.
e.
FM-200 release modules shall be Pyrotronics Model
RM-30U.
f.
A FM-200 “Hold” button shall be provided on the
control panel. This button, when pressed during the
“evacuation” time, shall activate a two-minute time
delay to hold the release of FM-200 into the affected
area. If the system is not reset within the two-minute
interval, the “evacuation” sequence will restart.
g.
The central control panel shall contain all logic circuitry
to provide for cross-zoning control and delay functions,
as described hereinafter under “System Operations”.
2.
FM-200 Purge Panel: Flush-mounted with purge delay, purge
ready, and system purging lights, purge key switch, Fire
Department time bypass switch, and reset key switch. This panel
shall contain the fifteen-minute purge delay, override and all
circuitry to control the purging of FM-200 gas from the affected
area.
3.
FM-200 Manual Release: The manual release station shall be
flush mounted. The station shall perform all the functions
described hereinafter under “System Operations”. Station shall
be Pyrotronics Series PN, double-action control.
4.
Audible Signals: The system audible signals shall be die-cast,
dustproof, 24 volts d.c., vibrating type, designed to be mounted
directly on a standard 100 mm. octagon outlet box.
5.
Magnetic Door Holders: The door holders shall have a holding
force of approximately 23 pounds. Unit shall consist of brushed
aluminum, pivotal mounted, contact plate, mounted on the door,
and a wall-mounted electro-magnet.
6.
Break-glass Stations:
ASCO Model 124, for emergency
shutdown of computer power and air conditioning units.
7.
Graphic Annunciator Panel: Graphic annunciator panel shall be
map type, mounted in face of control panel, and one shall be
mounted in back box. This annunciator shall contain one pilot
light for each smoke detector installed below the raised floor of
the area. Pilot lights shall illuminate when the smoke detectors
are in alarm condition. The annunciator shall be a map of the
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-47
Fire Protection
Issued for Construction
1 June 2004
area containing the general outline of the walls, doors, etc., and
shall be geographically oriented to the area. The pilot lights
shall be arranged according to the locations shown on the plans.
The map shall show the location of the panel and shall have the
words “YOU ARE HERE” imprinted on the face. The face of
the annunciator shall be constructed of Plexiglas plastic laminate
with matte finish. The lines representing the walls and doors of
the area and other information lettering shall be engraved in the
surface. Pilot lights shall be red and shall be cylindrical type,
with flat face of the smoke detectors under the floor. Pilot lights
shall utilize LED lamps.
Provide lamp test pushbutton,
momentary type, so that, when depressed, all the lamps will
illuminate. Provide ten (10) spare lamps.
8.
All wiring connections within each panel shall be accessible
from the front when the doors are open. Backwired panels will
not be accepted. Wiring between components on the doors and
stationary components within the cabinet shall be neatly
bundled, harnessed and protected, and installed with enough
slack so that doors may be opened and closed without damaging
the wiring.
9.
Refer to preaction sprinkler section for detection devices
specified for “cross-zoned” operation.
10.
System Operations
a.
The smoke detection system shall consist of detectors
wired and zoned as indicated on the electrical drawings,
central control panel, power supply and auxiliary
functions as specified within the Electrical
Specifications.
b.
The system shall function as follows when any single
detector operates within the area.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
1)
Light proper zone indication and fire indication
on central control panel and graphic annunciator
panel.
2)
Sound alarm bell/lights.
3)
Initiate signal to building fire alarm system.
(Coordinate contact closure requirements.)
15500-48
Fire Protection
Issued for Construction
1 June 2004
c.
d.
11.
Subsequent operation of a "cross-zoned" detector within
the affected area shall:
1)
Sound alarm horn/lights.
2)
Silence alarm bell/lights.
3)
Actuate circuits to energize 0-30 second
adjustable "evacuation timer".
4)
Deactivate magnetic door releases.
5)
Light proper zone indication and fire indication
on central control panel and graphic annunciator
panel.
6)
Actuate signal to preaction valve.
7)
Initiate second zone signal to actuate circuits to
operate associated dampers and shut down
associated fans and air conditioning units.
Subsequent expiration of evacuation timer shall:
1)
Actuate circuit to release FM-200 gas into the
affected area.
2)
Cause alarm horn/lights to pulsate.
3)
Actuate circuits to deactivate electrical supply to
all computer equipment via shunt trip breakers.
e.
Manual FM-200 release stations shall be provided in
each of the areas. The stations, when activated, shall
immediately perform functions as noted in Paragraph b.
above (except when manual station has been activated,
the 30 second delay and "FM-200 Hold" circuit shall not
interrupt the release of FM-200).
f.
After 15 minutes soaking time, the affected area can be
purged by energizing the purge control key switch. It
shall be impossible to commence the purging operation
until 15 minute soaking time has transpired, except by
use of the Fire Department keyed bypass switch.
Installation: The system shall be installed in a workmanlike
manner, and in accordance with Specifications and standards
approved by all the authorities having jurisdiction.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-49
Fire Protection
Issued for Construction
1 June 2004
C.
FM-200 Hardware
1.
Provide a fixed piping system of FM-200 fire extinguishing of
the total flooding type. The number and capacity of agent
storage containers shall be as scheduled on the drawings, and
shall be in accordance with recommendations of the National
Fire Protection Association Pamphlet No. 2001, 1999, based on a
7% concentration, achieved within 10 seconds and held for 10
minutes, based on a minimum temperature of 21°C. The system
shall include the following major items listed below:
a.
The system shall be a total flooding FM-200
extinguishing system.
b.
The FM-200 agent shall be super-pressurized, with dry
Nitrogen, to an operating pressure of 25.3 kg./cm.2 at
21°C. Containers shall be of high-strength alloy steel
construction that complies with the Department of
Transportation regulation for refillable pressure vessels
and conform to NFPA 2001.
c.
Containers shall be actuated by parallel wired initiators
through a FIKE P/N 10-1832 Agent Release Module
(ARM) located at each agent container.
d.
Each container shall have a pressure gauge and low
pressure switch to provide visual and electrical
supervision of the container pressure. The low pressure
switch shall be wired to the control panel to provide an
audible and visual "Trouble" alarm in the event the
container pressure drops below 20 kg./cm.2 The
pressure gauge shall be color coded to provide an easy
visual indication of container pressure.
e.
Each container shall have a pressure relief provision that
automatically operates when the internal temperature
exceeds 66°C.
f.
Each container shall be fitted with a FIKE P/N 02-2394XX Liquid Level Device. It shall be possible to
determine the container agent quantity without removing
the container from its mounting bracket, disconnecting
the distribution piping, or removing the FM-200 system
from service.
g.
Pre-engineered or engineered discharge nozzles shall be
provided within the manufacturer's guidelines to
distribute the FM-200 throughout the protected spaces.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-50
Fire Protection
Issued for Construction
1 June 2004
The nozzles shall be FIKE P/N 80-XXXX, designed to
provide proper agent quantity and distribution.
h.
1)
Nozzles shall be available in NPT pipe sizes 6.3
mm. through 50 mm. Each size shall be
available in the 180 and 360 degree distribution
patterns.
2)
Deflector plates shall be used with the FIKE
Series 80 nozzles when sensitive ceiling tiles
must be protected.
The FM-200 shall be discharged in a manner which will
insure even distribution of the gas through nozzles in the
hazard. The nozzles shall be sized and located to
provide the rates or discharge and coverage needed.
(Note: Pipe runs have been indicated on the drawings.
Provide FM-200 pipe sizes to deliver the required rate of
flow at each nozzle. Flow rates shall be calculated based
on
NFPA-2001
3-1.2.5
"Flow
Calculations".
Calculations and drawings shall be submitted as a
package.) Nozzles shall be fabricated of corrosion
resistant materials or shall be finished with a protective
coating. Nozzles in which the horn, or shell, and orifice
piece are separate elements shall be designed so that the
orifice piece is connected directly to the supply pipe.
Separate orifice plates, which can be accidentally left out
without being readily noticed, shall not be used.
D.
Complete hydraulic flow calculations shall be provided for all
engineered FM-200 systems. Calculations sheet(s) must include the
manufacturer's name. The individual sections of pipe and each fitting to
be used, as shown on the isometrics, must be identified and included in
the calculation. Total agent discharge time must be shown and detailed
by zone.
E.
Provide 1 pressure-demand self-contained air breathing apparatus as
approved by the local standards. Mount apparatus in case on exterior of
protected spaces, where directed.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-51
Fire Protection
Issued for Construction
1 June 2004
PART 3 - EXECUTION
3.01
GENERAL INSTALLATION
A.
Where piping and head arrangements are indicated on the drawings, run
and arrange piping approximately as indicated on the drawings and as
directed during installation, as straight and direct as possible, forming
right angles or parallel lines with building walls and other pipes, and
neatly spaced. Erect all risers plumb and true, parallel with walls and
other pipes and neatly spaced.
B.
This Subcontractor shall provide all equipment and appurtenances
necessary to complete the installation according to Code requirements,
whether indicated on the drawings or not. Include in proposal the
complete installation of the quantity of heads indicated on the drawing
with all required piping, valves, etc. The layout to be determined and
shop drawings prepared after the tenant layouts and reflected ceiling
plans are available.
C.
Install sprinkler heads in all areas on a true axis line in both directions in
center of tile with a maximum deviation of 12.7 mm. plus or minus from
the axis line as established by the Engineer for use of all trades. At the
completion of the installation, remove and reinstall any heads found to
exceed the above mentioned tolerance. Install flush plate sprinkler heads
within manufacturer's tolerances. Prior to installation of flush plates,
notify Engineer and Consulting Engineer for verification of installation.
Install "U" bends for all pendent heads. Any heads found out of
tolerance shall be removed and reinstalled.
D.
Do not install pipes or other apparatus in a manner which interferes with
the full swing of the doors.
E.
The arrangement, positions and connections of pipes, drains, valves, and
the like, indicated on the drawings shall be followed as closely as
possible, but the right is reserved by the Engineer to change locations,
and elevations, to accommodate conditions which may arise during the
progress of the work, without additional compensation to this
Subcontractor for such changes, provided that no additional heads are
required and changes are requested prior to the installation of the work.
The responsibility for accurately laying out the work rests with this
Subcontractor. Should it be found that any work is laid out so that
interferences will occur, report that to the Engineer before commencing
work.
F.
Ream all pipe smooth before installation. Do not bend, split, flatten nor
otherwise injure pipe.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-52
Fire Protection
Issued for Construction
1 June 2004
3.02
G.
Provide protective pans under or over individual pipes passing high
voltage ( 415V) electrical bus duct or switchgear equipment. Construct
the pans of 12 gauge black iron with a 150 mm. lip, the corners being
welded to make the pans watertight. Give each pan three coats of RustOleum paint and support with pipe hangers, and drain clear of the bus
duct or switchgear.
H.
Install all pendent sprinkler heads in exposed hung ceiling areas, in strict
accordance with shop drawings. The Engineer reserves the right to
reject any and all installed heads not in accordance with the approved
shop drawings.
TESTS
A.
Test the systems before any paint is applied.
B.
Test all systems in full accordance with applicable Underwriters' and
Municipal requirements, but in no case shall the fire standpipe/sprinkler
system be tested at less than 200 lbs. hydrostatic pressure. Apply the test
for a minimum of two (2) consecutive hours with no loss in pressure.
Prior to applying the hydrostatic test, the system shall be tested with 345
kPa compressed air for a period of ten minutes with no loss in pressure.
C.
Subject exterior water piping to a hydrostatic test of 200 lbs. gauge, after
the pipe is laid and the trench partially backfilled (joints shall be left
exposed). Apply the test pressure to each valved section and maintain for
a period of two hours with no appreciable loss of pressure. Leakage
while testing should not exceed 3-1/4 quarts per 10 joints per hour.
Carefully examine exposed pipe, joints, fittings, valves, and hydrants
during the open trench test. Cut out and replace joints showing seepage
or slight leakage as directed. Before finished grading or final pavement
and not less than 30 nor more than 40 days after the pressure test, a
measured leakage test of the entire pipeline may be required at the
discretion of the Engineer. No piping installation will be accepted until
or unless this leakage is less than 380 liters per 24 hours per mile of pipe
per 25 mm. nominal diameter for pipe in 3.6 m. lengths in accordance
with AWWA Standards evaluated on a pressure basis of 1,035 kPa. In
calculating leakage, the Engineer will make allowance for added joints
in the pipeline above the normal unit lengths of pipe. Should the test of
any individual section of line show leakage greater than the specified
limit, locate and repair the defective joints until the leakage is within the
specified limits.
D.
Furnish and pay for all devices, materials, supplies, labor and power
required in connection with tests. Make all tests in the presence and to
the satisfaction of the Engineer, Insurance Underwriters and City
Inspectors having jurisdiction.
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-53
Fire Protection
Issued for Construction
1 June 2004
E.
Repair, or if required by the Engineer replace, defective work with new
work without extra charge to the Owner. Repeat tests as directed, until
all work is proven satisfactory.
F.
Restore to its original condition any work damaged or disturbed by tests,
engaging the original Trades to do the work of restoration.
G.
Notify the Engineer and Inspectors having jurisdiction at least 48 hours
in advance of making the required tests, so that arrangements may be
made for their presence to witness the tests.
H.
Test equipment in service and demonstrate that the equipment performs
the work intended for it and that it complies with the requirements of
these Specifications for such equipment.
I.
FM-200 System Performance Test: A competent field engineer in the
employ of the equipment manufacturer shall inspect the completed
installation and supervise the test.
J.
1.
With the FM-200 containers disconnected, the entire smoke
detection system shall be tested (in presence of the Engineer) to
demonstrate conformance with Article 2.17, Paragraph B.1.,
"System Operations". Upon satisfactory completion of such test,
the system shall be tested in the presence of the Engineer,
insurance underwriters, and City Inspectors having jurisdiction.
2.
Pressure test all FM-200 piping at 3,725 kPa for 15 minutes
with a maximum 550 kPa pressure loss.
3.
Enclosure Integrity Test: All FM-200 protected areas shall be
examined and tested (in accordance with NFPA 2000 –
Appendix B) to locate and effectively seal any air leaks that
could result in a failure of the enclosure to hold the specified
FM-200 concentration for the specified holding period. Air
leakage rate shall be determined by the ASTM E779-81
"Standard Test Method for Determining Air Leakage Rate by
Fan Pressurization". A complete report as described by the
ASTM Standard shall be provided at the conclusion of the test.
Test apparatus shall be manufactured by Retrotec, Infiltrec or
Contec.
Preaction Sprinkler System Performance Test: A competent field
engineer in the employ of the equipment manufacturer shall inspect the
completed installation and supervise the test.
1.
The entire smoke detection system shall be tested (in presence of
the Engineer) to demonstrate conformance with Article 2.16,
Paragraph B.10., "System Operations". Upon satisfactory
completion of such test, the system shall be tested in the
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-54
Fire Protection
Issued for Construction
1 June 2004
presence of the Engineer, insurance underwriters, and City
Inspectors having jurisdiction.
3.03
PIPE AND MATERIAL FINISHES
A.
All piping, hardware, trim, etc., shall be finished in accordance with this
Article, unless otherwise specified hereinbefore.
B.
The following hardware or trim shall be furnished with the finish
indicated. Where chrome plating is indicated, the item shall be polished
prior to plating so that no bumps, pits or burrs are visible in the finished
product.
1.
Fire standpipe hose valves,
couplings, hose nozzles and
chains in cabinets
Polished brass
2.
Fire standpipe hose valves,
hose couplings, hose nozzles)
and chains not in cabinet
Polished brass (satin finish)
3.
Fire standpipe hose reels
Polished brass
4.
Fire standpipe siamese
Polished stainless steel,
exact color shall be as
selected by Engineer
END OF SECTION
Museum of Islamic Art
Doha, Qatar
Z:\worldox\docs\122690\spc\00015628.DOC
15500-55
Fire Protection
Issued for Construction
1 June 2004
Download