June 03, 2016 Project: EV-1379-2 ADDENDUM NO. 2 To: All Tenderers Re: The Corporation of the District of North Cowichan EMBC – DNC South End and Duncan Phase 3 Flood Protection Works – Contract No. 2 Tenderers are advised that Addendum No. 2 to the Tender Documents for The Corporation of the District of North Cowichan, EMBC – DNC South End and Duncan, Phase 3 Flood Protection Works – Contract No. 2 is hereby issued. This Addendum shall form part of the Contract for the referenced Project. Tenderers are responsible for acknowledging receipt of this Addendum, and for entering this Addendum in the Tender Form of the Tender Documents in order to validate their Tender. Sincerely, PARSONS Inc. Dave Renard Manager of Construction DWR/sh { EV-1379-2 ADDENDUM NO. 2 Section Various Page 1 of 2 Consulting Engineers: Parsons Inc. THE CORPORATION OF THE DISTRICT OF NORTH COWICHAN EMBC - DNC South End and Duncan Phase 3 Flood Protection Works - Contract No. 2 1.1 PRECEDENCE .1 1.2 This Addendum shall form part of the Tender Documents for The Corporation of the District of North Cowichan, EMBC – DNC South End and Duncan, Phase 3 Flood Protection Works – Contract No. 2 and shall take precedence over all requirements of the aforementioned Tender Documents with which it may prove to be at variance unless otherwise qualified by the Engineer or Owner. PURPOSE .1 1.3 The purpose of this Addendum is to: .1 Revise Drawings. .2 Issue Appendix to Tender Documents. REVISE DRAWINGS .1 Reference: Drawing EV-1379-2-C3 .1 .2 Reference: Drawing EV-1379-2-C4 .1 .3 Add Following General Notes: “1. Remove Existing Test Pile #2 Prior to Commencing Construction”. (Revise Test Pile Program Report in Appendix 2 to indicate that Test Pile #2 was not removed). “2. Conduct Survey of Adjacent Structures by Adjuster/Surveyor Prior to Commencing Pile Driving”. Independent Reference: Drawing EV-1379-2-S2 .1 .5 Revise Section ‘call-out bubbles’ to refer from Sheet C3 Reference: Drawing EV-1379-2-S1 .1 .4 Revise Section ‘call-out bubbles’ to refer to Sheet C4 Revise Typical Water Stop Detail by adding note: “Form Construction Joints with Water Stop in Flood Wall at Intervals of Not Greater Than 30 Metres.” (Construction joints are not continuous through footing). Reference: Drawing EV-1379-2-S8 .1 Revise 610 Diameter Steel Pipe Pile Detail to read: “610 mm [24”] Steel Pipe Pile 12.7 mm [0.500”] Wall Thickness”. I:\EV1379 - DNC - Flood Protection Works Phase 3\ev\data\Specs\Contract No.2\ADDENDA\Addendum No. 2\1379-2-ADD#2.DWR.rtf EV-1379-2 ADDENDUM NO. 2 Section Various Page 2 of 2 Consulting Engineers: Parsons Inc. THE CORPORATION OF THE DISTRICT OF NORTH COWICHAN EMBC - DNC South End and Duncan Phase 3 Flood Protection Works - Contract No. 2 1.4 ISSUE APPENDIX TO TENDER DOCUMENTS .1 Reference: Appendix 9 – Owner-Supplied Stand-By Generator .1 Shop Drawings and Product Data for Owner-Supplied Stand-By Generator are hereby issued. END OF SECTION I:\EV1379 - DNC - Flood Protection Works Phase 3\ev\data\Specs\Contract No.2\ADDENDA\Addendum No. 2\1379-2-ADD#2.DWR.rtf SHOP DRAWING REVIEW Detail Done By Contractor This review by PBX Engineering Ltd. is for the sole purpose of ascertaining conformance with the general design concept. This review shall not mean that PBX Engineering approves the detailed design in the shop drawings, responsibility for which shall remain with the Contractor, and shall not relieve the Contractor of their responsibility for errors or omissions in the shop drawings or for meeting all requirements on the Contract Documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site and for information that pertains solely to the fabrication process or techniques of construction. NO EXCEPTION TAKEN REJECTED SUBMIT SPECIFIED ITEM(S) MAKE CORRECTIONS NOTED REVISE AND RESUBMIT BY: DATE: 05/30/2016 - PO#: 632972 PROJECT: COWICHAN CANADA AVE PUMP STATION AVTRON: CP16030002 2.00 DATE: 5/5/16 CONTROL POWER CONNECTIONS SEE DETAIL "B" CONTROL PANEL (STANDARD LOCATION) SEE NOTE 3 OUTDOOR LOUVER SUPPLIED AS AN OPTION REMOVABLE DUCT ADAPTER NOTE: IF DUCT ADAPTER IS USED, MOUNT USING LEFT & RIGHT FLANGES ONLY. OTHERWISE USE TOP AND BOTTOM FLANGES OF THE LOAD BANK. TOP FLANGE CONTROL PANEL (ALTERNATE LOCATION) SEE NOTE 3 H= 46 W= 36 (RADIATOR (RADIATOR CORE HEIGHT) CORE WIDTH) A B C H + 4.00 AIRFLOW H= 46 DIRECTION OF ELEMENTS BUSS BAR CONNECTIONS SEE DETAIL "A" SEE NOTE 4 POWER DISTRIBUTION BLOCK SEE NOTE 4 W= 36 5.50 4.00 2.00 REF 2.00 BOTTOM FLANGE W + 20.00 3.75 1.75 13.00 OUTDOOR LOUVER REF 1.75 DETAIL "A" AIRFLOW RECOMMENDED CONDUIT ENTRY AREA DUCT ADAPTER FLANGE REF W= 36 REF 0.71 x 45° CHAMFER 4 CORNERS TOP & BOTTOM 1.00 2.00 TYP BOTTOM VIEW 4. POWER DISTRIBUTION BLOCK OR BUSS BARS SUPPLIED DEPENDING ON LOAD BANK VOLTAGE AND KW. 3. THE CONTROL PANEL IS NOT AT THIS LOCATION IF IT IS SUPPLIED OPTIONALLY AS A REMOTE 19" RACK MOUNT COMPONENT OR IF IT'S MOUNTED ON THE EXHAUST SIDE OF THE LOAD BANK AS SHOWN ALTERNATELY. 2. ALL DIMENSIONS ARE APPROX. 1. WEIGHT: NOTES: .500 DIA 4 HOLES 1.00 DETAIL "B" LIFTING HOLES 1.00 DIA TYP 4 PLACES FOR APPLICATION ENGINEERING USAGE ONLY THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF AVTRON MFG., INC. AND MAY NOT BE DISCLOSED TO OTHERS OR USED FOR MANUFACTURING PURPOSES WITHOUT THE WRITTEN CONSENT OF AVTRON MFG. CE640 CD980 G ADDED "BOTTOM VIEW". J.FLAUTO 11-13-06 F ADDED CHAMFERS FACKELMANN 3/15/05 TO TOP & BOTTOM RAILS, ADDED LOUVER DEPTH DIMENSION CD734 E REV'D & REDRAWN FACKELMANN 6/28/04 PER ECN ECN REV CHANGE CHG'D NO. LET. D.STACK DRAWN J.W.EMERY DATE DRAWING NUMBER E.JAMIOL 5/13/92 SB2203 CHECKED K.KUK CHK'D APPROVED D.BOHRER SCALE 1/16 LOAD BANK K711 SHT 1 OF 1 OUTLINE DRAWING ASCO NOTE: CONNECT TO UTILITY POSITION CONTACT IN TRANSFER SWITCH ASCO ASCO BILL OF MATERIALS: Genset: (see attached spec sheet, 4 pages) MTU Onsite Energy diesel generator set, standby power nameplated as follows: MODEL 6R1600 DS300 ALT. 433PSL6248 PH. 3 W. 4 P.F. 0.8 HZ. 60 VOLTS 347/600 kW 300 kVA 375 AMPS 361 Neoprene vibration isolators factory installed between genset and baseframe SHOP DRAWING REVIEW Engine: Detail Done By Contractor MTU 6R1600G70S, 10.5 liter, 418 hp, 4 cycle, turbocharged, aftercooled This review by PBX Engineering Ltd. is for the sole purpose of Isochronous frequency regulation, no‐load to full‐load (ADEC electronic governor) ascertaining conformance with the general design concept. This review shall not mean that PBX Engineering approves the detailed design in the shop drawings, responsibility for which shall +/‐0.25% steady state frequency regulation (ADEC electronic governor) remain with the Contractor, and shall not relieve the Contractor of their responsibility for errors or omissions in the shop drawings or for meeting all requirements on the Contract Documents. The Standard duty air inlet filter system, c/w inlet restriction indicator Contractor is responsible for dimensions to be confirmed and correlated at the job site and for information that pertains solely to the fabrication process or techniques of construction. Lube oil drain line extension and shutoff valve Lube oil system filled with recommended lube oil NO EXCEPTION TAKEN REJECTED Flexible fuel lines connected to engine supply and return fittings SUBMIT SPECIFIED ITEM(S) MAKE CORRECTIONS NOTED REVISE AND RESUBMIT Engine‐mounted primary/secondary fuel filters w/ single fuel/water separator 05/30/2016 BY: DATE: Cooling System: Unit mounted radiator, rated for 50ºC ambient temperature, c/w duct flange adapter Low coolant level switch Cooling system filled with recommended antifreeze/water mixture Accessories included: 2,500W (240VAC) thermostatically controlled block heater, c/w isolating valves Alternator: Marathon 433PSL6248 alternator, rated 300kW (375kVA) @ 105ºC. rise over 40ºC. ambient Marathon PMG excitation provides 10 second ‐ 300% short circuit capability, and Marathon DVR2000E+ digital volts/hz AVR provides +/‐0.25% no‐load to full‐load regulation Circuit Breaker: Qty. one (1) – 400 Amp 100% rated LSIG circuit breaker c/w auxiliary switch (unit‐mounted) Qty. one (1) – 300 Amp 80% rated LI circuit breaker for integral load bank (unit‐mounted) Genset Controller: Unit‐mounted Basler MGC‐2020 digital genset controller, utilizes microprocessor based technology to provide genset control, protection, monitoring and event logging. Equipped with generator metering, engine monitoring, genset control, engine protection, generator protection (27, 59, 81O, 81U), BESTCOMSPlus PC software. Standard LCD heater includes touch screen password protected programming capabilities and a standard USB communications port for re‐programming and loading of software upgrades. SAE J1939 Engine ECU communications, multilingual capability, remote communications to the optional RDP‐110 Remote Annunciator, 16 programmable contact inputs, 15 contact outputs (3‐ 30ADC and 12 programmable 2 ADC). UL recognized, CSA certified, CE approved, HALT (Highly Accelerated Life Tests) tested, IP 54 Front Panel rating with integrated gasket, NFPA110 Level Compatible, and CSA C282‐00) Digital AC metering (volts, amps, frequency, kW, kVA, kVAR, PF, etc.) Digital engine monitoring (oil pressure, coolant temp., battery DC volts, RPM, hours, etc.) Emergency stop pushbutton Accessories included: Three (3) Relays w/ 3 x Form C contacts each (Run, common trouble, common failure) Engine Electric System: 24VDC control/starting system, c/w battery charging alternator Accessories included: Qty. two (2) x 12VDC, 8D‐1150 CCA maintenance free battery, c/w rack and cables Battery Charger: 24VDC, 10A output, 120VAC input float/equalize battery charger Digital ammeter & voltmeter, input and output fuses, auto equalize, AC power lamp Accessories included: Alarm outputs (low DC volts, high DC volts, AC fail, charger fault) Enclosure: Type of Enclosure: Insulated, sound attenuated, aluminum, Nema 3R weather protective dropover enclosure with sub‐base fuel tank. Attenuation: The sound pressure level shall average 65dBA at 35' in a free field condition. Size: Approximately 20' – 0" long x 7' – 6" wide x 9' – 5" high. Length at the base is 16' – 0". Sub‐base tank adds 13" to the overall height. Lift lugs add 4" to the overall height. Final dimensions to be confirmed with approved drawings Weight: Approximately 16,000lbs (enclosure, genset and dry fuel tank). Construction: 10 gauge aluminum sheets, welded construction. Walls: 5" thick with wall studs approximately every 16". Designed to withstand wind loads as per NBC code. Roof: 5" deep with cross members approximately every 16". Designed to withstand snow loads as per NBC code. Roof has a 1" peak to minimize ponding of water. Insulation: 5" thick mineral wool. Interior Liner: 22 gauge perforated galvanized steel. Base: 520US usable gallon ULC‐S601, 13" deep double wall fuel tank with lift lugs, electrical stub up area, generator support crossmembers and complete with the following options: ‐ 2" fill ‐ 2” vent w/ whistle (piped to exterior) ‐ 2” level gauge ‐ 2” low fuel contact – 30% ‐ 2” high fuel alarm float – 90% ‐ 1” supply with check valve ‐ Emergency vent ‐ 1” return ‐ Secondary Emergency vent ‐ 2” leak detection float ‐ Two 2” spares Tank is pressure tested to 3 psi. Foundation design is by others. Doors: 8 of 10 gauge aluminum access doors with recessed locking handles with 3 point latches, hydraulic closures, weather stripping and drip edges above doors. Doors have weld‐on aluminum hinges with grease fittings and doors are removable only in the fully open position. Penetrations: Exhaust opening in the roof complete with rain shield. Muffler mounting support channels in the ceiling are included. Radiator fill cap opening in the roof complete with hinging cover. Flexible oil drain line plumbed to the exterior. Ventilation: Intake – Hood complete with silencer and galvanized bird screen. Discharge – Backdraft damper with discharge duct, silencer, hood and galvanized bird screen. Flex connection to wall. Electrical: One incandescent fixture. Power by others. One duplex receptacle. Power by others. Misc.: One fold down door mounted shelf provided. Paint: All surfaces cleaned to sspc‐sp1, all seams sealed, primed with epoxy primer. The exterior is top coated with semi‐gloss polysiloxane paint. Colour – TBD. See samples – http://www.alum‐tek.com/colors.html Exhaust System: Super critical grade muffler installed inside the enclosure c/w mounting bands, discharge elbow, and raincap. Exhaust flex installed. Miscellaneous: Two (2) copies Operation, Maintenance & Parts Manual & one (1) PDF copy Warranty: Two (2) year or 3,000 hours basic standby limited warranty Load Bank (Radiator Duct‐Mounted): 240kW rating @ 600VAC, 3‐phase See Avtron bill of materials for details Automatic Transfer Switch: None included DIESEL GENERATOR SET MTU 6R1600 DS300 300 kWe /60 Hz /Standby 208 - 600V Reference MTU 6R1600 DS300 (275 kWe) for Prime Rating Technical Data SYSTEM RATINGS Standby Voltage (L-L) Phase PF Hz kW kVA Amps skVA@30% Voltage Dip Generator Model Temp Rise Connection 208V* 3 0.8 60 300 375 1041 240V* 3 0.8 60 300 375 902 380V 3 0.8 60 300 375 570 440V 3 0.8 60 300 375 492 480V* 3 0.8 60 300 375 451 600V* 3 0.8 60 300 375 361 930 433CSL6216 130 °C/40 °C 930 433CSL6216 130 °C/40 °C 640 433CSL6216 130 °C/40 °C 860 433CSL6216 130 °C/40 °C 820 432CSL6212 130 °C/40 °C 720 432PSL6246 130 °C/40 °C 12 LEAD WYE 12 LEAD DELTA 12 LEAD WYE 12 LEAD WYE 12 LEAD WYE 4 LEAD WYE * UL 2200 Offered CERTIFICATIONS AND STANDARDS // Emissions – EPA Tier 3 Certified // Generator set is designed and manufactured in facilities certified to standards ISO 9001:2008 and ISO 14001:2004 // Seismic Certification – Optional – IBC Certification – OSHPD Pre-Approval // UL 2200 / CSA – Optional – UL 2200 Listed – CSA Certified // Performance Assurance Certification (PAC) - Generator Set Tested to ISO 8528-5 for Transient Response - Verified product design, quality and performance integrity - All engine systems are prototype and factory tested // Power Rating - Accepts Rated Load in One Step Per NFPA 110 - Permissible average power output during 24 hours of operation is approved up to 85%. 2 / // / MTU 6R1600 DS300 (300 kWe) - Standby STANDARD FEATURES* MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty 6R1600 Diesel Engine - 10.5 Liter Displacement - Common Rail Fuel Injection - 4-Cycle // Engine-generator resilient mounted // Complete Range of Accessories // // // // Generator - Brushless, Rotating Field Generator - 2/3 Pitch Windings - 300% Short Circuit Capability with Optional Permanent Magnet Generator (PMG) // Digital Control Panel(s) - UL Recognized, CSA Certified, NFPA 110 - Complete System Metering - LCD Display // Cooling System - Integral Set-Mounted - Engine-Driven Fan // STANDARD EQUIPMENT* // Engine Air Cleaner Oil Pump Oil Drain Extension and S/O Valve Full Flow Oil Filters Closed Crankcase Ventilation Jacket Water Pump Thermostats Blower Fan and Fan Drive Radiator - Unit Mounted Electric Starting Motor - 24V Governor – Electronic Isochronous Base - Formed Steel SAE Flywheel and Bell Housing Charging Alternator - 24V Battery Box and Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine // Generator NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130 °C Max. Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±1% Voltage Regulation 100% of Rated Load - One Step 5% Max. Total Harmonic Distortion // Digital Control Panel(s) Digital Metering Engine Parameters Generator Protection Functions Engine Protection CANBus ECU Communications Windows®-Based Software Multilingual Capability Remote Communications to RDP-110 Remote Annunciator Programmable Input and Output Contacts UL Recognized, CSA Certified, CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Compatible * Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations. 3 / // / MTU 6R1600 DS300 (300 kWe) - Standby APPLICATION DATA // Engine // Manufacturer Model Type Arrangement Displacement: L (Cu In) Bore: cm (in) Stroke: cm (in) Compression Ratio Rated RPM Engine Governor Max. Power: kWm (bhp) Speed Regulation Air Cleaner // MTU 6R1600G80S 4-Cycle 6-Inline 10.5 (641) 12.2 (4.8) 15 (5.91) 17.5:1 1,800 ECU 8 343 (460) ±0.25% Dry At 100% of Power Rating: L/hr (gal/hr) At 75% of Power Rating: L/hr (gal/hr) At 50% of Power Rating: L/hr (gal/hr) // 82 (21.6) 66 (17.5) 51 (15.4) Cooling - Radiator System Ambient Capacity of Radiator: °C (°F) Max. Restriction of Cooling Air: Intake and Discharge Side of Rad.: kPa (in. H20) Water Pump Capacity: L/min (gpm) Heat Rejection to Coolant: kW (BTUM) Heat Rejection to After Cooler: kW (BTUM) Heat Radiated to Ambient: kW (BTUM) Fan Power: kW (hp) 50 (122) 0.2 (0.8) 277 (73.1) 154 (8,758) 90 (5,118) 36.9 (2,099) 14.9 (20) Liquid Capacity (Lubrication) Total Oil System: L (gal) Engine Jacket Water Capacity: L (gal) System Coolant Capacity: L (gal) // Fuel Consumption 46 (12.2) 45 (11.9) 82 (21.7) Electrical Electric Volts DC Cold Cranking Amps Under -17.8 °C (0 °F) 24 950 // Air Requirements Aspirating: *m3/min (SCFM) Air Flow Required for Rad. Cooled Unit: *m3/min (SCFM) Remote Cooled Applications; Air Flow Required for Dissipation of Radiated Generator Set Heat for a Max. of 25 °F Rise: *m3/min (SCFM) 30 (1,059.4) 396 (13,985) 134 (4,733) * Air density = 1.184 kg/m3 (0.0739 lbm/ft3) // Fuel System Fuel Supply Connection Size Fuel Return Connection Size Max. Fuel Lift: m (ft) Recommended Fuel Total Fuel Flow: L/hr (gal/hr) -10 JIC 37° Female M20 x 1.5 Male Adapter Provided -6 JIC 37° Female M14 x 1.5 Male Adapter Provided 5 (16) Diesel #2 198 (60.4) // Exhaust System Gas Temp. (Stack): °C (°F) Gas Volume at Stack Temp: m3/min (CFM) Max. Allowable Back Pressure: kPa (in. H20) 440 (824) 72 (2,542.7) 15 (60.2) 4 / // / MTU 6R1600 DS300 (300 kWe) - Standby WEIGHTS AND DIMENSIONS Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings. System Open Power Unit (OPU) Dimensions (L x W x H) 3,658 x 1,883 x 1,855 mm (144 x 74.13 x 73 in) Weight (dry/less tank) 3,078 kg (6,785 lb) SOUND DATA Unit Type Level 0: Open Power Unit dB(A) Standby Full Load 87.2 Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust. EMISSIONS DATA NOx + NMHC 4.14 CO 0.52 RATING DEFINITIONS AND CONDITIONS PM 0.04 All units are in g/hp-hr and shown at 100% load (not comparable to EPA weighted cycle values). Emission levels of the engine may vary with ambient temperature, barometric pressure, humidity, fuel type and quality, installation parameters, measuring instrumentation, etc. The data was obtained in compliance with US EPA regulations. The weighted cycle value (not shown) from each engine is guaranteed to be within the US EPA Standards. C/F = Consult Factory/MTU Onsite Energy Distributor N/A = Not Available MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS 5514, and AS 2789. Average load factor: ≤ 85%. // Deration Factor: Altitude: Consult your local MTU Onsite Energy Power Generation Distributor for altitude derations. Temperature: Consult your local MTU Onsite Energy Power Generation Distributor for temperature derations. // 9300 192nd Street, Surrey B.C. V4N 3R8 Phone: (604) 888-1211 Fax: (604) 888-4749 © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 537 (77 3E) 2015-10 v1 Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set. MARATHON ELECTRIC SYNCHRONOUS AC GENERATOR TYPICAL DYNAMIC CHARACTERISTICS Base Model: 433PSL6248 Kilowatt ratings at 1800 RPM kW (kVA) 3 Phase Date: 1/19/2015 60 Hertz Class B 80º C 90º C Voltage* Continuous Lloyds 600 310 (388) 340 (425) 95º C ABS 352 (440) 12 Leads Dripproof or Open Enclosure 0.8 Power Factor Class F Class H 105º C 125º C British 105º C 130º C British 125º C 150º C Standard Continuous Standby Standard Continuous Standby 375 (469) 375 (469) 410 (513) 391 (489) 400 (500) 430 (538) Rise by resistance method, Mil-Std-705, Method 680.1b. Rating per BS 5000. Submittal Data: 600 Volts*, 513 kVA, 1800 RPM, 60 Hz, 3 Phase Mil-Std-705B Method Description 301.1b Insulation Resistance 302.1a High Potential Test Main Stator Main Rotor Exciter Stator Exciter Rotor PMG Stator 401.1a Stator Resistance, Line to Line High Wye Connection Rotor Resistance Exciter Stator Exciter Rotor PMG Stator 410.1a No Load Exciter Field Amps at 600 Volts Line to Line 420.1a Short Circuit Ratio 421.1a Xd Synchronous Reactance 422.1a X2 Negative Sequence Reactance 423.1a X0 Zero Sequence Reactance 425.1a X'd Transient Reactance 426.1a X''d Subtransient Reactance -Xq Quadrature Synchronous Reactance 427.1a T'd Transient Short Circuit Time Constant 428.1a T''d Subtransient Short Circuit Time Constant 430.1a T'do Transient Open Circuit Time Constant 432.1a Ta Short Circuit Time Constant of Armature Winding (3) Value > 1.5 Meg 2000 Volts 1500 Volts 1500 Volts 1500 Volts NS** 0.0175 Ohms 0.991 Ohms 18.5 Ohms 0.116 Ohms NS** Mil-Std-705B Method Description 505.3b Overspeed 507.1c Phase Sequence CCW-ODE 508.1c Voltage Balance, L-L or L-N 601.4a L-L Harmonic Maximum - Total (Distortion Factor) 601.4a L-L Harmonic Maximum - Single 601.1c Deviation Factor --TIF (1960 Weightings) 625.1c Mechanical Strength (High Wye Connection, Sustained 3 Phase Short Circuit Current) (3) 652.1a Shaft Current 652.1a Main Stator Capacitance to Ground 0.86 A DC 0.54 2.414 pu 0.162 pu 0.039 pu 0.117 pu 0.104 pu 1.182 pu 0.067 sec. 0.016 sec. 2.27 sec. 2.27 sec. Value 2250 RPM ABC 0.2% 5.0% 3.0% 5.0% <50 < 300% < 0.1 ma 0.028 mfd Additional Prototype Mil-Std Methods are Available on Request. ----------- Generator Frame 433 Type Ext. Voltage Regulated, Brushless Insulation Class H Coupling - Single Bearing Flexible Amortisseur Windings Full Exciter SE350*** Voltage Regulator 1%*** Voltage Regulation 1 Phase*** Sensing Cooling Air Volume Heat Rejection Rate Full Load Current Minimum Input Hp Required Efficiency at Rated Load Full Load Torque Excitation support system or PMG required to sustain short circuit currents. * Voltage refers to wye (star) connection, unless otherwise specified. **Not supplied as standard equipment. ***DVR®2000E+ voltage regulator supplied with PMG option. DVR®2000E+ voltage regulation 1/4%, 1 or 3 Phase sensing. 800 CFM 1373 CFM 481 CFM 568.5 Hp 94.3 % 1658 Lb-ft www.marathonelectric.com MARATHON ELECTRIC SYNCHRONOUS AC GENERATOR TYPICAL DYNAMIC CHARACTERISTICS Date: 1/19/2015 Base Model: 433PSL6248 60 HERTZ Recovery Time (Sec.) Recovery Time (Sec.) 0.5 0 0.5 0 LOAD APPLICATION LOAD REJECTION 30 30 % Voltage Rise % Voltage Dip 600 V 20 10 600 V 20 10 0 0 0 100 200 300 400 kW at 0.8 Power Factor 500 0 100 200 300 400 kW at 0.8 Power Factor 500 TYPICAL MOTOR STARTING CHARACTERISTICS 40 % Voltage Dip 600 V 30 20 SE350 DVR®2000E+ 10 0 0 500 1000 1500 2000 2500 Locked Rotor kVA TYPICAL GENERATOR EFFICIENCY 100 0.8 pf % Efficiency 600 V 90 1.0 pf 80 0 100 200 300 400 500 600 kW Output Voltage refers to wye (star) connection, unless otherwise specified. www.marathonelectric.com DVR®2000E+ / EC+ Digital Voltage Regulator Four Digit HMI Display From initial setup to monitoring regulator status, this display provides innovative, world class, fast and easy setup. Advanced Regulation Modes Single and Three phase Automatic Voltage Regulation. Manual Field Current Regulation mode. All modes compatible with control by external devices. VAR / PF Control – DVR2000EC+ Only Reactive power regulation (VAR) and Power Factor regulation (PF) modes enables paralleling with utility power. Generator Soft Start Controlled increase to rated voltage limits overshoot during voltage build-up in AVR modes. True RMS Voltage Sensing - Single or Three Phase Connect in the sensing mode you prefer. Directly sense 100 to 600 Volts ±10% at 50/60 Hz. Circuitry senses true RMS voltage rather than average voltage for superior load regulation. True Three Phase Power Monitoring Additional CT inputs enable you to sense current on all three phases. Frame Specific PID Selection Tuning your regulator for your Marathon Electric generator has never been easier. Simply select the appropriate frame size and your gains are set. Robust Generator Protection Features 14 different Alarm and Shutdown protection features, many customizable for your application including – ● ● ● ● Generator Startup Fault – DVR2000EC+ Only Field Over & Under Excitation Instantaneous Field Over Current Generator Over & Under Voltage A Regal Brand DVR®2000E+ / EC+ Specifications Voltage Regulation – 0.25% over load range at rated power factor and constant generator frequency. Humidity Testing – Per MIL-STD-705B, Method 711-D Salt Fog Testing – Per MIL-STD-810E Output Power – 75 Vdc, 3.0 Adc continuous rating and 150 Vdc, 7.5 Adc forcing capability for one minute. Exciter Field DC Resistance – 18 to 25Ω range Voltage Adjustment – Minimum if ±10% of nominal voltage range. Remote adjustment can be made up to 150 feet from voltage regulator. Input Power – 180 to 240 Vac, 250 to 300 Hz PMG power supply CAN Protocol – SAE J1939 Regulator Sensing – 100 to 600 Vac, 50/60 Hz, 1-phase/3-phase EMI Compatibility Immunity Meets EN 61000-6-2: 2005 Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments. Emission Operating Temperature – From to +70°C (-40°F to +158°F) -40°C Storage Temperature – From -40°C to +85°C (-40°F to +185°F) Ingress Protection – IP52 (front side mounted in conduit box); IP10 (rear side with protective cover) Shock – 20 Gs in 3 perpendicular planes Vibration – 2.5 G at 5 to 26 Hz; 0.050” double amplitude (27 to 52 Hz); 7 Gs at 53 to 500 Hz Weight – 3.5 lb. (1361 g) Meets EN 61000-6-4: 2007 Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments EMI Compatibility Tests Immunity Electrostatic Discharge (ESD): IEC 61000-4-2 Radiated RF: IEC 61000-4-3 Electrical Fast Transient (EFT) / Burst: IEC 61000-4-4 Conducted RF: IEC 61000-4-6 Power Frequency and Magnetic Field: IEC 61000-4-8 Emmision Radiated RF: EN 61000-6-4: 2007, 30 MHz to 1000 MHz Marathon Electric Manufacturing Corp. P.O. Box 8003 Wausau, WI 54402-8003 USA www.marathonelectric.com GPN045 - 12/5/2012 G:\Marketing_Generators\Marketing_Technician\Literature\DVR E+ - EC+ Flyer\DVR2000E+ EC+ Flyer (GPN045).docx A Regal Brand DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet MTU Onsite Energy Generator Set Controllers (MGC Series) are highly advanced integrated digital generator set control systems. The MGC-2000 Series is perfectly focused, combining rugged construction and microprocessor technology to offer a product that will hold up to almost any environment and is flexible enough to meet your application’s needs. The MGC-2000 Series provides generator set control, transfer switch control, metering, protection, and programmable logic in a simple, easy-to-use, reliable, rugged, and cost effective package. PRODUCT HIGHLIGHTS • • • • • • • • • • • • • • • • • • • • • • • • • Three-phase generator metering Engine metering Generator set control Engine protection Generator protection Var sharing over Ethernet BESTCOMSPlus® - Windows®-based software for optional remote operation (Software can be downloaded at www.mtuonsiteenergy.com) - Programming and setup software - Intuitive and powerful - Remote control and monitoring - Programmable logic - USB communications Automatic transfer switch compatible Exercise timer Suitable for use on rental generator sets with high/low line sensing, single or three phase sensing override, and wye/delta/grounded delta SAE J1939 Engine Control Unit (ECU) communications Automatic generator configuration detection Selection of integrating reset of instantaneous reset characteristics for overcurrent protection Multilingual capability Remote annunciation to RDP-110 Extremely rugged, fully potted design 16 programmable contact inputs, 12 programmable contact outputs ModBus™ communications with RS-485 (optional) UL recognized, CSA certified, CE approved Highly Accelerated Life Tests (HALT) tested IP 54 front panel rating with integrated gasket NFPA-110 compatible Microprocessor based Complete system metering Expandable to meet customer needs *Please refer to the MGC Series Controller Comparison Data Sheet for available configured options. // Page 1 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet DIAGRAM Front Panel Descriptions • • • • • • Liquid Crystal Display (A) Not in Auto Indicator (B) Alarm Indicator (C) Supplying Load Indicator (D) Alarm Silence Pushbutton (E) Lamp Test Pushbutton (F) • • • • • • Auto Pushbutton and Mode Indicator (G) Off Pushbutton and Mode Indicator (H) Run Pushbutton and Mode Indicator (I) Reset Pushbutton (J) Arrow Pushbuttons (K) Edit Pushbutton (L) • • • • • Loss of Excitation (40Q) Phase Imbalance (47) Overcurrent (51) (optional) Vector Shift (78) (optional) Rate of Change of Frequency (ROCOF) (81R) (optional) FUNCTIONS Generator Set Protection Generator ANSI Codes • Overvoltage (59) • Overfrequency (81O) • Reverse Power (32) • Undervoltage (27) • Underfrequency (81U) All generator set protection features are programmable as alarms, pre-alarms, status, or not used. Alarms (Shutdowns) • Low Oil Pressure • High Coolant Temperature • Low Coolant Level • Overspeed • Overcrank • • • • Coolant Temp Sender Fail (non-ECU engines) Oil Pressure Sender Fail (non-ECU engines) Emergency Stop Critical Low Fuel Level (optional) // Page 2 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet FUNCTIONS, Generator Set Protection, continued: Pre-Alarms (Warnings) • Low Oil Pressure • High Coolant Temperature • Low Coolant Temperature • Battery Overvoltage • Weak Battery Voltage • AEM Comms Failure • Breaker Open Failure • CEM Comms Failure • Generator Reverse Rotation • • • • • • • • • Engine kW Overload (three levels) Loss of Sensing Checksum Failure ECU Comms Fail Low Fuel Level High Fuel Level Active Diagnostic Trouble Codes (DTC) Breaker Close Failure Low Battery Voltage All alarms and pre-alarms can be enabled or disabled via the BESTCOMSPlus® PC software or the front panel. Additional custom alarms and pre-alarms are available upon request. Generator Set Metering • Generator parameters include voltage, current, real power (watts), apparent power (VA), and power factor (PF). • Engine parameters include oil pressure, coolant temperature, battery voltage, speed, fuel level, engine load, coolant level (from ECU), ECU specific parameters, and run-time statistics. Engine Control • • • • Cranking Control: Cycle or Continuous (Quantity and Duration fully programmable) Engine Cooldown: Smart Cooldown function saves fuel and engine life Successful Start Counter: Counts and records successful engine starts Timers: - Engine Cooldown Timer - Engine Maintenance Timer - Pre-Alarm Time Delays for Weak/Low Battery Voltage - Alarm Time Delay for Overspeed - Alarm Time Delay for Sender Failure - Arming Time Delays after Crank Disconnect: Low Oil Pressure High Coolant Temperature - Pre-Crank Delay - Continuous or Cycle Cranking Time Delay - Programmable Logic Timers // Page 3 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet FUNCTIONS, continued: Event Recording The MGC-2000 Series has an event recorder that provides a record of alarms, pre-alarms, engine starts, engine runtime loaded, engine runtime unloaded, last run date, and many other events that are all date and time stamped to help the user determine the cause and effect of issues related to the generator set. Contains 30 event records each retaining up to 99 occurrences in memory. Time, date, and engine hour detail is available for the most current 30 occurrences within each event record. Transfer Switch Control (Mains Failure) The MGC-2000 Series has the ability to detect a mains failure via a single- or three-phase bus input. A mains failure is established when any one of the following conditions are met: • Any phase of bus voltage falls below the dead bus threshold • Any phase of bus voltage is unstable due to overvoltage or undervoltage • Any phase of bus voltage is unstable due to overfrequency or underfrequency When conditions are met, the MGC-2000 Series will start the generator set and, when ready, will send generator and mains breaker commands to apply power to the load from the generator set. The MGC-2000 Series implements open or closed breaker transitions to and from the mains. When the mains returns and is considered stable, the MGC-2000 Series will transfer the load back to the mains and stop the engine. ModBus™ RTU When utilized, the user can send and receive information from the MGC-2000 Series via the RS-485 communications port and ModBus™ RTU protocol. This feature allows the MGC-2000 Series controlled generator set to be fully integrated into the building management system. Please see the MGC-2000 Series Controller Manual for the ModBus™ register list. Programmable Logic The MGC-2000 Series offers a very powerful, yet easy-to-use, programmable logic scheme, BESTlogic™Plus, for custom programming of the various inputs, outputs, alarms, and pre-alarms. It allows these elements to be integrated into a complete logic scheme so that the user can meet even the most complex specification. The programmable logic control includes the selection of logic gates and timers, with drag-and-drop technology to make it fast and simple. Remote Display Panel Annunciation The MGC-2000 Series can communicate to a remote display panel, Model RDP-110. This requires only two wires to annunciate all of the alarms and pre-alarms required by NFPA-110 Level I and II. External power is required. External Modem Interface The MGC-2020 and MGC-2050 controllers include an external modem interface permitting an external modem to be connected to the MGC controller via RS-232. A dial-out modem enables remote control, monitoring, and setting of the MGC-2000 Series. When an alarm or pre-alarm condition occurs, the MGC-2000 Series can dial up to four telephone numbers in sequence until an answer is received and the condition is annunciated. Note: Only an external modem interface is provided. The external modem must be provided by a third party. The external modem is only available on the MGC-2020 and MGC-2050 controller configurations of the MGC-2000 Series. // Page 4 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet FUNCTIONS, continued: SAE J1939 Communications SAE J1939 CANBus communications allows the MGC-2000 Series to communicate with the ECU to gather critical engine information like oil pressure, engine coolant temperature, RPM, battery voltage, and much more. By utilizing the ECU, the addition of analog engine senders is no longer required. This can save substantial money for the installer. It also eliminates any errors or discrepancies between the ECU data and the data displayed on the MGC-2000 Series that may be present due to analog sender inaccuracies or incompatibility. An additional benefit is access to the ECU’s diagnostic troubleshooting codes (DTCs). The DTCs provide information about the engine’s operating conditions and communicates these, via SAE J1939, to the MGC-2000 Series, eliminating the need for hand-held service tools to diagnose simple engine issues. SPECIFICATIONS Operating Power • Nominal: 12 or 24 VDC • Range: 6 to 32 VDC • Power Consumption: - Sleep Mode: 5W with all relays non-energized - Normal Operational Mode: 7.9W - Run mode, LCD heater off, six relays energized • Battery Ride-Through: Withstands cranking ride-through down to 0 V for 50 ms, starting at 10 VDC. Current Sensing (5 A CT Inputs) • Continuous Rating: 0.1 to 5.0 Aac • One Second Rating: 10 Aac • Burden: 1 VA Voltage Sensing • • • • Range: 12 to 576 V rms, line-to-line Frequency Range: 10 to 72 Hz Burden: 1 VA One Second Rating: 720 V rms Input Contacts Contact sensing inputs include one emergency stop input and 16 programmable inputs. The emergency stop input accepts normally closed, dry contacts. The remote emergency stop is limited to 75 ft. standard. Extended runs are available with optional relay. All programmable inputs accept normally open, dry contacts. The factory utilizes up to three of these inputs. Engine System Inputs • • • • Fuel Level Sensing Resistance Range: 0 to 250 Ω nominal Coolant Temperature Sensing Resistance Range: 10 to 2,750 Ω nominal Oil Pressure Sensing Resistance Range: 0 to 250 Ω nominal Engine Speed Sensing: - Magnetic Pickup or CANBus Magnetic Pickup Voltage Range: 3 to 35 V peak (6 to 70 V peak to peak) Magnetic Pickup Frequency Range: 32 to 10,000 Hz - Generator Frequency (alternate or redundant) Voltage Range: 12 to 576 V rms // Page 5 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet SPECIFICATIONS, continued: Output Contacts • (15) Total Programmable Outputs: (3) 30 A @ 28 VDC and (12) 2 A @ 30 VDC • The factory utilizes the following on each generator set which can be reprogrammed as needed: - (3) 30 A @ 28 VDC for Pre-start, Start, and Run (12) 2 A @ 30 VDC for General Purpose Metering • Generator and Bus Voltage (rms) - Metering Range: 0 to 576 VAC (direct measurement); up to 9,999 VAC (with appropriate voltage transformer) - Accuracy: ±1% of programmed rated voltage of ±2 VAC (subject to accuracy of voltage transformer when used) • Generator Current (rms) - Generator current is measured at the secondary windings of 5 A CTs. - Metering Range: 0 to 5,000 Aac - CT Primary Range: 1 to 5,000 Aac, in primary increments of 1 Aac - Accuracy: ±1% of programmed rated current or ±2 Aac (subject to accuracy of CTs) • Generator and Bus Frequency - Metering Range: 10 to 72 Hz - Accuracy: ±0.25% or 0.05 Hz • Apparent Power - Indicates total kVA and individual line kVA (four-wire, line-to-neutral or three-wire, line-to-line). - Accuracy: ±3% or the full-scale indication or ±2 kVA • Power Factor - Metering Range: 0.2 leading to 0.2 lagging - Accuracy: ±0.02 • Real Power - Indicates total kW and individual line kW (four-wire, line-to-neutral or three-wire, line-to-line) - Accuracy: ±3% of the full-scale indication or ±2 kW • Oil Pressure - Metering Range: 0 to 150 psi or 0 to 1,034 kPa - Accuracy: ±3% of actual indication or ±2 psi or ±12 kPa (subject to accuracy of sender) • Coolant Temperature - Metering Range: 0 °C to 204 °C (32 °F to 410 °F) - Accuracy: ±3% of actual indication or ±2° (subject to accuracy of sender) • Fuel Level - Metering Range: 0 to 100% - Accuracy: ±2% (subject to accuracy of sender) • Battery Voltage - Metering Range: 6 to 32 VDC - Accuracy: ±3% of actual indication or ±0.2 VDC • Engine RPM - Metering Range: 0 to 4,500 rpm - Accuracy: ±2% of actual indication or ±2 rpm // Page 6 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet SPECIFICATIONS, Metering, continued: • Engine Run Time - Engine run time is retained in non-volatile memory. - Metering Range: 0 to 99,999 h; Update Interval: 6 min - Accuracy: ±1% of actual indication or ±12 min • Maintenance Timer - Maintenance timer indicates the time remaining until generator set service is due. Value is retained in non-volatile memory. - Metering Range: 0 to 5,000 h; Update Interval: 6 min - Accuracy: ±1% of actual indication or ±12 min Generator Protection Functions • Overvoltage (59) and Undervoltage (27) - Pickup Range: 70 to 576 VAC - Activation Delay Range: 0 to 30 s • Overfrequency (81O) and Underfrequency (81U) - Pickup Range: 45 to 66 Hz - Pickup Increment: 0.1 Hz - Activation Delay Range: 0 to 30 s • Reverse Power (32) - Pickup Range: –50 to 5% - Pickup Increment: 0.1% - Hysteresis Range: 1 to 10% - Hysteresis Increment: 0.1% - Activation Delay Range: 0 to 30 s - Activation Delay Increment: 0.1 s • Loss of Excitation (40Q) - Pickup Range: –150 to 0% - Pickup Increment: 0.1% - Hysteresis Range: 1 to 10% - Hysteresis Increment: 0.1% - Activation Delay Range: 0 to 30 s - Activation Delay Increment: 0.1 s • Overcurrent (51) - Pickup Range: 0.18 to 1.18 Aac (1 A current sensing) - Time Dial Range: 0 • Phase Imbalance (47) - Pickup Range: 5 to 100 VAC - Pickup Increment: 1 VAC - Activation Delay Range: 0 to 30 s - Activation Delay Increment: 0.1 s • ROCOF (81R) (optional) - Pickup Range: 0.2 to 10 Hz/s - Pickup Increment: 0.1 Hz/s - Activation Delay Range: 0 to 10,000 ms - Activation Delay Increment: 1 ms - Accuracy: 0.2 Hz/s // Page 7 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet SPECIFICATIONS, Generator Protection Functions, continued: • Vector Shift (78) (optional) - Pickup Range: 2 to 90° - Pickup Increment: 1° - Accuracy: ±1° Environmental • Temperature - Operating: -40 °C to 70 °C (-40 °F to 158 °F) - Storage: -40 °C to 85 °C (-40 °F to 185 °F) • Humidity: IEC 68-2-38 • Salt Fog: ASTM B 17-73, IEC 68-2-11 (tested while operational) • Ingress Protection: IEC IP54 for front panel • Shock: 15 G in three perpendicular planes • Vibration: 5 to 29 to 5 Hz at 1.5 G peak for 5 min. 29 to 52 to 29 Hz at 0.036” DECS-A for 2.5 min. 52 to 500 to 52 Hz at 5 G peak for 7.5 min. - Swept over the above ranges for 12 sweeps in each of three mutually perpendicular planes with each 15 minute sweep. Agency Approvals • UL/CSA Approvals: “cURus” approved to UL 6200 and CSA C22.2 No.14 • NFPA Compliance: Complies with NFPA Standard 110, Standard for Emergency and Standby Power • CE Marked: Complies with applicable EC Directives ADDITIONAL SPECIFICATIONS Battery Backup for Real Time Clock The MGC-2000 Series provides a real-time clock with an internal backup battery. The battery will maintain timekeeping for approximately 10 years (depending on conditions) after power is removed from the controller. The clock is used by the event recorder and sequence of events functions to time-stamp events, and the exercise timer is used to start and stop the generator set when the exercise feature is utilized. Breaker Management The MGC-2000 Series is capable of controlling the generator breaker and the mains breaker. The status of the breakers is determined by using BESTlogic™Plus programmable logic to set up the GENBRK and MAINSBRK logic blocks. These logic blocks have outputs that can be configured to energize an output contact and control a breaker, as well as inputs for breaker control and status. The MGC-2000 Series will attempt to close a breaker only after verifying that it can be closed. If the breaker cannot be closed, the close request will be ignored. Only one breaker can be closed at a time. Synchronization is required before closing the breaker to a live bus. Closure to a dead bus can be performed after meeting dead bus threshold and timing requirements set by the user. OPTIONAL ACCESSORIES Analog Extension Module 2020 (AEM–2020) The optional AEM-2020 is a remote auxiliary device that provides additional MGC-2000 Series analog inputs and outputs. Its features include: • Eight Analog Inputs: The AEM-2020 provides eight analog inputs that are user-selectable for 4 to 20 mA or 0 to 10 VDC. Each analog input has under/over thresholds that can be configured as status only, alarm, or pre-alarm. When enabled, an out of range alarm alerts the user of an open or damaged analog input wire. The label text of each analog input is customizable. // Page 8 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet OPTIONAL ACCESSORIES, AEM-2020, continued: • Eight Resistance Temperature Detector (RTD) Inputs: The AEM-2020 provides eight user-configurable RTD inputs for monitoring generator set temperature. Each RTD input can be configured as status only, alarm, or pre-alarm to protect against high or low temperature conditions. When enabled, an out-of-range alarm alerts the user of an open or damaged RTD input wire. The label text of each RTD input is customizable. • Two Thermocouple Inputs: The AEM-2020 provides two thermocouple inputs for monitoring generator set temperature. Each thermocouple input can be configured as status only, alarm, or pre-alarm to protect against high or low temperature conditions. When enabled, an out-of-range alarm alerts the user of an open or damaged thermocouple input wire. The label text of each thermocouple input is customizable. • Four Analog Outputs: The AEM-2020 provides four analog outputs that are user-selectable for 4 to 20 mA or 0 to 10 VDC. A wide selection of parameters including oil pressure, fuel level, generator voltage, and bus voltage can be configured as analog outputs. Refer to Section 4, BESTCOMSPlus® Software of the MGC-2000 Series Controller Manual, for a full list of parameter selections. • Communications via CANBus: A Control Area Network (CAN) is a standard interface that enables communication between the AEM-2020 and the MGC-2000 Series. Contact Expansion Module 2020 (CEM-2020) The CEM-2020 is a remote device that provides additional MGC-2000 Series contact inputs and outputs, giving the user flexibility to use the same model MGC-2000 Series generator set controller for simple or complicated applications that require contact functionality or duplication of contacts for remote annunciation. Its features include: • 10 Contact Inputs: The CEM-2020 provides 10 programmable contact inputs with the same functionality as the contact inputs on the MGC-2000 Series. • 24 Output Contacts: The CEM-2020 provides 24 Form C programmable output contacts with the same functionality as the output contacts on the MGC-2000 Series. The output ratings of the Form C contacts are: // Page 9 of 10 DIGITAL GENERATOR SET CONTROLLER MGC-2000 Series Data Sheet OPTIONAL ACCESSORIES, CEM-2020, continued: Output No. Rating (Cont.) Additional Information 13–24 1 A @ 30 VDC This is a gold flash contact for low current circuits. 25–36 4 A @ 30 VDC • Communications via CANBus: The CEM-2020 communicates to the MGC-2000 Series via SAE J1939 CANBus communications and allows the user to program the functionality of these inputs and outputs in the BESTCOMSPlus® software. © MTU Onsite Energy. Subject to alteration due to technological advances. 2015-12 • The user can add labels for the inputs and outputs that appear in BESTCOMSPlus®, show up on the front panel, and in programmable logic. All the functionality can be assigned to these inputs and outputs as if they were an integrated part of the MGC-2000 Series. The CEM-2020 module has all of the environmental ratings of the MGC-2000 Series, including a model for UL Class1 Div2 applications. The CEM-2020 terminals accept a maximum wire size of 12 AWG, while the chassis ground requires 12 AWG wire. Flexibility is one of the benefits of the MGC-2000 Series, and this add-on module enhances that benefit even further. 100 Power Drive / Mankato, MN 56001 / 800-325-5450 MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com // Page 10 of 10 14 1.3 Functional Description ADEC – Functions Control functions Following engine functions are controlled: • Engine start • Engine stop • Sequences when “Override” feature is activated (safety system override), engine start with start interlock interrogation deactivated (“emergency start”). • Nominal speed switching between two set values (optional operation as 50 Hz or 60 Hz genset). • Injection quantity as a function of engine loading and speed. • Torque regulation Engine start The starting sequence is controlled by the software integrated in the engine governor as follows. Starting sequence activation The SAM takes a few seconds to boot up. It signals operational availability on the CAN bus by an appropriate PV. Only then may starting be initialized. Under normal operating conditions bothe the SAM and the engine governor are constantly switched on (standby mode). Start request The engine is started by a so-called “non-stored start”, i.e. the start signal must be applied until the engine has reached idling speed. The actual starting sequence itself is executed automatically. Furthermore, starting can be requested via the CAN bus. There are correspondingly three CAN receive variables. The start requests are OR operations. Stop request Starting is terminated if an external (manual) or internal (automatic) stop request from another part of the software is received. A stop request resets the start interlock time thus allowing immediate restarting in case of internal start termination providing that the engine is at a standstill and no other start request was active. Coolant temperature monitoring – Start termination The engine may suffer mechanical damage if started at too low a temperature. The coolant temperature is used to determine the engine temperature. Excessively low coolant temperature is indicated by a lamp. Indication by the lamp is independent of any alarm signal. Usually the alarms “LO T-Preheat” (for the first limit value) or “SS T-Preheat” (for the second limit value) are tripped when the corresponding limits are violated; even when the engine is at a standstill. When the second limit value is violated the internal “Stop starting sequence” signal is set providing that Override is not active. This trips a stop and the engine does not start. The alarm is reset again when the coolant limit value is reached (plus hysteresis). Starting The starter is activated via engine governor binary output TOP 4. The engine runs up to starting speed on the starter within a configurable period. If this is not the case starting is terminated and the “SS Starter Speed Not Reached” alarm is output. The starter disengages and a new starting sequence is automatically attempted after a configurable pause. The starter disengages when the disengagement speed (300 rpm) is reached. The start button may be released once the disengagement speed has been reached. Pressing the start button has no effect from this point on and only takes effect again when the engine has come to a standstill. The “SS Starter Speed Not Reached” alarm is set if the disengagement speed is not reached within a set time and “terminate start” is activated. Starting is also terminated if the starting signal is no longer received. Engine start with Override (“emergency start”) Various configurable start interlock criteria are bypassed when override is active on starting the engine: Engine stop An engine stop is tripped by interrupting the 24V supply at the binary input of the engine governor or by the engine protection system. Fuel is no longer injected as injector activation is disrupted. Any starting procedure which has been initiated is interrupted. E532233/00E 06-06 © MTU Use, Structure and Function 15 Override (safety system bypass) The “Override” feature is used to bypass safety functions tripped by limit value violations or sensor faults and to bypass start interlocks (see above). Operating states which would normally lead to engine shutdown are ignored when the “Override” function is activated. The following operational data can be configured to trip engine shutdown in case of limit value violation even in Override mode: • Coolant level • Coolant temperature • Coolant pressure • Charge air coolant level • Lube oil pressure • Lube oil temperature 50 Hz/60 Hz switching on bifrequency engines To increase the genset application scope the network frequency can be adjusted prior to engine start. The nominal speed is set as follows: • Network frequency 50 Hz: Nominal speed 1500 rpm • Network frequency 60 Hz: Nominal speed 1800 rpm Caution! Switching is only possible when the engine is at a standstill! Switching requires programming of corresponding performance maps and parameters in the governor and appropriate engine hardware. Monitoring functions The engine management system fulfils the following monitoring tasks: • Control of analog instruments; • Engine lube oil pressure • Engine coolant temperature • Transmission of all measurands, warnings and alarms to monitoring system via CAN bus. • Automatic shutdown in case of limit value violations. Refer to the measuring-point list for order-specific configuration data. Engine monitoring can basically be divided into two different areas: • Engine protection system, monitors the engine during operation, • Safety system, generates automatic engine shutdown in case of limit value violation. These two functional areas are constantly monitored by the internal “Integral Test System (ITS)” to ensure operational availability. Oil priming pump option An optional oil priming pump may be integrated in the system. The pump is activated manually via a binary input on the SAM. Closed-loop control functions Closed-loop engine control functions: • Speed regulation • Injection control with mapped commencement of injection. • Two adjustable speed droops. • Setpoint speed regulation • Analog or binary speed demand on CAN bus, CANopen and SDE J1939 • Analog speed setting 0 V to 10 VDC / 0 V to 5 VDC / 4 mA to 20 mA. • Binary speed demand via Up/Down signal • Frequency speed setting. • HP fuel governor. • Torque control Speed - injection control Functions of the closed-loop engine speed control integrated in the engine governor: • Maintaining the desired engine speed under changing load conditions. • Adjusting the engine speed when the setting is changed by the operator. E532233/00E 06-06 © MTU 16 Functional Description Fuel quantity control during engine start The quantity of fuel injected during engine start increases along a time ramp from a set initial value to a specified value. This ensures that the engine starts reliably. This fuel quantity control is effective until idling speed has been reached. Desired speed handling The desired speed is the command variable for the engine speed control loop. Providing that speed demand is set by Up/Down signals, the engine runs up to an internally programmed nominal speed when started (for 50 Hz network frequency: 1500 rpm, for 60 Hz network frequency: 1800 rpm). The engine runs up to the set value in case of analog speed demand. The starting sequence is completed when idling speed has been reached (“open-loop control” mode) and switching over to “closed-loop control” mode is effected. The following speed setting variants are possible: • Desired speed setting via an analog input: The setpoint speed may be adjusted within a (configurable) range around the preset synchronous speed (depending on the set network frequency) (relative speed control, the voltage/current or frequency controls the speed window only). Absolute speed control is also possible (the voltage/current or frequency can cover the entire speed range). The internal setpoint speed follows the applied speed setting value along a configurable acceleration/deceleration curve (speed ramp). The setting value last applied is maintained or the engine is set to a default speed should the applied signal fail. The response can be configured as desired: • Speed setting via CAN bus. • Speed setting via an analog speed setting input (0 V to 10 V). • Speed setting via an analog speed setting input (4 mA to 20 mA). • Frequency input. • Setpoint processing via binary inputs “Setpoint speed up”/“Setpoint speed down”: The setpoint speed can be adjusted within a (configurable) range around the preset synchronous speed (depending on the set network frequency). Briefly actuating the appropriate optocoupler input for less than 0.3 s increases or decreases the setpoint speed by 1 rpm. The setpoint speed is automatically adjusted at a configurable rate if the input is activated for longer than 0.3 seconds. Speed droop Speed droop calculation Speed droop influences the effective setpoint speed depending on engine power. Maximum, speed-dependent engine power is limited by the MCR curve. The setpoint speed is not influenced by speed droop at 100% power. The effective setpoint speed increases at lower power. This allows power to be balanced when operating a number of engines in a network. Switchable speed droop Two different speed droop settings can be selected at the engine governor. The speed droop is selected by a binary input at the engine governor. Speed droop is required to balance the load of coupled prime movers. Speed droop can be adjusted to meet plant requirements via the dialog unit. Quantity limitations Dynamic quantity limitation Dynamic quantity limits protect the engine against overloading and optimize exhaust emission values. The engine governor determines the maximum injection quantity based on preset and stored engine performance maps. Fuel quantity is limited as a function of speed (DBR). Fixed quantity limitation Fixed quantity limitations are used for power limitation and power reduction to protect the engine from sustained overload sustained overload. E532233/00E 06-06 © MTU Product data sheet Characteristics LDL36400U31X MOLDED CASE CIRCUIT BREAKER 600V 400A Product availability: Stock - Normally stocked in distribution facility 300A Trip Unit Commercial Status Commercialised Product or component type Molded Case Circuit Breaker Range of product PowerPact L [In] rated current 400 A Poles description 3P Breaking capacity 14 kA 600 V AC 18 kA 480 V AC 25 kA 240 V AC [Ue] rated operational voltage 600 V AC [Ics] rated service short-circuit breaking capacity 80 % Trip unit technology Electronic standard Micrologic 3.3 LI Product certifications CCC CSA IEC UL listed Mounting mode Unit mount Breaking capacity code D Electrical connection Lugs load Lugs line AWG gauge 2...500 AWG/kcmil aluminium/copper The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Main Ordering and shipping details Category 01116 - L ELEC TRIP UNIT MOUNT BREAKER/SW Discount Schedule DE2 GTIN 00785901083306 Nbr. of units in pkg. 1 Package weight(Lbs) 17.06 Product availability Stock - Normally stocked in distribution facility Returnability Y Country of origin US Contractual warranty Period May 30, 2013 18 months 1 PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Curves PowerPact L-Frame Electronic Trip Circuit Breakers— 250 A/400 A/600 A Frame Figure 95: Micrologic 3.3 Electronic Trip Unit Long Time Trip Curve MICROLOGIC™ ELECTRONIC TRIP UNITS Micrologic™ 3.3 Long Time Trip Curve 250A, 400A L-Frame The time-current curve information is to be used for application and coordination purposes only. Notes: 1. There is a thermal-imaging effect that can act to shorten the long-time delay. The thermal imaging effect comes into play if a current above the long-time delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately 20 minutes is required between overloads to completely reset thermal-imaging. 2. Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current. Curves apply from -35ºC to +70ºC (-31ºF to +158ºF) ambient temperature. 16 212 01/2013 ™ © 2011–2013 Schneider Electric All Rights Reserved PowerPact™ H-, J-, and L-Frame Circuit Breakers Trip Curves Figure 98: Micrologic 3.3/3.3S/5.3A/5.3E/6.3A/6.3E Electronic Trip Unit Instantaneous Trip Curve MICROLOGIC™ ELECTRONIC TRIP UNITS Micrologic™ 3.3/3.3S/5.3A or E/6.3A or E Instantaneous Trip Curve 400A L-Frame The time-current curve information is to be used for application and coordination purposes only. Notes: 1. There is a thermal-imaging effect that can act to shorten the long-time delay. The thermal imaging effect comes into play if a current above the long-time delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately 20 minutes is required between overloads to completely reset thermal-imaging. 2. Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current. 3. In = Maximum dial setting of Ir. 400A L-Frame: In = 400A = Max Ir setting Curves apply from -35ºC to +70ºC (-31ºF to +158ºF) ambient temperature. 215 © 2011–2013 Schneider Electric All Rights Reserved ™ 01/2013 2 - 2/0 AWG-500kcmil (Al/Cu) AL Lug Wire Size A,L,M,P: 13.39[340.0] Technical Information: UL Listed, CSA, IEC Rated ON=lugs, OFF=lugs 7.64[194.0] Certification: Mounting Type: 10.63[270.0] 2.76[70.0] 5.12[130.0] United States Corporate Headquarters Schneider Electric USA 1415 South Roselle Road Palatine, IL 60067 Customer Care Center : 1-888-778-2733 Web : www.schneider-electric.us LI, LS, LSI, or LSIG 3 100/65/25 kA UL and IEC ratings Standard 80% 4.80[122.0] Electronic Trip Unit Function: Number of Poles: Short Circuit Current Rating: Circuit Breaker Rating: 5.50[139.7] 9.57[243.0] Specification: Powerpact L-frame Circuit Breaker with Micrologic Electronic Trip Unit Provides overload and short circuit protection Industrial Panelboards and Switchboards 0.99[25.2] 2.36[60.0] 1.77[45.0] 10.24[260.0] Description: General Application: For Use With: L-Frame Dimensions Part No.: 22.02° Note: - Drawings Not To Scale - Drawings Subject to Change Without Notice - Dimensions are inches next to [Millimeters] 6.61[167.8] 4.80[122.0] 4.35[110.4] 4.13[105.0] 3.94[100.0] 2.63[66.8] Off ø0.20[5.2] 3.15[80.0] On 44.02° 100 A-H 160 A-H 220 A-H 220 A-H BATTERY CHARGER NRG Intelligent Engine Start Data Sheet The Smart Choice for Mission-Critical Engine Starting: • Fast, accurate, mission-critical charging gives best starting reliability • 4-rate, temperature-compensated output offers longest battery life • Replace nearly any charger without planning ahead • Industry-first battery-fault alarm helps dispatch service early • Lasting reliability — field MTBF > 1 million hours with industry-best warranty • IBC seismic certification meets latest building codes, no installation delays • Optional OSHPD pre-approval BENEFITS AND FEATURES Failure to start due to battery problems is the leading cause of inoperable engine generator sets. The NRG battery charger maximizes starting system reliability while slashing generator set servicing costs: • One NRG replaces almost any charger without extra site visits. Installers can select or change at any time 120, 208, or 240 volts AC input, 12 or 24-volt battery and output settings optimized for nearly any lead-acid or nickel cadmium battery. • Easy to understand user interface provides state-of-the-art system status including digital metering, NFPA 110 alarms, and a battery fault alarm that can send service personnel to the site before failure to start. • Batteries charged by NRG give higher performance and last longer. In uncontrolled environments, precision charging increases battery life and watering intervals 400% or more. • NRG meets all relevant industry standards — including UL, NFPA 110, and CE. Seismic Certification per International Building Code (IBC) 2000, 2003, 2006. All units are C-UL listed. 50/60 Hz units add CE marking to UL agency marks. EnerGenius reliability technology built into every charger includes: • • • • • • • All-electronic operation with generous component de-rating Disconnected/reversed/incorrect voltage battery alarm and protection Protection of connected equipment against load dump transients Widest temperature rating and overtemperature protection Superior lightning and voltage transient protection Demonstrated field MTBF > 1 million hours MTU Onsite Energy standard warranty terms apply // Page 1 of 5 BATTERY CHARGER NRG Intelligent Engine Start Data Sheet SPECIFICATIONS AC Input Voltage Input current Frequency Input protection 110-120/208-240 VAC, ±10%, single phase, field selectable 10A charger: 6.6/3.3 amps maximum 20A charger: 12.6/6.3 amps maximum 60 Hz ±5% standard; 50/60 Hz ±5% optional 1-pole fuse, soft-start, transient suppression Charger Output Nominal voltage rating Battery settings Regulation Current Electronic current limit Charge characteristic Temperature compensation Output protection 12/24 volt, field selectable Six discrete battery voltage programs - Low or high S.G. flooded - Low or high S.G. VRLA - Nickel cadmium 9, 10, 18, 19 or 20 cells ±0.5% (1/2%) line and load regulation 10 or 20 amps nominal 105% rated output typical—no crank disconnect required Constant voltage, current limited, 4-rate automatic equalization Enable or disable anytime, remote sensor optional Current limit, 1-pole fuse, transient suppression Standard Four (4) Rate Charging // Page 2 of 5 BATTERY CHARGER NRG Intelligent Engine Start Data Sheet User Interface, Indication and Alarms Digital meter Automatic meter alternately displays output volts, amps1 Accuracy ±2% volts, ±5% amp Alarms LED and Form C contact(s) per table: AC good Float mode Fast charge Temp comp active AC fail Low battery volts High battery volts Charger fail Battery Fault3 Alarm Code “C” (meets requirements of NFPA 110) LED LED LED LED LED and Form C contact2 LED and Form C contact2 LED and Form C contact2 LED and Form C contact2 LED and Form C contact2 Front panel status display 1. Three-position jumper allows user to select from three display settings: alternating volts / amps (normal), constant volts, or constant amps 2. Contacts rated 2A at 30 VDC resistive 3. Battery fault alarm indicates these fault conditions: - Battery disconnected - Battery polarity reversed - Mismatched charger battery voltage - Open or high resistance charger to battery connection - Open battery cell or excessive internal resistance Controls AC input voltage select 12/24-volt output select Battery program select Meter display select Fast charger enable/disable Temp compensation enable Remote temp comp enable Environmental Operating temperature Over temperature protection Humidity Vibration (10A unit) Transient immunity Seismic Certification Field-selectable switch Field-selectable two-position jumper Field-selectable six-position jumper Field-selectable three-position jumper Field-selectable two-position jumper Standard. Can be disabled or re-enabled in the field Connect optional remote sensor to temp comp port Simple field adjustments -20 °C to 60 °C, meets full specification to 45 °C Gradual current reduction to maintain safe power device temperature 5% to 95%, non-condensing UL 991 Class B (2G sinusoidal) ANSI/IEEE C62.41, Cat. B, EN50082-2 heavy industrial, EN 61000-6-2 IBC 2000, 2003, 2006, 2009; Maximum Sds of 2.28 g; Optional OSHPD pre-approval // Page 3 of 5 BATTERY CHARGER NRG Intelligent Engine Start Data Sheet Agency Standards Safety Agency marking EMC NFPA standards Optional agency compliance c-UL-us Listed to UL 1236 and CSA standard 22.2 no. 107.2. UL file E109740 CE: 50/60 Hz units DOC to EN 60335 60 Hz: c-UL-us Listed 50/60 Hz: c-UL-us Listed plus CE marked Emissions: FCC Part 15, Class B; EN 50081-2 Immunity: EN 61000-6-2 NFPA 70, NFPA 110. (NFPA 110 requires Alarms “C”) OSHPD pre-approval Construction Material Dimensions Printed circuit card Cooling Protection degree Damage prevention Electrical connections Non-corroding aluminum enclosure See Diagrams and Dimensions section of this document Surface mount technology, conformal coated Natural convection Listed housing: NEMA-1 (IP20). Optional IP21 drip shield. Optional NEMA 3R enclosure Fully recessed display and controls Compression terminal blocks Warranty Standard warranty MTU Onsite Energy standard warranty terms apply Optional Features Input Remote temp comp sensor Drip shield meets s/b (IP21) NEMA 3R housing Input frequency, 50/60 Hz Recommended where battery and charger are in different locations Protects from dripping water Enables outdoor installation (remote temp sensor recommended) // Page 4 of 5 BATTERY CHARGER NRG Intelligent Engine Start Data Sheet DIAGRAMS AND DIMENSIONS 20A Chargers NRG Ordering Information Output Volts 12/24 12/24 12/24 12/24 Output Amps 10 20 10 20 Frequency Model 60 Hz 60 Hz 50/60 Hz 50/60 Hz SUA83187 SUA90170 SUA89983 SUA94705 All models offer field-selectable input 120/208-240 volts. Available Configurations Enclosed Enclosed Enclosed Enclosed NFPA 110 Alarms Yes Yes Yes Yes Weight kg (lbs) 10.4 (23) 19.1 (42) 10.4 (23) 19.1 (42) © MTU Onsite Energy. Subject to alteration due to technological advances. 2014-11 10A Chargers MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com // Page 5 of 5 WATER HEATER CB, CL, and WL Series Data Sheet The CB, CL, and WL tank style engine heaters are designed to preheat diesel and gas engines in generator set applications. With easy start-up regardless of ambient temperature, they feature a built-in thermostat and heat engines from 6L to 25L displacement. Thermosiphon circulation of the coolant delivers heat throughout the entire engine for optimum performance. CERTIFICATIONS AND STANDARDS • CB and CL Models: c-UL-us Listed, CSA Certified, and CE Compliant • WL Model: CE Compliant SPECIFICATIONS Height: Length: Width: Weight: Heating Fluid: Power: Rated Voltage: Phase: Enclosure: Fluid Capacity: CL and WL Models CB Models CB Model 132 mm (5.2 in) 510 mm (20.1 in) 129 mm (5.1 in) 3 kg (6.9 lb) CL Model 147 mm (5.8 in) 597 mm (23.5 in) 158 mm (6.2 in) 4.5 kg (10 lb) WL Model 147 mm (5.8 in) 597 mm (23.5 in) 158 mm (6.2 in) 4.5 kg (10 lb) Engine coolant (50% glycol/50% water) 1.5, 2, 2.5, 3, 4, and 5 kW 120V – 575V 1 and 3 IP44 2 L (0.5 gal) 1.2 L (0.3 gal) // Page 1 of 2 WATER HEATER CB, CL, and WL Series Data Sheet SPECIFICATIONS, continued Model Number CB115410-200 CB120210-200 CB120410-200 CB120810-200 CB125210-200 CB125410-200 CB125810-200 CL130410-200 CL140210-200 CL140410-200 CL140810-200 CL150210-200 CL150212-200 CL150412-200 CL150810-200 WL325410-200 WL325810-200 WL340410-200 WL340810-200 WL350410-200 WL350810-200 8.61 bar (125 psi) 1" NPT Male / 1" NPT Female 38 °C (100 °F) 49 °C (120 °F) MTU Onsite Energy Part Number SUA98952 SUA98996 SUA98953 SUA98404 SUA96723 SUA90334 SUA96727 SUA97791 SUA99109 SUA52741 SUA99110 SUA98913 SUA82416 SUA83334 SUA96725 SUA96568 SUA97254 SUA96787 SUA99286 SUA98951 SUA92800 Watts Volts Phase Hz Amps 1,500 2,000 2,000 2,000 2,500 2,500 2,500 3,000 4,000 4,000 4,000 5,000 5000 5000 5,000 2,500 2,500 4,000 4,000 5,000 5,000 480 240 480 208 240 480 208 480 240 480 208 240 240 480 208 480 208 480 208 480 208 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 3.1 8.3 4.2 9.6 10.4 5.2 12 6.3 16.7 8.3 19.2 20.8 20.8 10.4 24 3 6.9 4.8 11.1 6 13.9 © MTU Onsite Energy. Subject to alteration due to technological advances. 2015-05 Max Pressure: Inlet / Outlet: Thermostat Range: On Off MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com // Page 2 of 2 DIESEL FUEL WATER SEPARATOR 500FG Data Sheet MTU Onsite Energy filter assemblies are designed of heavy duty construction and three-stage filtration using 10 or 30 Micron filter element(s). High capacity water separation (99% water removal efficiency) and fuel filtration process protects engine components from dirt, rust, algae, asphaltines, varnishes, and especially water, which is prevalent in engine fuels. These filters are easy to service with clear collection bowl(s) and self-venting water drain(s). Racor Model Number: MTU Onsite Energy Part Number (10 Micron): MTU Onsite Energy Part Number (30 Micron): Generator Set Model Power Range (Standby): Generator Set Model Power Range (Prime): 500FG SUA100603 SUA95404 230 - 300 kWe 210 - 275 kWe Height: Depth: Width: Weight (dry): 29.2 cm (11.5 in) 12.2 cm (4.8 in) 14.7 cm (5.8 in) 1.8 kg (4 lb) Maximum Flow Rate: (one unit online) Port Size: 227 lph (60 gph) ¾ in – 16 UNF (SAE J1926 female threads) Minimum Service Clearance: (above assembly) (below assembly) 12.7 cm (5 in) 5.1 cm (2 in) Clean Pressure Drop: Maximum Pressure: Water In Bowl Capacity (per bowl): Operating Temperature: 1.7 kPa (0.25 psi) 1.03 bar (15 psi) 109 ml (3.7 oz) -40 °C to 124 °C / -40 °F to 255 °F © MTU Onsite Energy. Subject to alteration due to technological advances. 2014-08 SPECIFICATIONS MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com // Page 1 of 1 SUBMITTAL DATA PROJECT: Canada Ave Pump Station CUSTOMER: Cullen Diesel Power VIBRATION ISOLATION AND SEISMIC RESTRAINT SHOP DRAWINGS Submittal Prepared By: Lloyd Silva Sr. Project Coordinator Phone: 604-294-9495 Email: lloyd@vibra-sonic.com Actual Slab Thickness Required (inches) : Minimum Slab Thickness Required (inches) : Input VIBRA-SONIC CONTROL AND MATERIALS HANDLING LTD. 4004 GRAVELEY STREET BURNABY, B.C. V5C 3T6 PHONE : (604) 294-9495 FAX: (604) 294-8033 Email : tony@vibra-sonic.com INFORMATION SUPPLIED BY CUSTOMER JOB NAME : Canada Ave Pump Station CUSTOMER: Cullen Diesel Power PO# : 100299610 DATE: 26-May-16 REF #: CDP-2000 PROJECT LOCATION : Duncan TAG : Emergency Generator Set DIRECT BOLT - Non-Isolated Weight (LBS) 19,744 C of G Height (inches) 50 B1 (inches) 180 Number of support points: Number of anchors / point: B2 (inches) 82 8 1 Area selected from N.B.C. for seismic calculations : Duncan Design Criteria : 'Post Disaster' Location in building : Slab on Grade Actual Slab Thickness Required (inches) : 17 1/2 Minimum Slab Thickness Required (inches) : 7 1/8 Canada Ave Pump Station Direct Bolt Generator R1 Page 1 of 2 Calcs JOB NAME: Canada Ave Pump Station CUSTOMER: Cullen Diesel Power DATE: May 26, 2016 Tag: Weight (W) = Acceleration VSC (A') NBC (A) = Zonal velocity (v) = Importance factor (I) = Ax = Ar = Cp = Sp = Cp . Ar . Ax = Vp = v . Sp . W . (I) = Seismic Force (Fph) x (A'/A) = Length spacing (b1) = Width spacing (b2) = Height to CofG (h) = Mason Isolator Type = Mount Height (H) = Number of support points (N) = Number of anchors / point (n) = Anchor Type = Anchor Diameter = Anchor;embed. = Tr (L.S.D.) = Vr (L.S.D.) = Ixx = Iyy = theta(rad) = Pt (L.S.D.) = Pc (L.S.D.) = Ps (L.S.D.) = Tf (L.S.D.) = Vf (L.S.D.) = Unity = Direct Bolt to structure Emergency Generator Set 19744.00 0.45 0.45 0.3 1.5 1.00 1.00 (Non-isolated) 1.00 1.00 8884.80 8884.80 180.00 82.00 50.00 NONE 0.00 8 1 Hilti HIT HY 200 5/8 5.625 5880 4215 36000.00 13448.00 0.69 716.48 4219.52 1110.60 716.48 Min Slab thickness = 7.125 1110.60 Actual Slab Thickness = 17.5 0.39 CONFIRM SITE CONDITIONS Min Bolt Centres = 10 Actual Bolt Centres = 82 Selection OK IF SYSTEM IS MOUNTED ON HOUSEKEEPING PAD, ANCHOR BOLTS MUST BE AT LEAST 10" FROM ANY EDGE OF SLAB. Stone Aggregate f'c=3000 psi Concrete Hilti HIT HY 200 adhesive Anchors (with Hilti standard ASTM F568, Class 5.8 threaded rods). All forces are to Limit States Design values (L.S.D.) Bolt design to CAN3-S16.1-M94 Canada Ave Pump Station Direct Bolt Generator R1 Page 2 of 2 ASCO Power Techn nologies 6255 Halle Drive Cleveland, OH 441255 T (216) 573 7600 F (216) 573 5953 emersonnetworkpoweer.com/loadbank SUBMITTAL BILL B OF MATERIA M AL D Date: 5/5/16 6 Subject: Ap S pproval Dra awings P Project: CO OWICHAN CANADA C A AVE PUMP P STATION A Avtron Projject: CP160 030002 B 263A Bull Avtron K711 K Radiator Mounte ed, Resistiive Load Bank B B 604 Bull Avtron Automatic A L Load Controller/Shed d (ALS) S SB2203 Avtron K711 K Radiator Mounte ed Load Ba ank Outlin ne S SB1635 Avtron K711 K Remo ote Control Panel Enc closure C C21397 Avtron Control C Pow wer Transfformer(C21 1400=600v) D D36480 Avtron K711 K Load Bank Conttrol Schem matic & Inte erconnect with auto omatic load d controlle er C C21409 Avtron K711 K Radiator Load Bank B Powe er Schemattic & Wiring Diagram m, 600 V Model K711(K711600--46-36-2D4F M F-A,B,F,L) UL/ULc Lis sted Radia ator/Duct Mounted M Lo oad B Bank: G Generator R Rating: 300 0 KW L Load Bank Rating: 24 40 KW at 60 00 Volts AC C, 3 Phase, 60 Hertz, 231 Amps per Phase T Tolerance: -0 to +5% overall Loa ad Tolerancce at rated Voltage. V D Duty Cycle: Rated forr continuouss operation. L Load Steps s:20, 20, 50, 50, 50 and d 50 KW Cooling Air: The load bank is dessigned to uttilize the en C ngine cooling air ratherr than an intternal co ooling fan found fo on co onventional load banks. The load bank is perrmanently mounted m to the front off the engine e generatorr and sized to match th he width and d height of the t engine radiator corre or exxhaust ductt opening. Control Pow C wer: 120 VAC, V 1 Phasse, 60 Hertzz, required for f control circuit c opera ation. An In ntegral 600:120 Voltt AC, 1 Pha ase, 60 Herttz Control Power Transformer iss provided for f 120 Voltt AC co ontrol circuit operation. Transform mer primary and secondary circuitss are fuse protected. p Operator Co O ontrols: Re emote Control Panel housed in a NEMA-4 wall w mount enclosure including: M Main Power ON/OFF Switch, Powe er ON Indiccator, Over--Temperatu ure indicatorr, and Master Load O ON/OFF Sw witch. Load selection iss provided by b individua al industrial lever-type toggle t switcches for on/off applica ation of res sistive load segments, s o provide one ed for each load step. Auto Load Dump A D Circ cuit: A remo ote load dump circuit iss provided as part of th he load ban nk co ontrol circuit. Provision ns are provided to trip the t load bank off-line from f a norm mally closed d set of ASCO Power Techn nologies 6255 Halle Drive Cleveland, OH 441255 T (216) 573 7600 F (216) 573 5953 emersonnetworkpoweer.com/loadbank auxiliary con ntacts from an a automattic transfer switch s or otther device.. In the eve ent of a utilitty failure, all load is rem moved. Automatic Load A L Contrroller:An Automatic A L Load step controller c is provided for maintain ning a m minimum loa ad on the ge enerator se et. The contrroller monitors the con nnected dow wnstream lo oads and w automatiically add or subtract lo will oad steps in n response to building load chang ges as to ma aintain a m minimum loa ad level on the t generattor set. The e controller includes i an n initial time--delay circu uit, and automatic tim me delayed load step application a c circuit. A customer su upplied conttact closure is equired for activation a and a transferr of control. A separate e current tra ansformer is supplied loose l for re m mounting an nd sensing of o downstre eam loads. (not ( currenttly available e in dual volltage units) T Load Eleme L ents: Avtro on HelidyneTM Resistorr Load Elem ments, fully supported s a across theirr entire le ength within n the air stre eam on stainless steel support rod ds, with seg gmented ce eramic insulators. N cool dow No wn period required! Safety Featu S ures: Branc ch circuit fu uses provide e fault prote ection on alll 3 phases of o switched load stteps 50 KW W and above e. Fuses are e fast acting g current lim miting type with w an inte errupting ratting of 200K A.I.C. An over-temperature switch is prrovided to sense s load bank b exhau ust temperature and iss electricallyy interlocked d with the lo oad applica ation controlls to preven nt load from m being appllied if an exxhaust over-temperatu ure conditio on is detecte ed. Operato or warning and caution n statementts are lo ocated on appropriate access a pan nels. Constructio C on: The loa ad bank is open o frame constructio on designed d for installa ation and operationind doors. The e heavy gau uge formed aluminized d steel fram me provides a rigid encclosure to o match the e width and height of th he engine radiator r corre or exhaust duct ope ening. It is designed to utilize all of the radiator air to coo ol the load elements. Load Conne L ections: Customer C loa ad connections are loccated in an enclosed re elay/control section th hat is integrral to one side of the lo oad bank. Copper C bus bars with standard s NE EMA 4-hole pattern or a single 3-phase pow wer distributtion block iss provided for f custome er load conn nections. Bolt on access pane els are prov vided to safe ely enclose all electrica al connectio ons and wiring. Mounting Features: Overhead M O liffting eye ho oles and rem movable duct flange ad dapters are provided on the standarrd K711 frame (not pro ovided on K711A). K The e duct adap pters or the 2” op/bottom mounting m fla anges can be b utilized fo or mounting g. to D Dimensions s: K K711 Frame e: W Width = 56” (Radiator Core C width 36” 3 + 20”) H Height = 50”” (Radiator Core C heightt 46” + 4’) D Depth= 13” Avtron K711/K711A/K711L Resistive Load Bank - 5 to 1250 KW Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most. Key Features •Economical - Uses Engine Air for Cooling •Reduces “Wet-Stacking” Problems •Provides Load for Routine Generator Testing •Corrosion Resistant Aluminized Steel Frame •Includes Lifting Eyes and Duct Flange for Easy Installation Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service. Avtron’s extensive line of Load Bank and Industrial Resis­tor Products are solid performers used throughout the world. The Avtron Model K711 Load Bank are intended for use as a supplemental load for lightly loaded engine gen sets. The Avtron K711/K711A/K711L load banks are designed for duct or radiator mounting and are available in a variety of frame dimensions. The load banks are permanently mounted to the front of the engine generator and sized to match the radiator or exhaust duct opening. The K711 load banks utilize the engine cooling air rather than an internal cooling fan found on conventional load banks. The primary cause of premature diesel engine failure is “wet-stack­ing” which is literally “wet” unburned fuel accumulating in the engine exhaust (“stack”), due to under-loading of the generator. Diesel engines that are lightly loaded or allowed to idle for long periods never reach their recommended full operating temperature. Over time, this unburned fuel coats the combustion chamber and pistons with a thick coating of tar and carbon build-up, reducing efficiency and life span of the engine considerably. A supplemental radiator load bank helps to “burn-off” these harmful carbon deposits, greatly increasing engine life. These units are offered in 208, 240, 480 or 600 volt versions (at 60 Hz) or 380, 400 or 416 volt versions (at 50 Hz). Load rating varies and ranges between 5 and 1250 KW. Most engine manufacturers recommend sizing the radiator load bank to 40-60% of engine nameplate rating to eliminate “wet-stacking” problems. The K711 load bank is controlled from a built-in control panel which contains the individual load-step toggle switches. The control panel is also available sized for standard 19" [482.6] rack mounting when remote installation of the panel is desired. The K711 family is intended for use as a supplemental load for lightly loaded engine generator sets. The load bank utilizes the engine cooling air to cool the resistive load elements. For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com. Quality System Certified to ISO 9001 K711 500 KW Resistive Radiator Mount Avtron Load Bank. Avtron K711 Resistive Load Bank - 5 to 1250 KW Specifications subject to change without notice. Construction Formed aluminized steel frame provides a rigid enclosure to match the height and width of the engine radiator or duct. Lifting eyes and a radiator duct flange are included to simplify installation. The standard K711 depth is 13" [330.2]. For applications where the amount of load element KW required exceeds the available 13" depth, then a “double-deep” K711A can be used instead, with a 26" [660.4] depth. Designed for NEMA-1 indoor installation, the K711/K711A is also available in NEMA3R outdoor construction as an option. The K711L frame can be used for special mounting of 1250 KW load banks to high capacity 2000/2500 KW generator sets. Options 4.00 [101.60] •Control Power Transformer •Outdoor Construction with Bolt-on Louver Assembly RECOMMENDED CONDUIT ENTRY AREA NOTE Designs for international 50/60 Hz voltages are also available. Consult factory. SEE DETAIL "B" (above) CONTROL PANEL (ALTERNATE LOCATION) 30° BOLT-ON DUCT ADAPTER * CONTROL PANEL (STANDARD LOCATION) OUTDOOR LOUVER (OPTIONAL) A W= (RADIATOR CORE WIDTH) H + 4.00 [101.60] H_ _ _ DIRECTION OF ELEMENTS C SEE DETAIL "A" (above) 13.00 [330.20] POWER POWER DISTRIBUTION BLOCK DISTRIBUTION BLOCK SUPPORT BRACKET K711L B H= (RADIATOR CORE HEIGHT) BUS BAR CONNECTIONS 26.00 [660.40] 6.00 [152.40] 2.00 TYP [50.80] W_ _ _ REF CONTROL POWER CONNECTIONS K711 K711A W + 20.00 [508.00] 2.00 [50.80] * NOTE: IF DUCT ADAPTER IS USED, MOUNT USING LEFT & RIGHT FLANGES ONLY. OTHERWISE USE TOP AND BOTTOM FLANGES OF THE LOAD BANK. 7.50 [190.50] DETAIL "A"- K711L W + 24.00 [609.60] W_ _ _ 2.00 REF [50.80] W_ _ _ 5.50 [139.70] 0.62 [15.75] 0.563 DIA [14.30] 8 HOLES 2.00 [50.80] LOAD CONNECTION BUS BAR 1.75 [44.45] H + 4.00 [101.60] H= (RADIATOR CORE HEIGHT) H_ _ _ W= (RADIATOR CORE WIDTH) (SCALE 2:1) 5.50 [139.70] A C Resistor Elements B 13.00 [330.20] C 42.00 [1066.80] RADIATOR (CUSTOMER SUPPLIED) AIRFLOW 2.00 REF [50.80] Emerson Network Power Avtron • 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A. 216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com EmersonNetworkPower.com/loadbank DUCT ADAPTER FLANGE REF AIRFLOW •Remote I/O for Interface with Switch Gear CONTROL PANEL The fully supported Avtron Helidyne™ resistive load elements are made of corrosion resistant chromium alloy wire and are engineered to operate at conservative temperature ratings. This provides more stable loading, extends resistance element operating life, and eliminates the need for a cool down period after load bank operation. DETAIL "B" OUTDOOR LOUVER REF •Remote Control Panel with Enclosure Cooling The local control panel contains a POWER ON -OFF switch, a MASTER LOAD ON-OFF switch, and individual load step toggle switches for application of individual load sections. A MANUAL/ AUTO switch is also provided (if the optional automatic load step controller is included). A remote rack-mounted control panel with wallmounted enclosure is available as an option. 1.00 [25.40] 1.00 [25.40] 0.500 DIA [12.70] 4 HOLES DETAIL "A" •ADMS™ Digital Metering System, Remote Mounted The K711/K711A/K711L requires exter­nal control power of 120 VAC, single phase, 50/60 Hz. A control power transformer is available as an option for sites where 120 VAC is not readily available. Controls 1.75 [44.45] •Automatic Load Step Controller Control Power The K711/K711A/K711L does not have its own cooling system. Instead, it relies on cooling air from the engine driven radiator fan or separately powered duct blowers. A built-in thermal switch drops all load if an overtemperature condition is detected. LIFTING HOLES 1.00 DIA [25.40] TYP 4 PLACES 3.75 [95.25] 5.00 [127.00] LOAD CONNECTION BUS BARS 12.13 [308.10] 4.00 [101.60] SEE DETAIL "A"- K711L All dimensions are in inches [millimeters]. Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. All the other marks are the property of their respective owners. ADMS™ and Helidyne™ are trademarks of Avtron. Specifications subject to change without notice. ©2015 Emerson Network Power Bulletin 263A• Rev. J Avtron Automatic Load Controller Automatic Load Shed Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most. The Avtron Automatic Load Controller (or Load Shed) is a standard option for radiator mounted or outdoor free standing style load banks. Key Features The Automatic Load Controller (Load Shed) is designed to add or remove load steps to maintain an approximate target load level on the generator to which the load bank is connected. •Automatically keeps a Minimum Load on Generator Set The Automatic Load Controller (Load Shed) is intended for use with standby or emergency backup power systems. The controller is employed during a utility service power outage when the standby generator is supplying power to the building load. •Used with Radiator and Freestanding Load Banks •Monitors Building Current The purpose of the Automatic Load Controller (Load Shed) is to maintain optimum loading of the generator and to prevent “wet stacking” on the generator which might occur when the building load alone is low in comparison to generator capacity. •Loose Current Transformer Provided •Factory Set Operating Points •Extended Time Versions also available Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service. Avtron’s extensive line of Load Bank and Industrial Resis­tor Products are solid performers used throughout the world. For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com. Quality System Certified to ISO 9001 Avtron Automatic Load Controller (Load Shed) toggle switch. Typical Automatic Load Controller (Load Shed) response graph. Avtron Automatic Load Controller Automatic Load Shed Specifications subject to change without notice. Operation When Automatic Load Controller (Load Shed) controls are initiated in the Automatic Mode, the controller will start the load bank by turning on the blower (free standing outdoor load banks only). After a time delay (typically two to five seconds), the controller begins adding load steps, with a time delay between the addition of each step. The load steps are added in sequence, usually from smallest to largest and removed in reverse sequence; first on/last off, last on/first off. The building load is continually monitored by means of a current transformer placed between the load bank and the building load. Correct placement of the current transformer is critical to proper operation of the automatic load controller (load shed). The current transformer does NOT monitor the load bank itself, and so does not monitor the total load on the generator. Only the building load is monitored, downstream from the generator and load bank. With current transformer input from actual building load, the controller adds or sheds load steps to supplement the building load and maintain optimum loading on the generator. The current transformer provides input to a series of current sensing relays. There is one adjustable current sensing relay for each load step. These settings are set at the factory and are based on generator KW capacity. Generator Size: The size of the generator is the single most important and essential piece of information needed when specifying an Automatic Load Controller (Load Shed). Generator size must be known to select the current transformer and determine load shed steps. As noted above, the generator can be overloaded if the load shed steps and current sensor settings are not appropriate for the generator. The current sensors enable a load step if the building load is less than the relay set point. The load step is disabled if the building load equals or exceeds the relay set point. The Automatic Load Controller (Load Shed) load steps are determined by the load steps available in the load bank. Load step resolution with the controller is different from the load step resolution on the load bank. The controller window is determined by the largest step in the controller. The window is the difference between the target maximum load at which load steps are shed, and the minimum load on the generator after the controller has dropped its largest step. Components The Avtron Automatic Load Controller (Load Shed) consists of a current transformer, an Avtron designed circuit board and a mode selector switch. The mode selector switch is added to the load bank control panel and is used to select load bank operation in either Manual or Automatic modes. MANUAL MODE: In the manual mode the automatic load controller (load shed) is disabled and the load bank can be used manually to test and exercise the generator. AUTOMATIC MODE: In the automatic mode, the load bank will sit idle until an external normally open contact closes initiate load controller (load shed) operations. Settings The provided current transformer is sized to handle the generators maximum current at 0.8 power factor. Current sense relays are set individually for each load step. The first current sensor is set for the target maximum load (typically 80%) minus the first load shed step, usually the smallest. The next current sensor and succeeding sensors are set for the previous level minus the next load shed step. Avtron Automatic Load Controller (Load Shed). Consideration must also be given for the load bank controls and fan motor(s) which may draw additional power from the generator. The potential exists that these additional current draws could overload the generator if not compensated for. Emerson Network Power Avtron • 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A. 216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com EmersonNetworkPower.com/loadbank Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. All the other marks are the property of their respective owners. Specifications subject to change without notice. ©2015 Emerson Network Power Bulletin 604• Rev. B ASCO Power Technologies 6255 Halle Drive Cleveland, OH 44125 T (216) 573 7600 F (216) 573 5953 www.avtronloadbank.com Limited Warranty This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business. General: Avtron Loadbank branded products and systems by ASCO Power Technologies, L.P., are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following One Year Limited Warranty against defects in material and workmanship. Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty. ONE YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP Terms of Warranty: The foregoing Limited Warranty is conditioned upon User’s compliance with the following: 1. The Avtron Product is deployed in accordance with Avtron specifications and state and local codes and standards, including installation by an electrician licensed in the state where used if required. 2. The Avtron Product is maintained in accordance with Avtron instructions and used under normal conditions for the purposes intended by Avtron. As provided herein, the Avtron product is warranted to be free of defects in material and workmanship for a period of one year from date of first use by the User, or fifteen months from the date of shipment, whichever expires first. The product shipment date will be determined only from the ASCO bill of lading. If any part or portion of the Avtron product fails to conform to the Warranty within the Warranty period, ASCO, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part. This is a parts Warranty ONLY that does not include services; all services shall be provided by a qualified service provider. Warranty Extends to First Purchaser for Use, Non-transferable: This Warranty is extended to the first person, firm, association or corporation for whom the Avtron product specified herein is originally deployed for use (the "User") in the fifty United States or Canada. This Warranty is not transferable or assignable without the prior written permission of ASCO. Assignment of Warranties: ASCO assigns to User any warranties which are made by manufacturers and suppliers of components of, or accessories to, the Avtron product and which are assignable, but ASCO makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components or accessories. Drawings, Descriptions: ASCO warrants for the period and on the terms of the Warranty set forth herein that the Avtron product will conform to the descriptions contained in the certified drawings, if any, applicable thereto, to ASCO's final invoices, and to applicable Avtron product brochures and manuals current as of the date of product shipment (“Descriptions”). ASCO does not control the use of any Avtron product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. Warranty Claims Procedure: Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact Avtron product service department at www.avtronloadbank.com and select the support tab or by phone at (216) 573-7600 and request a return authorization number for products to be returned. Subject to the limitations specified herein, ASCO will repair or replace, at its option, without charge for materials, subsequent to its inspection the defective product shipped to ASCO with a return authorization number. Avtron products shipped to ASCO without a return authorization number may be refused and returned freight collect to User at User's expense. Avtron products shipped by User to ASCO which have incurred freight damage due to User's improper packaging of the product will not be covered by this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned freight collect to User. Form 297-LB Rev. 01/2014 ASCO Power Technologies 6255 Halle Drive Cleveland, OH 44125 T (216) 573 7600 F (216) 573 5953 www.avtronloadbank.com If replacement parts, components or products are shipped or caused to be shipped by ASCO prior to inspection of the product claimed to be defective, the replacement parts, components or products shall be invoiced in the full current price amount and shipped freight collect F.O.B. ASCO’s facility. If ASCO’s inspection determines that the returned item(s) is covered by this warranty, User will be issued a credit in an amount equal to the parts prices previously invoiced. Warranty coverage will be provided only after ASCO’s inspection discloses the claimed defect and shows no signs of treatment or use which would void the coverage of this Warranty. All defective products and component parts replaced under this warranty become the property of ASCO. Warranty Performance of Component Manufacturers: It is ASCO’s practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects in the product components. Accordingly, ASCO may utilize third parties in the performance of Warranty work, including repair or replacement hereunder, where, in ASCO's opinion, such work can be performed in less time, with less expense, or in closer proximity to the Avtron product. Items Not Covered By Warranty: THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, negligence, inappropriate on site operating conditions, repair by non-Avtron designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, water, or other corrosive liquids or gases, Acts of God, theft, installation and/or deployment contrary to ASCO's recommendations or specifications, or in any event if the Avtron serial number has been altered, defaced, or removed. THIS WARRANTY DOES NOT COVER shipping costs, installation costs, or maintenance or service items and further, except as may be provided herein, does NOT include labor costs or transportation charges arising from the replacement of the Avtron product or any part thereof or charges to remove or reinstall same at any premises of User. REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD. THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN THE CONTROL AREA OR ANY REACTOR CONNECTED OR SAFETY APPLICATIONS OR WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR FOR INTEGRATION INTO MEDICAL DEVICES. Limitations: THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE AVTRON PRODUCT AS SET FORTH HEREIN. IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, AVTRON’S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE. IN NO EVENT SHALL ASCO ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL OR EXEMPLARY DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR OTHERWISE. Miscellaneous: NO SALESPERSON, EMPLOYEE OR AGENT OF ASCO IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. Warranty terms may be modified, if at all, only in writing signed by an ASCO officer. ASCO obligations under this Warranty are conditioned upon ASCO timely receipt of full payment of the product purchase price and any other amounts due. ASCO reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others. In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and provisions shall continue in full force and effect. This Warranty shall be governed by, and construed under, the laws of the State of New Jersey, without reference to the conflict of laws principles thereof. This Warranty represents the entire agreement between ASCO and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this subject. Form 297-LB Rev. 01/2014 STANDBY LIMITED WARRANTY Two (2) Year / 3,000 Hour Basic LIMITED WARRANTY Your MTU Onsite Energy product has been manufactured and inspected with care by experienced craftspeople. If you are the original consumer, MTU Onsite Energy warrants, for the limited warranty period indicated below, each product will be free from defects in materials and workmanship, and will perform under normal use and service from valid start-up performed by MTU Onsite Energy. This Limited Warranty shall apply only when the product has been properly installed, serviced, and operated in accordance with the applicable MTU Onsite Energy instruction manuals. If this Limited Warranty applies, the liability of MTU Onsite Energy shall be limited to the replacement, repair, or appropriate adjustment of the product, at MTU Onsite Energy’s option. This Limited Warranty does not apply to malfunctions caused by normal wear and tear, or by damage, unreasonable use, misuse, repair, or service by unauthorized persons. LIMITED WARRANTY PERIOD Engine Generator Set: Parts and labor for twenty-four (24) months will begin with the first commissioning of the product(s). In all cases, the warranty period will expire not later than thirty-six (36) months from the date of shipment ex-works MTU Onsite Energy or after 3,000 operation hours, whichever occurs first. Accessories: Parts and labor for one (1) year from date of shipment. For a description of accessories and items excluded from this Limited Warranty, review the listings below. LIMITED WARRANTY CONDITIONS Before there is any protection under this Limited Warranty, the distributor must: (1) complete the MTU Onsite Energy Warranty and the Start-Up Validation and Pre-Inspection form, and return them to MTU Onsite Energy within 60 days of the start-up date, and (2) complete the engine registration form and return it to the manufacturer as stated in the instructions with engine registration form (when applicable). In addition, this Limited Warranty is not valid or enforceable unless: (1) all supporting maintenance records are kept on file with the end user and made available upon request from factory, (2) the generator set is routinely exercised in accordance with operating instructions, and (3) the installation meets the general guidelines, standards, recommendations (as laid out in the Installation Guide provided with the product), and all local standards and codes applicable in the location of installation. Engine generator sets that are stored by Owner / Buyer longer than 180 days from date of shipment are subject to special requirements. Contact MTU Onsite Energy’s Service Center for instructions. TO OBTAIN WARRANTY SERVICE Warranty service may only be performed by MTU Onsite Energy authorized service providers. Service provided by unauthorized persons will void this Limited Warranty. Non-MTU Onsite Energy replacement part(s) will void this Limited Warranty. Contact your nearest MTU Onsite Energy Service Representative to obtain warranty service. For assistance in locating your nearest authorized service representative, see contact information at the bottom of this page. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED. NO WARRANTIES SHALL BE IMPLIED OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE, INCLUDING BUT NOT LIMITED TO A WARRANTY OF MERCHANTABILITY OR A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. MTU ONSITE ENERGY SHALL NOT BE LIABLE FOR ANY CLAIM GREATER IN AMOUNT THAN THE PURCHASE PRICE OF THE PRODUCT AT ISSUE, AND IN NO EVENT SHALL MTU ONSITE ENERGY BE LIABLE OE-M-GEN-S-006 2014-01 // Page 1 of 3 STANDBY LIMITED WARRANTY Two (2) Year / 3,000 Hour Basic FOR ANY SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES. STATE LAWS REGARDING THE RIGHTS OF CONSUMERS MAY VARY FROM STATE TO STATE. 1. The following items are not considered nor will they be covered under this Limited Warranty. If there are questions as to coverage under this Limited Warranty, it is advisable to contact the factory in advance of filing a claim. a. Battery or batteries of any type or kind. The battery manufacturer’s warranty, if any, is the only warranty that applies to batteries. Any warranty claim should be handled with the manufacturer according to its policies. b. Adjustments to fuel systems or governor system at time of start-up or any time after. A warranty claim for such adjustments is acceptable only when a defective part has been replaced, returned to the factory, and approved as defective. c. Normal maintenance costs, including but not limited to adjustments, loose and/or leaking fittings or clamps, and tune-ups performed during start-up or anytime thereafter. d. Due to shipping, manufacturer is not responsible for loose connections. All connections must be checked at time of start-up. e. Non-MTU Onsite Energy replacement part(s) will void this Limited Warranty. f. Products that are modified in any form without the written consent of MTU Onsite Energy will void this Limited Warranty. g. Shipping damage of any type. h. Any installation errors or damage of the equipment when shipped as ordered. i. Any overtime travel or labor to make repairs under warranty. j. Any special access fees required to gain access to MTU Onsite Energy equipment, including but not limited to any training or safety policy requirements to gain access. k. Additional costs associated with inaccessible installations, including but not limited to removal and reinstallation of the generator set. l. Rental equipment used during warranty work including but not limited to generators, rigging equipment such as a crane or boom truck, load banks, and special test equipment above factory requirements. m. Excess mileage charges. Any authorized service provider may perform warranty service anywhere, but will only be paid for mileage expenses from the nearest service center and limited to 400 miles / 644 Kilometers round-trip. n. Any equipment not factory approved and engineered for use on MTU Onsite Energy products. This includes but is not limited to aftermarket items such as special fuel systems, enclosures, exhaust systems, or switch gear that had been sought out and quoted by a third party to be included in billing of the MTU Onsite Energy equipment. o. Misuse or abuse during installation and thereafter. p. Normal wear and tear, maintenance, and consumable items that are not required as part of a warranty repair. Consumable items include but are not limited to belts, hoses, coolant, oil, filters, and fuses. q. Acts of nature or acts of God such as lightning, wind, flood, tornado, hurricane, or earthquake. r. Any damage due to situations beyond the control of the manufacturing of the product or workmanship of the product. s. Installation or operation outside the guidelines as stated in the Installation Guide and Owner’s Manual. t. Diesel engine “Wet Stacking” due to lightly loaded diesel engines. u. Misapplication of the equipment such as usage outside the original design parameters as stated on the nameplate of the equipment. v. Travel expense on portable equipment. w. Trailer lights, wiring, and brakes. OE-M-GEN-S-006 2014-01 // Page 2 of 3 STANDBY LIMITED WARRANTY Two (2) Year / 3,000 Hour Basic More than one trip to the job site because a service vehicle was not stocked with normal service parts. Lodging expense of person(s) performing service, unless approved in advance by factory. Engine fluids. Units purchased at the standby power rating that are being used in a prime power application. Any repair labor time that is determined to be excessive, e.g., two or more people performing a oneperson job. ac. Any expenses associated with investigating performance complaints in which no defect is found. ad. Any associated costs for replacing components that are found not to be defective. ae. Any adjustments covered in the start-up and inspection forms that are to be completed during start-up. 2. The accessories that are limited to one (1) year parts and labor from date of shipment include but are not limited to: a. Cords, receptacles, and cord reels b. Gas flex pipes c. Housing lights, space heaters, and associated equipment © MTU Onsite Energy. Subject to alteration due to technological advances. x. y. z. aa. ab. 100 Power Drive / Mankato, MN 56001 / 800-325-5450 MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com OE-M-GEN-S-006 2014-01 // Page 3 of 3