Installation Manual

advertisement
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION.
FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS
MAY VOID YOUR WARRANTY!
The main power to any existing system must be disconnected prior to the installation.
The LUMEON 360™ is intended to be used for new outline lighting systems or as a replacement of existing
neon, fluorescent and other types of contour luminaries systems. When LUMEON 360™ is used to replace an
existing system, all existing system electrical components must be removed and replaced with LUMEON 360™
compatible components.
For neon outline lighting, the components to be replaced include neon tubes,
neon power supplies, and all secondary wiring.
For fluorescent outline lighting, the components to be replaced include fluorescent luminaries, and if used,
remote ballasts, and ballast secondary wiring.
Install in accordance with the NEC and Local Electrical Codes.
LUMEON 360™ SYSTEM INSTALLATION MANUAL
A./ REMOVAL OF EXISTING SYSTEM
1./ Disconnect main power to the existing luminary system by turning off the disconnect switch and
the main circuit breaker.
Note: Use AC power tester to verify that main power is off.
2./ Remove all existing transformers (or ballasts) and all wiring from transformer to the junction box
or disconnect switch.
1.
3./ Carefully remove all glass tubes, tube supports, sockets and secondary wiring.
Note: All removed material must be properly disposed to meet your local, state
and federal regulations.
Note: Existing neon tube supports can be used for installation of LUMEON 360
system. Spacing between tube supports must meet the requirements in section B4.
All neon tube supports must be the same type.
4./ Determine if existing transformer boxes and conduits are suitable for new wiring (see requirements
in section B13) and remove if not suitable.
B./ INSTALLATION OF LUMEON 360 SYSTEM
2.
1./ Determine the starting point for the installation. The starting point should be the same location as
the mounting location of first power unit. (Sample Dwg. 1)
2./ From the supplied layout drawing, determine length of first LUMEON 360™ tube group.
3./ Using a chalk string and a level, mark a line where tube supports for LUMEON 360™ tube will
be installed.
3.
4./ Mark the mounting position of all tube supports in the run. (Pic. 1 )
Note: Tube supports must be installed no more than 3 inches from end of the
LUMEON 360™ tube. Maximum spacing between two neighboring tube supports
should not exceed 24 inches.
5./ Mount all tube supports for the installed run. (Pic. 2 and 3 )
4.
6./ Attach all LUMEON 360™ tubes in the run to installed tube supports. (Pic. 4)
Note: If using standard neon tube supports, mounting method of the LUMEON 360™
tube is the same as mounting method for neon glass tube.
Note: If using LUMEON 360™ tube suport clips, position the tube above the clip with
flat area perpendicular to the mounted surface, insert tube into the clip and twist 90
degrees. Tube will lock in the clip.
Note: Do not push the ends of LUMEON 360™ tubes against each other. The PVC
rubber end caps should not be compressed at any time. PVC rubber End caps will
allow heat related length expansion of LUMEON 360™ tubes. (Pic. 5)
7./ Hold the two wires from the neighboring tubes as shown (Pic. 6 ). Cut the wires
approximately one inch from the tube support.
5.
6.
9./ Repeat steps 7 and 8 for other tube wires.
7.
8.
Continued on page 2
9.
© 20011-2015 LUMIFICIENT Corporation
Note: Do not use standard wire nuts to connect the tubes.
Doing so will void the warranty.
Use only UL Waterproof wire nuts to connect the tubes.
PATENTS PENDING
8./ Insert both wire ends to connectors (supplied with each order).
10.
11.
12.
Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with any
applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical Code (NEC).
B./ INSTALLATION OF LUMEON 360 SYSTEM (continued from page 1)
13.
10./ Fold the leads under the tube support and attach LUMEON 360™ tube. (Pic. 10 and 11)
Note: If using LUMEON 360™ tube support (mounting) clips, wires must be inserted
to the rectangular grove in the clip. (Pic. 12 )
11./ Connect all neighboring LUMEON 360™ tubes in this particular run.
Note: Individual runs are marked on supplied layout drawing by different colors.
Note: See chart below for proper loading of the LED Power Unit. (Attach. 1)
12./ Insulate the end leads on last LUMEON 360™ tube in installed run by inserting each wire end to
a separate UL waterproof wire nut connector. (Pic. 13 )
Note: Do not insert both wires to the same connector. Doing this will create a direct
electrical short which will damage the system.
15./ Verify that all accessible dead metal in the system is grounded to the power supply ground
connection. The metal base of a tube support does not need to be grounded.
16./ Connect the mounted power unit to the leads from first LUMEON 360™ tube. Manufacturer
recommends to use UL waterproof wire nut connectors (supplied with each order) to
electrically connect 12 AWG power limited cable leads with 18 AWG leads on LUMEON 360™
tube (Pic. 16,(17). (continued on next page)
NOTE: Do not use standard wire nut connectors.
Doing so will void the warranty. Use only UL Waterproof wire nuts.
Continued on page 3.
PATENTS PENDING
14./ Verify if a disconnect switch is present. National Electrical Code (NEC) requires a disconnect
switch with all electrical signs. If a disconnect switch is not present, it must be installed
between the main breaker and first power unit.
© 20011-2015 LUMIFICIENT Corporation
14.
13./ Mount the Power Unit near the beginning of the installed run. (Pic. 14 ) Transformer may
appear different than model shown depending on which model is specified for the installation.
Note: Power units shall not be mounted closer than 4 inches side to side and
1 inch end to end.
Note: Outdoor units are protected by a NEMA 3R rain tight enclosure. If mounted on
exterior wall without an additional wet rated enclosure, ensure that the Power Unit
is mounted vertically with conduit openings down.
Use only power units rated for exterior use. ( Attach. 1)
Note: It is required to use UL rated metallic or nonmetallic conduit between the junction
box and the power unit enclosure. Follow your local, state and federal regulations
for high voltage AC wiring.
Note: Do not connect outputs of two Power Units in parallel or in series!!!
Continued from page 2.
16./ (continued) Connect the 12 AWG power limited cable leads with the Class 2 Tr ansfor mer . The r ecommended
triple-output transformer is equipped with output screw terminals for direct connection. If using the recommended
single-output transformer, connect the output with the 12 AWG power limited cable with UL waterproof wire nuts.
Note: Confirm that all breaker switches inside of Power Units are in the ON Position.
Note: Follow primary voltage wiring instructions listed on the Power Unit lid for appropriate primary
voltage used on installation site.
Note: In interior applications, listed PLTC Class 2 rated cable is required for secondary wiring between Power Unit and LUMEON 360™ tubes. If low voltage wiring is routed though walls, attic
or other concealed space, the wiring must be enclosed in conduit or be rated for resistance to fire
in accordance with Article 725 of the NEC. Listed QPTZ power limited cable has been evaluated
for this application.
Note: Type PLTC cable that is sunlight resistant does not require enclosure in conduit
when used in concealed spaces and is also suitable where exposed to weather.
Note: The maximum length of low voltage power cable is 50 feet. Use of any cable other
than 10 or 12 AWG cable is not recommended and will void the product warranty.
Note: Follow your local, state and federal regulations for low voltage wiring.
Note: High voltage primary wiring, including wiring within 120VAC junction box, should comply with
any applicable grounding and bonding requirements in Article 600 of the 2005 National Electrical
Code (NEC).
© 20011-2015 LUMIFICIENT Corporation
18./ Test the sign by turning main power on.
Note: Do not touch any metal parts while testing.
Note: If Lumeon 360™ system is not working, please contact Customer Support by calling
1-877-383-4032.
PATENTS PENDING
17./ Repeat steps 2 to 16 for installation of each successive Lumeon 360™ run.
Last Updated: 02/17/15
FOR TECHNICAL ASSISTANCE OR CUSTOMER SUPPORT CALL (877) 383 4032
LUMIFICIENT CORPORATION
8752 Monticello Lane N, Maple Grove, MN 55369, U.S.A.
Phone: (763) 424-3702 Fax: (763) 390-3135 E-mail: technical@lumificient.com
120VAC
601-24-3R
24VAC
24VAC
24VAC
Output
Voltage
2.5A
4.0A
4.0A
Output Current Per
Terminal
1
3
3
Output
Terminals
(-30)°C - 55°C / (-22)°F - 131°F
(-30)°C - 55°C / (-22)°F - 131°F
(-30)°C - 55°C / (-22)°F - 131°F
Operating Temperature
1 x 32 feet
3 x 35 feet
3 x 35 feet
Maximum Footage
Per terminal (ALL
COLORS)
None
None
None
None
None
None
Interior enclosure
requirements
Exterior enclosure
requirements
Justin Inc.
Justin Inc.
Justin Inc.
Manufacturer
© 20011-2015 LUMIFICIENT Corporation
PATENTS PENDING
** Use of any different Class 2 Power Units than those listed above will void the Lumeon 360™ System limited warranty offered by Lumificient Corporation and may not by in compliance with UL 48 requirements.
Please contact Lumificient Corporation for an updated list of recommended Class 2 Power Units. Additional recommendations will accompany this manual as they are approved.
277VAC
120/240 VAC
C2288-24
C2288-24-277
Input Voltage
Type
Attachment 1
LIST OF RECOMMENDED CLASS 2 POWER UNITS FOR USE WITH LUMEON 360™ SYSTEM**
© 20011-2015 LUMIFICIENT Corporation
PATENTS PENDING