E0.0 - ELECTRICAL LEGEND

advertisement
GROUND
HVAC CONTRACTOR
JUNCTION BOX
MOUNTING HEIGHT - TO CENTERLINE OF ITEM
MTD
MTG
NC
NIC
MOUNTED
MOUNTING
NORMALLY CLOSED
NOT IN CONTRACT
NO
PC
PH
NORMALLY OPEN
PLUMBING CONTACTOR
PHASE
R
RD
TC
TYP
DEVICE TO BE REMOVED AND RELOCATED TO ANOTHER AREA
DEVICE RELOCATED FROM ANOTHER AREA
TECHNOLOGY CONTRACTOR
TYPICAL
UNO
V
W
WG
UNLESS OTHERWISE NOTED
VOLTAGE
WIRE
WIRE GUARD SIZED SPECIFICALLY FOR DEVICE IT IS SERVING
WP
WEATHERPROOF
PLAN NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH
NOTE IS SHOWN.
WIRE & CONDUIT CONCEALED IN WALL OR ABOVE CEILING
WIRE & CONDUIT IN OR BELOW FLOOR SLAB OR BELOW GRADE
ELECTRICAL CONNECTION REQUIRED
E
J
CIRCUIT HOMERUN, PANEL BOARD AND CIRCUIT NUMBER
INDICATED.
DASHED SYMBOL INDICATES THAT PARTICULAR OUTLET OR
DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS
WHERE REQUIRED. UNLESS OTHERWISE NOTED, LINE TYPE
TYPICAL FOR ALL DEVICES TO REMAIN.
EXISTING OUTLET OR DEVICE TO REMAIN, MAINTAIN EXISTING
CIRCUITRY. UNLESS OTHERWISE NOTED, LINE TYPE TYPICAL
FOR ALL DEVICES TO REMAIN.
JUNCTION BOX
HEAVY DUTY DISCONNECT SWITCH
ELECTRIC MOTOR
CIRCUIT BREAKER PANEL (FLUSH MOUNTED)
CIRCUIT BREAKER PANEL (SURFACE MOUNTED)
MISCELLANEOUS PANEL (FLUSH MOUNTED)
MISCELLANEOUS PANEL (SURFACE MOUNTED)
FIRE ALARM AUDIO & ADA VISUAL LIGHT (80" MH)
FIRE ALARM ADA VISUAL SIGNALING LIGHT (80" MH)
F
L
CEILING MOUNTED SMOKE DETECTOR
P - PRE ACTION (ALTERNATE PHOTO ELECTRIC/ FLAME
DETECTION TYPE.
DUCT MOUNTED SMOKE DETECTOR
DUCT MOUNTED DETECTOR REMOTE TEST STATION AND
ALARM INDICATOR LIGHT, WALL MOUNTED AT (80" MH)
UNLESS NOTED OTHERWISE
FIRE ALARM CONTROLLED PROGRAMMABLE RELAY
S
S
SR
R
V
W
F
D
4B
VALVE TAMPER SWITCH
WATER FLOW SWITCH
FIRE ALARM SIGNAL PULL-STATION STATION (46" MH)
3
SECTION A-A
A
1. FLOOR OR WALL ASSEMBLY MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF)
CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS
32 IN.
2. METALLIC SLEEVE (OPTIONAL) NOM 32 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST OR
GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.
3. THROUGH-PENETRANT ONE METALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND PERIPHERY OF
OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT
CONTACT. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED:
A. STEEL PIPE NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER PIPE NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
D. COPPER TUBING NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. CONDUIT NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.
F. CONDUIT NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).
4. FIRESTOP SYSTEM THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED
INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR
FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID OR CAVITY MATERIAL* -- SEALANT MIN 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE
ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS
CONTACT LOCATIONS BETWEEN PIPE AND CONCRETE, A MIN 1/4 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED
AT THE CONCRETE/PIPE INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF WALL. HILTI
CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT*BEARING THE UL CLASSIFICATION MARKING.
GENERAL NOTES
R2
120/277 KIRLIN #RR00817-58
HE WILLIAMS
#SPGS-222-24T5HO-A-EB2-UNV
11
LED 3000K
R
?
1
SHALLOW VOLUMETRIC 2X2 FIXTURE
2
-
-
24
T5 3500K
R
COLUMBIA, CORELITE, MARK,
MERCURY
1
8" RECESSED PREMIER HALOGEN EXAM LIGHT
WITH STEP-DOWN TRANSFORMER
-
1
- 250
T4Q
R
1
R3
120/277 INDY #L6-15-3500K-U-G2-L600P-C-S
6" LED CAN, OPEN REFLECTOR, CLEAR WITH
SATIN FINISH.
-
-
-
-
1500 LUMEN
LED
R
LIGHTOLIER, COOPER, LITHONIA,
PRESCOLITE
R4
HE WILLIAMS #SPGS-222-24T5HO-A120/277 EB2-UNV WITH KENALL LVC (EQUAL BY
HILLROM)
SHALLOW VOLUMETRIC 2X2 FIXTURE WITH
MOMENTARY STEP RELAY.
2
-
-
24
T5 4100K
R
COLUMBIA, CORELITE, MARK,
MERCURY
HEALTHCARE LIGHTING
#HUC5-23-MVOLT-LED35
LED 2' UNDER COUNTER LIGHT
-
-
-
12
LED
S
KENALL, ALKCO, FAILSAFE
1
UC2 120/277
9461 Kenwood Road
Cincinnati, Ohio 45242
Tel. (513) 861-3200
Fax (513) 861-0403
www.pfbarchitects.com
1
1,2
R5
120/277
FORUM #SRT-44-FF-65LED35WOL-4-UNV-WH-F
4' 4" WIDE LED WITH LENS
-
-
-
45
LED 2700
LUMEN
R
NEORAY, TIMO, PAL
1
X1
120/277
HE WILLIAMS
#EXIT/CA-SF-R-WF-WHT-AC
EXIT LIGHT
-
-
-
-
LED
W
SURE-LITES, DUAL-LITE, LITHONIA,
CHLORIDE
1
NOTES:
1.- PROVIDE GLR FUSES FOR ALL FIXTURES ON EMERGENCY POWER.
2.- PROVIDE STEP RELAY AND SEE DETAIL FOR MORE INFO.
3.- INSTALL MOUNTING CLIPS PER MANUFACTURER'S RECOMMENDATIONS. CONNECT WITH #12 WIRE. PROVIDE FLEXIBLE CONDUIT TO LOWER BACK OF COVE WITH BUSHED END. MOUNT TRANSFORMER
ABOVE CEILING.
E.- REFER TO ARCHITECTURAL ELEVATIONS FOR DEVICE LOCATIONS AND MOUNTING
HEIGHTS WHEN LOCATED AT OR ABOVE CASEWORK. COORDINATE EXACT DEVICE
LOCATIONS PRIOR TO ROUGH-IN AND INSTALLATION.
VOLTAGE
STARTER
DISCONNECT MEANS
BID/PERMIT
SET
CONTROL
EQUIPMENT
HP OR
KW
NOTES
AC-1
14.4KW
+ 1/5HP
2
1 EC
1 SET OF (3) #10 & 1 #10 GND.
IN 3/4" CONDUIT.
AC-2
14.4KW
+ 1/5HP
2
1 EC
1 SET OF (3) #10 & 1 #10 GND.
IN 3/4" CONDUIT.
FEEDER SIZE
F.- ALL EQUIPMENT LOCATIONS ARE APPROXIMATE CONTRACTOR SHALL FIELD VERIFY ALL
REMOVALS AND COORDINATE ALL WORK WITH OWNER PRIOR TO WORK.
G.- HFC CABLE SHALL BE PERMITTED ONLY IN EXISTING BUILDING WHERE NEW
RECEPTACLES ARE TO BE INSTALL IN EXISTING DRYWALL AND STUD WALLS. ALL DEVICES
SHOWN ON SUCH WALLS SHALL BE FLUSH MOUNTED.
FW project number
9210010
H.- EC SHALL BE RESPONSIBLE FOR ROUGH IN OF ALL TECHNOLOGY DEVICES SHOWN ON
THE POWER AND SYSTEM PLANS.
NOTES:
1.- PROVIDE A 30A-3P NF DISCONNECT SWITCH WITH UNIT AND 120V TOGGLE
SWITCH DISCONNECT.
2.- UNIT HAS A 120V CONNECTION FOR THE MOTOR AND 480V, 3Ø,
CONNECTION FOR THE HEATER. HEATER WIRE SIZE IS SHOWN ONLY.
I.- PROVIDE J-HOOKS FOR ALL COMMUNICATIONS CABLING AND HOSPITAL LOW VOLTAGE
SYSTEMS. J-HOOKS ARE TO BE SPACED NO FURTHER THAN 5' APART. CABLES SHALL BE
BUNDLED TOGETHER.
J.- E.C. SHALL DISCONNECT ALL POWER TO EQUIPMENT OF OTHER TRADES DESIGNATED
FOR DEMOLITION OR RELOCATION. COORDINATE ALL WORK REQUIRED WITH
CONTRACTORS OF OTHER TRADES. IN SUCH CASES WHERE THE EQUIPMENT IS BEING
REMOVED, E.C. SHALL REMOVE ALL ASSOCIATED WIRING, CONDUIT, AND BOXES BACK TO
SOURCE. TURN OVER ALL REMOVED ELECTRICAL EQUIPMENT TO OWNER.
CEILING MOUNTED NURSE CALL DOME LIGHT
CEILING MOUNTED NURSE CALL ZONE LIGHT
NURSE CALL STAFF STATION (46" MH)
EMERGENCY NURSE CALL STATION WITH PULL CORD FOR
PATIENT USE (33" MH IN TOILET ROOMS, 90" MH IN SHOWERS
AND WET AREAS, 46" MH IN ALL OTHER AREAS)
POWER SUPPLY FOR ELECTRIC LATCH. SEE NOTATION FOR
CIRCUITING.
POWER SUPPLY FOR PLUMBING SENSOR. COORDINATE WITH
PLUMBING CONTRACTOR.
NURSE CALL TELEVISION INTERFACE. PROVIDE CABLING,
RACEWAY AND FACEPLATE CURBELL WPA-0152 WITH CURBELL
#JU36-050 JUMPER.
NURSE CALL AUX JACK (BED CONNECTION)
NURSE CALL STAFF LOCATOR, WALL MOUNTED SWITCH
S.- EC SHALL MAKE SURE ALL EXISTING PANELS ARE BALANCED WITH IN 10% BETWEEN ALL
PHASES.
SL
120/277
D.- COORDINATE EXACT LOCATIONS OF LIGHTING FIXTURES TO BE INSTALLED IN
MECHANICAL ROOMS WITH HC, PC AND FPC.
SE
BC
-
C.- ALL EMERGENCY LIGHTING FIXTURES (GENERATOR TRANSFER DEVICES), NIGHT LIGHTS,
AND EXITS SHALL BE CONNECTED TO UNSWITCHED LEGS UNLESS NOTED OTHERWISE.
R.- ELECTRICAL COMPONENTS, EQUIPMENT, AND SYSTEMS SHALL BE DESIGNED AND
CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF NFPA 70.
NT
R1
B.- LIGHT FIXTURES ARE SHOWN IN APPROXIMATE LOCATIONS. REFER TO ARCHITECTURAL
REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATION OF FIXTURES. EXTERIOR
MOUNTING HEIGHTS INDICATED ON PLANS ARE FOR REFERENCE ONLY. COORDINATE ALL
HEIGHTS AND LOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.
DESK-MOUNTED NURSE CALL MASTER CONTROL STATION
NURSE CALL STAFF EMERGENCY STATION (46" MH)
PS
120/277 BEGA #9554LED
A.- GENERAL NOTES APPLY TO ALL SHEETS.
CB
EL
B1
NOTES APPLY TO
ALL SHEETS
SINGLE POLE WALL SWITCH (46" MH)
GANGED SWITCH ASSEMBLY FOR MULTI-LEVEL LIGHTING
APPLICATIONS, INNER LAMP(S) SHALL BE SWITCHED
SEPARATELY FROM OUTER LAMPS, UNLESS NOTED OTHERWISE
LIGHT SWITCH SUBSCRIPTS:
LVD - 0-10V DIMMER (VERIFY WITH EQUIPMENT
CONTROLLED.
M - MOMENTARY 'ON' SWITCH. HUBBELL HBL1556 OR
EQUAL.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH)
RECEPTACLE SUBSCRIPTS:
WP -WEATHERPROOF WITH "IN-USE" TAYMAC COVER,
VERTICAL MOUNT WITH GF RECEPTACLE.
GF - GROUND FAULT CIRCUIT INTERRUPTER
TV - TELEVISION SERVICE LOCATION (REFER TO
TECHNOLOGY DRAWINGS FOR MH). PROVIDE
RECEPTACLE SEPARATE BACKBOX ADJACENT TO
TELEVISION SERVICE LOCATION AND CIRCUIT AS
SHOWN ON PLANS. COORDINATE ALL LOCATIONS
WITH TECHNOLOGY AND CASEWORK CONTRACTOR.
EMERGENCY CODE BLUE BUTTON (46" MH)
T
-
APPROVED EQUALS
EQUIPMENT STARTERS AND DISCONNECTS
SD
NS
-
LAMP TYPE
4A
ELECTROMAGNETIC DOOR HOLDER (WALL MOUNTED)
SMOKE DAMPER, REFER TO CONTROL DETAIL
Z
SQUARE BOLLARD WITH SLOPED FRONT
FIXTURE DESCRIPTION
5300 Maryland Way
Suite 101
Brentwood, TN
37027
615.649.4707 phone
615.649.4689 fax
REFER TO NOTE(S)
A
MANUFACTURER AND CATALOG
NUMBER
MANUAL
INTEGRAL
SEE NOTE
FURNISHED BY
GND
HC
JB
MH
E
1
DISCONNECT SWITCH
MANUAL STARTER
CORD & PLUG
STARTER / DISCONNECT
SWITCH OR BREAKER
SEE NOTE
FURNISHED BY
EMERGENCY
P-1
4B
2
ELECTRICAL CONTRACTOR
EM
#
3
WATTS / LAMP
BUILDING AUTOMATION SYSTEM
CONDUIT
EXISTING TO REMAIN
AC - AIRCRAFT CABLE
C - CHAIN
G - GROUND
P - POLE
R - RECESSED
S - STEM/PENDANT
SM - SURF. MOUNT
T - TRACK
UC - UNDER CABINET
W - WALL
QUANTITY
HID
AMERICAN WIRE GAUGE
MOUNTING OPTIONS
INCANDESCENT
AWG
BAS
C
E
EC
LAMPS
FLUORESCENT
ABOVE FINISHED FLOOR - TO BOTTOM OF ITEM
ABOVE FINISHED GRADE - TO BOTTOM OF ITEM
F RATING = 3-HR.
T RATING = 0-HR.
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - 4 CFM/SQ FT
NEMA SIZE
MAGNETIC
MANUAL
MANUAL STARTER &
CONTACTOR
VARIABLE FREQ DRIVE
INTEGRAL OVERLOAD
IN MOTOR CONTROL CNTR
SEE NOTE
FURNISHED BY
AFF
AFG
LIGHTING FIXTURES:
120V-1PH
208V-1PH
2O8V-3PH
277V-1PH
480V-3PH
AMPERE(S)
A
SYSTEM #C-AJ-1226
VOLTAGE
(ALL MAY NOT APPLY)
DESIGNATION
FIXTURE
ELECTRICAL LEGEND
SHEET
NUMBER
L.- COORDINATE PHASING OF EQUIPMENT OF OTHER TRADES WITH SPECIFIC CONTRACTORS
AND GC. PERFORM ELECTRICAL WORK ASSOCIATED WITH EQUIPMENT AS REQUIRED BY
PHASING PLAN BY OTHERS.
MOMENTARY SWITCH CONTROLS
AMBIENT LIGHT
M
O.- REFER TO ARCHITECTURAL PHASING PLANS FOR SCHEDULE OF WORK.
P.- COORDINATE ALL LIGHT SWITCHES AND OTHER ELECTRICAL EQUIPMENT LOCATIONS
WITH MEDICAL GAS AND PLUMBING CONTRACTORS PRIOR TO ROUGH-IN. VERIFY SPACE
FOR EQUIPMENT THROUGH COORDINATION DRAWINGS. COORDINATE ALL DEVICE HEIGHTS
WITH ARCHITECTURAL ELEVATION DRAWINGS.
seals
SHEET NAME
E0.0
ELECTRICAL LEGEND AND DETAILS
E1.1
GROUND FLOOR ELECTRICAL DEMOLITION PLAN
E2.1
GROUND FLOOR LIGHTING NEW WORK PLAN
E3.1
GROUND FLOOR POWER NEW WORK PLAN
E4.1
ELECTRICAL RISER AND PANEL SCHEDULES
C 2013 By
FreemanWhite, Inc.
R4 FIXTURE
TWO #14'S
UCMC project number
12-069-01
Date
January 17, 2014
ELECTRICAL SHEET INDEX
EXAM ROOM PATIENT LIGHT CONTROL
K.- RECONNECT ALL EXISTING AND RELOCATED DEVICES AND EQUIPMENT TO ORIGINAL
PANEL UNLESS OTHERWISE NOTED ON PLANS. RECONFIGURE AND EXTEND CIRCUIT AS
NECESSARY. PROVIDE OWNER WITH UPDATED, TYPED PANEL SCHEDULE.
M.- COORDINATE ALL MOUNTING HEIGHTS BETWEEN ALL TRADES. COORDINATE PANEL
LOCATIONS WITH PLUMBING CONTRACTOR TO ENSURE NO OVERHEAD WATER PIPING.
-
MOMENTARY SWITCHES AND
PILLOWSPEAKER SWITCHES
WIRE IN PARALLEL.
Q.- ALL WIRING SHALL BE TO 517 IN PATIENT CARE AREAS. REFER TO NEC FOR ADDITIONAL
REQUIREMENTS.
drawn by
JL
checked by
DYN
T.- SEE SPECIFICATIONS FOR LABELING OF EQUIPMENT.
U.- SEE TECHNOLOGY DRAWINGS FOR ADDITIONAL CONDUIT AND BACKBOX ROUGH-IN
LOCATIONS. NURSE CALL SHALL BE UNDER THE SCOPE OF THE ELECTRICAL CONTRACTOR TO
ROUGH-IN ALL BOXES AND CONDUITS.
H2
H1
addenda/revisions
LOW-VOLTAGE
RELAY
H N
NP
NO
NAME
DATE
TWO #14'S
BED PADDLE
277V LIGHT
CIRCUIT
TWO #14'S
M
BED PADDLE CONTROLS AMBIENT LIGHT
THRU MOMENTARY CONTACT
LOW VOLTAGE MOMENTARY SWITCH
CONTROLS READING & AMBIENT LIGHTS
THIS DRAWING REFLECTS ALL CHANGES
PREVIOUSLY MADE ON THIS SHEET. VERIFY
THAT PREVIOUS CHANGES HAVE BEEN
INCORPORATED INTO THE CONTRACT BEFORE
PROCEEDING WITH ANY WORK NOT
SPECIFICALLY REFERENCED BY THIS REVISION.
ELECTRICAL
LEGEND AND
DETAILS