P001_004.fm Page 1 Lundi, 15. novembre 2004 5:24 17 HV/LV distribution transformers TRIHAL cast resin dry type transformers 160 to 3150 kVA insulation level 24 kV - low voltage 400 to 433 V - 50 Hz thermal class F - ambient 40°C, altitude 1000 m c standards In accordance with standards: ■ IEC 60076-1 to 60076-5; ■ IEC 60076-11 (2004); ■ CENELEC (European Committee for Electrotechnical standardization) harmonization documents HD 538-1 S1: 1992 and EN 60726: 2003 / A2: 1991 / A3: 1992 concerning dry type transformers. ■ IEC 60905. common electrical characteristics frequency (1) maximum ambient temperature secondary voltage at no load (1) HV tapping range (off-circuit) (1) vector group partial discharges (5) 50Hz 40°C 400 to 433V between phases, 231 to 250V phase to neutral 2.5%, 5% Dyn (delta, star neutral brought out) 10 pC at 1.3 Un electrical characteristics for insulation level: 7.2 kV and 12 kV rated power (kVA) (1) (*) rated primary voltage (1) rated insulation level (3) losses (W) 400 630 800 160 (2) 250 5 to 11kV (dual voltage on request) 7.2kV for 5kV - 12kV for 11kV 610 820 1150 1370 1700 no load losses 3100 4300 6700 7700 load losses at 75°C 2300 load losses at 120°C 2700 3500 4900 7600 8800 rated impedance voltage (%) 4 4 4 6 6 no-load current (%) 2.3 2 1.5 1.3 1.3 13.5 13 13 10 10 switching current Ie/In (peak value) time constant 0.13 0.18 0.25 0.3 0.3 at 120°C 97.48 97.89 98.14 98.25 98.39 efficiency (%) load 100% cos ϕ = 0.8 load 75% cos ϕ = 0.8 at 120°C 97.83 98.17 98.40 98.53 98.63 62 65 68 70 72 noise level (3) acoustic power LWA dB(A) acoustic pressure LPA at 1 m 53 54 56 57 59 1000 1250 1600 2000 2500 3150 2000 8800 10000 6 1.2 10 0.34 98.52 98.75 73 60 2500 10500 12000 6 1.2 10 0.35 98.57 98.78 75 61 2800 12300 14000 6 1.2 9 0.42 98.70 98.90 76 62 3500 14900 17000 6 1.1 9 0.45 98.73 98.92 77 62 4300 18300 21000 6 1 9 0.5 98.75 98.94 81 66 5200 21800 25000 6 1 9.5 0.5 98.82 98.99 81 66 800 1000 1250 1600 2000 2500 3150 2000 8200 9400 6 1.3 10 0.3 98.25 98.50 72 59 2300 9600 11000 6 1.2 10 0.3 98.36 98.61 73 59 2800 11400 13100 6 1.2 10 0.35 98.43 98.66 75 61 3100 14000 16000 6 1.2 10 0.4 98.53 98.76 76 62 4000 17400 20000 6 1.1 9.5 0.4 98.52 98.75 78 63 5000 20000 23000 6 1 9.5 0.5 98.62 98.82 81 66 6300 23000 26000 6 1 9.5 0.5 98.73 98.90 81 66 electrical characteristics for insulation level: 17.5 kV and 24 kV rated power (kVA) (1) (*) rated primary voltage (1) rated insulation level (3) losses (W) 400 630 160 (2) 250 15 to 22kV (dual voltage on request) 17.5kV for 15kV - 24kV for 22kV 650 880 1200 1650 no load losses 3300 4800 6800 load losses at 75°C 2350 load losses at 120°C 2700 3800 5500 7800 rated impedance voltage (%) 6 6 6 6 no-load current (%) 2.3 2 1.5 1.3 10.5 10.5 10 10 switching current Ie/In (peak value) time constant 0.13 0.18 0.25 0.26 efficiency (%) load 100 % cos ϕ = 0.8 at 120°C 97.45 97.71 97.95 98.16 load 75% cos ϕ = 0.8 at 120°C 97.79 98.03 98.24 98.43 noise level (3) acoustic power LWA 62 65 68 70 dB(A) acoustic pressure LPA at 1 m 51 53 56 57 (*) the rated power is defined by natural air cooling (AN). Should there be particular constraints, it may be increased by 40 % by forced cooling addition (AF). Please consult us. (1) other possibilities upon request, consult us. (2) non standard ratings available on request. (3) reminder of insulation levels: rated insulation level (kV) 7.2 12 17.5 24 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 kV B.I.L. 1.2/50 µs 60 75 95 125 (4) according to IEC 551. (5) according to IEC 270. P001_004.fm Page 2 Lundi, 15. novembre 2004 5:24 17 HV/LV distribution transformers TRIHAL cast resin dry type transformers 160 to 3150 kVA insulation level 24 kV - low voltage 400 to 433 V - 50 Hz thermal class F - ambient 40° C, altitude 1000 m E/2 J J L dimensions and weights without enclosure housing (IP00) I Ø 13 prises de réglage C M H B Dimensions and weights indicated in the table below are provided as an example for single voltage transformers with insulation level 12kV (1st table) and 24 kV (2nd table), according to electrical characteristics shown page 1. Consequently, these tables give you approximate dimensions and weights for insulation level from 7.2 to 12kV (1st table) and from 17.5 to 24kV (2nd table). Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us). mise à la terre Ø 125 (160) 40 (50) D D E A insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V rated power (kVA) dimensions (mm) 160 Lenght A 1290 Width B 700 Connection height or Maximum height C 1325 Roller pitch D 520 Frame width E 645 Roller diam. F 125 Roller width G 40 860 Weight without enclosure (kg) 250 1315 705 1335 520 645 125 40 955 400 1325 795 1345 670 795 125 40 1185 630 1425 810 1540 670 795 125 40 1630 800 1455 825 1650 670 795 125 40 1770 1000 1525 945 1675 820 945 125 40 2125 1250 1605 945 1860 820 945 125 40 2580 1600 1665 945 2035 820 945 125 40 3210 2000 1760 1195 2180 1070 1195 160 50 3910 2500 1870 1195 2270 1070 1195 160 50 4480 3150 2100 1195 2345 1070 1195 160 50 6750 800 1540 830 1745 670 795 125 40 1930 1000 1630 945 1795 820 945 125 40 2350 1250 1615 945 2065 820 945 125 40 2750 1600 1825 950 2060 820 945 125 40 3670 2000 1885 1195 2325 1070 1195 160 50 4495 2500 1975 1195 2345 1070 1195 160 50 4975 3150 2295 1195 2400 1070 1195 160 50 7700 insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V rated power (kVA) dimensions (mm) 160 Lenght A 1290 Width B 700 Connection height or Maximum height C 1325 Roller pitch D 520 Frame width E 645 Roller diam. F 125 Roller width G 40 860 Weight without enclosure (kg) 2 250 1315 705 1335 520 645 125 40 955 400 1420 805 1425 670 795 125 40 1295 630 1480 820 1735 670 795 125 40 1695 France Transfo P001_004.fm Page 3 Lundi, 15. novembre 2004 5:24 17 HV/LV distribution transformers TRIHAL cast resin dry type transformers 160 to 3150 kVA insulation level 24 kV - low voltage 400 to 433 V - 50 Hz thermal class F - ambient 40° C, altitude 1000 m dimensions and weights with IP31 metal enclosure I Dimensions and weights indicated in the table below are provided as an example for single voltage transformers with insulation level 12kV (1st table) and 24 kV (2nd table), according to electrical characteristics shown page 1. Consequently, these tables give you approximate dimensions and weights for insulation level from 7.2 to 12kV (1st table) and from 17.5 to 24kV (2nd table). Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us). Ø 13 prises de réglage mise à la terre Ø 125 (160) C 40 (50) D B D A insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V rated power (kVA) dimensions (mm) Total weight (kg) 160 Lenght A 1650 Width B 950 Height C 1750 Roller pitch D 520 Frame width E 645 Roller diam. F 125 Roller width G 40 1040 250 1650 950 1750 520 645 125 40 1135 400 1700 1020 1900 670 795 125 40 1380 630 1700 1020 1900 670 795 125 40 1825 800 1700 1020 1900 670 795 125 40 1965 1000 2000 1170 2400 820 945 125 40 2390 1250 2000 1170 2400 820 945 125 40 2845 1600 2150 1170 2480 820 945 125 40 3535 2000 2330 1270 2650 1070 1195 160 50 4280 2500 2330 1270 2650 1070 1195 160 50 4850 3150 2600 1270 2650 1070 1195 160 50 7200 800 1800 1020 2050 670 795 125 40 2140 1000 2000 1170 2400 820 945 125 40 2615 1250 2150 1170 2480 820 945 125 40 3070 1600 2150 1170 2480 820 945 125 40 3995 2000 2330 1270 2650 1070 1195 160 50 4860 2500 2330 1270 2650 1070 1195 160 50 5340 3150 2600 1270 2650 1070 1195 160 50 8150 insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V rated power (kVA) dimensions (mm) Total weight (kg) France Transfo 160 Lenght A 1650 Width B 950 Height C 1750 Roller pitch D 520 Frame width E 645 Roller diam. F 125 Roller width G 40 1040 250 1650 950 1750 520 645 125 40 1135 400 1700 1020 1900 670 795 125 40 1490 630 1800 1020 2050 670 795 125 40 1905 3 P001_004.fm Page 4 Lundi, 15. novembre 2004 5:24 17 HV/LV distribution transformers TRIHAL cast resin dry type transformers 160 to 3150 kVA insulation level 24 kV - low voltage 400 to 433 V - 50 Hz thermal class F - ambient 40° C, altitude 1000 m minimum clearances required HV and LV standard connection connections cable support X LV LV n TRIHAL transformers without enclosure housing (IP 00) HV X X The winding resin coating and the plug-in connectors don’t ensure any protection against touch when the transformer is energized. HV X 120 120 mini mini insulation (kV) full wall 7.2 12 17.5 - 24 90 120 220 The contrator must ensure that cables and busbars are adequately supported to prevent mechanical stresses from being imposed on the transformer terminals, busbars or bushings. dimensions X (mm) grid wall 300 300 300 According to HD 637-1 Don’t take into account the access to tapping on the UV side. minimum clearances required TRIHAL transformers with IP 31 metal enclosure HV and LV connection 200 mm LV HV cable support HV n cable support 200 mm 200 mm LV 500 mm* *500 mm. for an access to tapping on the HV side, but 200 mm. minimum. LV terminations 23.5 4 x Ø 14 160 to 400 kVA* 500 to 800 kVA* 1000 to 1250 kVA* thickness 5 thickness 6 thickness 10 160 80 40 4 x Ø 16 50 50 4 x Ø 14 Ø 13 35 25 100 50 50 33 4 x Ø 14 80 33 23.5 33 33 Ø 14 70 33 15 40 HV terminations 2000 kVA* thickness 10 2500 kVA* thickness 210 1600 kVA* thickness 12 The contrator must ensure that cables and busbars are adequately supported to prevent mechanical stresses from being imposed on the transformer terminals, busbars or bushings. *Valid for aluminium terminations. Schneider Electric Industries SAS Adresse postale : france transfo BP 10140 F-57281 Maizières-lès-Metz cedex France tél : 33 (0)3 87 70 57 57 fax: 33 (0)3 87 51 10 16 http://www.schneider-electric.com AMTED 399003EN ART. 17813 /4 Due to the evolution of standards and materials, the present document will bind us only after confirmation from technical department. Publication : Schneider Electric SAS Conception, réalisation : COREDIT Impression : imprimerie Tecnodim GEa 26 k 11/2004