Technical datasheets IEC 62040-3 MGE Galaxy 300

advertisement
DCL-CONS-34007212 2009-10-15
MGE™ Galaxy™ 300
MGE™ Galaxy™ 300 10kVA
MGE™ Galaxy™ 300 15kVA
MGE™ Galaxy™ 300 20kVA
MGE™ Galaxy™ 300 30kVA
MGE™ Galaxy™ 300 40kVA
Technical
data sheets:
manufacturer’s
declaration
according to
IEC 62040-3
Technical Data sheets MGE™ Galaxy™ 300-AC
MGE™ Galaxy™ 300
10, 15, 20, 30, 40kVA / IEC 62040-3
Technical data sheets - Manufacturer declaration
UPS tests
Characteristic of equipment
reference only
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
Construction
Model catalogue reference
MGE™ Galaxy™ 300
(manufacturer’s reference)
Three Phases In Three
Phases Out UPS
10/20/30/40kVA
&
MGE™ Galaxy™ 300
Three Phases In one Phase
Out UPS 10/20/30kVA
5.1.1
Model
VA ou W
10kVA – 8kW
MGE™ Galaxy™ 300 UPS Unitary or Parallel 10kVA
Power, rated
Apparent -
15kVA – 12kW
MGE™ Galaxy™ 300 UPS Unitary or Parallel 15kVA
Active
20kVA – 16kW
MGE™ Galaxy™ 300 UPS Unitary or Parallel 20kVA
With Cosϕ=0,8
30kVA – 24kW
MGE™ Galaxy™ 300 UPS Unitary or Parallel 30kVA
40kVA – 32kW
MGE™ Galaxy™ 300 UPS Unitary or Parallel 40kVA
UPS Configuration
Topology
Double conversion with
Bypass
5.3.4
Classification of UPS by performance
VFI SS 113
Mechanical
Dimensions (Height x Width x Depth)
mm
See separate declaration
If details, to specify them in the separate declaration
(Paragraphe 1)
Mass or Weight
kg
See separate declaration
If details, to specify them in the separate declaration
(Paragraphe 1)
Mass or Weight with batteries (if
kg
integrated)
See separate declaration
(Paragraphe 1)
Measurements in accordance with standard
Acoustic noise at 1m
6.5.5
- Normal mode
dBA
≤56dBA
ISO 7779 (0,15m < d < 8m according to dimensions of
- Stored energy mode
dBA
≤56dBA
the source of noise, with ,preference 1m).
Safety
Access (operator access or restricted
IEC 62040-1
Restricted Access
access)
Degree of protection against hazards and
IP
water ingress
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
IP 20
In accordance with IEC 60529
IP XX
first X (/ foreign body) 2nd X (/ water)
2
UPS tests
Characteristic of equipment
reference only
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
UPS category C3
CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-
Electromagnetic Compatibility
Emission
UPS Cat
See separate declaration
(paragraph 6)
2: 2005
- Immunity to electrostatic discharges
- Immunity to radiated
IEC 62040-2
Immunity
UPS Cat
UPS category C3
- conducted a.c mains
See separate declaration
- conducted a.c output
(paragraph 6)
- Radiated - electric field
- Radiated - magnetic field
Environmental
Ambient storage temperature range
°C
-10° C to +60 ° C
T° specified, equipment without batteries
For Altitude < 1000m and moisture 20 to 95%
4.2.1.1
Ambient service temperature
°C
-15° C to +40° C
T° specified, for Batteries
0° C to +35° C
Continuous maximum ambient service temperature
at rated Current, Cosϕ=0,8
0° C to + 25°C
Continuous maximum ambient service temperature
with Battery inside the Unit
Maximun service altitude
m
4.2.1.2
≤1000m and
P = nP – 10% all the 1000m
Until 1000m included
For 1500 to 5000m, coefficient of downgrading from
0,85 to 0,59
Relative humidity range
%
4.1.3
Storage : 0% to 90%
Operation : 05% to 90%
( without condensation )
Relative humidity without condensing at ambient
temperature
5.6
4.2.1.1
Communication circuits
(List communication / signalling circuits)
See separate declaration
(paragraph 5)
Electrical characteristics - Input
Voltage (steady-state, r.m.s)
V
- rated
220V or 230V or 240V
Nominal value of input voltage, and thresholds of
380V or 400V or 415V
passage in stored energy mode by input voltage
exceeding the tolerance
To specify : if there is no a change of mode to
5.2.1.a
stored energy mode by U + 10% or if the thresholds
depend on the load use
Minimal value of input votage allowing the refill
battery during normal operation UPS
5.2.1.b
- tolerance
%
Frequency
Hz
±2%
50Hz or 60Hz
Nominal value of input frequency and thresholds of
a change of mode to stored energy mode of the
- rated
UPS, by input frequency exceeding the tolerance
5.2.1.c
If it there not a change of mode to stored energy
mode, to specify the minimum and maximum
frequency possible for the UPS
5.2.1.d
- tolerance
%
±10% (45 to 65Hz)
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
3
UPS tests
Characteristic of equipment
reference only
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
≤13A / (10kVA)
Input steady current with ,100% rated VA and W, on
– rated (with the energy storage device
≤20A / (15kVA)
linear and non linear load
charged)
≤26A / (20kVA)
Current r.m.s.
5.2.2.c
Units and/or
A
≤40A / (30kVA)
≤53A / (40kVA)
maximum (with low input volt and energy
A
storage device charging)
≤16A / (10kVA)
≤23A / (15kVA)
5.2.2.f
≤29A / (20kVA)
≤42A / (30kVA)
≤56A / (40kVA)
5.2.2.h
5.2.2.g
- total harmonic distortion (THD p.u.)
%
- overload (% of rated current against time)
%, s
- in-rush (% of rated current against time)
%, s
<9%
≤125%, 120s
≤150%, 10s
5.2.2.e
<I nominal
(rated input RMS current)
Maximum peak value of current measured after mains
power down of 1 second and 5 minutes
(if the perturbance < 1s it is not retained )
5.2.2.d
5.2.2.k
5.2.2.i
5.2.2.a
power factor
>0,97
With input current at >50% rated VA and W on linear
load and non linear load
AC power distribution system
-(TN, TT, IT) compatibility
- short-circuit power required
TT, TN (S or C), IT
Ssc
See separate declaration
(paragraph 2)
- phases required (1,2 or 3)
Tree Phases 3P+N+G
5.2.2.b
- neutral required (yes / no)
Yes
5.2.3
Additional or unusual conditions
NA
Output waveform
5.3.1.2
Waveform - Normal mode
Sinusoidal
Sinusoidal or non sinusoidal
5.3.1.2
Waveform - Stores energy mode
Sinusoidal
Sinusoidal or non sinusoidal
Transfer - Normal mode / Stored energy
Break
No break
Break time / Make time ( if applicable )
ms
On battery
mode
No Break
Complies with figure 1
Without Break
Rated voltage ±2% with a come
back to ±1% in 100ms
Transfer transients and times measured at the time of
tranfer load from UPS to an alternative source and
return, by command or defect of switches of coupling
and bypass
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
4
UPS tests
Characteristic of equipment
reference only
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
Electrical output characteristics - Static and Dynamic characteristics - Normal mode
5.3.2
AC power distribution system
- compatibility (TN, TT, IT)
TT, TN (S or C), IT
- phases available (1,2 or 3)
One Phase 1P+N+G
Or Tree Phases 3P+N+G
- neutral available (yes / no)
Yes
Voltage (steady state, r.m.s.)
Rated Output voltage
V r.m.s
220V, 230V, 240V default value
Operation at 415 VAC/60 Hz is not possible
for One phase
380V, 400V, 415V default value
for Tree phases
Output voltage normal mode variation
%
Rated voltage ±2% adjustable
Output voltage measured at the two ends of the
range of rated power factor and with nominal rated
votage
Voltage variation = maximum and minimum
measured value
Stored energy mode variation
%
Rated output apparent power
VA
±2%
10kVA
15kVA
20kVA
30kVA
40kVA
Rated output active power across a
W
8kW
linear load
12kW
16kW
24kW
32kW
Rated output active power across a
W
Same as linear load
reference non linear load
Total voltage distortion across a linear load
%
<3%
Total voltage distortion across stored
%
<2%
%
<5%
UPS mode with nominal rated output power VA
energy mode, linear
Total voltage distortion across a reference
100% unbalanced 100% non-linear loads (IEC
62040-3)
non linear load
UPS mode with nominal rated output power VA and
dc voltage load capacitor ≤ 1.22 x of UPS output
voltage
Voltage unbalance and phase
%, °
<1.5%
%, s
Complies with IEC 62040-3
phase at full load
displacement, 100 % load unbalance
Voltage transient and recovery time, 100
2 phases with 0,5xnominal linear load and the other
% step load
To note Fig 1, 2 or 3 to specify the performance and
to announce if the performances are >
- Linear load P ( W) :
measurements UPS peak voltage, for variation 0%
to 100% then 100% to 20% of nP
- Non linear load P ( VA ) :measurement of the
transitory variation of U, for variation 33% to 66%
then 66% to 99% then 99% to 66% then 66% to
33% of nP
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
5
UPS tests
Characteristic of equipment
reference only
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
- linear
%, s
Complies curve 1 with IEC
- Non-linear
%, s
Complies curve 3 with IEC
- transfer normal mode / storage energy
%, s
Complies curve 1with IEC
62040-3
62040-3
6.4.2.11.1/2
mode
62040-3
To note Fig 1, 2 or 3 and specified UPS
Performance with nominal power W and resistive
linear load
- mains voltage stopped with 0 and maximum of
sinusoide , during t > 1s
_ 3 times minimum, to ensure itself of the
repetitivity, during t > 1s
- Return mains voltage to all angular positions of the
sinusoide
Frequency (steady-state) :
Rated Output frequency (nominal)
Hz
50Hz or 60Hz Same as Input
- normal mode variation
%
±0,5Hz
(adjustable from ±0,25Hz to
±4Hz)
±0,05Hz
- stored energy mode variation
%
- free-running variation
%
Same as above
Synchronization (max ± % range of rated
%
47.5-52.5 Hz for 50Hz
frequency)
Max synch phase error (referred to a 360°
Operation at 415 VAC/60 Hz is not possible
Thresholds of maximum frequency for which the
UPS remains synchronized with the mains
To specify also ,UPS freqency variation with stored
energy mode
Same as above
58.5-62.5 Hz for 60Hz
°
< 3°
On line : if non transfer by a change of mode to
stored energy mode, to note 0
cycle)
Off line : To note the measurements of dephasing
compared with the fundamental, at the time of the
transfer of source when the mains return
Max slew-rate
Hz / s
0,66 Hz/Sec
Current (r.m.s.) :
- rated
A
≤15A / (10kVA)
Tree Phases 3P+N+G
≤23A / (15kVA)
≤30A / (20kVA)
≤46A / (30kVA)
≤61A / (40kVA)
----------------------≤46A / (10kVA)
-----------------------------------One Phase 1P+N+G
≤68A / (15kVA)
≤91A / (20kVA)
≤136A / (30kVA)
- Overload capability (% of rated current /
5.3.2.l
%/s
time duration)
See separate declaration
(Paragraphe 2)
Overload applied on the output terminals of the UPS
when the UPS is in normal mode at resistive load
Measurements of the time duration during which the
output voltage remains in the rated range
- Limitation (% of rated current / time
%/s
duration)
- Fault clearing capability (normal / stored
6.4.2.10.3 /4
See separate declaration
(Paragraphe 4)
A gL fuse
50kA
for the 3/3:
10kVA,15kVA,20kVA,3/1:10kVA,15kVA,20kVA
energy mode)
80kA
units
for the 3/3:40kVA,3/1:30kVA units
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
6
UPS tests
Characteristic of equipment
reference only
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
Load power factor :
- rated
0.8
- displacement (permissible lead-lag
Battery operation cannot support overload
From 0,5 leading to 0,5 lagging
range)
5.3.2 r) / 6.4.1.6
AC / a.c efficiency in normal mode
- 100 % load
%
See separate declaration
- 75 % load
%
See separate declaration
(Paragraphe 4)
- 50 % load
%
See separate declaration
(Paragraphe 4)
- 25 % load
%
See separate declaration
(Paragraphe 4)
(Paragraphe 4)
Bypass – automatic (static or
electro-mechanical)
Transfer time break
static
ms
0ms to 20ms
Transfer without interruption conditions:
The bypass AC-input voltage is within tolerances
and inverter/bypass transfers are possible without
load interruption if:
- Bypass phase voltage under tolerance
- Frequency is within tolerance
- Phase displacement between the inverter voltage
and the bypass AC-input voltage is in tolerance
5.3.2.l
rated current
A
Overload current (% of rated current / time
%/s
duration)
See Inverter values
See separate declaration
(Paragraphe 2)
Overload applied on the output terminals of the UPS
when the UPS is in normal mode at resistive load
Measurements of the time duration during which the
output voltage remains in the rated range
- maintenance (internal or external)
Internal
- isolation transformer (yes / no )
Bypass protection fuse or circuit breaker
rating
5.5
5.3.3
No
See separate declaration
(Paragraphe 2)
Stand-alone switch (list any and its product
NA
standard)
Additional or unusual conditions
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
NA
7
UPS tests
Characteristic of equipment
reference only
5.4
5.4.2.2 d
Units and/or
Manufacturer's declared
Minimum performance
informations
values
requirements, methods and references
Stored energy mode of operation
Technology
Maintenance-free sealed LeadAcid battery with suspended
electrolyte: leakproof
5.4.2.2 a
5.4.2.2 b
Life Design life or float service life
years
Up to 5-year
The guaranteed backup time is defined for 0.7*Pn
and cos ϕ =0.8.
Quantity of cells and strings
Varied with power rate
5.4.2.2 c
Nominal voltage (total)
V d.c.
5.4.2.2 e
Nominal Ah capacity (C10)
Ah
5.4.2.2 f
Stored energy time (back-up time at 100 %
±192 / ±180
Normal temperature of test ,25° C
Varied with power rate
Normal temperature of test ,25° C
According to the battery
Normal temperature of test ,25° C
10 hours - to 90% ±5%
Internal charger:
rated load)
5.4.2.2 g
Restored energy time (recharge time to 90
capacity after full discharge at min. Config.
% capacity)
--------------------------------------24 hours - to 90% ±5%
5.4.2.2 h
Ambient reference temperature
5.4.2.2 i
Earth condition / Isolation
°C
5.4.2.2 j
r.m.s. ripple current
%
5% C10AH
5.4.2.2 k
Nominal discharge current
A
Varied with power rate
5.4.2.2 l
Default current rating
A d.c.
NA
5.4.2.2 m
Cable volt drop recommendation (% at
%
NA
---------------------------------------------------------------------CLA: capacity after full discharge at min. Config.
25°C
Grounding
At max constant current charging mode
nominal discharge current)
5.4.2.2 n
Protection requirements by others
5.4.2.2 o
Charging regime
5.4.2.2 p
Charge voltage (float, boost) and tolerance
5.4.2.2 q
End of discharge voltage
NA
Constant current charge, and
To specify, if batteries recharge with constant
after, constant voltage charge
limiting current
V d.c
±218V / ±204V
V d.c
From 1,65V to 1,9V
band
(±154V / ±148V)
5.4.2.2 r
Charge current limit (or range)
5.4.2.3
Additional or unusual conditions
5.8
A d.c.
(according to the battery)
Normal temperature of test ,25°C
7A
Internal charger
21A
CLA
NA
Control and monitoring signals
Optional
Separate declaration for complete list of
indications and remote alarm/monitoring or
interface devices
See separate declaration
(paragraph 5)
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
8
MGE™ Galaxy™ 300
10, 15, 20, 30, 40kVA / IEC 62040-3
Technical data sheets - Separate declaration
1. Dimensions and weight of equipment:
UPS Without packaging and With Battery:
MGE™ Galaxy™
300
3:1 10-15kVA and 3:3 10-20kVA
Type
Height(mm)
Length(mm)
Depth(mm)
Weight( kg)
3:3 30-40kVA and 3:1 20kVA, 30kVA
Single
Parallel
1300
400
860
375-390 Kg
375-390 Kg
Single
Parallel
1300
500
860
435-615 Kg
435-615 Kg
Auxiliary Cabinet:
MGE™ Galaxy™ 300
Type
Height(mm)
Length(mm)
Depth(mm)
Weight( kg)
Single
1300
660
850
105-610 Kg
2. Electrical Output characteristics - Static characteristics - Normal Mode
THDU linear load :
AC input voltage 400 V / output voltage 400 V Cos phi=0.8
MGE™ Galaxy™ 300 3/3 :
THDU (%)
20kVA
40kVA
25%Pn
0.6
0.4
50%Pn
0.92
0.5
75%Pn
1.03
0.5
100%Pn
1.11
1.2
25%Pn
0.77
0.71
1.05
50%Pn
0.77
1.07
1.05
75%Pn
0.81
1.45
1.05
100%Pn
0.76
1.8
1.05
25%Pn
1.61
1.8
50%Pn
2.53
2.6
75%Pn
3.09
3.5
100%Pn
3.76
4.8
25%Pn
2.24
1.52
1.49
50%Pn
3.32
2.02
2.22
75%Pn
3.98
2.47
2.76
100%Pn
4.48
3.27
3.66
MGE™ Galaxy™ 300 3/1 :
THDU (%)
15kVA
20kVA
30kVA
THDU non-linear load :
AC input voltage 400 V / output voltage 400 V Cos phi=0.7
MGE™ Galaxy™ 300 3/3 :
THDU (%)
20kVA
40kVA
MGE™ Galaxy™ 300 3/1 :
THDU (%)
15kVA
20kVA
30kVA
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
9
Rectifier thermal-overload capacity curve :
Inverter thermal-overload capacity curve :
Bypass-overload capacity curve :
AC-bypass thermal-overload capacity limited by the overtemp protection. The thermal overload signal generated by a thermostat located
on heatsink: thermal protection at 85°C.
Bypass short-circuit capability :
-3/3 UPS bypass SCR short circuit capacity
MGE™ Galaxy™ 300
10 kVA
15 kVA
20 kVA
30 kVA
Short-circuit capacity I2t (A2S)
7200
7200
7200
15000
-3/1 UPS bypass SCR short circuit capacity
MGE™ Galaxy™ 300
10 kVA
15 kVA
20 kVA
30 kVA
Short-circuit capacity I2t (A2S)
15000
15000
15000
125000
40 kVA
15000
40 kVA
15000
Recommended upstream discrimination
For 3/3 UPS single mains systems
Rated power
10-20kVA
30kVA
40kVA
CB on Mains1
C65H-D-4P-63A/ C60H-D-4P-63A
C120H-D-4P-80A
C120H-D-4P-125A
For 3/3 UPS dual mains systems
Rated power
CB on Mains1
10-20kVA
C65H-D-4P-50A/ C60H-D-4P-50A
30kVA
C120H-D-4P-80A
40kVA
C120H-D-4P-100A
CB on Mains2
C65H-D-4P-63A/ C60H-D-4P-63A
C120H-D-4P-80A
C120H-D-4P-125A
For 3/1 single mains systems
Rated power
10kVA
15kVA
20kVA
30kVA
CB on Mains1
C120H-D-4P-80A
C120H-D-4P-125A
NSX250F TM200D 4P
NSX250F TM250D 4P
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
10
For 3/1 dual mains systems
Rated power
10kVA
15kVA
20kVA
30kVA
CB on Mains1
CB on Mains2
C65H-D-4P-50A/ C60H-D-4P-50A
C65H-D-4P-50A/ C60H-D-4P-50A
C65H-D-4P-50A/ C60H-D-4P-50A
C120H-D-4P-80A
C120H-D-2P-80A
C120H-D-2P-125A
NSX250F TM200D 3P
NSX250F TM250D 3P
Recommended downstream discrimination
These protection systems ensure discrimination on all of the output circuits connected to the unit. If the recommended downstream
protection is not installed, the result may be breaks in the supply of power longer than 20 milliseconds on all the other output circuits.
For 3/3 UPS
Rated power
10-20kVA
30kVA
40 kVA
Downstream CB
C65N-C-4P-6A
C65N-B-4P-10A
C65N-B-4P-16A
C65N-C-4P-10A
C65N-B-4P-20A
C65N-C-4P-10A
For 3/1 UPS
Rated power
10-15kVA
20 kVA
30 kVA
Downstream CB
C65N-B-2P-25A
C65N-C-2P-10A
C65N-B-2P-32A
C65N-C-2P-16A
C65N-B-2P-50A
C65N-C-2P-25A
The short circuit current of the installation must be less than the maximum current of the downstream circuit breaker.
3. Electrical Output characteristics - Dynamic characteristics – Unbalanced linear loade
Linear load Cos phi=0.8 to 400V (RL load): I1 = 0,5.IN; I2 = 0,5.IN; I3=1IN :
MGE™ Galaxy™ 300 3/3 :
THDU (%)
20kVA
40kVA
0.6/1.2/0.6
0.6/1.2/0.6
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
11
4. Efficiency
Efficiency on linear load :
On Normal mode :
AC input voltage 400 V / output voltage 400 V
MGE™ Galaxy™ 300 3/3 :
Efficiency in %
% load
UPS power in kVA
20
30
10
15
Avg.
Avg.
Avg.
Avg.
Avg.
40
25
83.19
89.45
90.47
90.33
91.45
50
90.47
92.11
92.42
92.7
93.05
75
92.11
92.67
92.76
93.23
93.01
100
92.42
92.76
92.7
93.01
92.81
10
15
MGE™ Galaxy™ 300 3/1 :
Efficiency in %
% load
UPS power in kVA
20
30
Avg.
Avg.
Avg.
Avg.
25
83.51
87.16
89.7
88.8
50
89.63
91.23
92.89
92.1
75
91.23
91.97
93.11
92.7
100
91.88
91.99
92.96
92.75
10
15
Losses
MGE™ Galaxy™ 300 3/3 :
Typical losses
in kW doubleconversion mode
25
Avg.
Avg.
Avg.
0.34
0.32
0.38
0.72
0.79
50
0.38
0.47
0.6
0.97
1.11
75
0.47
0.66
0.87
1.22
2.4
100
0.6
0.87
1.17
2.4
2.42
10
15
% load
UPS power in kVA
20
30
Avg.
40
Avg.
MGE™ Galaxy™ 300 3/1 :
Typical losses
in kW doubleconversion mode
25
Avg.
Avg.
Avg.
Avg.
0.43
0.45
0.42
0.75
50
0.47
0.58
0.57
1.02
75
0.58
0.8
0.84
1.4
100
0.72
1.05
1.14
1.88
% load
UPS power in kVA
20
30
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
12
5. Control and monitoring signals
List of indications and remote alarms, monitoring or interface device.
Information on display :
Operation of the FCIM board (dry contacts)
Input dry contacts
In this mode, the relays switch when the UPS changes status, but don’t bother customers with inopportune alarms that last less than 5S. The
information listed below is transmitted if the parameters were enabled in Service Tools.
Inputs configurable inside the list below :
Outputs
1
Operating status
condition
Emergency Power
OFF
Discription
EPO dry contact on FCIM board,connect with emergency power off switch on costumer
sites. ( normally closed, open when EPO active)
Output dry contacts
In this mode, the relays switch when the UPS changes status, but don’t bother customers with inopportune alarms that last less than 5S. The
information listed below is transmitted if the parameters were enabled in Service Tools.
Outputs volt-free contacts (25V / 5A max), configurable inside the list below:
Outputs
Operating status
condition
1.1
General alarm
1.2
Load on battery
power
Low battery warning
1.3
Discription
PFC fault OR
Inverter fault OR
Bypass static switch fault OR
Charger fault OR
EPO activated OR
Battery backup time ended, shift to wait mode OR
Battery temperature fault > 40°C or battery tempera ture sensor destroyed, charger
shutdown OR
Abnormal presence of voltage on the output before closing the bypass static switch.
(frequency converter) OR
UPS in downgraded mode OR
CAN communication fault OR
UPS personalization fault.
Inverter connected to the load and operating on battery power.
Battery operations due to a battery test are not signalled.
Battery has reached the low-battery warning level (voltage or time). The two thresholds
may be user set.
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
13
Standard and Optional cards for UPS :
This card provides three connections, one to an Ethernet 10/100 BT network, one to a JBUS/RS485 network and one to a modem.
It may be installed with the UPS energised.
The JBUS/RS485 connection may be used to connect the UPS to a building monitoring system via a JBUS/MODBUS network. It can also
be used to concentrate a number of UPS units on a single telephone line.
Rhodes2 card
The protocol used between Rhodes 2 Card and the HMIM board is SHUT/COPI
Rhodes 2 Card in Galaxy 300, interface with HMIM board to provide the following functions:
o
Protocol will be exMGE one : SHUT/COPI
o
On customer side, the software applications will be
o
PowerChute
o
ISX Central
o
RMS over Ethernet
o
TLS over Modem
o
Modbus monitor
The product is based on the RHODES2 platform and need a firmware adaptation in order to be compatible with the exMGE SHUT/COPI protocol
and database.
The 2 references AP9630, and AP9635 need to be compatible with this protocol.
A low cost Ethernet of Other global requirements (not specific to APC by Schneider UPS) are:
-
Modbus
-
English pages
-
3- phases mimics on page
-
For (Webserver, PowerChute, ISX Central, RMS)
-
And also an Ethernet & Modem Teleservice & Modbus card.
-
For the Teleservice card AP9635, it is required to integrate in addition:
-
Modbus protocol (Modbus RTC over RS485 bus) and Modbus data matrix
-
Connection via Modem to exMGE TLS Center
-
Connection via Modem to exMGE TLS-Connect diagnostic tools
-
UPS concentration for parallel configuration (up to 2 for Galaxy 300)
Features / Card
AP9630
AP9635
SHUT/COPI protocol
X
X
HID database
X
X
RS485 Modbus slave
X
TLS Center modem connection
X
TLS UPS concentration (RS485 Modbus master)
X
Functional summary
Model
AP9630
AP9635
10/100
1
1
USB
2
Sensors
1
Modem
Internal
Modbus
Internal
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
Flash
8
16
SD card
-
RAM
1
1
CAN
-
14
6. Electromagnetic compatibility
UPS from 10 to 40 kVA
Galaxy 300 UPSs have been certified for product standard EN 62040-2.
Immunity tests
Electrostatic discharges
Required by standard (minimum level)
Product result (immunity level)
IEC 61000-4-2: 1995 / EN 62040-2: 2005
8 kV in air and 4 kV for contact
8 kV in air and 4 kV for contact
Radiated radio-frequency fields
IEC 61000-4-3: 2002 / EN 62040-2: 2005
Required by standard (minimum level)
10 V/m modulated 80% AM at 1 kHz from 80 MHz to 1 GHz
Product result (immunity level)
Rapid transients in bursts
Required by standard (minimum level)
10 V/m modulated 80% AM at 1 kHz from 80 MHz to 1 GHz
Conducted immunity
Required by standard (minimum level)
Product result (immunity level)
IEC 61000-4-4: 2004 / EN 62040-2: 2005
2 kV on AC-input cables
2 kV on DC cables
2 kV on I/O cables
2 kV on AC-input cables
2 kV on DC cables
2 kV on I/O cables
IEC 61000-4-5: 1995 / EN 62040-2: 2005
1 kV coupling between lines
1 kV coupling between lines and earth
1 kV coupling between lines
2 kV coupling between lines and earth
IEC 61000-4-6: 2003 / EN 62040-2: 2005
10V/m modulated 80% AM at1 kHz from 150 kHz to 30 MHz
10V/m modulated 80% AM at1 kHz from 150 kHz to 30 MHz
Immunity to magnetic fields at network frequency
Required by standard (minimum level)
Product result (immunity level)
IEC 61000-4-8:2001 / EN 55024
30 A/m
30 A/m
Product result (immunity level)
Surges, high energy
Required by standard (minimum level)
Product result (immunity level)
Tests on emitted disturbances
Conducted emissions
Standard version
CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-2: 2005
UPS category C3 (controlled distribution)
Radiated emissions
Standard version
CISPR 16-1-2: 1999 / CISPR 22: 2005 / IEC 62040-2: 2005
UPS category C3 (controlled distribution)
Certifications
Presentation to standardisation organisations:
TÛV :
- CB Marking- Safety IEC 62040-1-1 2004
EMC : IEC 62040-2
CE (Marking)
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
15
7. Individual input harmonic current
in accordance with IEC 61000-3-2 standard.
( With nominal rms current)
MGE™ Galaxy™ 300 3/1 20kVA
load
25%
50%
75%
100%
Harmonics (in %)
17.17
8.08
7.81
6.53
H2
2.66
0.61
0.72
0.62
H3
12.57
5.6
5.41
4.96
H4
1.07
1
0.61
0.33
H5
5.58
2.37
2.16
1.91
H6
1.35
0.94
0.74
0.50
H7
4.9
1.93
1.37
1.4
H8
0.49
0.48
0.39
0.26
H9
2.6
2.26
1.75
0.68
H10
0.52
0.34
0.36
0.43
H11
2.5
1.35
1.08
1.12
H12
0.68
0.34
0.29
0.18
H13
1.48
1.02
0.94
0.83
H14
0.35
0.25
0.23
0.23
H15
0.95
0.63
0.61
0.66
H16
0.18
0.25
0.19
0.13
H17
1.41
0.84
0.75
0.73
H18
0.35
0.18
0.13
0.07
H19
0.35
0.35
0.39
0.33
H20
0.35
0.25
0.25
0.01
H21
0.35
0.44
0.43
0.37
H22
0.22
0.15
0.11
0.07
H23
0.18
0.25
0.25
0.33
H24
0.35
0.15
0.12
0.07
H25
0.52
0.44
0.45
0.37
H26
0.35
0.15
0.18
0.12
H27
0.64
0.22
0.17
0.22
H28
0.22
0.22
0.17
0.13
H29
0.48
0.25
0.25
0.32
H30
0.35
0.22
0.2
0.11
H31
0.8
0.25
0.16
0.25
H32
0.69
0.22
0.16
0.09
H33
0.18
0.22
0.16
0.18
H34
0.48
0.22
0.16
0.07
H35
0.45
0.22
0.25
0.09
H36
0.35
0.15
0.12
0.08
H37
0.45
0.22
0.14
0.12
H38
0.35
0.22
0.16
0.09
H39
0.22
0.15
0.18
0.07
H40
0.22
0.15
0.11
0.17
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
16
MGE™ Galaxy™ 300 3/1 15kVA
load
25%
50%
75%
100%
Harmonics (in %)
14.19
13.04
5.83
4.75
H2
0.28
0.65
0.37
0.39
H3
3.64
2.52
1.32
1.65
H4
1.05
0.55
0.44
0.22
H5
8.72
8.18
3.57
2.51
H6
0.38
0.36
0.13
0.2
H7
1.93
2.91
0.62
0.63
H8
0.06
0.05
0.12
0.08
H9
1.91
0.36
0.89
0.57
H10
0.38
0.36
0.13
0.15
H11
0.65
2.59
0.49
0.33
H12
0.37
0.36
0.11
0.09
H13
3.66
0.41
1.38
0.5
H14
0.06
0.05
0.18
0.1
H15
1.48
0.53
0.26
0.4
H16
0.65
0.05
0.06
0.07
H17
3.15
2.14
1.55
0.41
H18
0.06
0.16
0.26
0.18
H19
2.16
1.63
1.06
0.54
H20
0.38
0.41
0.26
0.08
H21
2.16
1.01
0.89
0.55
H22
0.06
0.36
0.26
0.05
H23
1.37
2.98
1.06
0.38
H24
0.06
0.36
0.26
0.08
H25
0.83
1.01
0.26
0.09
H26
0.06
0.16
0.11
0.09
H27
1.16
2.14
0.3
0.36
H28
0.65
0.16
0.11
0.28
H29
0.78
1.29
0.26
0.28
H30
0.38
0.05
0.39
0.22
H31
0.38
0.05
0.39
0.19
H32
0.06
0.41
0.3
0.19
H33
1.71
2.84
0.3
0.36
H34
0.06
0.05
0.11
0.1
H35
2.81
3.4
1.24
0.36
H36
0.65
0.05
0.46
0.19
H37
0.38
1.85
0.3
0.4
H38
0.65
0.36
0.3
0.16
H39
2.16
2.64
0.18
0.22
H40
0.38
0.54
0.18
0.12
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
17
MGE™ Galaxy™ 300 3/1 30kVA
load
25%
50%
75%
100%
Harmonics (in %)
16.95
8.67
7.71
6.86
H2
4.35
2.61
1.06
0.75
H3
11.64
4.14
5.77
5.46
H4
1.43
1.3
0.47
0.41
H5
5.33
1.91
1.74
2.37
H6
1.26
0.83
0.43
0.36
H7
2.78
1.56
0.74
1.05
H8
0.76
0.5
0.27
0.27
H9
1.44
0.87
0.61
0.75
H10
0.96
0.49
0.34
0.17
H11
1.57
1.12
0.77
0.79
H12
0.93
0.44
0.29
0.2
H13
1.06
0.59
0.62
0.63
H14
0.63
0.3
0.34
0.29
H15
0.87
0.72
0.51
0.55
H16
0.89
0.37
0.33
0.21
H17
1.04
0.56
0.47
0.34
H18
0.62
0.48
0.36
0.25
H19
1.05
0.5
0.34
0.45
H20
0.67
0.41
0.3
0.17
H21
0.83
0.65
0.28
0.37
H22
0.51
0.57
0.24
0.2
H23
1.03
0.35
0.42
0.29
H24
0.68
0.42
0.29
0.19
H25
1.26
0.59
0.44
0.37
H26
0.58
0.44
0.34
0.2
H27
0.92
0.57
0.34
0.31
H28
0.68
0.34
0.38
0.21
H29
0.72
0.42
0.24
0.21
H30
0.61
0.61
0.28
0.17
H31
0.62
0.4
0.26
0.26
H32
0.77
0.36
0.23
0.23
H33
0.65
0.56
0.3
0.2
H34
0.69
0.32
0.29
0.28
H35
0.71
0.36
0.22
0.2
H36
0.9
0.3
0.3
0.18
H37
0.79
0.34
0.25
0.17
H38
0.64
0.48
0.26
0.17
H39
0.53
0.45
0.24
0.23
H40
0.50
0.43
0.34
0.16
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
18
MGE™ Galaxy™ 300 3/3 20kVA
load
25%
50%
75%
100%
Harmonics (in %)
15.14
13.79
6.78
6.37
H2
1.97
1.13
1.05
0.95
H3
7.64
5.39
4.45
4.00
H4
0.29
0.92
0.25
0.52
H5
4.11
3.22
2.24
1.99
H6
0.54
0.60
0.31
0.20
H7
2.58
1.95
1.44
1.21
H8
0.36
0.35
0.42
0.28
H9
2.25
1.56
1.03
0.73
H10
0.37
0.19
0.23
0.2
H11
1.33
1.53
0.98
0.86
H12
0.35
0.21
0.20
0.17
H13
0.84
1.08
0.94
0.79
H14
0.4
0.47
0.35
0.15
H15
0.71
0.84
0.62
0.62
H16
0.34
0.26
0.39
0.17
H17
0.85
0.48
0.58
0.46
H18
0.50
0.23
0.13
0.23
H19
0.63
0.50
0.6
0.61
H20
0.16
0.09
0.22
0.23
H21
0.44
0.39
0.26
0.19
H22
0.46
0.21
0.18
0.24
H23
2.15
1.18
0.66
0.8
H24
0.16
0.13
0.11
0.18
H25
1.64
1.01
0.37
0.57
H26
0.16
0.26
0.19
0.10
H27
0.88
0.31
0.33
0.26
H28
0.49
0.06
0.12
0.21
H29
0.43
0.27
0.31
0.31
H30
0.46
0.29
0.18
0.09
H31
0.25
0.19
0.15
0.22
H32
0.44
0.29
0.09
0.08
H33
0.13
0.13
0.21
0.16
H34
0.62
0.30
0.04
0.06
H35
0.28
0.18
0.07
0.20
H36
0.37
0.27
0.11
0.18
H37
0.36
0.16
0.06
0.09
H38
0.36
0.17
0.09
0.14
H39
0.25
0.31
0.20
0.17
H40
0.32
0.19
0.13
0.13
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
19
MGE™ Galaxy™ 300 3/3 40kVA
load
25%
50%
75%
100%
Harmonics (in %)
14.01
9.13
6.66
5.98
H2
3.22
2.16
0.89
1.04
H3
0.46
1.38
1.27
2.33
H4
0.45
0.69
0.75
0.57
H5
11.9
6
7.78
5.87
4.81
H6
0.72
0.30
0.71
0.25
H7
0.81
0.44
0.62
0.16
H8
0.80
0.70
0.31
0.17
H9
2.75
1.37
0.70
0.61
H10
1.13
0.52
0.31
0.44
H11
0.95
0.40
0.29
0.54
H12
0.36
0.03
0.26
0.15
H13
1.03
0.89
0.77
0.56
H14
0.57
0.10
0.18
0.27
H15
0.18
0.29
0.37
0.20
H16
0.24
0.35
0.10
0.55
H17
0.46
1.15
0.35
0.11
H18
0.43
0.53
0.15
0.29
H19
0.88
0.67
0.73
0.54
H20
0.71
0.12
0.10
0.40
H21
0.86
0.47
0.30
0.44
H22
0.95
0.22
0.13
0.34
H23
0.37
0.40
0.29
0.30
H24
1.06
0.21
0.18
0.35
H25
0.79
0.09
0.10
0.13
H26
0.06
0.28
0.25
0.14
H27
0.84
0.90
0.24
0.31
H28
0.35
0.35
0.30
0.18
H29
1.28
0.47
0.25
0.25
H30
0.41
0.16
0.03
0.42
H31
0.23
0.57
0.29
0.16
H32
0.18
0.24
0.18
0.11
H33
0.37
0.06
0.11
0.19
H34
0.43
0.62
0.30
0.16
H35
0.97
0.45
0.12
0.33
H36
0.76
0.17
0.11
0.12
H37
0.78
0.40
0.11
0.13
H38
0.62
0.39
0.23
0.07
H39
0.71
0.47
0.36
0.32
H40
0.10
0.06
0.12
0.24
APC-MGE UPS SYSTEMS- Manufacturer's declaration according to IEC 62040-3
MGE Galaxy 300-AC
15/10/09
20