GENERAL CONCRETE NOTES REINFORCING NOTES STRUCTURAL STEEL/METALS MASONRY 1. Structural drawings are to be read in conjunction with other related drawings including existing drawings, for dimensions, elevations, roof and floor slopes and presence of openings, inserts, and existing underground services and mechanical/electrical elements. Do not scale off of the drawings or electronic/computer files, written dimensions always take precedent. Hard copy drawings are the official documents for the project and always take precedent over electronic/computer files. 1. a) All concrete shall conform to the requirements of CAN/CSA. A23.1. Cement shall be Type GU Portland Cement unless noted otherwise. Normal weight concrete for various purposes shall be as follows: 1. Reinforcing shall be new billet steel conforming to the following standards: 1. All structural steel work shall conform to CAN/CSA S16. 1. Masonry is designed in accordance with CAN/CSA S304.1. 2. All structural steel material shall conform to CSA G40.20/G40.21 with the following grades: 2. Masonry construction shall conform to CAN3-A371. Refer to Field Review and Testing section for testing requirements. 2. Prior to commencement of work, the Contractor shall compare all related drawings; confirm all dimensions and field measure/confirm all existing conditions. Report any discrepancies to the Architect and Engineer of Record ("Engineer" henceforth). MIN. 28 DAY STRENGTH MPa(psi) ELEMENTS MAX. SLUMP mm.(inch) MAX. SIZE EXPOSURE AGGREGATE CLASSIFICATION mm.(inch) Foundations and Footings 25 (3600) 75 (3") 20 (3/4") - Walls 30 (4350) 75 (3") 20 (3/4") F2 Columns 30 (4350) 75 (3") 20 (3/4") F2 Suspended slabs and beams 30 (4350) 75 (3") 20 (3/4") - 3. If discrepancies relating to structural work are found in the various documents, the more stringent provisions shall apply, unless approved by the Engineer. Specifications shall control over these drawings and General Notes only where the specifications provide for more stringent requirements. Contractor, suppliers and subtrades are to ensure that they are working with the 'Issued for Construction' drawings. 4. Bracing of the structure and all components during construction, including any underpinning, shall remain the sole responsibility of the Contractor. Arch. concrete (see Arch.) 5. These drawings show requirements for completed structure only. The design and inspection of falsework, shoring and reshoring is the responsibility of the Contractor and shall conform to WCB standards. Exterior 30 (4350) 75 (3") 20 (3/4") F2 Interior 30 (4350) 75 (3") 20 (3/4") - 6. All shop drawing reviews by the Engineer constitute review for general concepts only; the detailed design remains the responsibility of Contractor/Fabricator. All components shall be assembled and erected in accordance with final reviewed shop and erection drawings. No fabrication/erection shall proceed until review has been completed by the Engineer. Slabs on grade Exterior 32 (4650) 75 (3") 20 (3/4") C2 Interior 32 (4650) 75 (3") 20 (3/4") - 7. Design Loads: Topping concrete 32 (4650) 100 (4") 10 (3/8") - Masonry Grout 20 (3000) 200 (8") 10 (3/8") - a) Specified uniform loads (u.n.o. on plan) Live Load Roof Snow load based on: Importance = 1.25 Post-disaster Superimposed Dead loads Ss= 3.2 kPa Sr= 0.2 kPa 0.45 kPa Main Floor (4.8 kPa L.L. includes partitions) 0.4 kPa Lower floor 4.8 kPa 0.4 kPa Mechanical Room 4.8 kPa 0.4 kPa Stairs, Corridors and Storage 4.8 kPa 0.4 kPa Superimposed dead loads are non-structural dead loads including architectural topping, partitions (for LL<4.8 kPa) roofing material, pavers, ceiling finishes and mechanical/electrical conduits/fixtures. b) Seismic and Wind Seismic load based on: Importance = 1.5 Post-disaster Seismic Data Sa (0.2) Sa (0.5) 0.301 0.194 Sa (1.0) Sa (2.0) 0.108 0.063 PGA 0.145 Site Class D Fa = 1.28 Fv = 1.39 Rd = 1.5 Ro = 1.3 Wind load based on q 1/50 = 0.44 kPa Importance = 1.25 Post-disaster 8. These drawings show structural work required to meet provisions of Part 4 (and Part 9 where applicable) of the NBCC 2010. b) Slumps listed are before the addition of super plasticizers. Tolerance in specified slump shall be ± 20 mm (3/4"). c) No calcium chloride is permitted in any form in the concrete mixes. d) Submit mix designs to the Engineer and testing agency for review and approval prior to placement. Mix design submittals shall identify the elements for which they are intended. e) Fly ash replacement (where noted) is the mass of fly ash as a percentage of the total mass of cementing material. 10. All codes and documents referred to in these General Notes are to be the current adopted edition. 11. Supply of Record Drawings is outside the scope of services. FIELD REVIEW AND TESTING 1. The Contractor is solely responsible to give the Engineer reasonable advance notice of when structural work is ready for reviews by the Engineer (min. 24 hours prior to pour or concealment). Contractor is responsible for reviewing their own work and the work of their subtrades prior to review by the Engineer. 2. All structural work requires written review by the Engineer, including: a) b) c) d) Concrete Reinforcement Masonry Reinforcement (including non-load bearing partitions) Structural Steel (including decking) Wood framing (including sheathing) 3. Material testing shall be directed by the Engineer at the expense of the Owner. 4. Concrete testing shall be in accordance with CAN/CSA A23.2 and carried out by an independent testing agency approved by the Engineer. Unless permitted by the Engineer, a minimum of 3 test cylinders shall be cast for each 50 cu. meter/50 cu. yards or each day's pour, whichever is less. Test one at 7 days and two at 28 days (with two additional at 56 days when concrete mix exceeds 25% flyash replacement). Submit written reports for review by the Engineer. Test reports shall identify the locations where concrete is being tested with gridlines and elevations. 5. Submit concrete test results max. 24 hours after test. 6. The Owner shall appoint an independent CSA certified testing agency to carry out representative testing of bolt torque and welding on structural steel work, including decking. This testing shall take place prior to concealment of all structural steel. 7. All structural steel welds shall be tested by a qualified testing agency to the following criteria (u.n.o.): a) Ultra sonic test 100% of all shop and field complete penetration (CP) welds. b) Magnetic particle test 15% of all field fillet welds. c) Visual inspection of 100% of all shop and field welds. 8. Additional testing and field review resulting from rejection of more than 5% of work will be at the Contractor's expense. 2. Follow all recommendations given in soils report for preloading, backfill, drainage, sub-base preparation and other requirements. 3. Contractor is solely responsible to ensure that Geotechnical Engineer reviews and confirms allowable bearing pressure and approves subgrade installation prior to pouring concrete for footings foundations. 4. The Owner shall retain an approved testing agency to carry out density testing of subgrade and base material. Testing of subgrade material is to be carried out immediately prior to installation of slab on grade components and during lifts as specified by the Geotechnical Engineer. Care must be taken not to disturb subgrade after approval and prior to pouring concrete. a) b) c) d) e) f) g) 75mm (3") 50mm (2") 32mm (1 1/4") 40mm (1 1/2") 50mm (2") 25mm (1") 40mm (1 1/2") 40mm (1 1/2") 25mm (1") 40mm (1 1/2") 40mm (1 1/2") 75mm (3") 50mm (2") 32mm (1 1/4") 50mm (2") 50mm (2") 40mm (1 1/2") 50mm (2") 40mm (1 1/2") 40mm (1 1/2") ---40mm (1 1/2") 4. Site bending of bars is not permitted without prior approval of Engineer. 5. Provide epoxy coated rebars where noted on plan in accordance with CAN/CSA S413 (Parking Structures). Chair bars with plastic chairs and tie with plastic coated wire. 6. Minimum reinforcement shall be as follows unless otherwise noted: a) Wall reinforcement: 150mm (6") wall - 10M @ 300 (12") VERT., 10M @ 300 (12") HOR., CENTERED 200mm (8") wall - 15M @ 450 (18") VERT., 15M @ 450 (18") HOR., CENTERED 250mm (10") wall - 10M @ 400 (16") VERT., EACH FACE STAGGERED 10M @ 400 (16") HOR., EACH FACE STAGGERED 2-15M verts full height at ends of all walls unless noted otherwise 100mm (4") 10M @ 500 (20") o.c. EACH WAY 125mm (5") 10M @ 400 (16") o.c. EACH WAY 150mm (6") or less 10M @ 300 (12") o.c. EACH WAY 175mm (7") 15M @ 500 (20") o.c. EACH WAY 190mm to 215mm (7 1/2" to 8 1/2") 15M @ 450 (18") o.c. EACH WAY 225mm to 250mm (9" to 10") 15M @ 400 (16") o.c. EACH WAY 275mm to 300mm (11" to 12") 15M @ 350 (14") o.c. EACH WAY Concrete topping (ie: over steel deck) 152x152 MW 9.1 x MW 9.1 welded wire mesh 5. Unless otherwise noted, apply one shop coat of primer to all steel work, to CISC/CPMA 1-73A Primer for exterior exposure shall be zinc-chromate Type 1, conforming to CGSB1-GP-40d. 8. Apply 2 coats of Galvcon paint protection to hot dipped galvanized surfaces damaged by transportation, erection or site welding. 9. Unless noted otherwise, design structural steel connections for minimum half the shear or compression capacity of the members connected (design by the Fabricator's Engineer). Bolted connections shall consist of a minimum 2-19mmØ (3/4"Ø) A325 bolts with 9mm (3/8") connector plate, unless noted otherwise. 10. Submit 4 sets of shop drawings for the above to the Engineer for review prior to fabrication. Shop drawings shall show all details, and indicate all applicable design loads and material specifications and shall include an erection layout for all members. When member design forces are shown on plan or details, shop drawings shall be submitted and sealed by a Professional Engineer registered in the province of B.C. Do not proceed with fabrication until shop drawings have been approved by the Engineer. They shall be designed by Specialty Structural Engineers, registered in the province of British Columbia and RETAINED BY THE CONTRACTOR, who will seal all related shop drawings, review the components and their attachments in the field and provide all required sealed letters (Schedule S-B & S-C) to the Engineer. 11. The Professional Engineer sealing the Fabricators shop drawing is also responsible for all field review of their work and shall provide a letter to the Engineer confirming that the work has been completed in accordance with the final reviewed steel shop drawings and all structural requirements. 12. All fabrication and welding exposed to view to be appearance quality to the Architect's satisfaction. 13. See Architectural drawings for miscellaneous steel components. Any steel components not shown on the Structural drawings are considered to be Secondary components (see notes on Secondary components and their attachments). Assume 6mm (1/4") thickness, u.n.o. 14. Provide cap plates at open ends of HSS tubes (seal weld all around). Provide drain hole at base of HSS tubes. 15. Unless noted otherwise, welds shall be 6mm fillet welds. 16. Welding of reinforcing to embedded plates is permitted only with weldable deformed bar anchors with the following fillet weld sizes: 10M (3/8")Ø 15M (5/8")Ø 20M (3/4")Ø Make provisions to heat mix water or aggregate to maintain a minimum concrete temperature of 10°C. ii) Make provisions to heat the form work or soil surface. Concrete shall not be poured against any surface with a temperature less than 3°C (Calcium chloride or other de-icing salts are not permitted). iii) Cover concrete with insulation blanket for the first 36 hours after pouring concrete. Do not pour when temperature is expected to fall below -10°C within 3 days after pouring. iv) Make provisions for a heated enclosure to maintain the temperature of all concrete surfaces above 10°C for a minimum of 3 days after the pour. v) Provide alternate mix designs for cold weather. b) When the temperature is expected to rise above 25°C the Contractor shall: i) Make provisions to cool concrete to maintain a max. temperature of 30°C. ii) Make provisions to prevent concrete from drying. d) Other locations not identified above: 15M @ 400 (16") 7. All bars shall be continuous, properly lapped at splices. At corners and intersections; horizontal reinforcement shall be bent and lapped. 17. 8. Unless noted otherwise, lap lengths, including dowels, for 400 MPa (58 ksi) reinforcement shall be as follows: Epoxy coated bars Grout fill all voids on underside of all base plates and bearing plates in contact with concrete or masonry with a plastic consistency non-shrink grout with a minimum 7 day strength of 45 MPa (6500 psi). Follow manufacturer's specifications and instructions for mixing and placement. 18. If the structural steel member size specified on the structural drawings is not available then the Contractor shall notify the Engineer immediately and allow for the next available size up. 19. All embed plates with headed stud anchors to be fillet welded, unless approved by the Engineer (ie: fusion machine welds not permitted). Fillet weld sizes to be similar to note 16 u.n.o. 20. Contractor is responsible for the cost of any member upsizing due to availability of sizes/grades specified. 10M - 400mm (16") 15M - 600mm (24") 20M - 750mm (30") 25M - 1170mm (46") 30M - 1400mm (55") 10M - 500mm (20") 15M - 750mm (30") 20M - 980mm (39") 25M - 1530mm (60") 30M - 1840mm (72") a) Lap splices not shown on drawings shall not be allowed unless approved in writing by the Engineer. 9. Unless noted otherwise, openings in walls and slabs shall have 2-15M extra each side extending 600mm (2'-0") past corners, plus 2-15M x 1200mm (4'-0") diagonal each corner. 10. Welding of reinforcing to embedded plates is permitted only with weldable deformed bar anchors with the following fillet weld sizes: 10M (3/8")Ø - 6mm (1/4") 15M (5/8")Ø - 10mm (3/8") 20M (3/4")Ø - 12mm (1/2") 11. Provide contingency reinforcing additional to all other requirements, with "add" and "delete" unit prices included in bid. Include reinforcing required for non-structural concrete and masonry shown on the various drawings. 12. Reinforcing not indicated on the structural drawings needed for mechanical/electrical support (i.e. radiant piping, conduit, etc) is the responsibility of the contractor. SUSPENDED CONCRETE SLABS / SLAB BANDS AND BEAMS 2. Embedded conduits and pipes 9. Take measures to minimize shrinkage cracking including covering and dampening concrete in the curing stage. 11. Unless otherwise noted, where expansion anchors are required, use Hilti KB 3 or approved equal. Where chemical anchors are required, use Hilti HIT HY150 MAX epoxy, or approved equal. PRECAST CONCRETE 1. Steel roof decking and floor decking shall be as per plan. Roof decking shall conform to CSSBI 10M; floor decking shall conform to CSSBI 12M. Interior decking shall have a minimum zinc coating of ZF75 to CSSBI 101. Exterior decking shall have a minimum zinc coating of Z275 to the same standard. Unless noted otherwise on the drawings, provide 76mm deep (3") roof deck type RD306 and floor deck type HB938 by VicWest or approved equal. Place sheets in minimum 3 span lengths, unless noted otherwise on the drawings. 2. Unless noted otherwise, as a minimum, fasten deck to supports and perimeter elements with Hilti Direct fasteners (X-EDN19 THQ12, X-ENP-19 L15, X-EDNK22 THQ12 as applicable) @150mm o.c. longitudinal & @ 610/5 pattern transverse. Screw side lap with Hilti #10 screws (SLC) @ 300mm o.c. maximum. Refer to manufacturer's installation requirements and recommendations. Use button punch @300 for composite concrete decks. 4. Unless noted otherwise, reinforce all roof deck openings greater than 150mm (6") square and less than 400mm (18") square with L38x38x5 (L1 1/2"x1 1/2"x3/16") extended and puddle welded to minimum two flutes on each side of opening. Frame larger openings with L75x75x6 (L3"x3"x1/4") extending to main structural members or as shown on the drawings. 7. Storage of precast units on site shall be such to prevent staining, contamination by earth and penetration of water. 8. Concrete placed under water shall conform to CAN/CSA-A23.1. 8. The Contractor is responsible for providing all necessary bracing as required for construction loads, stability and for resistance to wind and seismic forces. b) Do not place embedded conduits or pipes within 300mm (12") of columns or walls and do not place embedded ducts within 600mm (24") of columns and walls. 6. Unless noted otherwise, provide L100x100x6 (L4"x4"x1/4") frame under all roof top mechanical units. Contractor shall be responsible to coordinate the number and locations of mechanical units with the Mechanical Consultant. c) Maximum conduit size in one layer shall be 1/4 slab thickness and maximum total size of conduits crossing shall be 1/3 slab thickness. 7. Unless noted otherwise, provide L75x75x6 (L3"x3"x1/4") continuous at perimeter of all steel deck floors and roofs. d) Separate parallel conduits minimum 3 times the larger diameter, center to center, with a minimum clear distances of 50mm (2"). e) Maximum in slab ducts shall be 50mm in a 175mm (2" in 7") slab, clear distance between ducts shall be minimum 600mm (24") and minimum distance to walls and columns shall be 900mm (36"). f) Position conduit between top and bottom reinforcement with no more than two layers of conduits crossing. Add reinforcing, relocate conduits or thickening slab at points of congestion as directed by the Engineer at the Contractor's expense. 8. Shop drawings for decking (4 sets) shall be submitted for review prior to fabrication and are to be sealed by a Professional Engineer registered in B.C. Shop drawings shall show all details and indicate all applicable design loads and material specifications. Design of deck to be verified by Fabricator's engineer for loads and spans shown on the drawings. Provide temporary shoring to composite decking as necessary. Any deck capacities and detailing discrepancies identified by the Fabricator's Engineer should be discussed with the Engineer prior to shop drawing final submittal. g) h) In beams, maximum conduits size parallel to the span must not exceed 2% of the cross section area of the member. Do not tie conduits / pipes along length of parallel reinforcing. Space minimum 25mm (1") from bars. 3. Sleeves and openings. a) Single openings/sleeves in slabs larger than 300mm (12") or a group of openings/sleeves total in area greater than 0.1 sq. meter in any 1 sq. meter (1 sq. ft. in 10 sq. ft.) is not permitted unless shown on structural drawings. b) Do not place openings/sleeves through slab within 600mm (24") of columns, ends and intersections of wall. c) Spacing between openings/sleeves through slab shall be not less than 2 times the larger opening size with minimum 100mm (4") clear distance. 9. The Contractor shall provide a suitable top finish to accept direct application of finish flooring/roofing per architects requirements. 10. Where structural concrete topping is to be applied, top surface of precast unit shall be raked (roughened) for bonding of topping, u.n.o. d) 11. Minimum topping thickness (as shown on plan) to be at crown of panel. Contractor to coordinate the panel bearing height to suit required elevations. Openings/sleeves through beams in any directions are not permitted without the written approval of the Engineer. 4. Beams, slab bands and slabs shall be cambered 6.4mm (1/4") for each 3000mm (10'-0") of span (both top and bottom surface). Where footing elevations vary, follow requirements of typical details shown on drawing. Contractor shall establish footing elevations based on all requirements including maximum slopes, and Electrical, Mechanical and Architectural information. 5. Submit locations of construction pour joints together with pour sequence to the Engineer for review prior to framing. 13. Footing elevations, if shown, are for bidding purposes only, are not final, and may vary according to site conditions. All footings must be taken to a bearing layer approved by the Geotechnical Engineer. 6. See concrete section of "Concrete Notes" for stripping of forms. Reshoring of suspended slabs must be approved by Shoring Engineer prior to stripping. Shores shall remain until specified strength has been reached and minimum 28 days after pour (minimum 56 days if fly ash content exceeds 25%). Bearing surfaces must be protected from freezing before and after footings are poured. 7. Minimum reinforcing: DRAWING LIST No. DWG. No. DWG. TITLE 5. Unless noted otherwise, reinforce all floor deck openings greater than 150mm (6") square and less than 400mm (18") square with 3-10M, 4-sides of opening, extend bars 200mm (8") min. past edge of opening, plus 1-10M x 600mm (24") at each corner. Frame larger openings with L100x100x6 (L4"x4"x1/4") extending to main structural members or as shown on drawing. Embedded conduits (ducts and pipes) are subject to approval by the Engineer, submit layout to the Engineer for review. 3. Precast/prestressed concrete work shall be in accordance with CSA A23.3 and A23.4. 4. Precast Manufacturer shall be submit 4 sets of shop drawings of all precast units to the Engineer for review prior to fabrication. Shop drawings shall show all details, including design loads, material specifications, embedded mechanical items, etc. Shop drawings to be sealed by a Professional Engineer registered in the province of British Columbia. a) b) c) d) Cold-drawn steel wire Welded steel wire fabric Deformed steel wire Steel bar reinforcing - G30.3 G30.5 G30.14 CSA-G30.18 7. Lap splices to be as follows, unless otherwise noted. Wire reinforcing 10M 15M 20M 25M 200mm (8") 450mm (18") 650mm (26") 900mm (36") 1300mm (51") a) b) c) d) See minimum reinforcing in Reinforcing Notes. 1-15M top and bottom continuous at edge of slab. 2-15M each side of openings (extending 600mm (2'-0") pass edge of opening). plus 1-15M 1200mm (4'-0") diagonal, top and bottom, at each corner. 2-15M 1200mm (4'-0") diagonal top at re-entrant corners. 1 S1.0 GENERAL NOTES 2 S2.0 LOWER FLOOR/FOUNDATION PLAN 3 S2.1 MAIN FLOOR PLAN 4 S2.2 ROOF PLAN 5 S3.0 TYPICAL SECTIONS AND DETAILS 6 S3.1 TYPICAL SECTIONS AND DETAILS 2-C15M @300 H2E - means two 15M bars spaced at 300mm (12") with 90° CSA standard hook at two ends. 7 S4.0 WALL ELEVATIONS 4-15M @300 H2E 450 - means four 15M bars spaced at 300mm (12") with 450mm (18") long 90° hook at two ends. 8 S4.1 WALL ELEVATIONS 9 S5.0 SECTIONS AND DETAILS 10 S5.1 SECTIONS AND DETAILS 11 S5.2 SECTIONS AND DETAILS 12 S5.3 CANOPY SECTIONS AND DETAILS 8. Unless noted otherwise: a) b) c) Reinforcement shown on plan thus: Top Reinforcement Bottom reinforcement Reinforcement notation callup: 12-20M4900 - means twelve 20M bars, 4900mm (16'-0") long. 2-C15M1800 - means two 15M bars, 1800mm (6'-0") long with 90° CSA standard hook. (length includes standard hook) Center slab and beam top reinforcement over supports. Hooks shown are CSA standard hooks. 9. See minimum reinforcing notes for slab temperature steel. Place temperature steel immediately above and transverse to slab bottom steel, u.n.o. 10. Shear studs indicated on plan to be Decon Studrails (or approved equivalent by the Engineer in accordance with ASTM-A108 & A1044 [Fy= 350 MPa (51 ksi), Fu= 450 MPa (65 ksi)]. Studs to be welded in accordance to AWS D1.1 & CSA W59. Refer to "Field Review and Testing" section for testing requirements. 8. Unless otherwise noted, provide 1-15M vertical full height at: a) Ends of walls b) Corners and intersections c) Each side of doors, other openings and control joints d) 800mm (32") o.c. for structural masonry wall, 1200mm (48") o.c. for non-load bearing masonry partition. 9. Provide hooked dowels from bottom of concrete base to match vertical masonry wall reinforcing. The Contractor and Masonry Contractor shall ensure that dowels are centered accurately with cells over. 10. All bars must be continuous, properly lapped at splices. At corners and intersections, horizontal reinforcement shall be bent and lapped. 11. Unless noted otherwise, horizontal reinforcement in regular block masonry shall consist of: a) b) c) 12. 9 ga. ladder type joint reinforcement at 400mm (16") on center, lap 200mm (8"). 2-15M above and below openings less than 2400mm (8'-0") wide; extend bars 600mm (24") past edges of openings. (See also requirements for lintels). 1-15M continuous in each of two grouted bond beams at 2400mm (8'-0") on center and at top of wall. Where H block masonry is specified on the drawings or specifications, horizontal reinforcing shall consist of the following (unless noted otherwise): a) b) c) 9 ga. ladder type joint reinforcement at 400mm (16") on center, lap 200mm (8"). 1-15M continuous at 1200mm (4'-0") on center and at top of wall. 2-15M above and below openings as in regular block masonry. 13. Cells to be grouted shall be kept clear of mortar and conduits or other materials unless approved by the Engineer. 14. Fill cells containing reinforcement and inserts with concrete as per the "Concrete Notes" section. Vibrate concrete completely in filled cells. 15. Unless approved by the Engineer, fill cells in 1200mm (4'-0") high lifts or, if clean-outs are provided, in 2400mm (8'-0") high lifts. 17. Unless noted otherwise, where control joints are noted, terminate 50% of all horizontal reinforcement (wires and bars) on each side of the joint. Unless noted otherwise, provide vertical wall control joints at maximum 15m (50'-0") o.c. and 7.5m (24'-6") from corners. Locations shall be approved by the Engineer and Architect. 18. In non-load bearing partitions, provide 50mm (2") min. clearance to all concrete columns and 25mm (1") clearance to slab over. Fill gap with compressible fire rated material where required. Provide dowels in concrete base at bottom of wall and lateral restraint at top of wall as per structural detail. 19. Unless noted otherwise, expansion anchors are not allowed in masonry. All drilled in anchors shall be the epoxy type. Use Hilti Hit HY150 MAX in solid or grouted masonry and Hilti Hit HY20 (complete with sleeve) in hollow masonry. 21. Hot and cold weather construction shall be in accordance with CAN/CSA A371. STEEL STUDS 1. Light gauge stud assemblies including connections to supporting structural elements shall be designed by a Professional Engineer retained by the Contractor in accordance with Part 4 of the B.C. Building Code, and CAN/CSA-S136. 2. Steel studs, joists and tracks to be as manufactured by Bailey Metal Products Ltd or equal, 20 Ga. (0.91mm) minimum, unless specified otherwise. 3. Follow good construction practices for installation, including use of bridging and details as recommended by the manufacturer. 4. Fasten with #12 sheet metal screws and to concrete with Hilti type DN direct fasteners or equal unless specified otherwise. 5. For non-load bearing steel stud assemblies, allow for minimum span/360 deflection of roof or floor structure over. 6. Provide 4 sets of sealed shop drawings and submit for review prior to fabrication. All shop drawings shall show all details and indicate all applicable design loads and material specifications. 7. Following erection, the same Professional Engineer shall inspect installation of all light gauge stud assemblies and submit a sealed letter stating that installation of same meets all design requirements. 3. Repair damaged deck coating with Galvacon paint. a) 1. Refer also to Concrete and Reinforcing notes. 2. Precast Manufacturer shall be responsible for the design, detail and delivery of all precast units to site. 6. Masonry reinforcing shall conform to the following standard: 20. Interlock courses at all wall corners and intersections. STEEL DECKING 1. See also concrete and reinforcing notes. 10. Unless otherwise noted, provide 3.2mm wide x T/4 deep(1/8" x T/4) deep control joints in two directions in grade slabs centered on column lines, and maximum at 4500mm (15 ft.) o.c. (T = slab thickness) 5. Masonry Contractor must discuss all masonry construction with the Engineer prior to commencing work. 16. Provide lintels over all openings or recesses, including those for mechanical or electrical service equipment. Unless noted otherwise, lintels less than 1200mm (4'-0") span shall be 200mm (8") deep, and lintels over 1200mm (4'-0") span and less than 2400mm (8'-0") span shall be 400mm (16") deep. See notes 11 and 12 above for reinforcing requirements. 6mm (1/4") 10mm (3/8") 12mm (1/2") 8. All hot and cold weather concrete work shall be carried out in accordance with CAN/CSA A23.1. i) 4. Use only Type 'S' mortar to CSA A179. No calcium chloride in any form is permitted in the grout or mortar mixes. 6. All steel work exposed to weather shall be hot dipped galvanized unless noted otherwise on the Structural or Architectural drawings. Hot dip galvanize all steel connectors (including fasteners) of wood members where exposure to rain during or after construction may cause rusting/staining of wood exposed to view, unless noted otherwise. c) Footing reinforcement: 7. Stripping of forms for structural elements is not allowed until concrete strength has reached 50% of the 28 day compressive strength for columns and walls, 70% of the 28 day compressive strength for slabs and beams and 75% of the compressive strength for slab and beams in parking structures (use % of 56 day compressive strength if fly ash content in concrete mix exceeds 25% replacement). Strength of concrete shall be determined from field-cured cylinders. See note 6 of 'Suspended Concrete Slabs/Slab Bands and Beams' for additional requirements. a) When temperature is expected to fall between 3°C and -10°C within 3 days of pouring concrete, the Contractor shall carry out one or more of the following procedures: 3. Concrete masonry units shall conform to CSA A165. Compressive strength for concrete masonry shall be 20 MPa (3000 psi) at 28 days with f'm = 12 MPa (1750 psi). Masonry Contractor shall provide to the Engineer written confirmation of unit strengths prior to installation. 4. Control heat/pace of weld when welding steel adjacent to other materials (wood, concrete, etc.) to prevent cracking, spalling or burning of adjacent material. 2-15M continuous plus hooked dowels of same size and spacing as wall vertical reinforcing. 6. Expansion and/or construction sequence joints shall be installed in concrete structures greater than 45m (150 ft.) in length, details and locations shall be discussed with and approved by the Engineer in writing prior to construction. 350W (G40.21) 300W ASTM A325 ASTM A307 400W (to CSA G30.18) 240W 304 3. All welding shall conform to CSA W59 and to be performed by welders under CSA W47.1, fabricators to CWB approval. Welds shall be E-70xx. Nelson stud welding shall meet specifications of the manufacturer and shall be tested by a qualified testing agency. Refer to "Field Review and Testing" for all weld testing requirements. 300mm (12") wall - 10M @ 300 (12") VERT., EACH FACE STAGGERED 10M @ 300 (12") HOR., EACH FACE STAGGERED a) Openings and conduits are not permitted in wall zones, within 990 mm (39") of wall ends and intersections and columns. c) Single openings larger than 300 mm (12") or a group of openings occupying together more than 300x300 mm (1.0 sq. ft.) in any 1 sq. meter (10 sq. ft.) area shall not be permitted without the approval of the Engineer. Rolled and HSS shapes Plates and bars Bolts Anchor bolts and miscellaneous hardware Reinforcing bars welded to structural steel A53 pipe Stainless steel 7. Where required, all hot dip galvanizing shall conform to CAN/CSA G164. 5. Blockouts, nailers, conduits, ducts, pipes, sleeves and other openings are subject to approval by the Engineer. 7. All footings shall be centered on columns and walls unless noted otherwise. 14. All surfaces placed in contact with ground Formed surfaces exposed to ground or weather Walls Column ties - interior Column ties - exterior Slabs Slab bands and Beams Parking slab - top - bottom Slab on grade (from top of slab) Other, unless otherwise noted 3. All reinforcing bars and stud rails shall be accurately placed, chaired and tied securely to prevent displacement and to maintain the specified cover. Install column reinforcement accurately with templates. Provide CSA standard hooked dowels from bottom of footing to match and lap with verticals. Install masonry dowels accurately to align with center of walls. Chairs shall be protected against rusting where required for appearance. Do not wet dowel reinforcement unless approved by the Engineer. Unless noted otherwise, exposed corners of slabs, beams, slab bands, columns and walls shall be beveled 20mm x 20mm (3/4"x3/4"). 6. Precast Manufacturer shall be a member in good standing with the Canadian Precast/Prestressed Concrete Institute (CPCI). 12. i) j) 4. See Architectural drawings for slab elevations, drainage, slopes and locations of reglets, reveals and chamfers. 6. Do not backfill retaining walls until full concrete strength is reached unless otherwise approved by the Engineer. Consult the Engineer prior to pour to confirm if floor/roof restraint required prior to backfilling. 11. Unless noted otherwise, design and supervision of excavation, shoring and underpinning of adjacent structures, where required, shall be carried out by a Professional Geotechnical Engineer retained by the Contractor. All costs are to be included in this contract. a) b) c) d) e) f) g) h) b) Slab reinforcing (or temperature reinforcing) 5. Precast Manufacturer shall be also responsible for the design of all lifting and bracing hardware and shall provide lifting inserts and any additional steel required for handling and lifting the units into place. 10. For all elevations and drainage slopes, see Architectural Drawings and requirements identified in the geotechnical report. Fire Resistance Rating 0-2 hrs. 3 hrs. 3. Take all precautions to ensure exposed concrete achieves finish desired by the Architect, including proper forming, mix design, site care and adequate vibration. Protect against damage during stripping and entire construction period. 5. Contractor shall be responsible for all temporary drainage during excavation. 9. Provide 50mm (2") thick concrete ground seal under footings/grade beam if required by site conditions. and/or by Geotechnical Engineer. 2. Reinforcement shall have concrete protection as follows, unless noted otherwise: a) Construction Tolerances b) Fabrication and placement of reinforcing c) Placement of concrete, including proper vibration and curing. FOUNDATIONS 1. Design of foundation is based on the soils report of Sept 9 2011, by GeoPacific Consultants with an allowable bearing pressure of 75 kPa for spread footings. All footings shall bear on soil capable of this pressure without failure or undue settlement. If native soil or fill are found during construction to have a lower allowable bearing pressure, notify the Engineer, and provide revised foundation to the Engineer's specifications. CSA G30.18 400 MPa CSA G30.18 400W MPa (welding to CSA W186) CSA G30.5 ASTM A775 Note: 1) Weldable reinforcement (including deformed bar anchors) must be clearly identified on each piece. 2) Reinforcement in concrete shear walls and frame members with force modification factors Rd greater than 2.0 shall be weldable grade in conformance with CSA Standard G30.18. 2. Perform all works in accordance with CAN/CSA A23.1, including the following: b) Where permitted, space openings 2 diameters, or minimum 150 mm (6") apart. 9. Design of Secondary component items including their attachment to the structure is the responsibility of others. a) 10M and larger b) Weldable reinforcement c) Welded wire mesh d) Epoxy coated reinforcement 9. See reinforcing notes for minimum reinforcing requirements for composite concrete topping over steel deck. 10. Design, fabricate and install steel deck to CSA s136 and Canadian Sheet Steel Building Institute standards u.n.o. 11. Design and detailing of the above items and their attachments are not the responsibility of the Engineer. They shall be designed by Specialty Structural Engineers, registered in the province of British Columbia and RETAINED BY THE CONTRACTOR, who will seal all related shop drawings, review the components and their attachments in the field and provide all required sealed letters (Schedule S-B & S-C) to the Engineer. ABBREVIATIONS A.BOLTS ADDL ALT B.L.L. B.U.L. BCE BOT B/U Cf CANTLV CLR CONC. CONT C'SINK C.I.P. C/W CJ D.L. DIAG. EL E.F. E.S. E.W. EXIST. FDN FTG GA. GALV GL H1E H2E HD H.D. GALV. HDR HORIZ I.F. - ANCHOR BOLTS - ADDITIONAL - ALTERNATE - BOTTOM LOWER LAYER - BOTTOM UPPER LAYER - BOTTOM CHORD EXTENSION - BOTTOM - BUILT UP - FACTORED COMPRESSION FORCE - CANTILEVERED - CLEAR - CONCRETE - CONTINUOUS - COUNTERSINK - CAST IN PLACE - COMPLETE WITH - CONTROL JOINT - DEAD LOAD - DIAGONAL - ELEVATION - EACH FACE - EACH SIDE - EACH WAY - EXISTING - FOUNDATION - FOOTING - GAUGE - GALVANIZED - GLULAM - HOOK ONE END - HOOK TWO ENDS - HOLD DOWN - HOT DIPPED GALVANIZED - HEADER - HORIZONTAL - INSIDE FACE LLH LLV L.L. LONGIT. LSL LVL L.V. Mf N. STUDS OPP O.F. P.C. PSL P/T REINF. RS R/W S.D.L. S.O.G. S.S. STAG STD STIFF STIRR Tf TJI T.L.L. TRANSV. T.U.L. T&B TYP U.D.L. U.N.O. U/S Vf VERT - LONG LEG HORIZONTAL - LONG LEG VERTICAL - LIVE LOAD - LONGITUDINAL - LAMINATED STRAND LUMBER - LAMINATED VENEER LUMBER - LENGTH VARIES - FACTORED MOMENT - NELSON STUDS - OPPOSITE - OUTSIDE FACE - PRECAST CONCRETE - PARALLEL STRAND LUMBER - POST-TENSION - REINFORCEMENT - ROUGH SAWN LUMBER - REINFORCED WITH - SUPERIMPOSED DEAD LOAD - SLAB ON GRADE - STAINLESS STEEL - STAGGERED - STANDARD - STIFFENER - STIRRUP - FACTORED TENSILE FORCE - TRUSS JOIST - TOP LOWER LAYER - TRANSVERSE - TOP UPPER LAYER - TOP AND BOTTOM - TYPICAL - UNIFORMLY DISTRIBUTED LOAD - UNLESS NOTED OTHERWISE - UNDER SIDE - FACTORED SHEAR FORCE - VERTICAL 8. Design and detailing of the above items and their attachments are not the responsibility of the Engineer. They shall be designed by Specialty Structural Engineers, registered in the province of British Columbia and RETAINED BY THE CONTRACTOR, who will seal all related shop drawings, review the components and their attachments in the field and provide all required sealed letters (Schedule S-B & S-C) to the Engineer. SECONDARY COMPONENTS AND THEIR ATTACHMENTS 1. Secondary components include but are not limited to the following: (Refer to all contract documents for secondary components) a) b) c) d) e) f) g) h) j) k) l) m) n) p) q) r) Architectural components such as guard and hand rails, flag posts, canopies, ceilings, etc. Site work elements exterior to the base building such as landscaping components, lamp standards, pools, signs, and civil work. Cladding, window mullions, glazing and store fronts. Skylights and glass canopies. Attachments and bracing for electrical and mechanical components. Glass block including attachments. Elevators, hoist beams and rail support members. Architectural precast and precast cladding. Window washing equipment and attachments. Interior and exterior light gauge steel stud walls. Roofing material. Architectural brick veneer. Parking slab membrane. Fall restraint anchors (and any additional required framing not shown on plan). Snow guards / fence. Library stacks. 2. Design and detailing of the above items and their attachments are not the responsibility of the Engineer. They shall be designed by Specialty Structural Engineers, registered in the province of British Columbia and RETAINED BY THE CONTRACTOR, who will seal all related shop drawings, review the components and their attachments in the field and provide all required sealed letters (Schedule S-B & S-C) to the Engineer. 3. Secondary components and their attachments shall be designed in accordance with Part 4 of the B.C. Building Code as in GENERAL section. 4. Sealed shop drawings of the secondary or non-structural components which may affect the primary structural system shall be submitted to the Engineer only for the review of their effect on the primary structural system. 5. Sub-contractor of these components is responsible for protection of connections of dissimilar metals against galvanic corrosion. 6. In addition to construction tolerance, secondary components shall be detailed for the following building movement and deflection: a) Vertical deflections of beams, slabs and decking: Differential deflections of edge beams and edges of slabs: L/180, (25mm min.) L/240, (16mm min.) b) Horizontal drift during wind and earthquake between floors: Drift without damage to components: Drift without collapse to components: 0.003 x height 0.010 x height for post-disaster buildings Movement at expansion joints (u.n.o.): Perpendicular: Parallel: Vertical: ± 50mm (2") min. ± 50mm (2") min. ± 25mm (1") min. c) Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 1 3 2 13500 16800 LEGEND CONCRETE WALL TYPE AS PER WALL SCHEDULE AND PLAN W 3 S4.1 4 S4.1 CONCRETE WALL BELOW 1 S5.0 2 S5.0 NON-LOAD BEARING CMU WALL LOAD BEARING CMU WALL W3 Z2 Z2 Z2 W3 Z2 W3 Z2 Z2 Z1 W3 Z1 Z1 Z2 W3 C4 SPAN DIRECTION OF HOLLOW CORE PANELS, SEE PLAN FOR SIZE W3 C INDICATES BEAM, HEADER OR HIP F2 x INDICATES POINT LOAD ON BEAM FROM FLOOR ABOVE F1 FOOTING TYPE SEE PLAN AND SCHEDULE B1 CONCRETE BEAM TYPE SEE PLAN AND SCHEDULE BP C1 1 STEEL BRACE FRAME TYPE SEE DWGS S4.0 & S4.1 FOR DETAILS ZONE REINF TYPE SEE SCHEDULE F2 Z1 10350 WATER TANK SLAB AND WALLS: PROVIDE CONCRETE WATERPROOFING ADMIXTURE (KRYSTOL INTERNAL MEMBRANE,XYPEX ADMIX C-500 OR APPROVED EQUAL) AT LOCATIONS INDICATED. INSTALL PRODUCT AS PER MANUFACTURERS INSTRUCTIONS AND SPECIFICATIONS. PROVIDE COMPLETE WATERSTOP SYSTEM AT ALL JOINTS IN ACCORDANCE WITH MANUFACTURER'S WARRANTY REQUIREMENTS F2 W4 BASE PLATE TYPE SEE DWG. S5.1 BF W1 F2 COLUMN TYPE AS PER SCHEDULE Z W4 Z1 STEP FTG UP 125 CONC. SLAB ON GRADE TYP R/W 10M @500 EACH WAY AT MID DEPTH ON 6 MIL POLY MOISTURE BARRIER ON COMPACTED GRANULAR SUB BASE AS PER GEOTECHNICAL ENGINEERS RECOMMENDATIONS W1 STEP FTG UP F3 300 300 DP. SLAB AT WATER TANKS R/W 15M @150 TOP & BOT EACH WAY W2 COLUMN SCHEDULE MARK SIZE C1 HSS 102x102x9.5 C2 HSS 152x152x8.0 C3 W310x97 C4 HSS 203x102x9.5 WATER TANK WATER TANK W2 W2 F3 W2 W4 Z1 W2 W2 W2 F1 F1 MARK W1 W1 4-15M VERTS 10M TIES @150 CONCRETE WALL SCHEDULE FOR STAIR REINF SEE SECT 4/S3.1 300 DP. FTG R/W 15M @400 TRANSV. TOP & BOT. & 8-15M LONGIT. BOT. REINFORCEMENT W1 200 W2 250 15M @150 EACH WAY, EACH FACE W3 250 15M @400 VERTS E.F., 10M @450 HORIZ. E.F. W4 200 15M @300 VERTS CENTERED 15M @450 HORIZ. CENTERED W5 150 CMU WALL REINF AS PER GENERAL NOTES W6 200 CMU WALL REINF AS PER GENERAL NOTES 15M @450 EACH WAY, CENTERED 200 W8 150 CMU WALL REINF AS PER GENERAL NOTES, ALL CELLS FULLY GROUTED W9 200 CMU WALL REINF AS PER GENERAL NOTES, ALL CELLS FULLY GROUTED 12450 Z1 FOR WALL AND FTG CONTINUATION SEE DWG S2.1 THICKNESS (MIN.) 15M @300 VERTS I.F., 15M @450 HORIZ. I.F. W7 FOR WALL AND FTG CONTINUATION SEE DWG S2.1 REINFORCEMENT 6-20M VERTS 10M TIES @150 W7 UP STEP FTG UP 2 S4.0 ZONE REINF. SCHEDULE MARK B S5.0 W7 STEP FTG UP 1000 B Z2 W1 Z1 W1 Z1 Z1 Z1 F2 FOOTING SCHEDULE 1000 W1 900 300 MARK SIZE REINFORCEMENT F1 450x200 THICK. STRIP FTG. 2-15M CONT. BOT. F2 1500x300 THICK. STRIP FTG. 4-15M LONGIT. BOT. 15M @450 TRANSV. BOT. F3 2200x300 THICK. STRIP FTG. 6-15M LONGIT. BOT. 10-15M TRANSV. BOT. F4 1500x1500x300 THICK. 5-15M EACH WAY BOT. F5 1750x1750x300 THICK. 6-15M EACH WAY BOT. F6 3000x1500x300 THICK. 6-15M LONGIT. BOT. 10-15M TRANSV. BOT. ALL FOOTINGS TO BEAR ON UNDISTURBED NATIVE SOIL, MINIMUM ALLOWABLE BEARING CAPACITY OF XXXXpsf (XXX kPa). GEOTECHNICAL ENGINEER TO CONFIRM BEARING CAPACITY ON SITE PRIOR TO POURING CONCRETE. IF FOOTINGS ARE TO BEAR ON COMPACTED FILL OR SOIL WITH LESS CAPACITY, NOTIFY STRUCTURAL ENGINEER AND INCREASE FOOTING SIZE ACCORDINGLY. A 1650 3300 1A 2 LOWER FLOOR / FOUNDATION PLAN 1:50 2A Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 1 3 2 13500 16800 LEGEND CONCRETE WALL TYPE AS PER WALL SCHEDULE AND PLAN W STEEL CANOPY BELOW SEE DWG S5.3 FOR DETAILS STEEL CANOPY BELOW SEE DWG S5.3 FOR DETAILS CONCRETE WALL BELOW NON-LOAD BEARING CMU WALL 3 S4.1 BF4 SPAN DIRECTION OF HOLLOW CORE PANELS, SEE PLAN FOR SIZE C1 150 WIDE CONCRETE CURB 6 S5.0 W9 BM2 C BP 1 3 BM1 C INDICATES BEAM, HEADER OR HIP BM1 W9 TYP 305 DP HOLLOW CORE PANELS 305 DP HOLLOW CORE PANELS + 50 MIN CONC TOPPING AT MIDDLE OF PANEL R/W 10M @450 E.W. + 100 MIN CONC TOPPING AT MIDDLE OF PANEL R/W 10M @300 E.W. SLOPE TOPPING TO ACHIEVE FLOOR DRAINAGE 5 S5.0 CONCRETE BEAM TYPE SEE PLAN AND SCHEDULE COLUMN TYPE AS PER SCHEDULE BASE PLATE TYPE SEE DWG. S5.1 BF STEEL BRACE FRAME TYPE SEE DWGS S4.0 & S4.1 FOR DETAILS ZONE REINF TYPE SEE SCHEDULE C BP 2 3 W9 W8 W8 W8 BF3 COLUMN SCHEDULE BP C1 1 B P C1 3 TYP B C BP 2 3 W9 3 BF5 9 S5.0 BF2 6 S5.0 200 CONC. SLAB ON GRADE R/W 10M @500 EACH WAY AT MID DEPTH ON 6 MIL POLY MOISTURE BARRIER ON COMPACTED GRANULAR SUB BASE AS PER GEOTECHNICAL ENGINEERS RECOMMENDATIONS 12 S5.0 MARK SIZE C1 HSS 102x102x9.5 C2 HSS 152x152x8.0 C3 W310x97 C4 HSS 203x102x9.5 CONCRETE WALL SCHEDULE MARK W7 15M @450 B.U.L. 200 CONC. SLAB ON GRADE R/W 10M @500 EACH WAY AT MID DEPTH ON 6 MIL POLY MOISTURE BARRIER ON COMPACTED GRANULAR SUB BASE AS PER GEOTECHNICAL ENGINEERS RECOMMENDATIONS SIM. C 9 S5.0 15M @450 B.U.L. B1 TYP 11 S5.0 15M3000 @300 15M3000 @300 20M @300 B.L.L. C BP 1 1 FOOTING TYPE SEE PLAN AND SCHEDULE TYP W8 BP C1 1 F1 10350 W8 2 S4.0 INDICATES POINT LOAD ON BEAM FROM FLOOR ABOVE BP C1 1 B P C1 1 10 S5.0 W8 W8 11 S5.0 x Z 7 S5.0 C BP 1 1 C BP 1 1 8 S5.0 LOAD BEARING CMU WALL 4 S4.1 THICKNESS (MIN.) REINFORCEMENT W1 200 15M @300 VERTS I.F., 15M @450 HORIZ. I.F. W2 250 15M @150 EACH WAY, EACH FACE W3 250 15M @400 VERTS E.F., 10M @450 HORIZ. E.F. W4 200 15M @300 VERTS CENTERED 15M @450 HORIZ. CENTERED 20M @300 B.L.L. F4 4 S5.0 600 600 W5 150 CMU WALL REINF AS PER GENERAL NOTES W6 200 CMU WALL REINF AS PER GENERAL NOTES TYP U.N.O. W6 W5 W7 DOWN F1 TYP U.N.O. W8 150 CMU WALL REINF AS PER GENERAL NOTES, ALL CELLS FULLY GROUTED W9 200 CMU WALL REINF AS PER GENERAL NOTES, ALL CELLS FULLY GROUTED C BP 2 3 12450 F1 TYP U.N.O. 15M @450 EACH WAY, CENTERED 200 BP C1 1 FOOTING SCHEDULE 3 S5.0 MARK SIZE F1 450x200 THICK. STRIP FTG. 2-15M CONT. BOT. F2 1500x300 THICK. STRIP FTG. 4-15M LONGIT. BOT. 15M @450 TRANSV. BOT. 2200x300 THICK. STRIP FTG. 6-15M LONGIT. BOT. 10-15M TRANSV. BOT. F4 3 S5.0 W6 F3 F1 TYP U.N.O. W5 TYP U.N.O. 1 C 2 BP W6 W6 W7 125 CONC. SLAB ON GRADE R/W 10M @300 EACH WAY AT MID DEPTH ON 6 MIL POLY MOISTURE BARRIER ON COMPACTED GRANULAR SUB BASE AS PER GEOTECHNICAL ENGINEERS RECOMMENDATIONS 300 WIDE SLAB THICKENING UNDER ALL NON-LOADBEARING CMU WALLS AS PER TYP DETAILS 4 S5.0 BF1 A F4 F5 1 S4.0 F6 1650 3300 1A 2 MAIN FLOOR PLAN 1:50 5-15M EACH WAY BOT. F5 1750x1750x300 THICK. 6-15M EACH WAY BOT. 3000x1500x300 THICK. 6-15M LONGIT. BOT. 10-15M TRANSV. BOT. ALL FOOTINGS TO BEAR ON UNDISTURBED NATIVE SOIL, MINIMUM ALLOWABLE BEARING CAPACITY OF XXXXpsf (XXX kPa). GEOTECHNICAL ENGINEER TO CONFIRM BEARING CAPACITY ON SITE PRIOR TO POURING CONCRETE. IF FOOTINGS ARE TO BEAR ON COMPACTED FILL OR SOIL WITH LESS CAPACITY, NOTIFY STRUCTURAL ENGINEER AND INCREASE FOOTING SIZE ACCORDINGLY. W7 3 S5.0 1500x1500x300 THICK. F6 BP C1 3 C BP 1 3 C BP 1 1 C BP 1 1 F1 TYP U.N.O. F4 F4 BP C1 1 F4 REINFORCEMENT 2A Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 1 3 2 13500 16800 LEGEND 2000 3 S4.1 5 S5.1 3 S5.1 2000 1750 CONCRETE WALL BELOW EDGE OF ROOF HSS 89x89x4.8 CROSS BRACE 4 S4.1 2000 5 S5.2 NON-LOAD BEARING CMU WALL LOAD BEARING CMU WALL HSS 102x102x13* W250x45 W250x45 INDICATES BEAM, HEADER OR HIP x INDICATES POINT LOAD ON BEAM FROM FLOOR ABOVE F1 FOOTING TYPE SEE PLAN AND SCHEDULE B1 CONCRETE BEAM TYPE SEE PLAN AND SCHEDULE BP C1 1 2000 125 SLAB 10350 W410x74 2000 3.45 kPa 3 EQUAL SPACES HSS 102x102x13* W460x97 CANTILV. 6 S5.2 3.45 kPa W460x97 76mm DP x 1.22 STEEL DECK TYP 2000 10M @300 H2E T.U.L. 5 S5.2 10M @300 B.L.L. W460x97 W410x60 L76x76x6.4 DIAG. BRACE L76x76x6.4 DIAG. BRACE *NOTE: LOW HEADER FOR GLAZING SUPPORT, TYP. HSS 102x102x13* 4 S5.1 SPAN DIRECTION OF HOLLOW CORE PANELS, SEE PLAN FOR SIZE C W250x45 W460x97 HSS 102x102x13* 76mm DP x 1.22 STEEL DECK TYP 76mm DP x 1.22 STEEL DECK TYP BF4 W460x97 CONCRETE WALL TYPE AS PER WALL SCHEDULE AND PLAN COLUMN TYPE AS PER SCHEDULE BASE PLATE TYPE SEE DWG. S5.1 BF STEEL BRACE FRAME TYPE SEE DWGS S4.0 & S4.1 FOR DETAILS Z L76x76x6.4 TYP AT PERIMETER OF ROOF W ZONE REINF TYPE SEE SCHEDULE STEEL CANOPY BELOW, SEE DWG S5.3 FOR DETAILS SCHOCK ISOKORB KST CONNETOR TYP ALONG GRID LINE 1 1000 SNOW LOAD 5500 1000 8.25 kPa HS S ST 10 U 2x B 1 C 02 O x6 L. . 4 2730 HSS FRAMES, TYP. 250 1000 SNOW LOAD 10M @300 B.U.L. 7.56 kPa 0 mm 0 mm W410x85 (LOW) W100x19 (HIGH) W460x97 (HIGH) W250x45 (LOW) W250x45 (LOW) 1750 BF5 B 100 4 S5.2 W250x28 CANTILV. AT HIGH ROOF W150x37 TYP AT LOW MECH PLATFORM HSS 89x89x4.8 CROSS BRACE 3.45 kPa EDGE OF ROOF HSS 102x102x13* W310x39 2 S4.0 W460x97 (UNDER LOW BEAM) W410x85 (LOW) SNOW LOAD W410x85 (LOW) W460x97 (HIGH) 10M @300 H2E T.L.L. 4 6. 2x 10 L. 2x O 10 C S UB HS ST 4.75 kPa W460x97 1000 5.5 kPa 6000 HSS 102x102x13* W250x45 SNOW LOAD HSS 102x102x13* HSS 102x102x6.4 HANGER BF3 W410x60 HSS 89x89x4.8 CROSS BRACE EDGE OF ROOF EXTENT OF LOW MECH PLATFORM W460x97 W250x28 CANTILV. BF2 W410x85 38mm DP x 1.22 STEEL DECK AT LOW MECH PLATFORM WITH 64mm CONCRETE TOPPING WITH WELDED WIRE MESH W460x97 W410x85 F S5.1 1 S5.2 2 S5.2 W250x28 CANTILV. 12450 4 EQUAL SPACES HSS 102x102x13* W410x85 (LOW) W100x19 (HIGH) W310x39 76mm DP x 1.22 STEEL DECK TYP W460x74 NON-LOADBEARING CMU WALLS FROM BELOW W460x89 1700 TYP W460x89 (UNDER) SLOPE ROOF DOWN 2 S5.1 SCHOCK ISOKORB KST CONNETOR TYP ALONG GRID LINE 1A Fast +Epp W410x85 (LOW) W100x19 (HIGH) structural engineers W410x85 (LOW) W100x19 (HIGH) HSS 102x102x13* W250x28 CANTILV. Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 tel 604 683 8797 fax 604 683 0492 HSS 102x102x4.8 CHEVRON BRACE BF1 HSS 102x102x13* W410x85 W460x97 W460x97 CANTILV. A W100x19 (HIGH) 3 S5.1 3 S5.1 EDGE OF ROOF 1 S4.0 L76x76x6.4 TYP AT PERIMETER OF ROOF 300 CONC. WALL R/W 15M @ 400 EACH WAY EACH FACE 1650 3300 1A 2 ROOF PLAN 1:50 2A T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada W460x89 W460x74 L76x76x6.4 DIAG. BRACE W100x19 (HIGH) CANTILEVER HSS 102x102x13* HSS 102x102x13* W310x39 CANTILV. W100x19 (HIGH) CANTILEVER W460x97 W410x85 L76x76x6.4 DIAG. BRACE 4 S5.1 W250x45 3.45 kPa W250x45 6400 W460x97 W460x97 1000 SLOPE ROOF DOWN 3 S5.2 BEND REINF. WITH HICKEY BAR AS PER CSA STANDARDS CSA STANDARD HOOK `D' 75 CL R. 1050 MAX. SEE ARCH. DWG FOR FOOTING REINF SEE SCHEDULE `D' `D' 600 MAX. STEP CONC. UPSTAND WHERE REQUIRED C/W 2-15M @ TOP CONT. AND DOWELS TO MATCH WALL VERTS. SIZE AND SPACING APPROVED BEARING CSA STANDARD HOOK CSA STANDARD HOOK 1 MAX. FOR WALL REINFORCING SEE GENERAL NOTES TENSION SPLICE FOR SLAB REINF. & DEPTH SEE PLAN TYPE 1 900 TYP. SEE PLANS `D' = FOOTING DEPTH TENSION SPLICE 2 EXTEND HOOK TO BACK FACE OF WALL TYP. 20x20 NOTCH FILLED WITH CAULKING OR DAMPROOF TO ARCH'S SPEC. BACKFILL WITH FREE DRAINING MATERIAL AS SPECIFIED IN SOILS REPORT DISCONTINUE EVERY SECOND HORIZ. BAR AT 'V' JOINT LOCATIONS 200 WIDE EXT. WATERSTOP OUTSIDE FACE OF WALL EXTEND HOOK TO BACK FACE OF WALL TYP. FOR FOOTING REINF SEE SCHEDULE - TYP. TOP OF WALL 1:20 TENSION LAP TENSION LAP TYPE 2 TYPICAL STEPPED STRIP FOOTING STANDARD HOOK EXTEND TO BACK FACE OF WALL TYP HORIZ. CORNER REINF. AT BACK FACE OF WALL SIZE & SPACING TO MATCH WALL HORIZ. REINF. SLAB REINF. & DEPTH SEE PLAN 32 TYP. 32 TYP. 4-20Øx200 LG EMBED ANCHOR BOLTS TYP. C/W DOUBLE NUT AT ANCHOR END OUTSIDE FACE VERT. REINF. TO MATCH WALL VERT REINF. + 1-15M HOR. TOP & BTM BASE PLATE FOR HSS COLUMNS: HSS 203x203, HSS 178x178 = 330x330x25 HSS 152x152, HSS 127x127 = 280x280x19 HSS 102x102, HSS 76x76 = 230x230x16 BASE PLATE 50 CLR 5 - 0.25x FLOOR HEIGHT 1:50 TENSION SPLICE TYP. TENSION SPLICE 0.25x FLOOR HEIGHT 2 FOR WALL REINF. AND THICKNESS SEE SCHEDULE AND GENERAL NOTES 1:20 200 WIDE WATERSTOP OUTSIDE FACE OF WALL TENSION SPLICE SEE GEN. NOTES FOR WALL REINF. AND THICKNESS SEE SCHEDULE AND GENERAL NOTES SINGLE CURTAIN 8 TYP. CONTINUOUS WALL - 1:20 DOUBLE CURTAIN CONTINUE ALL BARS ACROSS JOINT OR PROVIDE FULL TENSION SPLICES 38x89 KEY TYP. HORIZONTAL REINFORCEMENT AT WALL CORNERS UNO TYPICAL EXTERIOR WALL CONSTRUCTION JOINT - PLAN 11 - 1:20 ( MAY USE CONSTRUCTION JOINT AS WALL CONTROL JOINT ) 1:20 HSS COL. AS PER PLAN BASE PLATE AS ABOVE ON 20mm NON-SHRINK GROUT ALL STEEL BELOW CONC. SLAB TO BE PROTECTED WITH GALVACON PAINT SLAB ON GRADE AS PER PLAN CLEAN FREE DRAINING BACKFILL MATERIAL THICKEN SLAB TO PROVIDE MIN. 100 COVER AROUND BASE PLATE 100 32 TYP. RETAINING WALL SEE PLAN & SECTIONS FOR REINF. BASE PLATE FOR HSS COLUMNS: HSS 203x203, HSS 178x178 = 330x330x25 HSS 152x152, HSS 127x127 = 280x280x19 HSS 102x102, HSS 76x76 = 230x230x16 25 CLR. FOR FTG SIZE & REINF. SEE FOOTING SCHEDULE APPROVED BEARING SLAB ON GRADE SEE PLAN FOR REINF. 600 MIN. 50 CLR. SUB-BASE SEE SOIL REPORT PROVIDE 50 MIN. CLEARANCE TO ALL CONCRETE, COLUMNS, AND SLAB OVER. FILL GAP WITH COMPRESSIBLE FIRE RATED MATERIAL WHERE REQUIRED. 4-20Øx200 LG EMBED ANCHOR BOLTS TYP. C/W DOUBLE NUT AT ANCHOR END 32 TYP. 75 CLR. 90 300 MAX. DOWELS FROM SUSPENDED SLAB TO MATCH MASONRY WALL VERTS HOOKED DOWELS TO MATCH WALL VERT. REINF. EXTEND VERT. BARS TO TOP OF MASONRY & GROUT FILL TOP 2 COURSES HSS COL. AS PER PLAN TYP. HSS COLUMN AT FOOTING 1:20 BASE PLATE AS ABOVE ON 20mm NON-SHRINK GROUT 2-15M 1500 E.W. AT PEDESTAL 50 MAX. GAP FILLED WITH FIRE RATED COMPRESSIBLE MATERIAL BOTTOM REINF. CONT. THROUGH JOINT COMPACTED FILL TO THE GEOTECHNICAL ENGINEER'S APPROVAL NOTES: 1) THIS DRAWING TO BE READ IN CONJUNCTION WITH GEOTECHNICAL ENGINEER'S AND MECHANICAL ENGINEER'S DRAWINGS. 75 THICKEN SLAB TO PROVIDE COVER AROUND BASE PLATE BOND BEAM C/W 2-15M CONT. 2ND COURSE FROM TOP FOR CONC. PEDESTAL SEE PLAN 3000 MAX. KEY FROM 38x65 FOR SLAB UP TO 190 DP. KEY FROM 38x89 FOR SLAB FROM 200 TO 240 DP. KEY FOR SLAB 250 AND OVER USE 1/3 THE SLAB DEPTH L100x100x10 x300 LG. ALTERNATE SIDES @1220 O.C. OR TO MATCH WALL VERTS. FASTEN WITH 2-16Øx125 EXPANSION ANCHORS 200 APART TO U/S SLAB 250 TYP. DRAIN TILE SEE PLUMBING AND ARCH DWGS. 90 100 75 CLR. SLAB ON GRADE AS PER PLAN 200 OR 250 CONCRETE MASONRY WALL REINFORCED AS PER GENERAL NOTES SEE ARCHITECTURAL DWGS FOR LOCATIONS 2) FOR BACKFILLING REQUIREMENTS SEE GEOTECHNICAL ENGINEER'S SPECIFICATION AND DRAWINGS. THROUGH SLABS DOWELS TO MATCH WALL VERTS. HOOK AT BOTTOM (ALTERNATE: DRILL & GROUT DOWELS 127 INTO SLAB WITH EPOXY) 75 CLR 3) FOR DRAINAGE REQUIREMENTS SEE MECHANICAL ENGINEER'S SPECIFICATION AND DRAWINGS. ALL SLABBAND REINF. CONT. THROUGH JOINT CONT. KEY FROM SLAB (BEYOND) STOP AT SLABBAND - 1:20 1 FOR FOOTING SIZE & REINF SEE FOOTING SCHEDULE 9 3mm WIDE x T/4 DEEP SAWCUTS OR ZIPSTRIP (T = SLAB DEPTH) APPROVED SOLID BEARING TYPICAL HSS COLUMN AT FOOTING WITH CONCRETE PEDESTAL 2 SLAB THICKENING R/W 2-15M CONT. BOTTOM COLUMN ( CONCRETE OR STEEL ) 12 - 38 SLAB DEPTH 2 SHEAR KEYS START 50 FROM EACH FACE OF BEAM 3 - BEAM REINF. CONT. THROUGH JOINT THROUGH BEAMS TYP. CONSTRUCTION JOINT ( LOCATIONS TO BE SUBJECT TO STRUCTURAL ENGINEER'S APPROVAL ) 7 - TYP. SLAB ON GRADE CONTROL JOINT AT COLUMNS tel 604 683 8797 fax 604 683 0492 300 APPROVED BEARING TYPICAL NON-LOAD BEARING MASONRY WALL SECTION 1:20 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada 1:20 10 0 THROUGH SLABBANDS 5 EQ. SPACES structural engineers TYP. WALL FOOTING DETAIL 38x89 KEY, LENGTH 150 SHORTER THAN SLABBAND WIDTH AT EACH END Fast +Epp Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 EQ. EQ. SLAB DEPTH SLABBAND 6 SLAB REINF. AS PER PLAN 200 MIN. - 38x89 CONT. KEY 150 MIN. 2 BEAM - TYP. EXTERIOR WALL CONTROL JOINT (AT 10 m MAX. o.c.) - PLAN - 15M ANCHOR BAR TYP. ALL CORNERS TENSION SPLICE FOR WALL REINFORCING SEE GENERAL NOTES 1 MAX. 1 38x38 'V'-JOINT 10 APPROVED BEARING `D' = FOOTING DEPTH 2-15M EA. SIDE 2) FOR TENSION SPLICE LENGTHS SEE TABLE IN GENERAL NOTES. `D' 75 CL R. 'D' 4 NOTES: 1) HORIZ. DOWELS TO MATCH SIZE AND SPACING OF HORIZ. REINF. TENSION SPLICE `D' 600 MAX. STEP TENSION LAP "W" NOTE: SEE MECHANICAL AND ELECTRICAL DWGS FOR LOCATION, EXTENT AND THICKNESS OF HOUSEKEEPING PADS. 2-15M CONT. TOP NOTE: 15M @450 CONT. LAP 600 "H" BAR (1) 2. ASSUMED ALLOWABLE BEARING =144kPa FREE DRAINING BACKFILL MECHANICAL / ELECTRICAL HOUSE KEEPING PAD R/W 10M @300 EACH WAY MID DEPTH 200 75 SEISMIC ANCHORAGE BY OTHERS 3. GEOTECH ENGINEER TO INSPECT BACKFILL AND CONFIRM ASSUMED BEARING AND LOADING BAR (2) "B" 4. fc'=25MPa @28 DAYS fy=400MPa (DO NOT BACKFILL UNTIL CONCRETE HAS REACHED 28 DAYS STRENGTH) 38Ø WEEP HOLES @1200 CONCRETE SLAB PER PLANS 3 - 38x89 KEY CONT. FOR 250 AND 200 WALLS 38x138 KEY CONT. FOR 300 WALLS 1-15M CONT. 1:20 200 MIN. BAR (5) 75 CLR. "T" BAR (3) TYP. MECHANICAL/ELECTRICAL HOUSEKEEPING PAD DETAIL 50 CLR. "A" C10M @450 EACH WAY DRILL GROUT INTO STRUCTURAL SLAB WITH EPOXY GROUT (USE 4 DOWELS MIN. FOR SMALL PADS) 25 BAR (4) THIS DETAIL PROVIDES RESISTANCE TO HORIZONTAL (SLIDING) FORCES ONLY FROM EARTHQUAKE LOADING ON PAD AND EQUIPMENT. ADDITIONAL CONNECTIONS FOR UPLIFT FORCES FROM EQUIPMENT TO BE DESIGNED AND DETAILED BY SPECIALTY ENGINEER AND WILL REQUIRE ANCHORING THROUGH THE PAD AND INTO OR THROUGH THE STRUCTURAL SLAB. 150 MAX. HOUSEKEEPING PAD (SEE MECH/ELEC DWG'S) 50 CLR. 90 MIN. 38 CLR. 1. ASSUMED LATERAL EARTH PRESSURE AS FOLLOWSa) STATIC: EQUIVALENT FLUID PRESSURE OF 4.7xH(kPa) (WHERE H IS IN METERS) b) SEISMIC: EQUIVALENT FLUID PRESSURE OF 2.4xH(kPa) INVERTED (WHERE H IS IN METERS) c) SURCHARGE: 1.7kPa UNIFORM PRESSURE FROM 4.8kPa SURCHARGE AT TOP DRAIN TILE APPROVED BEARING BY GEOTECH. ENGINEERS SEE ARCH DWGS FOR STAIR DIMENSIONS "L" RETAINING WALL SCHEDULE H W L T A B BAR (1) <4200 300 2750 400 300 2800 C20M @250 C20M @125 C20M @125 BAR (3) BAR (4) <3600 250 2250 350 300 2100 C20M @350 C20M @175 C20M @175 -- 15M @300 CONT. <3000 200 1800 300 200 1500 C20M @300 C20M @300 C15M @175 -- 15M @300 CONT. <2400 200 1400 300 200 -- C15M @200 -- C15M @300 -- 15M @300 CONT. <1800 200 1100 250 100 -- C15M @400 -- C15M @250 -- 3-15M CONT. <1200 200 600 200 100 -- C15M @450 -- C10M @300 -- 2-15M CONT. - 38mm DEEP CONT.KEY 15M @450 EACH WAY 15 0 TYP. RETAINING WALL SECTION 1 BAR (5) 15M @450 EA. WAY 15M @225 CONT. 5 CL 0 R BAR (2) 10M @450 DOWEL DRILL & EPOXY GROUT 100mm 60 0 T.O.WALL OR GRADE COMPACTED FILL T.O.GRADE MIN. FROST PROTECTION 1:20 2-15M CONT. BOT 300 600 LAP 4 - TYP. STAIRS ON GRADE 1:20 T/2 T 0.2 T EDGE EACH SIDE WITH 3mm RADIUS SECOND POUR 1:3 SLOPE CONSTRUCTION JOINT T T/4 MIN. SAW CUT OR PLASTIC PREFORMED STRIP CAULK WITH SEMI-RIGID FILLER IN WET AREAS AS SHOWN ON DESIGN DRAWINGS CONTROL JOINT NOTES : 1. CONSTRUCTION JOINTS TO BE INSERTED WHERE CONSTRUCTION OPERATIONS ARE SUSPENDED FOR 30 MINUTES OR MORE. 2. CONTROL JOINTS TO BE SAW-CUT WITHIN 4 TO 12 HOURS AFTER CONCRETE HARDENS. 2 - TYP. CONSTRUCTION JOINTS SLAB ON GRADE ( LOCATIONS TO BE SUBJECT TO STRUCTURAL ENGINEER'S APPROVAL ) Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 1 1A 2 1650 3 2A 11850 13500 3300 3 S5.2 D S5.1 F S5.1 76mm STEEL DECKING AS PER PLAN W460 W410 CONC. COLUMN AS PER PLAN 8 4. 2x 10 2x 10 HS S HSS 102x102x6.4 WINDOW HEADER S HS HSS 102x102x6.4 WINDOW HEADER 10 2x 10 2x 4. 8 W410 BF 1 HSS 102x102 COLUMNS AS PER PLANS TYP T.O. MAIN FLOOR EL. 101.700 1 S2.1 1 WALL ELEVATION @ GRID A 1:50 1A 2 1650 3 2A 11850 13500 3300 2 S5.2 SIM. 4 S5.2 76mm STEEL DECKING AS PER PLAN C S5.1 F S5.1 LV. W250 CANTI W460 W460 W310 COLUMN AS PER PLANS W410 W460 W250 W250 W410 S HS HSS 102x102 COLUMNS AS PER PLANS TYP 89 13 S5.0 8 4. 9x 8 x HSS 152x152 COLUMN AS PER PLANS Fast +Epp HS S CMU WALL AS PER PLAN BF 5 89 x8 9x 4. 8 HSS 102x102 COLUMN AS PER PLANS structural engineers 200 CMU WALL 12 S5.0 T.O. MAIN FLOOR EL. 101.700 Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 T.O. LOWER FLOOR EL. 98.000 2 S2.1 WALL ELEVATION @ GRID B 1:50 3 2 1 16800 13500 76mm STEEL DECKING AS PER PLAN W460 HSS 102X102x6.4 HANGER W250 HSS 102x102x12.7 WINDOW HEADER HSS 102x102x12.7 HSS 102x102 COLUMNS AS PER PLAN TYP 200 CMU WALL S HS 9 x8 89 .8 x4 STEEL CANOPY SEE DWG S5.3 FOR DETAILS 10Mx900 U-BARS @300 10Mx900 U-BARS @300 HS S BF 4 89 x8 9x 4.8 7 S5.0 STEEL CANOPY SEE DWG S5.3 FOR DETAILS T.O. MAIN FLOOR EL. 101.700 7 S5.0 10Mx900 U-BARS @300 10Mx900 U-BARS @300 HSS 203x102 AS PER PLAN 2-25M 2-25M 1000 1000 T.O. LOWER FLOOR EL. 98.000 3 S2.1 WALL ELEVATION @ GRID C 1:50 C B A 10350 12450 B S5.1 A S5.1 W460 W410 HSS 102x102 COLUMN AS PER PLANS W460 W410 HSS 152x152 COLUMN AS PER PLANS HSS 152x152 COLUMN AS PER PLANS E S5.1 S HS x 89 HS S .8 x4 89 BF 3 89 x8 9x 4. 8 HS S HS .8 x4 89 x 89 S BF 2 89 x8 9x 4. 8 HSS 102x102 COLUMN AS PER PLANS Fast +Epp E SIM. S5.1 T.O. MAIN FLOOR EL. 101.700 structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada 200 CONC. WALL tel 604 683 8797 fax 604 683 0492 T.O. LOWER FLOOR EL. 98.000 4 S2.1 WALL ELEVATION @ GRID 2 1:50 C C GL GL 2A 250x250x19 BASE PLATE C/W 2-13Ø x200 LG N.STUDS @150 GA HSS 203 COL. AS PER PLAN 8 CONC. S.O.G. SEE PLANS FOR SIZE & REINF CONC. S.O.G. SEE PLANS FOR SIZE & REINF CONC. S.O.G. SEE PLANS FOR SIZE & REINF 300 B 300 200 CONC. S.O.G. SEE PLANS FOR SIZE & REINF AS PER ARCH CMU WALL AS PER PLANS 10M TIES @300 8-15M VERTS 38x89 CONT KEYWAY SOLID BEARING AS PER GEOTECH ENGINEER 38x89 CONT KEYWAY SOLID BEARING AS PER GEOTECH ENGINEER SOLID BEARING AS PER GEOTECH ENGINEER SOLID BEARING AS PER GEOTECH ENGINEER 2 1:20 S2.0 S2.0 SECTION 3 SECTION 3 1:20 S2.1 4 1:20 S2.1 C AS PER GEOTECH ENGINEER 1800 MIN. FROST PROTECTION DOWELS TO MATCH WALL REINF. ALT HOOK 38x89 CONT KEYWAY 100 200 CONC. WALL SIZE & REINF AS PER PLAN AND SCHEDULE 38x89 CONT KEYWAY SECTION 1 DOWELS TO MATCH WALL REINF. ALT HOOK BACKFILL BOTH SIDES OF WALL EQUALLY AS PER GEOTECH ENGINEER DOWELS TO MATCH WALL REINF ALT. HOOK CONC. WALL SIZE & REINF AS PER PLAN AND SCHEDULE 1800 MIN. FROST PROTECTION CONC. WALL SIZE & REINF AS PER PLAN AND SCHEDULE 600 DOWELS TO MATCH WALL REINF ALT. HOOK BACKFILL BOTH SIDES OF WALL EQUALLY 1800 MIN. FROST PROTECTION AS PER GEOTECH ENGINEER 600 CONC. WALL SIZE & REINF AS PER PLAN AND SCHEDULE BACKFILL BOTH SIDES OF WALL EQUALLY 600 AS PER GEOTECH ENGINEER BACKFILL BOTH SIDES OF WALL EQUALLY 1800 MIN. FROST PROTECTION 100 B S2.0 DETAIL 1:20 SECTION 1:20 C C B 75 HOOK DOWELS INTO CONC. TOPPING. SIZE & SPACING TO MATCH CONC WALL VERT REINF DOWELS TO MATCH CMU WALL VERT REINF HOOK DOWELS INTO CONC. TOPPING. SIZE & SPACING TO MATCH CONC WALL VERT REINF 900 HSS 102x102 COL AS PER PLANS HOOK DOWELS INTO CONC. TOPPING. SIZE & SPACING TO MATCH CONC WALL VERT REINF 900 CONC. TOPPING AS PER PLAN 15M @400 VERT DOWELS 600 600 CONC. TOPPING AS PER PLAN CMU WALL AS PER PLAN CONC. TOPPING AS PER PLAN 3-20M CONT 400 LG. NOTCH @1000 IN HOLLOWCORE AND 1200 FROM EACH END TO ALLOW FOR REBAR PLACEMENT AND CONC. FILL OF END CORE. PROVIDE TEMP. LATERAL RESTRAINT TO TOP OF WALL UNTIL THE S.O.G. AND HOLLOW CORE TOPPING IS CAST CORE PLUG BY PRECAST SUPPLIER CORE PLUG BY PRECAST SUPPLIER C10M1200 GROUTED INTO EACH HOLLOWCORE PANEL JOINT 900 900 2-C15M AS SHOWN AT EACH NOTCH C/W 15M HOR. CONT. AT EACH END OF HOOK 950 MIN. CONFIRM WITH ARCH 10M CONT. ANCHOR BARS PROVIDE TEMP. LATERAL RESTRAINT TO TOP OF WALL UNTIL THE S.O.G. AND HOLLOW CORE TOPPING IS CAST C10M1200 GROUTED INTO EACH HOLLOWCORE PANEL JOINT 10M CONT. ANCHOR BARS FOR REMAINDER OF DETAIL SEE SECTION 7/- 250 3-25M CONT TOP & BOT C/W 10M TIES @300 CORE PLUG BY PRECAST SUPPLIER C10M1200 GROUTED INTO EACH HOLLOWCORE PANEL JOINT S2.1 CONC. S.O.G. REINF AS PER PLAN PROVIDE TEMP. LATERAL RESTRAINT TO TOP OF WALL UNTIL THE S.O.G. AND HOLLOW CORE TOPPING IS CAST 50 100 MIN. HOLLOWCORE BEARING ON CMU WALL (BEARING PANEL BY PRECAST SUPPLIER) HOOK WALL VERT AT TOP AS SHOWN CONC. WALL REINF AS PER PLAN AND SCHEDULE 5 600 1 FOR BEAM REINF SEE SECTION 7/- 250 1-15M ANCHOR BAR 1 1-15M CONT EACH FACE 100 MIN. HOLLOWCORE BEARING ON CMU WALL (BEARING PANEL BY PRECAST SUPPLIER) 100 MIN. HOLLOWCORE BEARING ON CMU WALL (BEARING PANEL BY PRECAST SUPPLIER) CONC. TOPPING AS PER PLAN CONC. TOPPING AS PER PLAN 150 1000 DOWELS TO MATCH CMU WALL VERT REINF 950 MIN. CONFIRM WITH ARCH CMU WALL AS PER PLAN SECTION 6 1:20 S2.1 SECTION 7 1:20 S2.1 SECTION 8 1:20 S2.1 SECTION SECTION 9 1:20 S2.1 1:20 3 Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 2A 250 CONC. WALL BELOW 100 100 400 LG. NOTCH @1000 IN HOLLOWCORE AND 1200 FROM EACH END TO ALLOW FOR REBAR PLACEMENT AND CONC. FILL OF END CORE. 200 CONC. WALL REINF AS PER PLAN 15M DOWELS TO MATCH WALL VERTS. EPOXY 90mm INTO CONC. TOPPING CABLE TRAY ATTACHMENT BY OTHERS (C/W FULL STRENGTH COUPLER ATTACHMENT TO THREADED ROD 7.0 KN (UNFACTORED) MAX. LOAD 10 S2.1 SECTION 1:20 11 S2.1 SECTION 1:20 A - 100 BREAK FACE OF CMU WALL AND GROUT INFILL AFTER INSTALLATION HOLLOWCORE AS PER PLAN (FULLY GROUT ALL END CELLS AS SHOWN) TYP. 19mm BASE PLATE ON 25mm NON SHRINK GROUT C/W 2-19Ø ANCHOR BOLTS 6 45 100 45 200 100 350x350x19 BASE PLATE ON 25mm NON SHRINK GROUT C/W 4-25Ø x400 LONG THREADED RODS WITH DOUBLE NUT & WASHER AT BOTTOM 13 S4.0 HOLLOWCORE PANELS TO BE PLACED TIGHT TOGETHER. DRILL HOLE MIN. AS REQUIRED AFTER PLACEMENT TO ALLOW FOR THREADED ROD PROJECTION TYP CABLE TRAY SUPPORT IN HOLLOWCORE 1:10 122 55 150 MIN. PROJECT HOLLOWCORE PANELS AS PER PLAN 40 40 55 200 B tel 604 683 8797 fax 604 683 0492 HSS COL AS PER PLAN 153 450 CONC. TOPPING AS PER PLAN 100 600 HOLLOWCORE PANELS AND CONC. TOPPING AS PER PLAN IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada 250x250x10 BEARING PLATE 40 40 BEND WALL VERT REINF INTO TOPPING WITH HICKEY BAR CONC. TOPPING & REINF AS PER PLAN 122 6 150 CMU WALL AS PER PLAN 13Ø (A325) THREADED ROD AND NUT @1200 EACH WAY SET IN GROUTED JOINT BETWEEN HOLLOWCORE PANELS 12 S4.0 SECTION 1:10 T 604 731 7412 F 604 731 7620 mail@fastepp.com SECTION 1:10 B 2 2 C 40 65 STEEL DECK AS PER PLAN T.O. STEEL DECK 10mm KNIFE PLATE THRU COLUMN C/W 4-19Ø A325 BOLTS EACH SIDE ALIGN DECK FLUTE WITH STEEL BEAM BEAM AND DECKING AS PER PLANS 40 WT100x15.5 80 5 5 100 100 38 2 ERECTION BOLTS 15 8 8 WT100x15.5 W410 AS PER PLANS 40 65 W460 AS PER PLANS 100 40 40 5 17 80 80 15 0 HSS CROSS BRACE AS PER ELEVATIONS 38 38 D S4.0 25 150 0 15 8 8 HSS 152x152 AS PER PLANS 5 17 17 5 W460 AS PER PLANS HSS CROSS BRACE AS PER ELEVATIONS 1:10 HSS CROSS BRACE AS PER ELEVATIONS 10mm CAP PLATE 10mm KNIFE PLATE THRU COLUMN C/W 4-19Ø A325 BOLTS FOR REMAINDER OF KNIFE PLATE DETAIL SEE DETAIL A/- 19mm KNIFE PLATE DETAIL W250 AS PER PLANS 17 5 40 150 40 80 150 HSS 152x152 AS PER PLANS W460 AS PER PLAN 80 6 6 10mm KNIFE PLATE C/W 4-19Ø A325 THRU BOLTS HSS 102x102 AS PER PLANS 150 80 FOR REMAINDER OF KNIFE PLATE DETAIL SEE DETAIL A/- WP 15 0 80 100x6mm FULL HEIGHT PLATE C/W 3-19Ø A325 BOLTS EACH SIDE 40 80 6 WP 38 65 6 6 150 80 80 80 65 12 60 0 150 100 T.O. STEEL DECK 80 40 150 80 6 WP FOR REMAINDER OF KNIFE PLATE DETAIL SEE DETAIL A/- BEAM AND DECKING AS PER PLANS 100 HSS 152x152 AS PER PLANS 65 40 HSS CROSS BRACE AS PER ELEVATIONS S4.1 S4.0 80 DETAIL C 1:10 1:10 40 S4.1 DETAIL B 1:10 80 DETAIL A 106 262 75 244 75 10mm PLATE C/W 3-19Ø A325 BOLTS EACH SIDE 8 40 40 40 40 19mm BASE PLATE ON MAX. 20mm NON SHRINK GROUT C/W 2-19Ø A325 THREADED RODS EMBED 300 C/W DOUBLE NUT & 75x75 WASHER PLATE IN CONC. 38 50 50 100 HSS COL AS PER PLAN 75 75 HSS COL AS PER PLAN 5 17 0 15 100 75 75 HSS 152x152 AS PER PLANS 40 40 8 HSS 102x102 AS PER PLANS HSS COL AS PER PLAN 8 CONNECTION PLATE FOR X BRACE SEE DETAIL 19mm BASE PLATE ON MAX. 20mm NON SHRINK GROUT C/W 2-19Ø A325 THREADED RODS EMBED 300 C/W DOUBLE NUT & 75x75 WASHER PLATE IN CONC. 40 135 135 2 S2.2 19mm EMBED BASE PLATE C/W 6-15Mx400 LONG WELDABLE REBAR DOWELS SECTION 1:10 HSS CROSS BRACE AS PER ELEVATIONS T.O. CONC. WALL 12 19mm KNIFE PLATE 200 T.O. TOPPING 150 BASE PLATE TYPE 1 BASE PLATE TYPE 2 BASE PLATE TYPE 3 1:10 1:10 1:10 WP 6 BASE PLATE TYPE 3 1 1A 1700 MAX. 1490 SCHOCK ISOKORB KST CONNECTOR/ ISOLATION JOINT 76mm DP x1.22 STEEL DECKING E S4.1 DETAIL HSS 76x76x STUB COLUMNS AT EACH W100 BEAM 5 - W100x19 CONT 1:10 76mm DP x1.22 STEEL DECKING 8 GL 8 STEEL DECK AS PER PLAN HSS 76x76x STUB COLUMNS AT EACH W100 BEAM 76 WIDE x6mm STIFF PLATE TYP Fast +Epp T.O. STEEL DECK structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 6 76 WIDEx6mm STIFF PLATE EACH SIDE ROOF BEAM AS PER PLAN IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada W100x19 CONT 6 W410 BEAM AS PER PLAN 76mm DP x1.22 STEEL DECKING 20 GAP 8 50 50 DIAG. BRACE AS PER PLAN W410 BEAM AS PER PLAN 12 6 6 6 450 40 40 75 6mm PLATE 262x150x16 PLATE C/W 4-19Ø A325 BOLTS 150x10 THICK CONNECTION PLATE C/W 19Ø A325 BOLT IN 50 LONG VERT SLOTTED HOLE IN PLATE 277 6 SEE ARCH DWGS HSS 102 AS PER PLAN HSS 102x102 AS PER PLANS 5 SECTION - 1:10 6 6 HSS HEADER FOR GLAZING AS PER PLAN 6 6 3 S2.2 SECTION 1:10 4 S2.2 SECTION 1:10 T 604 731 7412 F 604 731 7620 mail@fastepp.com F S4.0 DETAIL 1:10 tel 604 683 8797 fax 604 683 0492 3 A B SEE ARCH DWGS 2A STEEL DECK AS PER PLAN 100 6mm BENT PLATE CONT BETWEEN W250 BEAMS STEEL DECK AS PER PLAN 100 CONT EDGE ANGLE AS PER PLAN 110x6mm FULL HEIGHT STIFF. PLATE BENT PLATE AS PER SECTION 2/- 100 ℄ W250 BEAM STEEL DECK AS PER PLANS. ALIGN BOT. OF FLUTE WITH CENTRE OF BEAM 100 STEEL DECK AS PER PLAN 50-150 50-150 80 160 80 SEE ARCH DWGS 80 80 80 TYP 80 50 6 40 75 W250 AS PER PLANS 160x100x10MM CONNECTION PLATE C/W 2-19Ø THREADED STUDS WELDED TO PLATE 80 50 80 6 6 10 40 40 80 40 40 CUT W250 TO 150 DEEP AND WELD BOTTOM FLANGE TO WEB. FLANGE PROFILE TO MATCH W250 TOP FLANGE 2-19Ø A325 BOLTS.PROVIDE SHAPED SHIM PLATES AT BOLT LOCATIONS 4A - 40 65 W250 AS PER PLANS 65 150 150 5 5 35 65 35 65 19Ø A325 THRU BOLTS TYP SECTION S2.2 3 1:10 S2.2 ADD STEEL PLATE AS REQUIRED TO MAINTAIN ROOF SLOPE. W310 COLUMN AS PER PLANS 10mm PLATE C/W 5-19Ø THRU BOLTS SECTION 2 1:10 C W460 AS PER PLANS 76x6mm STIFF PLATE EACH SIDE 100 S2.2 W460 AS PER PLANS 110x10mm PLATE W460 AS PER PLANS 1 W250 AS PER PLANS 100 WIDE x10mm FULL HEIGHT STIFF PLATE TYP SECTION SECTION 4 1:10 S2.2 1:10 2 STEEL DECK AS PER PLANS B W250 AS PER PLANS 5A - W250 AS PER PLANS 3 SLOPE AS PER ARCH DWGS 100 ℄ W250 BEAM SEE ARCH SEE ARCH 127 6 76 EMBED PLATE 10x150x200 LG C/W 2-13Øx76 LG N. STUDS ∠102x102x9.5 C/W 2-19Ø A325 BOLTS 6 76 ∠127x127x9.5x200 LG C/W 3-15M 600 AND 3-16Øx125 lg N. STUDS 25 6 W460 AS PER PLANS W460 AS PER PLAN 6mm PLATE 35 65 150 HSS 102x102x6.4 C/W 10mm CAP PLATE WITH 2-19Ø A307 THREADED RODS CP WELDED TO PLATE ℄ W310 COLUMN TYP STEEL DECK 76x0.91mm BETWEEN HSS FRAMES 6 100 HSS 127x76x9.5 HSS127x76 65 35 6mm BOTTOM PLATE SEE ARCH 127 100x10mm FULL HEIGHT CONNECTION PLATE C/W 4-19Ø THREADED STUDS WELDED TO PLATE. LAYOUT AS PER SECT 1/- 2A W250 AS PER PLANS 125 SLAB AS PER PLAN 125 SLAB AS PER PLAN 190 CMU AS PER PLAN. HOOK WALL VERTS 600 INTO SLAB. 5 S2.2 SECTION 1:10 5A - SECTION 1:10 6 S2.2 DETAIL 1:10 4A - SECTION 1:10 Fast +Epp structural engineers Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492 3 2 3 6 EQUAL SPACES 10mm THICK STEEL PLATE A - HSS 203x102x6.4 LLV TYP HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV 10mm THICK STEEL PLATE 2 - HSS 102x102x6.4 AT INTERMEDIATE LOCATIONS TYP A - HSS 203x102x6.4 LLV TYP HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV C 3 - 2 - C 2 - CONC. WALL AS PER PLAN TYP HSS 203x102x6.4 LLV NOTE: HOT DIP GALVANIZE ALL STEEL COMPONENTS CMU. WALL AS PER PLAN A - TYP 1 - PLAN - LOW CANOPIES @ GRID C & 3 NOTE: FOR ALL CANOPY LOCATIONS AND SIZES SEE ARCH DWGS HSS 203x102x6.4 LLV HSS 203x102x6.4 LLV 1:50 10mm THICK STEEL PLATE HSS 203x102x6.4 LLV PLACE 1-20M VERT IN EACH CELL WITH EMBED PLATE & IN EACH ADJACENT CELL 255 1200 153 25 TYP CMU WALL AS PER PLAN 15M2000 PLACED TIGHT TO HEAD OF N. STUD CONC. WALL AS PER PLAN CONC. WALL AS PER PLAN REMAINDER OF DETAIL AS PER SECTION 1/- 15M2000 PLACED TIGHT TO HEAD OF N. STUD 6 50-200 25 TYP 255x235x16 EMBED PLATE C/W 4-19Øx150 LG N. STUDS & 4-19Ø A307 THREADED RODS CP WELDED TO PLATE SEAL WELD SEAL WELD HSS AS PER PLAN SECTION 1A - 1:10 HSS T.O. STEEL VARIES SEE ARCH DWGS SECTION 1:10 A - END PLATE WELDED TO HSS AND BOLTED TO EMBED PLATE PLACE 6mm HIGH DENSITY TEFLON PAD BETWEEN STEEL PLATES NO FUSION WELDS ALLOWED - END PLATE WELDED TO HSS AND BOLTED TO EMBED PLATE G 1A - 1 15M2000 PLACED TIGHT TO HEAD OF N. STUD HSS 102x102 AS PER PLAN EMBED PLATE AS PER SECTION 2/- 25 TYP 25 TYP 235 16mm THICK PLATE BOLTED TO EMBED PLATE BEHIND END PLATE WELDED TO HSS AND BOLTED TO EMBED PLATE 10 3B - 6 10mm THICK PLATE PLACE 6mm HIGH DENSITY TEFLON PAD BETWEEN STEEL PLATES 1200 HSS AS PER PLAN 255x235x16 EMBED PLATE C/W 4-19Øx125 LG N. STUDS & 4-19Ø A307 THREADED RODS CP WELDED TO PLATE 1A - 10 PLACE 6mm HIGH DENSITY TEFLON PAD BETWEEN STEEL PLATES 3A - DETAIL 1:10 2 - SECTION 1:10 3 - SECTION 1:10 255 50 50 25 THREADED RODS FROM EMBED PLATE BEHIND 10mm PLATE SLOPED AS PER ARCH NOTCH OUT HSS 203x102 AROUND HSS 102x102 AND WELD ALL AROUND 50 MAX. 6 Fast +Epp 16mm THICK PLATE BOLTED TO EMBED PLATE BEHIND structural engineers 25 235 NO FUSION WELDS ALLOWED 153 25 10mm PLATE SLOPED AS PER ARCH WALL REINF AS PER PLAN AND SCHEDULE 25 TYP 153 WALL REINF AS PER PLAN AND SCHEDULE HSS 102x102 CONT. TO PLATE BEYOND 6 Suite 201 1672 West 1st Ave Vancouver BC Canada V6J 1G1 T 604 731 7412 F 604 731 7620 mail@fastepp.com G 3A - SECTION 1:10 3B - SECTION 1:10 IBI/HB Architects 700 - 1285 West Pender Street Vancouver BC V6E 4B1 Canada tel 604 683 8797 fax 604 683 0492