INFORMATION BULLETIN NO: B-L4 110513 2 FIREFIGHTERS EMERGENCY OPERATIONS (FEO) REQUIREMENTS Date of Issue: May 13, 2011 Attention: Building Owners, Property Managers, Elevator Consultants, and Licensed Elevating Contractors Recent changes to Provincial regulations adopted the CAN/CSA B44-2007 Safety Code for Elevators and Escalators (the “Elevator Code”). Specifically the Elevator Code clause 2.27.3 Firefighters’ Emergency Operation: Automatic Elevators requires FEO on: New Elevators Existing Electric Elevators where a Controller is installed as part of an alteration and; Existing Hydraulic Elevators where a change on the Type of Motion Control, Type of Operation Control or Emergency Operation as part of an alteration. A Risk Reduction Working Group consisting of BCSA Safety Officers, Electrical Engineer / Fire Alarm Designer, City of Vancouver building official / representative, Fire Chief, Elevator Manufacturer representative, Building Code Consultant/Engineer, Fire Alarm Company/Manufacturer, Provincial Building & Safety Standards Branch representative, and a Elevator Consultant/Engineer was formed to review the differences in requirements between the Elevator Code and the British Columbia Building Code (BCBC) in particular where FEO is not required in the BCBC. Committee recommendations will be presented to the Provincial Elevating Devices Safety Manager and a guideline will be issued accordingly. In the interim, the following table could be used to show the action required where applicable: Building Status Meets B44-07 Code Action Required New Is Building Fire System Provided? Yes Yes Connect & Operate New Not Required No Provide Fire System or Dedicated elevator fire detection and recall System Existing Yes Yes Connect & Operate Existing Yes No Update Fire System or Provide Dedicated elevator Fire detection and recall System Existing No No Provide Fire System or Dedicated elevator Fire detection and recall System BULLETIN NO: B-L4 110513 2 Page 1 of 2 505 SIXTH STREET, SUITE 200, NEW WESTMINSTER, BRITISH COLUMBIA, CANADA V3L 0E1 Toll Free: 1-866-566-7233 Fax: 778-396-2064 Web Site: www.safetyauthority.ca E-mail: info@safetyauthority.ca FRM-1127-03 (20111-04-06) As per code requirement 2.27.3.1.4 only the “FIRE RECALL” switch(es), or fire alarm initiating device located in the lobby at floors that are served by the elevator, or in the hoistway, or in an elevator machine room, in a control space, or in a control room (see 2.27.3.2) shall initiate Phase I Emergency Recall Operation. Fire alarm initiating devices are referred to as fire detectors in the NBCC. Pull stations will not be allowed to initiate fire recall as they are not considered fire alarm initiation devices. This arrangement is not applicable where FEO is required by the BCBC. As for the pit drain, requirement 2.2.2.5, the BCSA will consider a variance for existing buildings. Janice Lee, P.Eng. Provincial Safety Manager – Elevating Devices References: B.C. Reg. 101/2004 Elevating Devices Safety Regulation CSA B44-07 Safety Code for Elevators and Escalators For more information on the British Columbia Safety Authority, please visit our web site at: www.safetyauthority.ca BULLETIN NO: B-L4 110513 2 Page 2 of 2 505 SIXTH STREET, SUITE 200, NEW WESTMINSTER, BRITISH COLUMBIA, CANADA V3L 0E1 Toll Free: 1-866-566-7233 Fax: 778-396-2064 Web Site: www.safetyauthority.ca E-mail: info@safetyauthority.ca FRM-1127-03 (20111-04-06)