IRD SERIES R-404A WE MAKE INDOOR AIR BETTER ICE RINK DEFOGGER® (PACKAGED) 5 / 7.5 / 10 & 15-TON MODELS MOISTURE REMOVAL RANGE 800F (380C) TO 0 40 F (+4.50C) [PATENTED] APPLICATIONS: ARENAS NAS | SKATING | HOCKEY | CURLING TABLE OF CONTENTS DESIGN FEATURES 2 ELECTRICAL RATING 2 MOISTURE REMOVAL 3 ADDED HEAT 4 NUMBER OF UNITS PER INSTALLATION 4 INSTALLATION LAYOUT 5 PIPING DIAGRAM 5 PHYSICAL DIMENSIONS 6 NOTES 7 SPECIFICATIONS 8 R-407C UNITS AVAILABLE. FOR SPECIAL APPLICATIONS, OR HIGH TEMPERATURE APPLICATIONS (IE. ROLLER SKATING RINKS) CONTACT FACTORY. ELECTRICAL RATINGS R-404A DESIGN FEATURES •­AIRFLOW separated­from­all­refrigeration components,­inhibits­corrosion.­ •­EASy ACCESS for­service.­Servicing­of­unit can­be­done­while­unit­is­operating­. •­ENGINEERED for­ HIGH AIRFLOW with­design­techniques­to­maintain­optimal air­flow­through­the­dehumidification­coil and­maximize­moisture­removal. •­COIL fin­ material­ specially­ treated­ to facilitate­draining­of­entrained­moisture­on evaporator. •­TRUE SUB-COOLING circuit­to­improve system­efficiency. • SUCTION line­heat­exchanger­to­protect­the compressor­ from­ liquid­ slugging­ during­ the­defrost­cycle. •­CONTINUOUS fan­operation­to­prevent humidity­buildup­on­“off”­cycle. •­240-VOLT control­circuit. •­EXTERNAL high­and­low­pressure­service access­valves­and­sight­glass. • DEMAND defrost­system. •­STAINLESS STEEL heated­drain­pan­with large­1­1/4"­MPT­drain­connection. • INNOVATIVE design­ for­ short­ defrost cycles­providing­more­operational­time. MODEL RATED VOLTAGE COMPRESSOR RLA LRA BLOWER MOTOR HP FLA* DRAIN PAN MIN. CIRC. HEATER WATTS AMPS MAX OVERCUR. PROT. WIRE SIZE 60ºC/100 FT. IRD-­050-­4E­­­­­­­208-­‐240/1/60 ­­­­­­­­28.2 ­­­­­­­­­­­­129­­­­­­­­­­­2 ­­­­­­­­­­­­­9.2­­­­­­­­­­­­­­­195-­255 ­­­­­­­­­­­­­­­45 ­­­­­­­­­­­­­­­­­­­­­­­­70­­­­­­­­­­­­­­­­­­­­­­­­­­­6 IRD-­050-­5E­­­­­­­208-­‐240/3/60 ­­­­­­­­22.8 ­­­­­­­­­­­­164­­­­­­­­­­­2 ­­­­­­­­­­­6­-­5.8­­­­­­­­­­­­­195-­255 ­­­­­­­­­­­­­­­35 ­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­­­­­­­­­­8 IRD-­050-­7E ­­­­­­­­­­­480/3/60­­­­­­­­­­­­­12.2 ­­­­­­­­­­­­100­­­­­­­­­­­2 ­­­­­­­­­­­­­2.9 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­19 ­­­­­­­­­­­­­­­­­­­­­­­­30 ­­­­­­­­­­­­­­­­­­­­­­­­­­12 IRD-­050-­8E ­­­­­­­­­­­600/3/60 ­­­­­­­­­­­­­­­9 ­­­­­­­­­­­­­­­78­­­­­­­­­­­­2 ­­­­­­­­­­­­­2.9 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­15 ­­­­­­­­­­­­­­­­­­­­­­­­20 ­­­­­­­­­­­­­­­­­­­­­­­­­­14 IRD-­075-­5E ­­­­­­­208-­‐240/3/60 ­­­­­­­­26.9­­­­­­­­­­­­225­­­­­­­­­­­3 ­­­­­­­­­­­8.4­-­8 ­­­­­­­­­­­­­195-­255 ­­­­­­­­­­­­­­­43 ­­­­­­­­­­­­­­­­­­­­­­­­60­­­­­­­­­­­­­­­­­­­­­­­­­­­6 IRD-­075-­7E ­­­­­­­­­­­480/3/60­­­­­­­­­­­­­15.7 ­­­­­­­­­­­­114­­­­­­­­­­­3 ­­­­­­­­­­­­­­4­­­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­24 ­­­­­­­­­­­­­­­­­­­­­­­­35 ­­­­­­­­­­­­­­­­­­­­­­­­­­10 •­HOT GAS defrost:­quick­efficient­defrost, minimizes­compressor­cycling. IRD-­075-­8E ­­­­­­­­­­­600/3/60­­­­­­­­­­­­­11.2 ­­­­­­­­­­­­­80­­­­­­­­­­­­3 ­­­­­­­­­­­­­3.1 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­18 ­­­­­­­­­­­­­­­­­­­­­­­­25 ­­­­­­­­­­­­­­­­­­­­­­­­­­12 •­FACTORy assembled,­ wired,­ charged­ and­tested. IRD-­100-­7E ­­­­­­­­­­­480/3/60­­­­­­­­­­­­­17.9 ­­­­­­­­­­­­125­­­­­­­­­­­5 ­­­­­­­­­­­­­6.4 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­29 ­­­­­­­­­­­­­­­­­­­­­­­­45­­­­­­­­­­­­­­­­­­­­­­­­­­­8 IRD-­100-­5E­­­­­­­­208-­240/3/60 ­­­­­­­­­37.2 ­­­­­­­­­­­­239­­­­­­­­­­­5­­­­­­­­13.8­-­12.8­­­­­­­­­­195-­255­­­­­­­­­­­­­­­­61 ­­­­­­­­­­­­­­­­­­­­­­­­90­­­­­­­­­­­­­­­­­­­­­­­­­­­6 IRD-­100-­8E ­­­­­­­­­­­600/3/60­­­­­­­­­­­­­16.3 ­­­­­­­­­­­­­80­­­­­­­­­­­­5 ­­­­­­­­­­­­­5.1 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­26 ­­­­­­­­­­­­­­­­­­­­­­­­40 ­­­­­­­­­­­­­­­­­­­­­­­­­­10 IRD-­150-­5E ­­­­­­­­208-­240/3/60 ­­­­­26.9­(2X) ­­­­225­(2X)­­­­­­­5­­­­­­­­13.8­-­12.8­­­­­­­­­­195-­255 ­­­­­­­­­­­­­­­75 ­­­­­­­­­­­­­­­­­­­­­­­100 ­­­­­­­­­­­­­­­­­­­­­­­­­­4 IRD-­150-­7E ­­­­­­­­­­­480/3/60­­­­­­­­­15.7­(2X)­­­­­114­(2X) ­­­­­­­5 ­­­­­­­­­­­­­6.4 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­42 ­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­­­­­­­­­­6 IRD-­150-­8E ­­­­­­­­­­­600/3/60 ­­­­­­­­­11.2­(2X)­­­­­­80­(2X)­­­­­­­­5 ­­­­­­­­­­­­­5.1 ­­­­­­­­­­­­­­­­­­255­­­­­­­­­­­­­­­­­­­31 ­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­­­­­­­­­­8 NOTE:­IRD-­150­UNITS­HAVE­2­CIRCUITS.­­­BLOWER­MOTOR­IS­A­WATT­SAVER­TYPE 3 PERFORMANCE CHARACTERISTICS MOISTURE REMOVAL IN LB./HR. MODEL R-404A ENTERING AIR oF DB 100 90 RELATIVE HUMIDITy 80 70 60 50 IRD-050­­­­­­­­­­­­­80 ­­­­­­­­­­­­­­­­­­57.6­­­­­­­­­­­­­­­­­52.9 ­­­­­­­­­­­­­­­43.6 ­­­­­­­­­­­­­­­­34.7 ­­­­­­­­­­­­­­­­­25.4­­­­­­­­­­­­­­­­14.6 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70­­­­­­­­­­­­­­­­­­52.0 ­­­­­­­­­­­­­­­­44.9­­­­­­­­­­­­­­­­37.5­­­­­­­­­­­­­­­­­29.6­­­­­­­­­­­­­­­­­­21.5­­­­­­­­­­­­­­­­12.2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60­­­­­­­­­­­­­­­­­­43.4­­­­­­­­­­­­­­­­­37.1­­­­­­­­­­­­­­­­30.7­­­­­­­­­­­­­­­­­24.1­­­­­­­­­­­­­­­­­­20.0­­­­­­­­­­­­­­­­­9.7 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­34.7 ­­­­­­­­­­­­­­­­29.3­­­­­­­­­­­­­­­­24.1­­­­­­­­­­­­­­­­­18.4­­­­­­­­­­­­­­­­­­12.5­­­­­­­­­­­­­­­­­6.8 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­30.4­­­­­­­­­­­­­­­­­22.1­­­­­­­­­­­­­­­­17.6­­­­­­­­­­­­­­­­­13.4­­­­­­­­­­­­­­­­­­­9.0­­­­­­­­­­­­­­­­­­4.7 IRD-075­­­­­­­­­­­­­80­­­­­­­­­­­­­­­­­­80.2 ­­­­­­­­­­­­­­­­70.7­­­­­­­­­­­­­­­­61.9­­­­­­­­­­­­­­­­­51.7­­­­­­­­­­­­­­­­­­41.9 ­­­­­­­­­­­­­­­­31.5 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­­67.5­­­­­­­­­­­­­­­­­59.5­­­­­­­­­­­­­­­­51.3­­­­­­­­­­­­­­­­­42.3 ­­­­­­­­­­­­­­­­­33.6­­­­­­­­­­­­­­­­24.1 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60­­­­­­­­­­­­­­­­­­55.5 ­­­­­­­­­­­­­­­­48.0 ­­­­­­­­­­­­­­­40.8 ­­­­­­­­­­­­­­­­34.2 ­­­­­­­­­­­­­­­­­26.6­­­­­­­­­­­­­­­­18.1 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­43.2 ­­­­­­­­­­­­­­­­36.7 ­­­­­­­­­­­­­­­30.9 ­­­­­­­­­­­­­­­­25.2­­­­­­­­­­­­­­­­­­19.1 ­­­­­­­­­­­­­­­­13.4 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40 ­­­­­­­­­­­­­­­­­­31.1­­­­­­­­­­­­­­­­­27.0­­­­­­­­­­­­­­­­22.7­­­­­­­­­­­­­­­­­18.1­­­­­­­­­­­­­­­­­­13.6­­­­­­­­­­­­­­­­­9.4 IRD-100­­­­­­­­­­­­­80­­­­­­­­­­­­­­­­­­93.6 ­­­­­­­­­­­­­­­­83.0 ­­­­­­­­­­­­­­­71.2­­­­­­­­­­­­­­­­­57.2­­­­­­­­­­­­­­­­­­43.7­­­­­­­­­­­­­­­­29.9 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­­81.0­­­­­­­­­­­­­­­­­71.2 ­­­­­­­­­­­­­­­60.0 ­­­­­­­­­­­­­­­­48.2 ­­­­­­­­­­­­­­­­­35.6­­­­­­­­­­­­­­­­22.7 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60­­­­­­­­­­­­­­­­­­69.0 ­­­­­­­­­­­­­­­­59.6 ­­­­­­­­­­­­­­­58.3­­­­­­­­­­­­­­­­­40.1­­­­­­­­­­­­­­­­­­29.2­­­­­­­­­­­­­­­­18.6 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­54.2 ­­­­­­­­­­­­­­­­46.7 ­­­­­­­­­­­­­­­38.0 ­­­­­­­­­­­­­­­­29.8­­­­­­­­­­­­­­­­­­21.2­­­­­­­­­­­­­­­­13.2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­40.0 ­­­­­­­­­­­­­­­­34.2­­­­­­­­­­­­­­­­27.8­­­­­­­­­­­­­­­­­21.3­­­­­­­­­­­­­­­­­­14.8­­­­­­­­­­­­­­­­­8.8 IRD-150­­­­­­­­­­­­­80 ­­­­­­­­­­­­­­­­­160.4­­­­­­­­­­­­­­­141.3­­­­­­­­­­­­­­123.8­­­­­­­­­­­­­­­103.3­­­­­­­­­­­­­­­­­83.7­­­­­­­­­­­­­­­­63.0 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­135.0­­­­­­­­­­­­­­­119.0­­­­­­­­­­­­­­102.6­­­­­­­­­­­­­­­­84.6­­­­­­­­­­­­­­­­­­67.1 ­­­­­­­­­­­­­­­­48.2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60­­­­­­­­­­­­­­­­­­111.1 ­­­­­­­­­­­­­­­­95.9­­­­­­­­­­­­­­­­81.5­­­­­­­­­­­­­­­­­68.4­­­­­­­­­­­­­­­­­­53.1­­­­­­­­­­­­­­­­36.2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­86.4 ­­­­­­­­­­­­­­­­73.4­­­­­­­­­­­­­­­­61.7­­­­­­­­­­­­­­­­­50.4 ­­­­­­­­­­­­­­­­­38.2­­­­­­­­­­­­­­­­26.8 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­62.3 ­­­­­­­­­­­­­­­­54.0 ­­­­­­­­­­­­­­­45.4 ­­­­­­­­­­­­­­­­36.2­­­­­­­­­­­­­­­­­­27.2­­­­­­­­­­­­­­­­18.7 NOTE:­IRD-­‐150­UNITS­HAVE­2­CIRCUITS ADDED HEAT IN MBH MODEL ENTERING AIR oF DB 100 90 RELATIVE HUMIDITy 80 70 60 50 IRD-050­­­­­­­­­­­­­80 ­­­­­­­­­­­­­­­­­115.0­­­­­­­­­­­­­­­105.9 ­­­­­­­­­­­­­­96.7 ­­­­­­­­­­­­­­­­84.6 ­­­­­­­­­­­­­­­­­72.9­­­­­­­­­­­­­­­­77.3 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­­99.1­­­­­­­­­­­­­­­­­90.4 ­­­­­­­­­­­­­­­80.7­­­­­­­­­­­­­­­­­71.9­­­­­­­­­­­­­­­­­­63.7­­­­­­­­­­­­­­­­55.9 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60 ­­­­­­­­­­­­­­­­­­84.1­­­­­­­­­­­­­­­­­73.9 ­­­­­­­­­­­­­­­68.0­­­­­­­­­­­­­­­­­61.2­­­­­­­­­­­­­­­­­­53.5­­­­­­­­­­­­­­­­45.7 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50 ­­­­­­­­­­­­­­­­­­68.1­­­­­­­­­­­­­­­­­63.7 ­­­­­­­­­­­­­­­58.8 ­­­­­­­­­­­­­­­­52.0 ­­­­­­­­­­­­­­­­­44.7­­­­­­­­­­­­­­­­36.9 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­54.4­­­­­­­­­­­­­­­­­50.1 ­­­­­­­­­­­­­­­46.2­­­­­­­­­­­­­­­­­41.8­­­­­­­­­­­­­­­­­­37.7­­­­­­­­­­­­­­­­33.5 IRD-075­­­­­­­­­­­­­80 ­­­­­­­­­­­­­­­­­130.7­­­­­­­­­­­­­­­120.6­­­­­­­­­­­­­­106.3­­­­­­­­­­­­­­­­92.7 ­­­­­­­­­­­­­­­­­79.0 ­­­­­­­­­­­­­­­­67.1 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­109.3­­­­­­­­­­­­­­­­98.0­­­­­­­­­­­­­­­­87.9­­­­­­­­­­­­­­­­­76.0­­­­­­­­­­­­­­­­­­64.2­­­­­­­­­­­­­­­­52.3 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60 ­­­­­­­­­­­­­­­­­­87.9­­­­­­­­­­­­­­­­­80.2 ­­­­­­­­­­­­­­­70.7 ­­­­­­­­­­­­­­­­60.0 ­­­­­­­­­­­­­­­­­50.5­­­­­­­­­­­­­­­­44.0 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50­­­­­­­­­­­­­­­­­­69.5 ­­­­­­­­­­­­­­­­60.0 ­­­­­­­­­­­­­­­53.5 ­­­­­­­­­­­­­­­­46.3 ­­­­­­­­­­­­­­­­­39.2­­­­­­­­­­­­­­­­32.7 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­46.2 ­­­­­­­­­­­­­­­­46.9 ­­­­­­­­­­­­­­­40.4 ­­­­­­­­­­­­­­­­36.2­­­­­­­­­­­­­­­­­­31.5­­­­­­­­­­­­­­­­26.1 IRD-100­­­­­­­­­­­­­80 ­­­­­­­­­­­­­­­­­165.0­­­­­­­­­­­­­­­149.1­­­­­­­­­­­­­­132.8­­­­­­­­­­­­­­­114.2 ­­­­­­­­­­­­­­­­­97.2 ­­­­­­­­­­­­­­­­81.8 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­140.9­­­­­­­­­­­­­­­125.6­­­­­­­­­­­­­­110.2­­­­­­­­­­­­­­­­94.8­­­­­­­­­­­­­­­­­­81.0­­­­­­­­­­­­­­­­65.6 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60 ­­­­­­­­­­­­­­­­­111.0 ­­­­­­­­­­­­­­­100.4 ­­­­­­­­­­­­­­88.3­­­­­­­­­­­­­­­­­76.1­­­­­­­­­­­­­­­­­­64.0­­­­­­­­­­­­­­­­51.8 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50 ­­­­­­­­­­­­­­­­­­89.1­­­­­­­­­­­­­­­­­79.4 ­­­­­­­­­­­­­­­68.9 ­­­­­­­­­­­­­­­­59.9 ­­­­­­­­­­­­­­­­­48.6­­­­­­­­­­­­­­­­38.9 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­64.0 ­­­­­­­­­­­­­­­­58.3­­­­­­­­­­­­­­­­51.8­­­­­­­­­­­­­­­­­46.2 ­­­­­­­­­­­­­­­­­39.7­­­­­­­­­­­­­­­­29.2 IRD-150 80 ­­­­­­­­­­­­­­­­­261.4 ­­­­­­­­­­­­­­­241.2­­­­­­­­­­­­­­212.6­­­­­­­­­­­­­­­185.4­­­­­­­­­­­­­­­­158.0­­­­­­­­­­­­­­134.2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­70 ­­­­­­­­­­­­­­­­­218.6­­­­­­­­­­­­­­­196.0 ­­­­­­­­­­­­­ 175.8­­­­­­­­­­­­­­ 152.0­­­­­­­­­­­­­­­ 128.4 ­­­­­­­­­­­­­104.6 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­60 ­­­­­­­­­­­­­­­­­175.8­­­­­­­­­­­­­­­160.4­­­­­­­­­­­­­­141.4­­­­­­­­­­­­­­­120.0­­­­­­­­­­­­­­­­101.0­­­­­­­­­­­­­­­88.0 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­50 ­­­­­­­­­­­­­­­­­139.0­­­­­­­­­­­­­­­120.0­­­­­­­­­­­­­­107.0­­­­­­­­­­­­­­­­92.6­ ­­­­­­­­­­­­­­­­78.4­­­­­­­­­­­­­­­­65.4 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­40­­­­­­­­­­­­­­­­­­92.4 ­­­­­­­­­­­­­­­­93.8 ­­­­­­­­­­­­­­­80.8­­­­­­­­­­­­­­­­ 72.4­­­­­­­­­­­­­­­­­63.0 ­­­­­­­­­­­­­­­ 52.2 NOTE:­IRD-­150­UNITS­HAVE­2­CIRCUITS GUIDELINES FOR UNIT NUMBER OF UNITS APPLICATION IRD 050 IRD 075 IRD 100 Curling-up­to­4­rinks­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­1­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ Curling-more­than­4­rinks­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­2­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ Skating-with­no­spectator ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­1­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ Skating-up­to­500­spectators­(1­side­of­rink) ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­2­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ Skating-500­to­1000­spectators­(2­sides­of­rink) ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­3­­­­­­­­­­­­­­­­­­­­­­­­­­­­Or­2 ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ Skating-1000­to­1500­spectators­(4­sides­of­rink) ­­­­­­­­­­­­­­­­­­­­­­­­­­­4­­­­­­­­­­­­­­­­­­­­­­­­­­­­Or­3­ Multiple­ice­surfaces­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­x NOTE:­IRD-150­UNIT­REfER­TO­fACTORY 4 INSTALLATION R-404A 1. Direct­the­airflow­along­the­boards;­do­not­direct­air­over­the­surface. 2. Discharge­duct­equipped­with­horizontally­and­vertically­adjustable­louvers (supplied­by­others). SUGGESTED PLATFORM 3. Unit­should­be­15­to­25­feet­above­ice­surface.­(Y) 4. Unit­should­be­at­a­minimum­of­4­feet­from­nearest­obstruction.­(X) LOCATING THE DEFOGGER® PIPING DIAGRAM REFRIGERATION CyCLE HOT GAS DEFROST CyCLE 5 PROPOSED DIFFUSER PHySICAL DIMENSIONS R-404A ­­­1.­­Humidistat ­­­2.­­Running­compressor­light 13 14 ­­­3.­­Toggle­switch­for­emergency WID E 12 ­­­4.­­Power­supply­entry EP DE ­­­5.­­High­and­low­pressure­taps 11 ­­­6.­­Access­door­for­electrical­ and­compressor ­­­7.­­Access­door­for­expansion­valve ­­­8.­­Liquid­sight­glass ­­­9.­­Compressor­removal­access­door 1 2 3 ­10.­­Mounting­bolts­for­discharge­ diffuser 4 ­­11.­­Blower­motor­and­belt­access­door 8 7 10 ­12.­­Drain­pan­access­door­ (Drain­1­1/4­MPT) 6 9 ­13.­­Air­filter­access­door 5 ANC HOR ANC WIDE C/C HOR +1 1/2 ­14.­­Air­intake­and­evaporator­coil­face MODEL# OVERALL DIMENSIONS (INCHES) WIDE IRD-050 IRD-075 IRD-100 DEEP HIGH ANCHOR C/C WIDE DEEP BLOWER DISCHARGE (INCHES) WIDE HIGH 60 48 37­1/2 61­1/4 40­5/8 18­5/8 15­7/8 1524 1219 953 1556 1032 473 403 60 48 37­1/2 61­1/4 40­5/8 18­5/8 15­7/8 1524 1219 953 1556 1032 473 403 66 44 53­3/4 67­1/3 40­5/8 22­1/4 19­1/4 1676 1118 1365 1710 1032 565 489 51.5 54­3/4 76­5/8 48­1/4 22­1/4 19­1/4 1308 1391 1946 1226 565 489 IRD-150 75.375 1915 AIR VOLUME R O CH/C P AN C EE D FILTERS CFM 4500 5500 7500 10000 LB. 16x20x2­(2) 20x20x2­(2) 932 406x508x25.4­(2) 508x508x25.4­(2) 423 16x20x2­(2) 20x20x2­(2) 932 406x508x25.4­(2) 508x508x25.4­(2) 423 20x25x2­(4) 1306 508x­635x25.4­(4) 593 16x25x2­(6) 1650 406x­635x25.4­(6) 750 STANDARD­UNIT­IS­DESIgNED­fOR­0­EXTERNAL­STATIC­PRESSURE;­fOR­UNITS­WITH­MORE­THAN­0.25"­ESP,­CONTACT­fACTORY 6 UNIT NET WEIGHT NOTES R-404A 7 SPECIFICATIONS R-404A The­contractor­shall­furnish­and­install­where­shown on­ the­ plan­ (­ ­ ­ ­ ­ ­ ­ )­ Thermoplus Air ICE­RINK­DEfOggER® of­the­size­indicated. DEFROST HEAT EXCHANGER shall­ be­ included­in­each­unit­to­eliminate­flood­back­on­defrost­cycle. Installation­shall­include­mounting­platform­and­ discharge­ diffuser.­ Each­ unit­ shall­ be­ factory­ assembled­and­include­the­following: RECEIVER shall­ be­ sized­ to­ hold­ the­ total­ refrigerant­charge­for­easy­service­of­the­unit.­Rotolock­valves­shall­be­supplied­at­inlet­and­outlet­to isolate­the­refrigerant­charge. CASING shall­be­heavy­gauge­steel­painted­white­ with­powder­paint.­Internal­heated­drain­pan­shall be­constructed­of­stainless­steel­with­1­1/4­MPT­ connection. UNIT shall­be­anchored­to­the­platform­with­integral­anchoring­rails­included­in­the­casing. AIRFLOW shall­be­separated­from­refrigeration­ components­ for­ easy­ servicing­ of­ unit­ while­ in­ operation. COMPRESSOR shall­be­heavy­duty,­scroll,­suction­cooled­with­internal­motor­protection,­liquid slugging­protection­and­centrifugal­oil­pump­for long­trouble­free­operation.­Compressor­will­have internal­suspension­system­and­shall­be­installed with­external­rubber­vibration­absorber­for­vibration-free­operation.­Compressors­shall­be­supplied with­a­crankcase­heater­to­prevent­refrigerant­migration­and­rotolock­valve­for­service. SUCTION ACCUMULATOR with­boil­out­coil­ shall­be­included­in­each­unit­in­the­refrigerant­path to­ensure­liquid-free­refrigerant­at­the­compressor. Also­improves­system­efficiency­by­subcooling­the liquid. EXPANSION VALVE shall­ be­ balanced­ port type,­specially­engineered­to­operate­efficiently­at low­ head­ pressure,­ thus­ reducing­ the­ power consumption­at­low­ambient. COILS (Evaporator,­ Condenser,­ Subcooler­ and Desuperheater)­shall­be­constructed­of­die­formed, collared,­ self-spacing­ aluminum­ plate­ fin­ and­ copper­tube­staggered­in­direction­of­airflow­and mechanically­ bonded­ to­ give­ metal­ to­ metal­ contact­for­maximum­heat­transfer­and­patented desuperheating­of­the­refrigerant­circuitry.­All­coils shall­ be­ leak­ pressure­ tested­ after­ welding­ at­ 400­psig. FILTERS shall­be­2­inches,­throw-away­type,­in­an accessible­filter­rack­with­access­door. CENTRIFUGAL BLOWERS shall­be­forward­ curved­ statically­ and­ dynamically­ balanced, designed­ for­ efficient­ operation­ and­ shall­ have­ permanently­lubricated­ball­bearings.­Blowers­shall operate­constantly­to­maintain­even­humidity­within the­controlled­area. PIPING shall­be­copper­tube,­brazed­connections. Access­fittings­for­high­and­low­pressure­shall­be located­outside­the­enclosure.­Each­system­shall­be evacuated,­dehydrated,­and­charged­with­operating charge­of­R-404A.­Each­system­shall­be­tested­for­ performance­and­rating. CONTROLS shall­be­located­in­an­accessible,­prewired,­ central­ control­ panel.­ Control­ panel­ shall include­compressor­contactor,­blower­motor­starter, high­ and­ low­ pressure­ switch,­ time­ delay­ timer, defrost­control,­­ and­low­ambient­thermostat.­Additionally,­a­humidistat­shall­be­supplied­and­installed outside­the­control­panel,­on­the­exterior­of­the­unit along­with­"Compressor­running"­indicator­light­and "On-Off"­for­emergency­shutdown­of­the­blower­and compressor. PUMP DOWN CyCLE All­units­to­operate­on­a pump­down­cycle­for­a­liquid­free­starting­of­the compressor­and­to­minimize­refrigerant­migration. DEFROST SySTEM shall­ be­ of­ the­ Demand­ Defrost­ type,­ time­ actuated­ and­ temperature­ terminated.­ The­ hot­ gas­ defrost­ cycle­ shall­ be­ energized­on­fixed­time­intervals­if­ice­is­present­ on­ the­ evaporator­ and­ shall­ stop­ when­ the­ evaporator­is­ice­free. BLOWER MOTOR shall­be­open­drip­proof,­ball bearing­ type,­ permanently­ lubricated.­ Overload relay­shall­be­provided­to­protect­all­current­phases. Thermoplus Air Inc. reserves the right to make any changes in the design or specifications of any product, at any time, without prior notice. USA & CANADA 1­888­336­PLUS­(7587) fax:­(450)­436-5970 262­Scott­Street,­Saint-Jérôme,­Québec,­Canada­­J7Z­1H1 Tel.:­(450)­436-7555­­fax:­(450)­436-5970 1 www.thermoplus.com © Copyright­2015­by­Thermoplus­Air­Inc.