DCL-CONS-34007212 2009-10-15 MGE™ Galaxy™ 300 MGE™ Galaxy™ 300 10kVA MGE™ Galaxy™ 300 15kVA MGE™ Galaxy™ 300 20kVA MGE™ Galaxy™ 300 30kVA MGE™ Galaxy™ 300 40kVA Technical data sheets: manufacturer’s declaration according to IEC 62040-3 Technical Data sheets MGE™ Galaxy™ 300-AC MGE™ Galaxy™ 300 10, 15, 20, 30, 40kVA / IEC 62040-3 Technical data sheets - Manufacturer declaration UPS tests Characteristic of equipment reference only Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references Construction Model catalogue reference MGE™ Galaxy™ 300 (manufacturer’s reference) Three Phases In Three Phases Out UPS 10/20/30/40kVA & MGE™ Galaxy™ 300 Three Phases In one Phase Out UPS 10/20/30kVA 5.1.1 Model VA ou W 10kVA – 8kW MGE™ Galaxy™ 300 UPS Unitary or Parallel 10kVA Power, rated Apparent - 15kVA – 12kW MGE™ Galaxy™ 300 UPS Unitary or Parallel 15kVA Active 20kVA – 16kW MGE™ Galaxy™ 300 UPS Unitary or Parallel 20kVA With Cosϕ=0,8 30kVA – 24kW MGE™ Galaxy™ 300 UPS Unitary or Parallel 30kVA 40kVA – 32kW MGE™ Galaxy™ 300 UPS Unitary or Parallel 40kVA UPS Configuration Topology Double conversion with Bypass 5.3.4 Classification of UPS by performance VFI SS 113 Mechanical Dimensions (Height x Width x Depth) mm See separate declaration If details, to specify them in the separate declaration (Paragraphe 1) Mass or Weight kg See separate declaration If details, to specify them in the separate declaration (Paragraphe 1) Mass or Weight with batteries (if kg integrated) See separate declaration (Paragraphe 1) Measurements in accordance with standard Acoustic noise at 1m 6.5.5 - Normal mode dBA ≤56dBA ISO 7779 (0,15m < d < 8m according to dimensions of - Stored energy mode dBA ≤56dBA the source of noise, with ,preference 1m). Safety Access (operator access or restricted IEC 62040-1 Restricted Access access) Degree of protection against hazards and IP water ingress APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 IP 20 In accordance with IEC 60529 IP XX first X (/ foreign body) 2nd X (/ water) 2 UPS tests Characteristic of equipment reference only Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references UPS category C3 CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040- Electromagnetic Compatibility Emission UPS Cat See separate declaration (paragraph 6) 2: 2005 - Immunity to electrostatic discharges - Immunity to radiated IEC 62040-2 Immunity UPS Cat UPS category C3 - conducted a.c mains See separate declaration - conducted a.c output (paragraph 6) - Radiated - electric field - Radiated - magnetic field Environmental Ambient storage temperature range °C -10° C to +60 ° C T° specified, equipment without batteries For Altitude < 1000m and moisture 20 to 95% 4.2.1.1 Ambient service temperature °C -15° C to +40° C T° specified, for Batteries 0° C to +35° C Continuous maximum ambient service temperature at rated Current, Cosϕ=0,8 0° C to + 25°C Continuous maximum ambient service temperature with Battery inside the Unit Maximun service altitude m 4.2.1.2 ≤1000m and P = nP – 10% all the 1000m Until 1000m included For 1500 to 5000m, coefficient of downgrading from 0,85 to 0,59 Relative humidity range % 4.1.3 Storage : 0% to 90% Operation : 05% to 90% ( without condensation ) Relative humidity without condensing at ambient temperature 5.6 4.2.1.1 Communication circuits (List communication / signalling circuits) See separate declaration (paragraph 5) Electrical characteristics - Input Voltage (steady-state, r.m.s) V - rated 220V or 230V or 240V Nominal value of input voltage, and thresholds of 380V or 400V or 415V passage in stored energy mode by input voltage exceeding the tolerance To specify : if there is no a change of mode to 5.2.1.a stored energy mode by U + 10% or if the thresholds depend on the load use Minimal value of input votage allowing the refill battery during normal operation UPS 5.2.1.b - tolerance % Frequency Hz ±2% 50Hz or 60Hz Nominal value of input frequency and thresholds of a change of mode to stored energy mode of the - rated UPS, by input frequency exceeding the tolerance 5.2.1.c If it there not a change of mode to stored energy mode, to specify the minimum and maximum frequency possible for the UPS 5.2.1.d - tolerance % ±10% (45 to 65Hz) APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 3 UPS tests Characteristic of equipment reference only Manufacturer's declared Minimum performance informations values requirements, methods and references ≤13A / (10kVA) Input steady current with ,100% rated VA and W, on – rated (with the energy storage device ≤20A / (15kVA) linear and non linear load charged) ≤26A / (20kVA) Current r.m.s. 5.2.2.c Units and/or A ≤40A / (30kVA) ≤53A / (40kVA) maximum (with low input volt and energy A storage device charging) ≤16A / (10kVA) ≤23A / (15kVA) 5.2.2.f ≤29A / (20kVA) ≤42A / (30kVA) ≤56A / (40kVA) 5.2.2.h 5.2.2.g - total harmonic distortion (THD p.u.) % - overload (% of rated current against time) %, s - in-rush (% of rated current against time) %, s <9% ≤125%, 120s ≤150%, 10s 5.2.2.e <I nominal (rated input RMS current) Maximum peak value of current measured after mains power down of 1 second and 5 minutes (if the perturbance < 1s it is not retained ) 5.2.2.d 5.2.2.k 5.2.2.i 5.2.2.a power factor >0,97 With input current at >50% rated VA and W on linear load and non linear load AC power distribution system -(TN, TT, IT) compatibility - short-circuit power required TT, TN (S or C), IT Ssc See separate declaration (paragraph 2) - phases required (1,2 or 3) Tree Phases 3P+N+G 5.2.2.b - neutral required (yes / no) Yes 5.2.3 Additional or unusual conditions NA Output waveform 5.3.1.2 Waveform - Normal mode Sinusoidal Sinusoidal or non sinusoidal 5.3.1.2 Waveform - Stores energy mode Sinusoidal Sinusoidal or non sinusoidal Transfer - Normal mode / Stored energy Break No break Break time / Make time ( if applicable ) ms On battery mode No Break Complies with figure 1 Without Break Rated voltage ±2% with a come back to ±1% in 100ms Transfer transients and times measured at the time of tranfer load from UPS to an alternative source and return, by command or defect of switches of coupling and bypass APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 4 UPS tests Characteristic of equipment reference only Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references Electrical output characteristics - Static and Dynamic characteristics - Normal mode 5.3.2 AC power distribution system - compatibility (TN, TT, IT) TT, TN (S or C), IT - phases available (1,2 or 3) One Phase 1P+N+G Or Tree Phases 3P+N+G - neutral available (yes / no) Yes Voltage (steady state, r.m.s.) Rated Output voltage V r.m.s 220V, 230V, 240V default value Operation at 415 VAC/60 Hz is not possible for One phase 380V, 400V, 415V default value for Tree phases Output voltage normal mode variation % Rated voltage ±2% adjustable Output voltage measured at the two ends of the range of rated power factor and with nominal rated votage Voltage variation = maximum and minimum measured value Stored energy mode variation % Rated output apparent power VA ±2% 10kVA 15kVA 20kVA 30kVA 40kVA Rated output active power across a W 8kW linear load 12kW 16kW 24kW 32kW Rated output active power across a W Same as linear load reference non linear load Total voltage distortion across a linear load % <3% Total voltage distortion across stored % <2% % <5% UPS mode with nominal rated output power VA energy mode, linear Total voltage distortion across a reference 100% unbalanced 100% non-linear loads (IEC 62040-3) non linear load UPS mode with nominal rated output power VA and dc voltage load capacitor ≤ 1.22 x of UPS output voltage Voltage unbalance and phase %, ° <1.5% %, s Complies with IEC 62040-3 phase at full load displacement, 100 % load unbalance Voltage transient and recovery time, 100 2 phases with 0,5xnominal linear load and the other % step load To note Fig 1, 2 or 3 to specify the performance and to announce if the performances are > - Linear load P ( W) : measurements UPS peak voltage, for variation 0% to 100% then 100% to 20% of nP - Non linear load P ( VA ) :measurement of the transitory variation of U, for variation 33% to 66% then 66% to 99% then 99% to 66% then 66% to 33% of nP APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 5 UPS tests Characteristic of equipment reference only Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references - linear %, s Complies curve 1 with IEC - Non-linear %, s Complies curve 3 with IEC - transfer normal mode / storage energy %, s Complies curve 1with IEC 62040-3 62040-3 6.4.2.11.1/2 mode 62040-3 To note Fig 1, 2 or 3 and specified UPS Performance with nominal power W and resistive linear load - mains voltage stopped with 0 and maximum of sinusoide , during t > 1s _ 3 times minimum, to ensure itself of the repetitivity, during t > 1s - Return mains voltage to all angular positions of the sinusoide Frequency (steady-state) : Rated Output frequency (nominal) Hz 50Hz or 60Hz Same as Input - normal mode variation % ±0,5Hz (adjustable from ±0,25Hz to ±4Hz) ±0,05Hz - stored energy mode variation % - free-running variation % Same as above Synchronization (max ± % range of rated % 47.5-52.5 Hz for 50Hz frequency) Max synch phase error (referred to a 360° Operation at 415 VAC/60 Hz is not possible Thresholds of maximum frequency for which the UPS remains synchronized with the mains To specify also ,UPS freqency variation with stored energy mode Same as above 58.5-62.5 Hz for 60Hz ° < 3° On line : if non transfer by a change of mode to stored energy mode, to note 0 cycle) Off line : To note the measurements of dephasing compared with the fundamental, at the time of the transfer of source when the mains return Max slew-rate Hz / s 0,66 Hz/Sec Current (r.m.s.) : - rated A ≤15A / (10kVA) Tree Phases 3P+N+G ≤23A / (15kVA) ≤30A / (20kVA) ≤46A / (30kVA) ≤61A / (40kVA) ----------------------≤46A / (10kVA) -----------------------------------One Phase 1P+N+G ≤68A / (15kVA) ≤91A / (20kVA) ≤136A / (30kVA) - Overload capability (% of rated current / 5.3.2.l %/s time duration) See separate declaration (Paragraphe 2) Overload applied on the output terminals of the UPS when the UPS is in normal mode at resistive load Measurements of the time duration during which the output voltage remains in the rated range - Limitation (% of rated current / time %/s duration) - Fault clearing capability (normal / stored 6.4.2.10.3 /4 See separate declaration (Paragraphe 4) A gL fuse 50kA for the 3/3: 10kVA,15kVA,20kVA,3/1:10kVA,15kVA,20kVA energy mode) 80kA units for the 3/3:40kVA,3/1:30kVA units APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 6 UPS tests Characteristic of equipment reference only Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references Load power factor : - rated 0.8 - displacement (permissible lead-lag Battery operation cannot support overload From 0,5 leading to 0,5 lagging range) 5.3.2 r) / 6.4.1.6 AC / a.c efficiency in normal mode - 100 % load % See separate declaration - 75 % load % See separate declaration (Paragraphe 4) - 50 % load % See separate declaration (Paragraphe 4) - 25 % load % See separate declaration (Paragraphe 4) (Paragraphe 4) Bypass – automatic (static or electro-mechanical) Transfer time break static ms 0ms to 20ms Transfer without interruption conditions: The bypass AC-input voltage is within tolerances and inverter/bypass transfers are possible without load interruption if: - Bypass phase voltage under tolerance - Frequency is within tolerance - Phase displacement between the inverter voltage and the bypass AC-input voltage is in tolerance 5.3.2.l rated current A Overload current (% of rated current / time %/s duration) See Inverter values See separate declaration (Paragraphe 2) Overload applied on the output terminals of the UPS when the UPS is in normal mode at resistive load Measurements of the time duration during which the output voltage remains in the rated range - maintenance (internal or external) Internal - isolation transformer (yes / no ) Bypass protection fuse or circuit breaker rating 5.5 5.3.3 No See separate declaration (Paragraphe 2) Stand-alone switch (list any and its product NA standard) Additional or unusual conditions APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 NA 7 UPS tests Characteristic of equipment reference only 5.4 5.4.2.2 d Units and/or Manufacturer's declared Minimum performance informations values requirements, methods and references Stored energy mode of operation Technology Maintenance-free sealed LeadAcid battery with suspended electrolyte: leakproof 5.4.2.2 a 5.4.2.2 b Life Design life or float service life years Up to 5-year The guaranteed backup time is defined for 0.7*Pn and cos ϕ =0.8. Quantity of cells and strings Varied with power rate 5.4.2.2 c Nominal voltage (total) V d.c. 5.4.2.2 e Nominal Ah capacity (C10) Ah 5.4.2.2 f Stored energy time (back-up time at 100 % ±192 / ±180 Normal temperature of test ,25° C Varied with power rate Normal temperature of test ,25° C According to the battery Normal temperature of test ,25° C 10 hours - to 90% ±5% Internal charger: rated load) 5.4.2.2 g Restored energy time (recharge time to 90 capacity after full discharge at min. Config. % capacity) --------------------------------------24 hours - to 90% ±5% 5.4.2.2 h Ambient reference temperature 5.4.2.2 i Earth condition / Isolation °C 5.4.2.2 j r.m.s. ripple current % 5% C10AH 5.4.2.2 k Nominal discharge current A Varied with power rate 5.4.2.2 l Default current rating A d.c. NA 5.4.2.2 m Cable volt drop recommendation (% at % NA ---------------------------------------------------------------------CLA: capacity after full discharge at min. Config. 25°C Grounding At max constant current charging mode nominal discharge current) 5.4.2.2 n Protection requirements by others 5.4.2.2 o Charging regime 5.4.2.2 p Charge voltage (float, boost) and tolerance 5.4.2.2 q End of discharge voltage NA Constant current charge, and To specify, if batteries recharge with constant after, constant voltage charge limiting current V d.c ±218V / ±204V V d.c From 1,65V to 1,9V band (±154V / ±148V) 5.4.2.2 r Charge current limit (or range) 5.4.2.3 Additional or unusual conditions 5.8 A d.c. (according to the battery) Normal temperature of test ,25°C 7A Internal charger 21A CLA NA Control and monitoring signals Optional Separate declaration for complete list of indications and remote alarm/monitoring or interface devices See separate declaration (paragraph 5) APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 8 MGE™ Galaxy™ 300 10, 15, 20, 30, 40kVA / IEC 62040-3 Technical data sheets - Separate declaration 1. Dimensions and weight of equipment: UPS Without packaging and With Battery: MGE™ Galaxy™ 300 3:1 10-15kVA and 3:3 10-20kVA Type Height(mm) Length(mm) Depth(mm) Weight( kg) 3:3 30-40kVA and 3:1 20kVA, 30kVA Single Parallel 1300 400 860 375-390 Kg 375-390 Kg Single Parallel 1300 500 860 435-615 Kg 435-615 Kg Auxiliary Cabinet: MGE™ Galaxy™ 300 Type Height(mm) Length(mm) Depth(mm) Weight( kg) Single 1300 660 850 105-610 Kg 2. Electrical Output characteristics - Static characteristics - Normal Mode THDU linear load : AC input voltage 400 V / output voltage 400 V Cos phi=0.8 MGE™ Galaxy™ 300 3/3 : THDU (%) 20kVA 40kVA 25%Pn 0.6 0.4 50%Pn 0.92 0.5 75%Pn 1.03 0.5 100%Pn 1.11 1.2 25%Pn 0.77 0.71 1.05 50%Pn 0.77 1.07 1.05 75%Pn 0.81 1.45 1.05 100%Pn 0.76 1.8 1.05 25%Pn 1.61 1.8 50%Pn 2.53 2.6 75%Pn 3.09 3.5 100%Pn 3.76 4.8 25%Pn 2.24 1.52 1.49 50%Pn 3.32 2.02 2.22 75%Pn 3.98 2.47 2.76 100%Pn 4.48 3.27 3.66 MGE™ Galaxy™ 300 3/1 : THDU (%) 15kVA 20kVA 30kVA THDU non-linear load : AC input voltage 400 V / output voltage 400 V Cos phi=0.7 MGE™ Galaxy™ 300 3/3 : THDU (%) 20kVA 40kVA MGE™ Galaxy™ 300 3/1 : THDU (%) 15kVA 20kVA 30kVA APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 9 Rectifier thermal-overload capacity curve : Inverter thermal-overload capacity curve : Bypass-overload capacity curve : AC-bypass thermal-overload capacity limited by the overtemp protection. The thermal overload signal generated by a thermostat located on heatsink: thermal protection at 85°C. Bypass short-circuit capability : -3/3 UPS bypass SCR short circuit capacity MGE™ Galaxy™ 300 10 kVA 15 kVA 20 kVA 30 kVA Short-circuit capacity I2t (A2S) 7200 7200 7200 15000 -3/1 UPS bypass SCR short circuit capacity MGE™ Galaxy™ 300 10 kVA 15 kVA 20 kVA 30 kVA Short-circuit capacity I2t (A2S) 15000 15000 15000 125000 40 kVA 15000 40 kVA 15000 Recommended upstream discrimination For 3/3 UPS single mains systems Rated power 10-20kVA 30kVA 40kVA CB on Mains1 C65H-D-4P-63A/ C60H-D-4P-63A C120H-D-4P-80A C120H-D-4P-125A For 3/3 UPS dual mains systems Rated power CB on Mains1 10-20kVA C65H-D-4P-50A/ C60H-D-4P-50A 30kVA C120H-D-4P-80A 40kVA C120H-D-4P-100A CB on Mains2 C65H-D-4P-63A/ C60H-D-4P-63A C120H-D-4P-80A C120H-D-4P-125A For 3/1 single mains systems Rated power 10kVA 15kVA 20kVA 30kVA CB on Mains1 C120H-D-4P-80A C120H-D-4P-125A NSX250F TM200D 4P NSX250F TM250D 4P APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 10 For 3/1 dual mains systems Rated power 10kVA 15kVA 20kVA 30kVA CB on Mains1 CB on Mains2 C65H-D-4P-50A/ C60H-D-4P-50A C65H-D-4P-50A/ C60H-D-4P-50A C65H-D-4P-50A/ C60H-D-4P-50A C120H-D-4P-80A C120H-D-2P-80A C120H-D-2P-125A NSX250F TM200D 3P NSX250F TM250D 3P Recommended downstream discrimination These protection systems ensure discrimination on all of the output circuits connected to the unit. If the recommended downstream protection is not installed, the result may be breaks in the supply of power longer than 20 milliseconds on all the other output circuits. For 3/3 UPS Rated power 10-20kVA 30kVA 40 kVA Downstream CB C65N-C-4P-6A C65N-B-4P-10A C65N-B-4P-16A C65N-C-4P-10A C65N-B-4P-20A C65N-C-4P-10A For 3/1 UPS Rated power 10-15kVA 20 kVA 30 kVA Downstream CB C65N-B-2P-25A C65N-C-2P-10A C65N-B-2P-32A C65N-C-2P-16A C65N-B-2P-50A C65N-C-2P-25A The short circuit current of the installation must be less than the maximum current of the downstream circuit breaker. 3. Electrical Output characteristics - Dynamic characteristics – Unbalanced linear loade Linear load Cos phi=0.8 to 400V (RL load): I1 = 0,5.IN; I2 = 0,5.IN; I3=1IN : MGE™ Galaxy™ 300 3/3 : THDU (%) 20kVA 40kVA 0.6/1.2/0.6 0.6/1.2/0.6 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 11 4. Efficiency Efficiency on linear load : On Normal mode : AC input voltage 400 V / output voltage 400 V MGE™ Galaxy™ 300 3/3 : Efficiency in % % load UPS power in kVA 20 30 10 15 Avg. Avg. Avg. Avg. Avg. 40 25 83.19 89.45 90.47 90.33 91.45 50 90.47 92.11 92.42 92.7 93.05 75 92.11 92.67 92.76 93.23 93.01 100 92.42 92.76 92.7 93.01 92.81 10 15 MGE™ Galaxy™ 300 3/1 : Efficiency in % % load UPS power in kVA 20 30 Avg. Avg. Avg. Avg. 25 83.51 87.16 89.7 88.8 50 89.63 91.23 92.89 92.1 75 91.23 91.97 93.11 92.7 100 91.88 91.99 92.96 92.75 10 15 Losses MGE™ Galaxy™ 300 3/3 : Typical losses in kW doubleconversion mode 25 Avg. Avg. Avg. 0.34 0.32 0.38 0.72 0.79 50 0.38 0.47 0.6 0.97 1.11 75 0.47 0.66 0.87 1.22 2.4 100 0.6 0.87 1.17 2.4 2.42 10 15 % load UPS power in kVA 20 30 Avg. 40 Avg. MGE™ Galaxy™ 300 3/1 : Typical losses in kW doubleconversion mode 25 Avg. Avg. Avg. Avg. 0.43 0.45 0.42 0.75 50 0.47 0.58 0.57 1.02 75 0.58 0.8 0.84 1.4 100 0.72 1.05 1.14 1.88 % load UPS power in kVA 20 30 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 12 5. Control and monitoring signals List of indications and remote alarms, monitoring or interface device. Information on display : Operation of the FCIM board (dry contacts) Input dry contacts In this mode, the relays switch when the UPS changes status, but don’t bother customers with inopportune alarms that last less than 5S. The information listed below is transmitted if the parameters were enabled in Service Tools. Inputs configurable inside the list below : Outputs 1 Operating status condition Emergency Power OFF Discription EPO dry contact on FCIM board,connect with emergency power off switch on costumer sites. ( normally closed, open when EPO active) Output dry contacts In this mode, the relays switch when the UPS changes status, but don’t bother customers with inopportune alarms that last less than 5S. The information listed below is transmitted if the parameters were enabled in Service Tools. Outputs volt-free contacts (25V / 5A max), configurable inside the list below: Outputs Operating status condition 1.1 General alarm 1.2 Load on battery power Low battery warning 1.3 Discription PFC fault OR Inverter fault OR Bypass static switch fault OR Charger fault OR EPO activated OR Battery backup time ended, shift to wait mode OR Battery temperature fault > 40°C or battery tempera ture sensor destroyed, charger shutdown OR Abnormal presence of voltage on the output before closing the bypass static switch. (frequency converter) OR UPS in downgraded mode OR CAN communication fault OR UPS personalization fault. Inverter connected to the load and operating on battery power. Battery operations due to a battery test are not signalled. Battery has reached the low-battery warning level (voltage or time). The two thresholds may be user set. APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 13 Standard and Optional cards for UPS : This card provides three connections, one to an Ethernet 10/100 BT network, one to a JBUS/RS485 network and one to a modem. It may be installed with the UPS energised. The JBUS/RS485 connection may be used to connect the UPS to a building monitoring system via a JBUS/MODBUS network. It can also be used to concentrate a number of UPS units on a single telephone line. Rhodes2 card The protocol used between Rhodes 2 Card and the HMIM board is SHUT/COPI Rhodes 2 Card in Galaxy 300, interface with HMIM board to provide the following functions: o Protocol will be exMGE one : SHUT/COPI o On customer side, the software applications will be o PowerChute o ISX Central o RMS over Ethernet o TLS over Modem o Modbus monitor The product is based on the RHODES2 platform and need a firmware adaptation in order to be compatible with the exMGE SHUT/COPI protocol and database. The 2 references AP9630, and AP9635 need to be compatible with this protocol. A low cost Ethernet of Other global requirements (not specific to APC by Schneider UPS) are: - Modbus - English pages - 3- phases mimics on page - For (Webserver, PowerChute, ISX Central, RMS) - And also an Ethernet & Modem Teleservice & Modbus card. - For the Teleservice card AP9635, it is required to integrate in addition: - Modbus protocol (Modbus RTC over RS485 bus) and Modbus data matrix - Connection via Modem to exMGE TLS Center - Connection via Modem to exMGE TLS-Connect diagnostic tools - UPS concentration for parallel configuration (up to 2 for Galaxy 300) Features / Card AP9630 AP9635 SHUT/COPI protocol X X HID database X X RS485 Modbus slave X TLS Center modem connection X TLS UPS concentration (RS485 Modbus master) X Functional summary Model AP9630 AP9635 10/100 1 1 USB 2 Sensors 1 Modem Internal Modbus Internal APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 Flash 8 16 SD card - RAM 1 1 CAN - 14 6. Electromagnetic compatibility UPS from 10 to 40 kVA Galaxy 300 UPSs have been certified for product standard EN 62040-2. Immunity tests Electrostatic discharges Required by standard (minimum level) Product result (immunity level) IEC 61000-4-2: 1995 / EN 62040-2: 2005 8 kV in air and 4 kV for contact 8 kV in air and 4 kV for contact Radiated radio-frequency fields IEC 61000-4-3: 2002 / EN 62040-2: 2005 Required by standard (minimum level) 10 V/m modulated 80% AM at 1 kHz from 80 MHz to 1 GHz Product result (immunity level) Rapid transients in bursts Required by standard (minimum level) 10 V/m modulated 80% AM at 1 kHz from 80 MHz to 1 GHz Conducted immunity Required by standard (minimum level) Product result (immunity level) IEC 61000-4-4: 2004 / EN 62040-2: 2005 2 kV on AC-input cables 2 kV on DC cables 2 kV on I/O cables 2 kV on AC-input cables 2 kV on DC cables 2 kV on I/O cables IEC 61000-4-5: 1995 / EN 62040-2: 2005 1 kV coupling between lines 1 kV coupling between lines and earth 1 kV coupling between lines 2 kV coupling between lines and earth IEC 61000-4-6: 2003 / EN 62040-2: 2005 10V/m modulated 80% AM at1 kHz from 150 kHz to 30 MHz 10V/m modulated 80% AM at1 kHz from 150 kHz to 30 MHz Immunity to magnetic fields at network frequency Required by standard (minimum level) Product result (immunity level) IEC 61000-4-8:2001 / EN 55024 30 A/m 30 A/m Product result (immunity level) Surges, high energy Required by standard (minimum level) Product result (immunity level) Tests on emitted disturbances Conducted emissions Standard version CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-2: 2005 UPS category C3 (controlled distribution) Radiated emissions Standard version CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-2: 2005 UPS category C3 (controlled distribution) Certifications Presentation to standardisation organisations: TÛV : - CB Marking- Safety IEC 62040-1-1 2004 EMC : IEC 62040-2 CE (Marking) APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 15 7. Individual input harmonic current in accordance with IEC 61000-3-2 standard. ( With nominal rms current) MGE™ Galaxy™ 300 3/1 20kVA load 25% 50% 75% 100% Harmonics (in %) 17.17 8.08 7.81 6.53 H2 2.66 0.61 0.72 0.62 H3 12.57 5.6 5.41 4.96 H4 1.07 1 0.61 0.33 H5 5.58 2.37 2.16 1.91 H6 1.35 0.94 0.74 0.50 H7 4.9 1.93 1.37 1.4 H8 0.49 0.48 0.39 0.26 H9 2.6 2.26 1.75 0.68 H10 0.52 0.34 0.36 0.43 H11 2.5 1.35 1.08 1.12 H12 0.68 0.34 0.29 0.18 H13 1.48 1.02 0.94 0.83 H14 0.35 0.25 0.23 0.23 H15 0.95 0.63 0.61 0.66 H16 0.18 0.25 0.19 0.13 H17 1.41 0.84 0.75 0.73 H18 0.35 0.18 0.13 0.07 H19 0.35 0.35 0.39 0.33 H20 0.35 0.25 0.25 0.01 H21 0.35 0.44 0.43 0.37 H22 0.22 0.15 0.11 0.07 H23 0.18 0.25 0.25 0.33 H24 0.35 0.15 0.12 0.07 H25 0.52 0.44 0.45 0.37 H26 0.35 0.15 0.18 0.12 H27 0.64 0.22 0.17 0.22 H28 0.22 0.22 0.17 0.13 H29 0.48 0.25 0.25 0.32 H30 0.35 0.22 0.2 0.11 H31 0.8 0.25 0.16 0.25 H32 0.69 0.22 0.16 0.09 H33 0.18 0.22 0.16 0.18 H34 0.48 0.22 0.16 0.07 H35 0.45 0.22 0.25 0.09 H36 0.35 0.15 0.12 0.08 H37 0.45 0.22 0.14 0.12 H38 0.35 0.22 0.16 0.09 H39 0.22 0.15 0.18 0.07 H40 0.22 0.15 0.11 0.17 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 16 MGE™ Galaxy™ 300 3/1 15kVA load 25% 50% 75% 100% Harmonics (in %) 14.19 13.04 5.83 4.75 H2 0.28 0.65 0.37 0.39 H3 3.64 2.52 1.32 1.65 H4 1.05 0.55 0.44 0.22 H5 8.72 8.18 3.57 2.51 H6 0.38 0.36 0.13 0.2 H7 1.93 2.91 0.62 0.63 H8 0.06 0.05 0.12 0.08 H9 1.91 0.36 0.89 0.57 H10 0.38 0.36 0.13 0.15 H11 0.65 2.59 0.49 0.33 H12 0.37 0.36 0.11 0.09 H13 3.66 0.41 1.38 0.5 H14 0.06 0.05 0.18 0.1 H15 1.48 0.53 0.26 0.4 H16 0.65 0.05 0.06 0.07 H17 3.15 2.14 1.55 0.41 H18 0.06 0.16 0.26 0.18 H19 2.16 1.63 1.06 0.54 H20 0.38 0.41 0.26 0.08 H21 2.16 1.01 0.89 0.55 H22 0.06 0.36 0.26 0.05 H23 1.37 2.98 1.06 0.38 H24 0.06 0.36 0.26 0.08 H25 0.83 1.01 0.26 0.09 H26 0.06 0.16 0.11 0.09 H27 1.16 2.14 0.3 0.36 H28 0.65 0.16 0.11 0.28 H29 0.78 1.29 0.26 0.28 H30 0.38 0.05 0.39 0.22 H31 0.38 0.05 0.39 0.19 H32 0.06 0.41 0.3 0.19 H33 1.71 2.84 0.3 0.36 H34 0.06 0.05 0.11 0.1 H35 2.81 3.4 1.24 0.36 H36 0.65 0.05 0.46 0.19 H37 0.38 1.85 0.3 0.4 H38 0.65 0.36 0.3 0.16 H39 2.16 2.64 0.18 0.22 H40 0.38 0.54 0.18 0.12 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 17 MGE™ Galaxy™ 300 3/1 30kVA load 25% 50% 75% 100% Harmonics (in %) 16.95 8.67 7.71 6.86 H2 4.35 2.61 1.06 0.75 H3 11.64 4.14 5.77 5.46 H4 1.43 1.3 0.47 0.41 H5 5.33 1.91 1.74 2.37 H6 1.26 0.83 0.43 0.36 H7 2.78 1.56 0.74 1.05 H8 0.76 0.5 0.27 0.27 H9 1.44 0.87 0.61 0.75 H10 0.96 0.49 0.34 0.17 H11 1.57 1.12 0.77 0.79 H12 0.93 0.44 0.29 0.2 H13 1.06 0.59 0.62 0.63 H14 0.63 0.3 0.34 0.29 H15 0.87 0.72 0.51 0.55 H16 0.89 0.37 0.33 0.21 H17 1.04 0.56 0.47 0.34 H18 0.62 0.48 0.36 0.25 H19 1.05 0.5 0.34 0.45 H20 0.67 0.41 0.3 0.17 H21 0.83 0.65 0.28 0.37 H22 0.51 0.57 0.24 0.2 H23 1.03 0.35 0.42 0.29 H24 0.68 0.42 0.29 0.19 H25 1.26 0.59 0.44 0.37 H26 0.58 0.44 0.34 0.2 H27 0.92 0.57 0.34 0.31 H28 0.68 0.34 0.38 0.21 H29 0.72 0.42 0.24 0.21 H30 0.61 0.61 0.28 0.17 H31 0.62 0.4 0.26 0.26 H32 0.77 0.36 0.23 0.23 H33 0.65 0.56 0.3 0.2 H34 0.69 0.32 0.29 0.28 H35 0.71 0.36 0.22 0.2 H36 0.9 0.3 0.3 0.18 H37 0.79 0.34 0.25 0.17 H38 0.64 0.48 0.26 0.17 H39 0.53 0.45 0.24 0.23 H40 0.50 0.43 0.34 0.16 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 18 MGE™ Galaxy™ 300 3/3 20kVA load 25% 50% 75% 100% Harmonics (in %) 15.14 13.79 6.78 6.37 H2 1.97 1.13 1.05 0.95 H3 7.64 5.39 4.45 4.00 H4 0.29 0.92 0.25 0.52 H5 4.11 3.22 2.24 1.99 H6 0.54 0.60 0.31 0.20 H7 2.58 1.95 1.44 1.21 H8 0.36 0.35 0.42 0.28 H9 2.25 1.56 1.03 0.73 H10 0.37 0.19 0.23 0.2 H11 1.33 1.53 0.98 0.86 H12 0.35 0.21 0.20 0.17 H13 0.84 1.08 0.94 0.79 H14 0.4 0.47 0.35 0.15 H15 0.71 0.84 0.62 0.62 H16 0.34 0.26 0.39 0.17 H17 0.85 0.48 0.58 0.46 H18 0.50 0.23 0.13 0.23 H19 0.63 0.50 0.6 0.61 H20 0.16 0.09 0.22 0.23 H21 0.44 0.39 0.26 0.19 H22 0.46 0.21 0.18 0.24 H23 2.15 1.18 0.66 0.8 H24 0.16 0.13 0.11 0.18 H25 1.64 1.01 0.37 0.57 H26 0.16 0.26 0.19 0.10 H27 0.88 0.31 0.33 0.26 H28 0.49 0.06 0.12 0.21 H29 0.43 0.27 0.31 0.31 H30 0.46 0.29 0.18 0.09 H31 0.25 0.19 0.15 0.22 H32 0.44 0.29 0.09 0.08 H33 0.13 0.13 0.21 0.16 H34 0.62 0.30 0.04 0.06 H35 0.28 0.18 0.07 0.20 H36 0.37 0.27 0.11 0.18 H37 0.36 0.16 0.06 0.09 H38 0.36 0.17 0.09 0.14 H39 0.25 0.31 0.20 0.17 H40 0.32 0.19 0.13 0.13 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 19 MGE™ Galaxy™ 300 3/3 40kVA load 25% 50% 75% 100% Harmonics (in %) 14.01 9.13 6.66 5.98 H2 3.22 2.16 0.89 1.04 H3 0.46 1.38 1.27 2.33 H4 0.45 0.69 0.75 0.57 H5 11.9 6 7.78 5.87 4.81 H6 0.72 0.30 0.71 0.25 H7 0.81 0.44 0.62 0.16 H8 0.80 0.70 0.31 0.17 H9 2.75 1.37 0.70 0.61 H10 1.13 0.52 0.31 0.44 H11 0.95 0.40 0.29 0.54 H12 0.36 0.03 0.26 0.15 H13 1.03 0.89 0.77 0.56 H14 0.57 0.10 0.18 0.27 H15 0.18 0.29 0.37 0.20 H16 0.24 0.35 0.10 0.55 H17 0.46 1.15 0.35 0.11 H18 0.43 0.53 0.15 0.29 H19 0.88 0.67 0.73 0.54 H20 0.71 0.12 0.10 0.40 H21 0.86 0.47 0.30 0.44 H22 0.95 0.22 0.13 0.34 H23 0.37 0.40 0.29 0.30 H24 1.06 0.21 0.18 0.35 H25 0.79 0.09 0.10 0.13 H26 0.06 0.28 0.25 0.14 H27 0.84 0.90 0.24 0.31 H28 0.35 0.35 0.30 0.18 H29 1.28 0.47 0.25 0.25 H30 0.41 0.16 0.03 0.42 H31 0.23 0.57 0.29 0.16 H32 0.18 0.24 0.18 0.11 H33 0.37 0.06 0.11 0.19 H34 0.43 0.62 0.30 0.16 H35 0.97 0.45 0.12 0.33 H36 0.76 0.17 0.11 0.12 H37 0.78 0.40 0.11 0.13 H38 0.62 0.39 0.23 0.07 H39 0.71 0.47 0.36 0.32 H40 0.10 0.06 0.12 0.24 APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3 MGE Galaxy 300-AC 15/10/09 20