Test safety switch Reset safety switch Remove bridge across safety switch Remove bridge across safety switch Reset safety switch *If no fault found repeat for fixed appliances like stoves, hot water service, air Test safety conditioner, etc. switch Remove faulty appliance CHECK FOR Repeat clamp test each appliance NO NO Clear fault. Reading below 5mA Insulation breakdown or contamination in circuit connections Reading above 5mA YES YES Clamp test each protected sub-circuit Reading above 5mA ELECTRICIAN'S ON SITE FAULT FINDING GUIDE YES YES YES Same reading? NO NO READING BELOW THAT AT SAFETY SWITCH BRIDGE 488 486D 486CD Cat. No 489D YES Reset safety switch Test safety switch Test safety switch Remove bridge across safety switch Clear fault reading below 5mA Nail through cable or bridged CHECK terminals FOR in circuit appliances Neutral to earth fault NO OR YES Test safety switch Reset safety switch Remove bridge across safety switch Clear fault reading below 5mA Lighting neutral returns via power circuit Neutrals and earth wires crossed at connections Reading equals 100% of load current Note 2: Under no circumstances should the press to test function be utilised while RCD is bridged. Note 1: Bridging of MCB / RCDs negates the MCB function and may result in fusing the main fuse with faulty wiring. In these instances, fault currents could be significant and suitable precautions should be taken. Reading equals 50% of load current CLIPSAL CLIPSAL Reset safety switch Remove bridge across safety switch Clear fault reading below 5mA Indicates other faulty appliances Indicates ZERO fault in cable READING run or connections Reading below 50% of load current Reading above 5mA NO Re-connect each light and appliance one at a time and re-test* Bridge and clamp test safety switch in OFF position Unplug all appliances Safety switch trips F1831 WARRANTY 1. The benefits conferred herein are in addition to, and in no way shall be deemed to derogate; either expressly or by implication, any or all other rights and remedies in respect to this Clipsal Product, which the consumer has under the Trade Practices Act or any other similar State or Territory Laws. 2. The Warrantor is Clipsal Australia Pty Ltd of 12 Park Terrace Bowden, South Australia 5007, Telephone (08) 8269 0511. With registered offices in all Australian States. SA 153 Francis Road, Wingfield 5013. Telephone (08) 8268 0400 NSW 122 Canterbury Road, Padstow 2211. Telephone (02) 9794 9200 VIC 83-89 Queens Parade, North Fitzroy 3068. Telephone (03) 9207 3200 QLD (Brisbane) 919 Nudgee Road, Nudgee 4014. Telephone (07) 3244 7444 (Townsville) 736-740 Ingham Road, Mount Louisa 4814. Telephone (07) 4729 3333 WA 23 Truganina Road, Malaga 6062. Telephone (08) 9442 4444 TAS (Launceston) Unit 23/34 Innocent Street, Kings Meadows 7249. Telephone (03) 6343 5900 NT 16 Albatross Street, Winnellie 0820. Telephone (08) 8947 0278 3. This product range is guaranteed against faulty workmanship and materials for a period of two years from the date of installation. 4. Clipsal Australia Pty Ltd reserves the right to determine whether to repair or replace any faulty product free of charge for parts and labour or to give a refund in respect of the faulty product. 5. This warranty is expressly subject to the device being installed, wired, tested, operated and used in accordance with the manufacturer's instructions. 6. Should the product, the subject of the claim, be found to be in good working order all costs of the claim shall be met by the consumer. 7. When making a claim the consumer shall forward the device to the nearest office of Clipsal Australia Pty Ltd together with adequate particulars of the defect within 28 days after the appearance of the defect. Clipsal Australia Pty Ltd ABN 27 007 873 529 12 Park Terrace, Bowden, South Australia 5007 Telephone (08) 8269 0511 Facsimile (08) 8340 1724 RCD Series RCBM Series 4RC Series 4RCBM Series 4RCBE Series Installation Instructions Residual Current Devices, Combination Residual Current Devices and Miniature Circuit Breakers TYPICAL INSTALLATION DIAGRAMS AND INSTRUCTIONS Please Read Carefully. 1. Total current of protected circuits shall not exceed maximum current of the RCD. 2. Fixed appliances eg. stoves and hot water services, may cause deceptive tripping of RCD. It is recommended to connect them independent of RCD or on separate RCD protected circuits. 3. Ensure “Main Earth” and Main Neutral are in perfect condition. 4. Maximum admissible backup fuse as protection against short circuits. RCD CURRENT RATING FAULT LEVEL BACK UP FUSE gL 4RC Series ONLY UP TO 40A 10kA 63A 63A 6kA 63A 80A 10kA 80A 100A 10kA 100A RC Series ONLY 40A 6kA 63A 63A 6kA 63A CLIPSAL RESIDUAL CURRENT DEVICE WIRING DIAGRAMS RCD may be mounted in any position, load and line terminal may be connected top or bottom. OL - Overload Protection: Fuse or MCB. 4RC Series Max size cable accommodated 25mm2 up to 80A and 35mm2 up to 100A. RC Series Max size cable accommodated 25mm2 CLIPSAL RC and 4RC SERIES RESIDUAL CURRENT DEVICE WIRING DIAGRAMS SINGLE PHASE — 1 CIRCUIT OFF PEAK HOT WATER SWITCH A A MAINS SWITCH OL E OL OL 2 OL 4N OL CLIPSAL RCD 3N 1 N MAIN NEUTRAL LINK NEUTRAL LINK DO NOT EARTH VV VV VV N A H.W.S. TO UNPROTECTED CIRCUITS N A N A V V V V N A N A TO RCD PROTECTED CIRCUITS SINGLE PHASE — 2 CIRCUIT OFF PEAK HOT WATER SWITCH A A MAINS SWITCH 2 4 6 OL OL 8N OL CLIPSAL RCD E 1 3 5 7N V V V N A N V A TO RCD PROTECTED CIRCUITS N MAIN NEUTRAL LINK V V A TO H.W.S. N OFF PEAK HOT WATER SWITCH SINGLE PHASE — 3 CIRCUIT A A MAINS SWITCH 2 4 8N 6 OL OL OL V V V V VV OL CLIPSAL RCD 1 E 3 5 7N NEUTRAL LINK N A N A DO NOT EARTH N A A TO RCD PROTECTED CIRCUITS TO H.W.S. V V N MAIN NEUTRAL LINK WARNING (COMBINED MAX. DEMAND OF THESE THREE CIRCUITS MUST NOT EXCEED RATING OF RCD) N 5. Where 4 pole devices, are used as 2 pole devices connect Active and Neutral conductors as shown on wiring diagram on the RCD for test button to operate. MAINS SWITCH THREE PHASE OR TWO PHASE 120˚ CIRCUITS /OUTLETS A A A E 2 OL OL 4 6 8N CLIPSAL RCD OL 1 N 3 5 OL OL OL V V 7N MAIN NEUTRAL LINK NOTE: FOR BALANCED 2 AND 3 ∅ CIRCUITS NO NEUTRAL IS REQUIRED V V V VV V NEUTRAL LINK DO NOT EARTH V V N A N A N A TO UNPROTECTED CIRCUITS N A A A TO RCD PROTECTED CIRCUITS CLIPSAL RCBM, 4RCBM AND 4RCBE SERIES COMBINED MCB/RCD WIRING DIAGRAM A SINGLE PHASE MAIN SWITCH E 2 4N 1 3N OL N MAIN NEUTRAL LINK V V A N TO UNPROTECTED CIRCUITS V V A N TO RCD PROTECTED CIRCUIT