INVENTORY AND INFORMATION FOR EMERGENCY BACKUP

advertisement
INVENTORY AND INFORMATION
FOR
EMERGENCY BACKUP GENERATOR AND ASSOCIATED EQUIPMENT
AT
BCWSA’S WATER BOOSTER STATION 3A
Prepared by: Carroll Engineering Corporation (September 2015)
The Bucks County Water and Sewer Authority (BCWSA) is seeking bids on a Cummins/Onan
Model 1500DFMB/64211J (1500 kW) Emergency Generator System, a Simplex Saturn-HV
1500 Resistive Load Bank, a 13.2 kV Primary Switch, and a 2,400 Volt Transformer.
The generator and switchgear panel have been housed inside BCWSA’s Water Booster Station
3A and maintained as an emergency backup generator system since the installation in 1994. The
load bank was also installed in 1994, and sits outside the building on a concrete pad. The
Primary Switch and Transformer also sit outside the building on concrete pads, and they have
been installed since the pump station was first constructed in the 1980’s.
The generator system has been regularly exercised by BCWSA personnel, with preventive
maintenance routinely performed. The most recent company to perform preventive maintenance
on this generator system was Engines, Inc. located in Northampton, Pennsylvania. Their work
reports on this generator system, from July 2011 through December 2014, indicate no major
issues involving the generator. Their last work report was an annual inspection visit with full
service on December 31, 2014, and no issues were noted.
The generator system generally consists of the diesel engine/generator, switchgear panel and
load bank. The generator has approximately 262 hours of run time. The generator is fully
operational and was regularly serviced up until 2014, when modifications to the BCWSA water
system rendered this Water Booster Station unnecessary.
Photographs of the equipment, taken around August 2015, are included on the following pages.
The equipment included in this sale consists of the following. Note that the information
presented below was obtained from Operation and Maintenance Manual documents prepared at
the time of equipment installation.
Engine Generator:
 1500.0 DFMB
 1500 kW
 2400/4160 volt
 3 phase delta
 Approx. Dimensions (entire unit) = 99” High x 75” Wide x 223” Long
 Approx. Dry Weight (entire unit) = 24,200 lbs.
Cooling System:
 Radiator cooled
15-2620.01 (1526200002 (copy))
Page 1 of 3
Fuel System:
 Diesel fuel (tank not included)
Starting Battery:
 12 volt DC, 225 amp/hr (4 total)
Instruments:
 AC Ammeter
 Voltmeter
 Frequency Meter
 Running Time Meter
Safeties:
 12 light pre-alarm package
Misc. Accessories:
 60 Hertz, Standby Power
 Alternator – 60 Hertz, 3 phase, 2400/4160 volt, 105/80C
 Exciter/Regulator – PMG, 3 phase sensor
 Engine Governor – Cummins, EFC, normally closed
 Battery Charging Alternator – Normal output
 Engine Starter – 24 VDC Motor
 Low coolant level shutdown
 AC control with meters
 Audible alarm, engine shutdown
 Relays – 3 auxiliary 3PDT, 12 remote annunciator contacts
 Emergency Stop Switch
 Engine air cleaner, normal duty
 Engine exhaust manifold – dry
 Engine Oil Heater – 208/240 VAC, single phase
 Coolant Heater – two 4 kW, 208/240/480 volt reconnectible
 Dual Inlet Critical Silencer
 Insulation Blankets for Manifold
 Raincap and Mounting Elbow
 Roof Thimbles (2 total)
 Exhaust Flexes (2 total)
 Vibration Isolators (12 total)
 Remote Annunciator Panel
 Wall Mount Battery Charger – 10 amp, 24 VDC/120 VAC
15-2620.01 (1526200002 (copy))
Page 2 of 3
Switchgear
 Onan Model SPCL 9999R/76A
 2400 volt
 Includes Automatic Transfer Switch System and Load Bank Circuit Breaker
 Approx. Dimensions (entire panel) = 90” High x 68” Wide x 60” Deep
Load Bank:
 Saturn – HV 1500 Resistive Load Bank
 480 VAC
 3 Phase
 60 Hz
 1500 kW Capacity
 Load Steps = 50, 100, 100, 500, 750 (kW)
 120 VAC Control Power
 Cooling System:
o 60,000 CFM Airflow
o Vertical Direction
o 20 HP Motor
o Fan Circuit Breaker = 100A Frame / 40A Trip
 Approx. Dimensions (entire unit) = 98” High x 72” Wide x 198” Long
o Add 40” in Height when removable exhaust hood is installed
 Approx. Dry Weight (entire unit) = 12,500 lbs.
Primary Switch:
 13.2 kV
 ½ Cabinet labeled “P.E. Co. Meterig Transformers”
 ½ Cabinet labeled “Line Load Break Switch”
Transformer:
 Manufactured by General Electric
 Liquid Filled, 2,400 Volt
 Approx. Dimensions = 90” High x 99” Wide x 121” Deep
 Approx. Wet Weight = 12,650 lbs.
Generator System Operation and Maintenance Manual
 1 Set bound in 3-ring binder (original from time of installation)
15-2620.01 (1526200002 (copy))
Page 3 of 3