TDS MT 277

advertisement
TDS MT
• Transient
Discriminating
(TD) Technology –
provides increased
service life
• Primary protection
– suitable for high
exposure sites
and point-ofentry protection
applications
• TDS-MT
configurable to
L-L, L-N, L-G or
N-G protection
• TDS-MTU provides
simultaneous
L-N, L-G & N-G
protection
• Small foot print
– effective use of
real estate
• 5 segment
electronic status
indication – displays
percentage of
capacity remaining
• CE, UL® 1449 Ed. 3
Listed
The CRITEC® TDS-MOVTEC family of surge diverters offers economical
and reliable protection from voltage transients in even the most strenuous
applications.
The small foot print provides integrators and OEMs with an effective use
of real estate when installing within panels and equipment.
Transient Discriminating (TD) Technology, which meets the safety standards
of UL®1449 Edition 3, provides a superior life by eliminating the common
temporary over-voltage failure mode of most SPDs. TD Technology is essential
for any site where abnormal over-voltages can occur or where the possible
catastrophic failure of traditional technologies can not be tolerated.
Alarm contacts are provided which may be used to shut down the system
or to activate an external warning if the internal surge material is below
optimum condition.
Model
Nominal Voltage, Un
System Compatibility
Max Cont. Operating Voltage, Uc
Stand-off Voltage
Frequency
Operating Current @ Un
Aggregate Surge Rating
Max Discharge Current, Imax
Nominal Discharge Current, In
Impulse Current, Iimp
Protection Modes
Technology
Voltage Protection Level, Up
Status
Dimensions H x D x W: mm (in)
Weight: kg (lbs)
Enclosure
Connection
Back-up Overcurrent Protection
Temperature
Humidity
Approvals
Surge Rated to Meet
Aggregate Surge Rating
Max. Discharge Current Imax
Voltage Protection Level, Up
@500A 8/20μs (UL SVR)
@Cat B3, 3kA 8/20μs
@20kA 8/20μs
TDSMT120
TDSMT277
TDSMTU277
110-120 V
230-277 V
TN-C, TN-S, TN-C-S, IT, TT
170VAC
400VAC
240V
480V
50/60Hz
25 mA
200kA 8/20μs
See table
100kA 8/20μs
See table
80kA 8/20μs
20kA 10/350μs
Single mode (L-L, L-N, L-G or N-G)
L-G, L-N, N-G
MOV/Silicon, TD Technology
760V @ 20kA
980V @ 20kA
See table
480V @ 3kA
750V @ 3kA
330V @ 500A
700V @ 500A
5 segment LED bar graph per phase, Normally Open Contact
140 x 45 x 150 (5.51 x 1.77 x 5.91)
0.6 (1.32)
UL94V-0 thermoplastic
≤16 mm² (#6AWG) connecting to M6 bolt
100A
-35°C to 55°C (-31°F to 131°F)
0% to 90%
AS3260, C-Tick, IEC® 950, UL® 1449 Ed 3 Recognized Component Type 2
ANSI®/IEEE® C62.41.2 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2 Cat A,
ANSI®/IEEE® C62.41.2 Scenario II, Exposure 3, Cat B, Cat C
100kA 8/20μs, 10kA 10/350μs
UL® 1449 Ed3 In 20kA mode
L-N
80kA
40kA
L-G
80kA
40kA
45 mm
N-G
40kA 8/20μs
20kA 8/20μs
140 mm
700V 700V 600V
<750V <870V <850V
<1200V <1290V <1200V
150 mm
Impulse Magnitude (8/20μs)
Features
CRITEC® Transient Discriminating MOVTEC
Expected Surge Life
L
TD
TD
N
TD
TD
Number of Impulses, per mode
TDS MT 120
TDS MT 277
TDS MTU 277
ANSI is a registered trademark of the American National Standards Institute. IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Incorporated.
IEC is a registered trademark of the International Electrotechnical Commission. UL is a registered trademark of Underwriters Laboratories, Inc.
WARNING
ERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials. Instruction sheets are available at www.erico.com and
from your ERICO customer service representative. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause
product malfunction, property damage, serious bodily injury and death.
Copyright ©2008 ERICO International Corporation. All rights reserved.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
www.erico.com
TDS MPM
CRITEC® Transient Discriminating
MOVTEC Protection Module
Features
• Modular design
– allows easy
replacement of
surge modules
• 5 segment
electronic status
indication –
displays percentage
of capacity
remaining
• Lug connection
– allows Kelvin
(in and out)
connection of
large cables
• Transient
Discriminating
(TD) Technology –
provides increased
service life
The CRITEC® Transient Discriminating
MOVTEC Protection Module (TDS-MPM)
integrates three CRITEC TDS-MOVTEC
units into one enclosure to simplify three
phase protection applications.
The TDS-MPM is ideal for primary pointof-entry protection applications where it
is connected to the main service panel.
Model
Nominal System Voltage, Un
Distribution System
System Compatibility
Max Cont. Operating Voltage, Uc
Stand-off Voltage
Frequency
Operating Current @ Un
Aggregate Surge Rating
Max Discharge Current, Imax
Nominal Discharge Current, In
Impulse Current, Iimp
Protection Modes
Technology
Status
Dimensions H x D x W: mm (in)
Weight: kg (lbs)
Enclosure
Connection
Mounting
Back-up Overcurrent Protection
Temperature
Humidity
Approvals
Surge Rated to Meet
TDSMPM277
240/415 V & 277/480 V
3Ph Y 4W+G
TN-C, TN-S, TN-C-S, TT
400/692VAC
440V N-PE; 480/831V L-N
50/60Hz
25 mA
200kA 8/20μs (L-N)
100kA 8/20μs L-N (NEMA®-LS1)
130kA 8/20μs N-PE (NEMA-LS1)
80kA 8/20μs
20kA 10/350μs L-N; 50kA 10/350μs L-PE
All modes protected
TD Technology and MOV/Silicon L-N
Triggered Spark Gap N-PE
(#16AWG) connecting wire
5 segment LED bar graph per phase
Normally open contact, 250V~/10A, ≤1.5mm²
306 x 170 x 241 (12.0 x 6.7 x 9.5)
5 (11)
Metal, IP33 (NEMA-2)
≤16 mm² (#6AWG) connecting to M6 bolt
Wall mount
100A
-35°C to 55°C (-31°F to 131°F)
0% to 90%
AS3260, C-Tick, IEC® 950
ANSI®/IEEE® C62.41.2 Cat A, Cat B, Cat C
Voltage Protection Level, Up L-N
N-PE
@Cat B3, 3kA 8/20μs
<750V <1.5kV
@20kA 8/20μs
<980V <2.3kV
Impulse Magnitude (8/20μs)
• Primary protection
– suitable for high
exposure sites and
point-of-entry
facility protection
170
mm
Expected Surge Life
L1
TD
TD
L2
L3
TD
306
mm
N
Number of Impulses, per mode
241 mm
ANSI is a registered trademark of the American National Standards Institute. IEEE is a registered trademark the Institute of Electrical
and Electronics Engineers, Incorporated. IEC is a registered trademark of the International Electrotechnical Commission. NEMA is a
registered trademark the National Electrical Manufacturers Association. UL is a registered trademark Underwriters Laboratories, Inc.
WARNING
ERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials.
Instruction sheets are available at www.erico.com and from your ERICO customer service representative. Improper installation,
misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction,
property damage, serious bodily injury and death.
Copyright ©2008 ERICO International Corporation. All rights reserved.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
www.erico.com
E710S-WWEN
E794LT07WWEN
0088.1M8
Download