Regenerative AC Load Bank

advertisement
PEL Series
60kVA
Regenerative
AC Load Bank
www.InteproATE.com
THE POWER TEST EXPERTS
PEL Series
60kVA
Product Overview
The PEL Regenerative AC Electronic Load sets a new standard for
efficient testing of AC power devices. With the growing cost of power
energy, conservation has become a major concern and companies
are continually searching for ways to reduce costs. At over 90%
efficient the PEL regenerates power from the Equipment Under Test
(EUT) to the utility grid resulting in significant cost savings. The PEL
series is built around 60kVA chassis which may be paralleled for
higher power requirements.
PEL-33060
The PELs accept standard AC input ranges from 120 to 480V and
provide a grid-synchronized, regenerated AC power output from 120
to 480V. Three modes of load settings include Constant Current,
Constant Resistance and Constant Power. The PELs also provides
adjustable power factor from 0.3 to 1.0 to simulate poor power factor
load conditions. Add independent phase control and it’s apparent
why the PEL sets new standards for loading power devices.
The PAS-F offers load sequence transient generation for creating
complex, variable and repeatable load variations.
Program Mode
Independent programming for single or three phase
www.InteproATE.com
© 2016 Intepro Systems, LP. Specifications subject to change without notice.
PEL Series • 60kVA • Regenerative AC Load Bank
2
Featured Benefits
• Support single and three phase EUT’s
• Independent phase control
• Independent phase control
• Low input and output distortion
• Regenerates up to >90% of energy to the grid
• Compact design that minimizes floor space
requirements
• Applied digital synchronization technology with 0.98 utility power factor
• Selectable CC, CR, CP and Power factor
load control
• Load profile transient generation
• Integrated high accuracy measurements
• 7” touch panel interface
• Modbus RS485 and LAN Ethernet remote interfaces
• Built in power measurement system
Why choose PEL?
The PEL series is the smart alternative to the resistive loads typically used in test environments that
covert energy to heat which often results in costly cooling systems. By regenerating energy back to
the utility grid the PEL reduces energy cost and lowers the cost of ownership. The PEL also provide
accurate performance measurements for the Unit Under Test (UUT) for all phases of test from
engineering development, system evaluation, compliance testing and manufacturing tests including
burn-in.
Measure Mode
IIntegrated measurements of the load (EUT) and power
regenerated back to the grid.
www.InteproATE.com
© 2016 Intepro Systems, LP. Specifications subject to change without notice.
PEL Series • 60kVA • Regenerative AC Load Bank
3
PEL
UTILITY GRID
EUT
PEL
Options
Remote Options
• Webcomm Ethernet Connection
Best-in-Class
The PEL solutions are easily serviced by Intepro Systems, LP, an ISO 9001 certified company.
Intepro prides itself on best-in-class service support by minimizing the pains associated with system
failure and maximizing uptime of our products. In the unfortunate and rare event of failure, the
standard one year warranty includes ON-SITE repair. Returning high power products back to the
factory is expensive, impacts development schedules and furthers risk associated with lengthy transit
times. Extended service level agreements and yearly calibrations are available for up to five years.
www.InteproATE.com
© 2016 Intepro Systems, LP. Specifications subject to change without notice.
PEL Series • 60kVA • Regenerative AC Load Bank
4
Model Name
PEL-33060
Input Voltage
120V/208V, 220V/380V, or 277V/480V+/-10%
Input Frequency
Input
Working Mode
45~65Hz
Phase/Wire
3Phase/4Wire or Single Phase/2 Wire +G
Input Current
90A (Maximum)
Input THD
<4%
Input Power Factor
0.3~1
Constant Current (CC)
90A, PF: 0.3~1
Constant Resistor (CR)
2.4~44Ω(Each Phase), PF:0.3~1
Constant Power (CP)
0~20kVA(Each Phase), PF:0.3~1
120V/208V: 166A (Maximum)
Grid Connect Current
Grid-Connected Side
220V/380V: 90A (Maximum)
277V/480V: 72A (Maximum)
Grid Connect iTHD
<3%
Grid Connect Power Factor
0.99
Grid Connect Efficiency
Over Voltage/Under Voltage, Over Frequency/Under Frequency, Over Current,
IGBT Over Current, Over Temperature, Emergency Stop
Protection
Input Voltage
Input Frequency
Input Current
Input Power Factor
Measurement
>90%
Input Power (kW)
Grid Connect Voltage
Grid Connect Frequency
Grid Connect Current
Grid Connect PF
Grid Connect Power
Accuracy: 0.2V+0.1%FS
Resolution: 0.01V
Accuracy: 0.01Hz+0.01%FS
Resolution: 0.01Hz
Accuracy: 0.2A+0.1%FS
Resolution: 0.01A
Accuracy: +/-0.01
Resolution: 0.01
Accuracy: 0.2kW+0.1%FS
Resolution: 0.01kW
Accuracy: 0.2V+0.1%FS
Resolution: 0.01V
Accuracy: 0.01Hz+0.01%FS
Resolution: 0.01Hz
Accuracy: 0.2A+0.1%FS
Resolution: 0.01A
Accuracy: +/-0.01
Resolution: 0.01
Accuracy: 0.2kW+0.1%FS
Resolution: 0.01kW
Humidity: 0~90% Non-Condensing
Operate Environment
Working Temperature: -5~50deg C
Cooling Method
Fan
Dimension (WxDxH) mm/in
31.50x31.50x82.68 / 800x800x2100
www.InteproATE.com
© 2016 Intepro Systems, LP. Specifications subject to change without notice.
PEL Series • 60kVA • Regenerative AC Load Bank
5
Case Dimensions
(width x depth x height)
• 31.50 x 31.50 x 82.68 (in) / 800 x 800 x 2100 (mm)
Input Voltage Range
100V
110V
115V
110/190 V
115/200 V
1Ø2W+G
120/208 V
120V
127/220 V
200V
220/380 V
208V
220V
230V
230/400 V
1Ø2W+G or 3Ø3W+G
(∆-Connection)
240/415 V
254/440 V
240V
100/200 V
380V
110/220 V
400V
115/230 V
415V
440V
3Ø4W+G or 3Ø4W+N+G
(Y-Connection)
3Ø3W+G
(∆-Connection)
1Ø3W+G
Consult Intepro System for other Input Voltages
480V
Contact Us
United States
United Kingdom
China
Intepro Systems America, LP
14712-A Franklin Ave
Tustin, CA 92780
Tel: 1 714 953 2686
sales@inteproate.com
www.inteproate.com
Intepro UK Ltd.
9 Lakeside Business Park
Swan Lane, Sandhurst Berkshire
GU47 9DN / UK
Tel: 44 012 5287 5600
Intepro Power Electronics
(Shenzhen) Co., Ltd
No. 828, Block 7,
Fourth Industrial Area
Nanyou, Nashan District
Shenzhen, China 518052
Tel: 0086 755 86500020
www.InteproATE.com
© 2016 Intepro Systems, LP. Specifications subject to change without notice.
PEL Series • 60kVA • Regenerative AC Load Bank