17e32 – Transformer Heating Test INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING PLEASE TAKE SUITABLE SAFETY PRECAUTIONS AT ALL TIMES . RETAIN THE TEST SAMPLE AFTER TESTING. Introduction: Participants are supplied with a transformer. The instructions require an input voltage to be applied to the primary winding and a resistive load attached to the both of the secondary outputs. Applicable Standards • • IEC 61558-1 Due to the similarities in test procedures, other product standards may be applicable, including: IEC 60335-1; IEC 60598-1; IEC 61010-1; IEC 60065; IEC 60950-1, IEC 62368-1 and other standards requiring temperature rise tests using change in winding resistance method. Participant Objectives: By completing this PTP, participants may compare their results by change in resistance method to determine heating of transformer primary and secondary windings. Issued: 12 August 2016 (C) IFM Quality Services Pty Ltd Page 1 of 3 17e32 – Transformer Heating Test INSTRUCTIONS Instructions: 1. Prior to testing, store the EUT in an ambient environment of 21°C – 25°C for at least 24 hours. Maintain these environmental conditions while performing tests. 2. Test the EUT after fixing it onto the centre of a dull black painted plywood board with 2 screws. The board shall be approximately 20 mm thick and have dimensions at least 300 mm x 300 mm. The environment shall be free of draughts. The board shall sit level and horizontal. 3. Each input and output conductor should be 2 m long with thickness (cross sectional area) as close as possible to 1.5 mm2. These 2 m long conductors are to be attached to any existing leads of the EUT. 4. The test shall be conducted at 50 Hz. 5. Set up the EUT, power supply, and measuring equipment such that: a) The input to the primary winding is 240 V ac. b) Simultaneously, apply resistive loads to both secondary windings to achieve 2.0 A each. c) The ambient (room) temperature is determined at a horizontal plane to the EUT approximately 50 cm from the EUT. d) The test is performed until steady-state conditions are reached. e) The requested additional data relating to temperatures, time, current and voltage are recorded and reported. 6. Assume the EUT has NO T-rating. 7. Measure the heating of all primary and secondary windings using the change in resistance method. 8. For the calculation, use the factor 234.5. 9. Secondary winding 1 terminals are on the same side of the transformer as the primary winding terminals. a. Secondary winding 2 terminals are on the opposite side of the transformer as the primary winding. (Secondary winding 2 is shown on the photograph on page 1.) b. When loading the secondary windings, connect 0V-12V. Due Date The due date for results is 24th February 2017. Results will not be accepted via the online result entry facility after this date. Results submitted after the due date will only be accepted upon payment of an AUD$250 late fee. Direct all questions or comments to: ingridflemming@ifmqs.com.au Reporting the results: For information regarding the reporting of results, please refer to the Result Entry Guide: http://www.ifmqs.com.au/proficiency/Guides/Internet%20Result%20Entry%20Guide%20-%20Electrical.pdf Refer to Table 1 for explanation of questions. Issued: 12 August 2016 (C) IFM Quality Services Pty Ltd Page 2 of 3 17e32 – Transformer Heating Test INSTRUCTIONS Table 1: Explanation of Questions Question number Test/Question Explanation Each artefact has been screened and measurements recorded. Please verify the unit number in the results entry screen. See top of artefact. The IEC standard that has been applied for this PTP. If more than one standard is to be applied, results for each standard MUST be recorded under a separate participant entry. Q01 Unit number Q02 IEC Standard Q03 Adjust voltage? (yes / no) Q04 Initial voltage primary Voltage applied to the input primary at the beginning of the test. (V) Q05 Initial current primary Current at the input primary at the beginning of the test. (A) Q06a Initial current secondary 1 Current at the secondary winding 1 at the beginning of the test. (A) Q06b Initial current secondary 2 Current at the secondary winding 2 at the beginning of the test. (A) Q07a Initial volts secondary 1 Voltage obtained at the secondary winding 1 at the beginning of the test (V) Q07b Initial volts secondary 2 Voltage obtained at the secondary winding 2 at the beginning of the test (V) Q08a Resistive load secondary 1 Value of the resistive load applied to achieve the required output current 1. (Ω) Q08b Resistive load secondary 2 Value of the resistive load applied to achieve the required output current 2. (Ω) Q09 Initial ambient Q10 Initial resistance primary Q11a Q11b Initial resistance secondary 1 Initial resistance secondary 2 Is the applied voltage adjusted (either manually or automatically) during the test? Ambient temperature at the beginning of the test. (°C) Primary winding resistance at the beginning of the test. (Ohm) Secondary winding 1 resistance at the beginning of the test. (Ω) Secondary winding 2 resistance at the beginning of the test. (Ω) Q12 Time to steady state Time elapsed in minutes until steady state was reached. (min) Q13 Final voltage primary Voltage applied to the input primary after steady state was reached. (V) Q14 Final current primary Current at the input primary after steady state was reached. (A) Q15a Final current secondary 1 Current at the secondary winding 1 after steady state was reached. (A) Q15b Final current secondary 2 Current at the secondary winding 2 after steady state was reached. (A) Q16a Final volts secondary 1 Voltage obtained at the secondary winding 1 after steady state was reached. (V) Q16b Final volts secondary 2 Voltage obtained at the secondary winding 2 after steady state was reached. (V) Q17 Final ambient Q18 Final resistance primary Q19a Q19b Final resistance secondary 1 Final resistance secondary 2 Ambient temperature after steady state was reached. (°C) Primary winding resistance after steady state was reached. (Ohm) Secondary winding 1 resistance after steady state was reached. (Ω) Secondary winding 2 resistance after steady state was reached. (Ω) Q20 Temp rise primary Q21a Temp rise secondary 1 Temperature rise of secondary 1 winding. (K) Q21b Temp rise secondary 2 Temperature rise of secondary 2 winding. (K) Issued: 12 August 2016 Temperature rise of primary winding. (K) (C) IFM Quality Services Pty Ltd Page 3 of 3