D-2 – SIMPLEX FIRE ALARM SYSTEM DESIGN STANDARDS The Life Safety of students and facility occupants is of the highest priority at Colorado College and the design of the Life Safety Fire Alarm system is not to be compromised. Colorado College provides all Residential and Academics Facilities with a Fire Alarm System designed to comply with and exceed minimum Fire Codes, including the following codes; • Uniform Fire Code • International Fire Code • NFPA 72 • A.D.A. Colorado College maintains a close working relationship with the Colorado Springs Fire Department, and the Fire Department is closely involved in the design, installation, and operation of the Life Safety Fire Alarm systems installed on the Campus. All work on any Fire Alarm system requires an installation permit by the Colorado Springs Fire Department. All Fire Alarm systems on the Campus are interconnected via a fiber optic network, and all system events from any Facility are displayed on graphic display computer screens in the Colorado College Security Office as well as on Network Display Units in the Power Plant for backup monitoring. Alarms from any campus facility are also transmitted to the SimplexGrinnell U.L Listed Monitoring Central Station for automatic Fire Department notification and dispatch. Each facility is provided with a Simplex Addressable Fire Alarm Control Panel and interconnected onto the Fiber Optic Network via a dedicated fiber loop configured per NFPA style 7. The design of the Life Safety System within each building includes the following components; • Main Fire Alarm Control Panel; Simplex 4100u or Simplex 4010 (small system) Installed in the building main electrical room or non public mechanical / utility room. • Remote Alarm Annunciator; Simplex 4603 or Simplex 4606 (compatible w/4010) • Manual Pull Stations; Simplex 4099-9003 installed at each building exit and at the entrances to the stairwells on all floors not at grade level. CC EDITION 10/04 SIMPLEX FIRE ALARM SYSTEM DESIGN STANDARDS D-2.1 • Smoke Detectors; Simplex 4098-9714 installed in each room with Fire Alarm Control equipment, within all commons areas and corridors, within electrical and telephone equipment rooms, attic areas, and mechanical areas. Sleeping rooms are provided with detectors that include sounder bases – programmed such that sleeping room smoke detectors initiate supervisory signals at the panel and the security office (not alarm) while at the same time activate the sounder base at the detector. The sounders are also programmed to activate upon any other alarm within the building itself to insure adequate alarm signal (sound pressure level) within the sleeping area and at the pillow level. Smoke detectors shall process smoke intrusion using the UL Listed / NFPA recognized Alarm Verification process except when directly activating control events per NFPA. • Heat Detector; Simplex 4098-9733 installed in mechanical spaces that are not heated and mechanical rooms that are too dusty/dirty to be detected with smoke detectors. • Duct Smoke Detectors; Simplex 4098-9756 installed within all fan units serving in excess of 2,000 cubic feet per minute (CFM) of air. Exhaust fans need not be equipped with duct smoke detectors. All fans shall be shut down upon detection of smoke within the associated duct smoke detector, or upon closure of smoke dampers within the building to prevent damage to ductwork. • Sprinkler Monitor Modules; Simplex 4090-9001 installed adjacent to, and for the purpose of monitoring all sprinkler waterflow switches and all sprinkler control valve (tamper) switch positions. An exterior horn/strobe to indicate sprinkler waterflow shall be installed above the fire department connection, and controlled by the Fire Alarm System. • Horn/Strobes; Simplex 4903 series horn/strobes and 4904 series strobe lights with white trim installed per NFPA 72. All facilities shall be compliant with ADA and select residential rooms within dormitories will be equipped with strobe lights for the hearing impaired. All sleeping areas shall be provided with notification devices capable of producing 75 db alarm signal at the pillow level. This level of signal shall be provided with a sounder base on the apartment detector and or mini-horn within the sleeping room itself. • Elevator Recall shall be provided for all elevators. Smoke detectors shall be installed in all elevator lobbies and machine rooms. Shafts are not to be sprinklered in Colorado Springs, so no smoke detectors will be required in the shaft, nor will there be a requirement for shunt trip heat detectors. Elevator recall shall include primary and alternate levels of recall, and a 3rd point to indicate an unsafe elevator condition (flashing hat within the elevator car). Control modules are Simplex 4090-9002. CC EDITION 10/04 SIMPLEX FIRE ALARM SYSTEM DESIGN STANDARDS D-2.2 • Smoke Damper Control; Smoke dampers shall be controlled by system connected smoke detectors and control modules per the Uniform/International Building Code. • Access Control System Interface; where doors are secured in the closed and locked position by the Simplex Access Control System, Interface modules are to be provided at each door location to release the door upon a building Fire Alarm condition. Simplex 4090-9002. As all components are an integral part of the overall Campus Network, the College has standardized on Simplex as the manufacturer for this equipment. All additions and modifications to the Colorado College Campus Fire Alarm system shall require the reprogramming of the Graphic Command Center in the Campus Security Office. All wiring is to be concealed and care is to be taken to insure proper support of conductors and to insure the integrity of the wiring will not be compromised by normal building operations including maintenance operations. The local SimplexGrinnell district office in Colorado Springs provides support for the Fire Alarm and Access Control systems installed in Colorado College. The contact information is as follows; SimplexGrinnell 915 Valley Street Colorado Springs, CO 80915 Phone Fax Contact (719) 277-0559 (719) 574-1253 Dave Sargent CC EDITION 10/04 SIMPLEX FIRE ALARM SYSTEM DESIGN STANDARDS D-2.3