Technical Data TD158002EN AEGIS Series line filters and surge protectors Effective August 2015 Technical data 2.87 (72.9) 2.87 (72.9) 4.44 (112.8) 2.51 (63.8) 4.83 (122.8) 4.83 (122.8) 4.98 (126.5) 4.98 (126.5) DIN rail to be mounted with screws provided using slots as template DIN rail to be mounted with screws provided using slots as template Figure 1. AGPHxxxxx dimensions Figure 2. AGPVxxxxx dimensions Table 1. AEGIS PH and PV specifications PH 120 Vac PH 240 Vac PV 120 Vac PV 240 Vac Specification 3, 5, 10, 15, 20 A 3, 5, 10, 15, 20 A 1, 3, 5 A 1, 3, 5 A DIN mounting UL 1283 5th Edition and UL 1449 4th Edition Filtering EMI/RFI filtering attenuation at 100 kHz L–G, L–N, and N–G protection modes Peak kA per phase/mode UL nominal discharge current (In) UL voltage protection rating (VPR) L–G / L–N / N–G MCOV Short-circuit current rating (SCCR) Alarm contacts Warranty (years) a Communication line protection (UL 497A) Yes Yes Yes 75 dB Yes 60/30 5 kA 330/400/330 150 5 kA Yes 15 No Yes Yes Yes 75 dB Yes 60/30 5 kA 600/700/600 275 5 kA Yes 15 No Yes Yes Yes 50 dB Yes 40/20 5 kA 330/400/330 150 5 kA No 15 No Yes Yes Yes 50 dB Yes 40/20 5 kA 600/700/600 275 5 kA No 15 No a With product registration. EATON www.eaton.com 3 Technical Data TD158002EN AEGIS Series line filters and surge protectors Effective August 2015 AEGIS CF The AEGIS Series CF devices provide the widest current ratings with line filtering and surge protection, and are available with optional communication line protection and status contacts. 1.36 (34.5) The AEGIS CF can be used where: 4.78 (121.4) • Higher kA of protection is required • Good filtering of electromagnetic interference (EMI) and radio frequency interference (RFI) is desired • Communication line protection is needed • 120/230/240 Vac or 24/48 Vdc circuits up to 60 A are to be protected 1.68 (42.6) Optional DIN Rail Mounting Kit (DINRAILKIT-1OACF) 1.25 (31.8) 2.47 (52.7) 3.75 (95.3) 4.41 3.36 (112.0) (85.2) 5.21 (132.3) 4.25 (108.0) Ø 0.19 (Ø 4.8) 3.36 (85.2) Figure 4. xxCFxxx10 dimensions 3.34 (85.0) 0.98 (24.8) 4.77 (121.1) 0.10 (2.5) 1.25 (31.8) 2.92 (74.2) 3.30 (83.8) Figure 3. AGCF12010-CP dimensions 3.12 (79.4) Figure 5. AGCFxxx10-DIN and AGCFxxx10-DIN2 dimensions 4 EATON www.eaton.com Technical Data TD158002EN AEGIS Series line filters and surge protectors Effective August 2015 2.25 (57.2) 4.69 (119.2) 4.72 2.59 3.50 (119.9) (65.7) (88.9) 3.20 (81.2) (4X) Ø 0.19 (Ø 4.8) 5.25 (133.4) 5.78 (146.7) 6.75 (171.5) 0.35 (8.9) DIN mounting each side (4X) 7.29 (185.0) (4X) Ø 0.19 (Ø 4.8) Non DIN mtg. Clear protective cover 3.79 (96.1) 1.88 (47.8) 3.23 (82.0) Optional DIN rail mounting kit (DINRAILKIT-30ACF) 4.50 (114.3) Optional DIN rail mounting kit (DINRAILKIT-60ACF) Figure 6. AGCFxxx15 and AGCFxxx30 dimensions Figure 7. AGCFxxx60 dimensions Table 2. AEGIS CF specifications CF 24 Vdc CF 48 Vdc CF 120 Vac Specifications 10 A 10 A 10 A 10 A 10 A 10 A 30 A 60 A 15 A 30 A 60 A 10 A DIN mounting UL 1283 5th Edition and UL 1449 4th Edition IEC 61000-4.5 Filtering EMI/RFI filtering attenuation at 100 kHz L–G, L–N, and N–G protection modes Peak kA per phase/mode UL nominal discharge current (In) UL voltage protection rating (VPR) L–G / L–N / N–G MCOV Short-circuit current rating (SCCR) Alarm contacts Warranty (years) b Communication line protection (UL 497A) Yes — No — Yes — No — Yes Yes No Yes Yes a Yes Yes a Yes Yes a — Yes a Yes Yes a Yes Yes Yes Yes Yes Yes Yes 40 dB 40 dB Yes Yes 40 dB Yes Yes 40 dB Yes Yes 40 dB Yes Yes 40 dB Yes Yes 40 dB Yes Yes 40 dB — — 40 dB — Yes 40 dB — Yes 40 dB Yes Yes 40 dB Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 6/2 N/A 6/2 N/A 20/6 N/A 20/6 N/A 30/10 3 kA 40/20 5 kA 80/40 5 kA 80/40 5 kA 120/60 3 kA 120/60 3 kA 120/60 3 kA 30/10 3 kA N/A N/A N/A N/A 500/500/500 500/500/500 500/500/500 500/500/500 800/800/800 800/800/800 800/800/800 990/980/960 30 30 10 kA 10 kA 50 10 kA 50 10 kA 150 10 kA 150 10 kA 150 10 kA 150 10 kA 275 10 kA 275 10 kA 275 10 kA 275 N/A No 10 No No 10 No No 10 No No 10 No No 10 No Yes a 10 Yes a Yes a 10 Yes a No 10 No Yes a 10 Yes a Yes a 10 Yes a No 10 No No 10 No CF 230 Vac CF 240 Vac a Optional. b With product registration. EATON www.eaton.com 5 Technical Data TD158002EN AEGIS Series line filters and surge protectors Effective August 2015 AEGIS CN Table 3. AEGIS CN specifications The AEGIS CN Series provides low-cost surge protection in a compact package. 24 Vdc 48 Vdc 120 Vac Specifications 30 A 30 A 30 A 30 A DIN mounting UL 1449 4th Edition Filtering L–G, L–N, and N–G protection modes Peak kA per phase/mode UL nominal discharge current (In) UL voltage protection rating (VPR) L–G / L–N / N–G MCOV Short-circuit current rating (SCCR) Alarm contacts Warranty (years) b Communication line protection (UL 497A) Yes a — No Yes Yes a — No Yes Yes a Yes No Yes Yes a — No Yes 20/6 N/A 46/20 N/A 80/40 5 kA 80/40 3 kA N/A N/A 500/500/500 800/800/800 30 10 kA 50 10 kA 150 10 kA 275 10 kA No 10 No No 10 No No 10 No No 10 No The AEGIS CN can be used where: • Only surge and transient voltage protection is needed • 120/230 Vac or 24/48 Vdc circuits up to 30 A are to be protected 2.25 3.20 (57.2) (81.2) 4.69 (119.2) (4X) Ø 0.19 (Ø 4.8) 5.25 (133.4) 5.78 (146.7) a Optional b With product registration. 1.88 (47.8) Optional DIN rail mounting kit (DINRAILKIT-30ACF) Figure 8. AGCNxxx30 dimensions 6 EATON www.eaton.com 3.23 (82.0) 230 Vac Technical Data TD158002EN AEGIS Series line filters and surge protectors Effective August 2015 Performance data • ANSI/UL 1449 Fourth Edition voltage protection ratings • UL 1283 Fifth Edition electromagnetic interference filter ratings Table 4. Specifications AEGIS Series Rating PH PV CF CN Application Single-phase, two- or three-wire grounded systems 100–127 Vac, 200–240 Vac N/A Single-phase, two- or three-wire grounded systems 100–127 Vac, 200–240 Vac N/A 3, 5, 10, 15, and 20 A 50/60 Hz L–N, L–G, and N–G 150 V and 275 V 74 dB at 100 kHz 1, 3, and 5 A 50/60 Hz L–N, L–G, and N–G 150 V and 275 V 56 dB at 100 kHz Single-phase, two- or three-wire grounded systems 100–127 Vac, 200–250 Vac 5–38 Vdc, 24–65 Vdc, 48–149 Vdc, 150–300 Vdc 10, 15, 30, and 60 A 50/60 Hz L–N, L–G, and N–G 150 V and 275 V 48 dB at 100 kHz Single-phase, two- or three-wire grounded systems 100–127 Vac, 200–250 Vac 5–38 Vdc, 24–65 Vdc, 48–149 Vdc, 150–300 Vdc 30 A 50/60 Hz L–N, L–G, and N–G 150 V and 275 V N/A 10 kHz to 100 MHz 60 kA / 30 kA 10 kHz to 100 MHz 40 kA / 20 kA 10 kHz to 100 MHz Up to 120 kA / 60 kA N/A Up to 80 kA / 40 kA –40 °F to +122 °F (–40 °C to +50 °C) <1 nanosecond UL 1449 4th Edition, UL 1283 5th Edition and CSA –40 °F to +122 °F (–40 °C to +50 °C) <1 nanosecond UL 1449 4th Edition, UL 1283 5th Edition and CSA –40 °F to +140 °F (–40 °C to +60 °C) <1 nanosecond xxCF230xx UL 1283 5th Edition, EMI filter xxCF120xx UL 1449 4th Edition, UL 1283 5th Edition xxCFxxx10-DIN2 UL 1449 4th Edition, IEC 61000-4.5 Type 2 10 years LED Yes c Optional –40 °F to +140 °F (–40 °C to +60 °C) <1 nanosecond xxCNxxx30 UL 1449, UL 1283 5th Edition, EMI filter xxCN12030 UL 1449 4th Edition 15 A—Eaton P/N: WMXT1C15 or equiv. 15 A circuit breaker 30 A—Eaton P/N: WMZT1C40 or equiv. 40 A circuit breaker 60 A—Eaton P/N: EGC3100FFG or equiv. 100 A circuit breaker Eaton P/N: WMZT1C40 or equiv. 40 A circuit breaker Input voltage range—AC Input voltage range—DC Amperage Frequency Protection modes MCOV Noise attenuation (normal mode) Filter bandwidth Peak surge current per phase / per mode Operating temperature Response time Agency approvals UL 1449 Type Warranty a Status indicator Form C contacts Communication line protection (UL 497A) External circuit breaker b Type 2 15 years LED Yes No Type 2 15 years LED No No Eaton P/N: WMZT1C25 or equiv. 25 A circuit breaker Eaton P/N: WMZT1C07 or equiv. 7 A circuit breaker xxCFxxx10-DIN2 UL 1449 4th Edition, IEC61000-4.5 Type 2 10 years LED No No a With product registration. b External circuit breaker sold separately. c Optional on 30 A and 60 A models only. EATON www.eaton.com 7