Technical Data

advertisement
Technical Data TD158002EN
AEGIS Series line filters 
and surge protectors 
Effective August 2015

Technical data
2.87
(72.9)
2.87
(72.9)
4.44
(112.8)
2.51
(63.8)
4.83
(122.8)
4.83
(122.8)
4.98
(126.5)
4.98
(126.5)
DIN rail to be mounted
with screws provided
using slots as template
DIN rail to be mounted
with screws provided
using slots as template
Figure 1. AGPHxxxxx dimensions
Figure 2. AGPVxxxxx dimensions
Table 1. AEGIS PH and PV specifications
PH 120 Vac
PH 240 Vac
PV 120 Vac
PV 240 Vac
Specification
3, 5, 10, 15, 20 A
3, 5, 10, 15, 20 A
1, 3, 5 A
1, 3, 5 A
DIN mounting
UL 1283 5th Edition and UL 1449 4th Edition
Filtering
EMI/RFI filtering attenuation at 100 kHz
L–G, L–N, and N–G protection modes
Peak kA per phase/mode
UL nominal discharge current (In)
UL voltage protection rating (VPR) L–G / L–N / N–G
MCOV
Short-circuit current rating (SCCR)
Alarm contacts
Warranty (years) a
Communication line protection (UL 497A)
Yes
Yes
Yes
75 dB
Yes
60/30
5 kA
330/400/330
150
5 kA
Yes
15
No
Yes
Yes
Yes
75 dB
Yes
60/30
5 kA
600/700/600
275
5 kA
Yes
15
No
Yes
Yes
Yes
50 dB
Yes
40/20
5 kA
330/400/330
150
5 kA
No
15
No
Yes
Yes
Yes
50 dB
Yes
40/20
5 kA
600/700/600
275
5 kA
No
15
No
a With product registration.
EATON www.eaton.com
3
Technical Data TD158002EN
AEGIS Series line filters
and surge protectors

Effective August 2015
AEGIS CF
The AEGIS Series CF devices provide the widest current ratings
with line filtering and surge protection, and are available with
optional communication line protection and status contacts.
1.36
(34.5)
The AEGIS CF can be used where:
4.78
(121.4)
•
Higher kA of protection is required
•
Good filtering of electromagnetic interference (EMI) and
radio frequency interference (RFI) is desired
•
Communication line protection is needed
•
120/230/240 Vac or 24/48 Vdc circuits up to 60 A are
to be protected
1.68
(42.6)
Optional DIN Rail
Mounting Kit
(DINRAILKIT-1OACF)
1.25
(31.8)
2.47
(52.7)
3.75
(95.3)
4.41 3.36
(112.0) (85.2)
5.21
(132.3)
4.25
(108.0)
Ø 0.19
(Ø 4.8)
3.36
(85.2)
Figure 4. xxCFxxx10 dimensions
3.34
(85.0)
0.98
(24.8)
4.77
(121.1)
0.10
(2.5)
1.25
(31.8)
2.92
(74.2)
3.30
(83.8)
Figure 3. AGCF12010-CP dimensions
3.12
(79.4)
Figure 5. AGCFxxx10-DIN and AGCFxxx10-DIN2 dimensions
4
EATON www.eaton.com
Technical Data TD158002EN
AEGIS Series line filters 
and surge protectors 
Effective August 2015

2.25
(57.2)
4.69
(119.2)
4.72
2.59 3.50 (119.9)
(65.7) (88.9)
3.20
(81.2)
(4X) Ø 0.19
(Ø 4.8)
5.25
(133.4)
5.78
(146.7)
6.75
(171.5)
0.35
(8.9)
DIN mounting
each side (4X)
7.29
(185.0)
(4X) Ø 0.19
(Ø 4.8)
Non DIN mtg.
Clear protective cover
3.79
(96.1)
1.88
(47.8)
3.23
(82.0)
Optional DIN rail
mounting kit
(DINRAILKIT-30ACF)
4.50
(114.3)
Optional DIN rail mounting kit (DINRAILKIT-60ACF)
Figure 6. AGCFxxx15 and AGCFxxx30 dimensions
Figure 7. AGCFxxx60 dimensions
Table 2. AEGIS CF specifications
CF 24 Vdc
CF 48 Vdc
CF 120 Vac
Specifications
10 A
10 A
10 A
10 A
10 A
10 A
30 A
60 A
15 A
30 A
60 A
10 A
DIN mounting
UL 1283 5th Edition and
UL 1449 4th Edition
IEC 61000-4.5
Filtering
EMI/RFI filtering
attenuation at 100 kHz
L–G, L–N, and N–G
protection modes
Peak kA per phase/mode
UL nominal discharge
current (In)
UL voltage protection rating
(VPR) L–G / L–N / N–G
MCOV
Short-circuit current
rating (SCCR)
Alarm contacts
Warranty (years) b
Communication line
protection (UL 497A)
Yes
—
No
—
Yes
—
No
—
Yes
Yes
No
Yes
Yes a
Yes
Yes a
Yes
Yes a
—
Yes a
Yes
Yes a
Yes
Yes
Yes
Yes
Yes
Yes
Yes
40 dB 40 dB
Yes
Yes
40 dB
Yes
Yes
40 dB
Yes
Yes
40 dB
Yes
Yes
40 dB
Yes
Yes
40 dB
Yes
Yes
40 dB
—
—
40 dB
—
Yes
40 dB
—
Yes
40 dB
Yes
Yes
40 dB
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6/2
N/A
6/2
N/A
20/6
N/A
20/6
N/A
30/10
3 kA
40/20
5 kA
80/40
5 kA
80/40
5 kA
120/60
3 kA
120/60
3 kA
120/60
3 kA
30/10
3 kA
N/A
N/A
N/A
N/A
500/500/500 500/500/500 500/500/500 500/500/500 800/800/800 800/800/800 800/800/800 990/980/960
30
30
10 kA 10 kA
50
10 kA
50
10 kA
150
10 kA
150
10 kA
150
10 kA
150
10 kA
275
10 kA
275
10 kA
275
10 kA
275
N/A
No
10
No
No
10
No
No
10
No
No
10
No
No
10
No
Yes a
10
Yes a
Yes a
10
Yes a
No
10
No
Yes a
10
Yes a
Yes a
10
Yes a
No
10
No
No
10
No
CF 230 Vac
CF 240 Vac
a Optional.
b With product registration.
EATON www.eaton.com
5
Technical Data TD158002EN
AEGIS Series line filters
and surge protectors

Effective August 2015
AEGIS CN
Table 3. AEGIS CN specifications
The AEGIS CN Series provides low-cost surge protection in a
compact package.
24 Vdc
48 Vdc
120 Vac
Specifications
30 A
30 A
30 A
30 A
DIN mounting
UL 1449 4th Edition
Filtering
L–G, L–N, and N–G
protection modes
Peak kA per phase/mode
UL nominal discharge
current (In)
UL voltage protection rating
(VPR) L–G / L–N / N–G
MCOV
Short-circuit current
rating (SCCR)
Alarm contacts
Warranty (years) b
Communication line
protection (UL 497A)
Yes a
—
No
Yes
Yes a
—
No
Yes
Yes a
Yes
No
Yes
Yes a
—
No
Yes
20/6
N/A
46/20
N/A
80/40
5 kA
80/40
3 kA
N/A
N/A
500/500/500
800/800/800
30
10 kA
50
10 kA
150
10 kA
275
10 kA
No
10
No
No
10
No
No
10
No
No
10
No
The AEGIS CN can be used where:
•
Only surge and transient voltage protection is needed
•
120/230 Vac or 24/48 Vdc circuits up to 30 A are to be protected
2.25 3.20
(57.2) (81.2)
4.69
(119.2)
(4X) Ø 0.19
(Ø 4.8)
5.25
(133.4)
5.78
(146.7)
a Optional
b With product registration.
1.88
(47.8)
Optional DIN rail
mounting kit
(DINRAILKIT-30ACF)
Figure 8. AGCNxxx30 dimensions
6
EATON www.eaton.com
3.23
(82.0)
230 Vac
Technical Data TD158002EN
AEGIS Series line filters 
and surge protectors 
Effective August 2015

Performance data
•
ANSI/UL 1449 Fourth Edition voltage protection ratings
•
UL 1283 Fifth Edition electromagnetic interference filter ratings
Table 4. Specifications
AEGIS Series
Rating
PH
PV
CF
CN
Application
Single-phase, two- or three-wire
grounded systems
100–127 Vac, 200–240 Vac
N/A
Single-phase, two- or three-wire
grounded systems
100–127 Vac, 200–240 Vac
N/A
3, 5, 10, 15, and 20 A
50/60 Hz
L–N, L–G, and N–G
150 V and 275 V
74 dB at 100 kHz
1, 3, and 5 A
50/60 Hz
L–N, L–G, and N–G
150 V and 275 V
56 dB at 100 kHz
Single-phase, two- or three-wire
grounded systems
100–127 Vac, 200–250 Vac
5–38 Vdc, 24–65 Vdc,
48–149 Vdc, 150–300 Vdc
10, 15, 30, and 60 A
50/60 Hz
L–N, L–G, and N–G
150 V and 275 V
48 dB at 100 kHz
Single-phase, two- or three-wire
grounded systems
100–127 Vac, 200–250 Vac
5–38 Vdc, 24–65 Vdc,
48–149 Vdc, 150–300 Vdc
30 A
50/60 Hz
L–N, L–G, and N–G
150 V and 275 V
N/A
10 kHz to 100 MHz
60 kA / 30 kA
10 kHz to 100 MHz
40 kA / 20 kA
10 kHz to 100 MHz
Up to 120 kA / 60 kA
N/A
Up to 80 kA / 40 kA
–40 °F to +122 °F (–40 °C to +50 °C)
<1 nanosecond
UL 1449 4th Edition, UL 1283
5th Edition and CSA
–40 °F to +122 °F (–40 °C to +50 °C)
<1 nanosecond
UL 1449 4th Edition, UL 1283
5th Edition and CSA
–40 °F to +140 °F (–40 °C to +60 °C)
<1 nanosecond
xxCF230xx UL 1283 5th Edition,
EMI filter
xxCF120xx UL 1449 4th Edition,
UL 1283 5th Edition
xxCFxxx10-DIN2 UL 1449 4th Edition,
IEC 61000-4.5
Type 2
10 years
LED
Yes c
Optional
–40 °F to +140 °F (–40 °C to +60 °C)
<1 nanosecond
xxCNxxx30 UL 1449, UL 1283
5th Edition, EMI filter
xxCN12030 UL 1449 4th Edition
15 A—Eaton P/N: WMXT1C15
or equiv. 15 A circuit breaker
30 A—Eaton P/N: WMZT1C40
or equiv. 40 A circuit breaker
60 A—Eaton P/N: EGC3100FFG
or equiv. 100 A circuit breaker
Eaton P/N: WMZT1C40
or equiv. 40 A circuit breaker
Input voltage range—AC
Input voltage range—DC
Amperage
Frequency
Protection modes
MCOV
Noise attenuation (normal
mode)
Filter bandwidth
Peak surge current per
phase / per mode
Operating temperature
Response time
Agency approvals
UL 1449 Type
Warranty a
Status indicator
Form C contacts
Communication line
protection (UL 497A)
External circuit breaker b
Type 2
15 years
LED
Yes
No
Type 2
15 years
LED
No
No
Eaton P/N: WMZT1C25
or equiv. 25 A circuit breaker
Eaton P/N: WMZT1C07
or equiv. 7 A circuit breaker
xxCFxxx10-DIN2 UL 1449 4th Edition,
IEC61000-4.5
Type 2
10 years
LED
No
No
a With product registration.
b External circuit breaker sold separately.
c Optional on 30 A and 60 A models only.
EATON www.eaton.com
7
Download