11 Electrical.compressed_Part1

advertisement
5.
ALL EMERGENCY LIGHTING FIXTURES SHALL BE MARKED SO AS TO BE IDENTIFIED BY VISUAL INSPECTION FOR
TESTING PURPOSES. IDENTIFICATION SHALL BE BY ONE 1/2" RED SELF-STICK DOT ON THE VERTICAL PORTION OF
LOUVER OR ON THE TOP OF THE LENS.
6.
WHERE MULTIPLE BALLASTS ARE INDICATED FOR MULTI-LAMP T8 FIXTURES, THE OUTER LAMPS SHALL BE ON ONE
BALLAST AND SWITCH, AND THE INWARD LAMPS ON ANOTHER BALLAST AND SWITCH.
7.
EXACT LOCATION AND ORIENTATION OF OCCUPANCY SENSORS SHALL BE AS RECOMMENDED BY MANUFACTURER TO
OBTAIN COMPLETE COVERAGE. IF THE CONTRACTOR USES A SENSOR THAT HAS A COVERAGE PATTERN DIFFERENT
FROM THAT WHICH IS SPECIFIED, AND AS A RESULT ADDITIONAL SENSORS ARE REQUIRED TO COMPLETELY COVER A
SPACE, THE CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS AS REQUIRED (CONNECTED IN PARALLEL WITH
EACH OTHER) AT NO ADDITIONAL COST TO THE OWNER. ALL OCCUPANCY SENSOR TIME DELAYS SHALL BE SET TO NO
MORE THAN 30 MINUTES.
8.
WHERE LINE-VOLTAGE OCCUPANCY SENSORS ARE SHOWN IN CONJUNCTION WITH WALL SWITCHES, CONNECT
SENSORS IN SERIES WITH SWITCHES SUCH THAT LIGHTS WILL BE ON ONLY WHEN MOTION IS DETECTED AND
SWITCHES ARE ON. WHERE MULTIPLE OCCUPANCY SENSORS ARE SHOWN CONNECTED TO ONE SWITCHING CIRCUIT,
CONNECT SENSORS IN PARALLEL SUCH THAT CIRCUIT WILL BE ENERGIZED WHEN ANY SENSOR DETECTS MOTION.
WHERE ONE OCCUPANCY SENSOR IS SHOWN CONNECTED TO MULTIPLE SWITCHING CIRCUITS, EACH SWITCHING
CIRCUIT SHALL BE CONTROLLED BY THE OCCUPANCY SENSOR (IN SERIES WITH THE WALL SWITCH[ES] IF PRESENT).
9.
UNLESS INDICATED OTHERWISE, SWITCHES AND OCCUPANCY SENSORS IN A ROOM/SPACE SHALL CONTROL ALL
LIGHTING FIXTURES IN THAT ROOM/SPACE.
10.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ALL PANELBOARD FEEDER ENTRANCE LOCATIONS
(TOP, BOTTOM, SIDE).
11.
12.
PROVIDE ALL 120-VOLT POWER NEEDED FOR THE FIRE ALARM SYSTEM. PROVIDE CIRCUIT BREAKER LOCKS AND
CLEARLY INDICATE IN THE DIRECTORY THAT THEY ARE FIRE ALARM CIRCUITS. PROVIDE RED BREAKER, RED BREAKER
LOCK OR RED DOT ON DEAD FRONT COVER BESIDE BREAKER. POWER SUPPLY QUANTITIES SHALL BE DETERMINED BY
THE FIRE ALARM SUPPLIER AND INCLUDED IN BID. ALL POWER SUPPLIES SHALL BE LOCATED IN UTILITY-TYPE SPACES
(MECH/ELEC/COMM ROOMS, HOUSEKEEPING CLOSETS, TRASH ROOMS, ETC.).
ALL ROOMS WITH AN INTERCOM CALL-IN SWITCH SHALL BE ON THEIR OWN SEPARATE ZONE. NEW CORRIDOR
INTERCOM SPEAKERS SHALL BE ZONED WITH THE EXISTING CORRIDOR SPEAKERS. NEW PREP ROOM INTERCOM
SPEAKERS SHALL BE ZONED WITH THE RESPECTIVE CLASSROOM SPEAKERS.
13.
CAREFULLY COORDINATE LOCATIONS OF ALL LIGHTING FIXTURES, OCCUPANCY SENSORS, CEILING SPEAKERS, SMOKE
DETECTORS, FIRE ALARM NOTIFICATION APPLIANCES AND OTHER ELECTRICAL CEILING DEVICES WITH SPRINKLER
HEADS AND HVAC CEILING DEVICES.
14.
WHERE RE-USE OF EXISTING CONDUIT, WIRING AND/OR OUTLET BOXES IS INDICATED, ALSO PROVIDE NEW MATERIALS
IF NECESSARY.
15.
16.
17.
WHERE OUTLETS ARE SHOWN ABOVE A COUNTER OR SIMILAR SURFACE WITH A SPECIFIC MOUNTING HEIGHT,
COORDINATE MOUNTING HEIGHT WITH BOTH THE SURFACE BELOW AND WITH ANY WALL MOUNTED ARCHITECTURAL
ITEMS ABOVE (TACKBOARDS, ETC.) BEFORE ROUGH-IN.
FOR WALL DEVICES MOUNTED ABOVE ARCHITECTURAL ITEMS (SUCH AS FIRE ALARM STROBES MOUNTED ABOVE
MARKERBOARDS, TACKBOARDS OR TV'S), COORDINATE MOUNTING HEIGHTS OF WALL DEVICES SUCH THAT THEY DO
NOT INTERFERE WITH ARCHITECTURAL ITEMS.
SEE ARCHITECTURAL DRAWINGS FOR RATED WALL, FLOOR AND CEILING CONSTRUCTION, AND PROVIDE NECESSARY
RATED DEVICES AND FIRE SEALANT FOR PENETRATIONS. WHERE NEW DEVICES ARE SHOWN RECESSED IN RATED
PARTITIONS, CAREFULLY COORDINATE LOCATIONS AND OFFSETS.
18.
PROVIDE ALL 120-VOLT POWER NEEDED BY THE BAS. COORDINATE WITH THE CONTROLS SPECIFICATIONS AND
CONTRACTOR.
19.
MODIFY EXISTING PANEL SCHEDULES TO ACCURATELY REFLECT ALL CHANGES MADE AS PART OF THIS CONTRACT.
ALL NEW BREAKERS IN EXISTING PANELS SHALL MATCH EXISTING AIC.
20.
21.
22.
23.
24.
FOR ALL EXTERIOR UNDERGROUND CONDUIT AND WIRING, CAREFULLY COORDINATE ALL WORK WITH EXISTING SOIL
CONDITIONS AND WITH EXISTING UTILITIES IN ORDER TO AVOID CONFLICTS. NOTIFY ENGINEER IF ROUTING MUST BE
DIFFERENT FROM WHAT IS SHOWN ON THE DRAWINGS.
THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING BID IN ORDER TO VERIFY ALL EXISTING CONDITIONS,
TO DETERMINE THE FULL EXTENT OF DEMOLITION WORK REQUIRED, AND TO DETERMINE THE FULL EXTENT OF
RELOCATION AND MODIFICATION WORK REQUIRED FOR ELECTRICAL WORK (DUE TO OTHER DISCIPLINES INTERFERING
OR ANY OTHER REASON). THE CONTRACTOR SHALL BE FULLY RESPONSIBLE TO COORDINATE ALL ELECTRICAL WORK
WITH BOTH NEW AND EXISTING PIPING, DUCTWORK, CONDUIT, ETC. NO CHANGE ORDERS WILL BE APPROVED FOR
ADDITIONAL WORK DUE TO THE CONTRACTOR NEGLECTING TO VISIT THE SITE AND GATHER ALL NECESSARY
INFORMATION.
1
PLAN NOTE DESIGNATION.
A1
LIGHTING FIXTURE TYPE DESIGNATION.
1
REVISION DESIGNATION.
ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS
PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.
CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND
OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION
OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF
CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE
UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.
© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2015, 2016
LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED. SYMBOL SIZE VARIES WITH
LIGHTING FIXTURE TYPE.
LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, CONNECTED ON EMERGENCY
CIRCUIT (TYPICAL FOR ALL LIGHTING FIXTURES WITH FILLED CIRCLE).
KEY PLAN
LIGHTING FIXTURE, LED, INCANDESCENT, FLUORESCENT OR HID, WALL MOUNTED.
EXIT SIGN, CEILING MOUNTED. SHADED QUADRANT(S) INDICATES FACE(S). PROVIDE
ARROWS AS INDICATED ON DRAWINGS. LIGHTING FIXTURE TYPE "X1", UNO.
Sa
GENERAL USE SWITCH, SINGLE POLE. LOWER CASE ALPHABETIC SUBSCRIPT, WHERE
SHOWN, INDICATES LOADS CONTROLLED. (TYPICAL FOR ALL SWITCHES)
4'-0"
SL1
SWITCH, LOW VOLTAGE LIGHTING CONTROL, WALL-BOX MOUNTED. NUMBER INDICATES
TYPE AS SCHEDULED ON DRAWINGS OR IN SPECIFICATIONS.
4'-0"
SO1
SWITCH WITH INTEGRAL OCCUPANCY SENSOR, WALL-BOX MOUNTED. NUMBER INDICATES
TYPE AS SCHEDULED ON DRAWINGS OR IN SPECIFICATIONS.
O1
OCCUPANCY SENSOR, STANDARD ON/OFF SWITCHING, CEILING MOUNTED. NUMBER
INDICATES TYPE AS SCHEDULED ON DRAWINGS OR IN SPECIFICATIONS.
4'-0"
B
C
A
1'-4" TO BOT
RECEPTACLE, DUPLEX, WALL. ALPHA-NUMERIC OR NUMERIC SUBSCRIPT, WHERE SHOWN,
INDICATES CIRCUIT. (TYPICAL FOR ALL RECEPTACLES)
1'-4" TO BOT
PROJECT
NORTH
RECEPTACLE, DUPLEX GFCI, WALL.
1'-4" TO BOT
REVISIONS
1
COMMUNICATIONS AND POWER OUTLETS, WALL MOUNTED. NUMBER INDICATES THE
CONFIGURATION AND MOUNTING AS DETAILED ON ELEC DRAWINGS.
1
COMMUNICATIONS AND POWER OUTLETS, CEILING MOUNTED. NUMBER INDICATES THE
CONFIGURATION AND MOUNTING AS DETAILED ON ELEC DRAWINGS.
01
W
WIRELESS ACCESS POINT (WAP), CEILING MOUNTED, BY OWNER'S SEPARATE VENDOR.
S
SMOKE DETECTOR, CEILING.
8'-0"
F
8'-0"
F
4'-0"
I
30
FIRE ALARM HORN OR SPEAKER WITH INTEGRAL VISUAL DEVICE, WALL. NUMBER
INDICATES VISUAL DEVICE MINIMUM CANDELA RATING.
30
FIRE ALARM VISUAL DEVICE, WALL. NUMBER INDICATES VISUAL DEVICE MINIMUM
CANDELA RATING.
INTERCOM SYSTEM CALL-IN STATION, WALL.
INTERCOM SYSTEM SPEAKER, CEILING. "T" = TWO-WAY TALKBACK TYPE, WHERE PRESENT.
T
12'-0"
INTERCOM SYSTEM HORN SPEAKER, WALL. "T" = TWO-WAY TALKBACK TYPE, WHERE
PRESENT.
T
M
SECURITY SYSTEM MOTION SENSOR, CEILING. LETTER, WHERE SHOWN, INDICATES TYPE.
A
6'-0"
208/120 VOLT PANELBOARD.
6'-0"
480/277 VOLT PANELBOARD.
5'-0"
COMBINATION MAGNETIC MOTOR STARTER AND NON-FUSIBLE SAFETY SWITCH, WALL
MOUNTED. NUMBER INDICATES 3-POLE/30 AMP RATING/ NEMA SIZE 0 STARTER.
3/30/0
2B-3
CIRCUIT DESIGNATION. DESIGNATION SHOWN INDICATES PANEL 2B AND CIRCUIT
NUMBER 3.
CONDUIT CONCEALED IN WALL OR ABOVE CEILING.
NOTE (ELECTRICAL ABBREVIATIONS):
1. ALL ABBREVIATIONS LISTED MAY NOT APPLY TO THIS PROJECT. REFER TO OTHER ABBREVIATION LISTS
ELSEWHERE IN THESE DOCUMENTS FOR ABBREVIATIONS NOT LISTED HERE.
SR1
SURFACE RACEWAY. NUMBER, WHERE SHOWN, INDICATES TYPE AS SCHEDULED ON
DRAWINGS OR IN SPECIFICATIONS.
CT12
CABLE TRAY, WALL MOUNTED OR SUSPENDED WITH BOTTOM MINIMUM 3" ABOVE
ACCESSIBLE CEILING OR MINIMUM 8'-6" AFF TO BOTTOM WHERE EXPOSED. CLEAR
SPACE ABOVE CABLE TRAY SHALL BE 4" MINIMUM. NUMBER INDICATES CABLE TRAY
WIDTH IN INCHES.
4"CS
CONDUIT SLEEVE, THROUGH WALL. MOUNT 3" ABOVE HIGHEST ACCESSIBLE CEILING
ON EITHER SIDE OF WALL OR MINIMUM 8'-6" AFF WHERE EXPOSED. SIZE AND
QUANTITY SHALL BE AS INDICATED ON THE DRAWINGS. BUSH CONDUITS AT EACH END.
NOTES (ELECTRICAL LEGEND):
1. THESE ARE STANDARD ELECTRICAL SYMBOLS AND MAY NOT ALL APPEAR ON THE PROJECT DRAWINGS. HOWEVER,
WHEREVER AN ELECTRICAL SYMBOL APPEARS ON THE PROJECT DRAWINGS, THE ITEM SHALL BE FURNISHED AND
INSTALLED.
UNDERSLAB BRANCH CIRCUIT CONDUITS FOR RECEPTACLES (AND FOR DATA/AV BOXES IN DESKS) SHALL HAVE NO
MORE THAN TWO (2) 90 DEGREE BENDS - ONE WHERE ENTERING THE SLAB FROM ABOVE AND ONE WHERE ENTERING
THE OUTLET FROM THE SLAB.
2. MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO TOP OF OUTLET OR EQUIPMENT, UNO. WHERE THE MOUNTING
HEIGHT INDICATED ON THE DRAWINGS IS DIFFERENT FROM THE LEGEND, THE DRAWING TAKES PRECEDENT. SEE
DRAWINGS FOR MOUNTING HEIGHTS NOT INDICATED IN THE LEGEND.
EACH EF WILL HAVE ITS OWN MOTOR OPERATED DAMPER (MOD) - POWER THE MOD FROM THE FAN CIRCUIT UNLESS
NOTED OTHERWISE. EACH EF WILL ALSO HAVE ITS OWN LINE-VOLTAGE WALL SWITCH BY DIVISION 23 - WIRE THROUGH
THESE SWITCHES.
3. SEE ELECTRICAL ABBREVIATIONS FOR ALPHABETIC SUBSCRIPT WITH SYMBOL, UNO.
CONDUITS AND SLEEVES SHOWN ON THE E3.X SERIES OF DRAWINGS ARE FOR THE OWNER'S DATA/PHONE CABLES,
BUT THEY MAY BE SHARED BY OTHER LOW-VOLTAGE SYSTEM CABLES EXCEPT FOR FIRE ALARM
DOUBLE DUPLEX
RECEPTACLE
DOUBLE-GANG BOX WITH SINGLEGANG PLASTER RING FOR DATA
CABLING (CABLING AND FINAL
FACEPLATE BY OWNER'S SEPARATE
VENDOR - PROVIDE BLANK
FACEPLATE)
DOUBLE-GANG 3-1/4" DEEP BOX
WITH WALL PLATE FOR A/V
CONNECTIONS (CABLING AND
FACEPLATE AS INDICATED ON E0.2)
DOOR
2"
3"
2"
2"
DEVICES SHOWN IN SAME
AREA ON PLANS SHALL ALIGN
VERTICALLY WITH DEVICES
ABOVE AND/OR BELOW
LIGHT SWITCH(ES)
RECEPTACLE OR
TELECOMM OUTLET
2"
1'-4" TO
BOTTOM
THERMOSTAT OR
I CALL-IN SWITCH
4'-0" TO TOP
T
2"
2" CONDUIT STUBBED UP ABOVE
NEAREST A.C.T. CEILING AND BUSHED
1" CONDUIT UP FROM FLOOR
(STUBBED UP ABOVE NEAREST A.C.T.
CEILING AND BUSHED)
RACEWAY VERTICAL TURN-UP TO CEILING.
ABOVE CEILING, PROVIDE 2" BUSHED
CONDUIT STUB FOR COMMUNICATIONS
COMPARTMENT AND 3/4" CONDUIT FOR
POWER COMPARTMENT.
NOTE: SYMBOL INDICATES 3 BOXES AT EACH LOCATION. SYMBOL IS SHOWN ON THE
POWER PLANS FOR LOCATIONS AND ON THE COMMUNICATIONS PLANS FOR REFERENCE.
7'-6" TO TOP MINIMUM
OR 8'-0" TO TOP MAXIMUM
F FIRE ALARM
NOTIFICATION DEVICE
F
2" CONDUIT UP FROM FLOOR
(STUBBED UP ABOVE NEAREST A.C.T.
CEILING AND BUSHED)
SYMBOL
3
DETAIL - IN DESK
MODULE FRAME WITH TWO KEYSTONE PORTS
FOR A/V CONNECTIONS AS INDICATED ON E0.2
FINISHED
FLOOR
RECORDEX INFINIX SCM PROJECTOR MOUNTING KIT
FURNISHED BY OWNER AND INSTALLED BY THIS
CONTRACTOR, SET BACK APPROXIMATELY 10 FEET FROM
TEACHING WALL (COORDINATE EXACT LOCATION WITH
OWNER). SUPPORT UNIT FROM STRUCTURE AND NOT
FROM CEILING. INSTALL ONLY THE PLATE AND THE
RECEPTACLE (NOT THE PIPE OR PROJECTOR).
FRAME/BRACKET FOR DATA
CONNECTIONS (DATA
CONNECTIONS TO BE PROVIDED BY
OWNER'S SEPARATE VENDOR)
2"
1" CONDUIT
18" AFF TO CENTER
NOTE:
DOUBLE-GANG BOX WITH SINGLE-GANG
PLASTER RING (CABLING AND FACEPLATE
AS INDICATED ON E0.2)
DUPLEX RECEPTACLE
- NOT ALL DEVICES SHOWN ARE USED IN ALL LOCATIONS. REFER TO THE ELECTRICAL FLOOR PLANS
FOR DEVICE LOCATIONS.
- WHERE DEVICE HEIGHTS INDICATED ON FLOOR PLANS ARE DIFFERENT FROM WHAT IS SHOWN IN
THE DETAIL, THE HEIGHTS INDICATED ON FLOOR PLANS SHALL TAKE PRECEDENCE.
- DEVICES SHOWN SIDE-BY-SIDE ON THE PLANS THAT ARE NOT GANGED TOGETHER SHALL HAVE 2"
OF SEPARATION BETWEEN THE FACEPLATES UNLESS NOTED OTHERWISE OR UNLESS MORE
SEPARATION IS REQUIRED TO MAINTAIN FIRE RATING OF WALL.
- FOR WALL DEVICES MOUNTED ABOVE ARCHITECTURAL ITEMS (SUCH AS FIRE ALARM STROBES
MOUNTED ABOVE MARKERBOARDS, TACKBOARDS OR SMARTBOARDS), COORDINATE MOUNTING
HEIGHTS OF WALL DEVICES SUCH THAT THEY DO NOT INTERFERE WITH ARCHITECTURAL ITEMS.
A/V CONNECTIONS AS INDICATED ON E0.2
DUPLEX RECEPTACLES
FLOOR
EMPTY KNOCKOUT (DO NOT
CUT CEILING TILE)
PROVIDE DUPLEX RECEPTACLE IN
KNOCKOUT (CUT CEILING TILE)
TYPICAL WALL DEVICE LOCATION DETAIL
NO SCALE
DOUBLE-GANG 3-1/4" DEEP BOX (CABLING
AND FACEPLATE AS INDICATED ON E0.2)
DUPLEX RECEPTACLE
NO SCALE
NOTE: SYMBOL IS SHOWN ON THE POWER
PLANS FOR LOCATIONS AND ON THE
COMMUNICATIONS PLANS FOR REFERENCE.
SYMBOL
NO SCALE
1
DETAIL
RETURN DUCT
CHASE WALL
BEHIND
TEACHER'S DESK
IF THERE IS NO RETURN DUCT CHASE ON THE FLOOR PLAN WHERE THE RACEWAY TURN-UP TO THE CEILING IS
SHOWN IN THIS DETAIL, PROVIDE A VERTICAL RACEWAY TURN-UP TO THE CEILING WHERE INDICATED ON THE
DRAWINGS, WITH A 2" COMMUNICATIONS AND A 3/4" POWER CONDUIT TRANSITION TO RACEWAY ABOVE THE CEILING.
SYMBOL
NO SCALE
3
DETAIL - IN SURFACE RACEWAY
NOTE: SYMBOL INDICATES 4 BOXES AT
EACH LOCATION. UPPER BOXES SHALL
BE AT 7'-0" AFF TO BOTTOM, AND
LOWER BOXES SHALL BE 16" AFF TO
BOTTOM, UNLESS NOTED OTHERWISE.
SYMBOL IS SHOWN ON THE POWER
PLANS FOR LOCATIONS AND ON THE
COMMUNICATIONS PLANS FOR
REFERENCE.
SYMBOL
NO SCALE
CONST.
NORTH
MM-DD-YR
NAME
DESCRIPTION OF CHANGES
232 HORNET ROAD, FISHERSVILLE , VA 22939
SEE SPECIFICATION SECTION 26 0519 FOR REQUIREMENTS REGARDING OVERSIZING CONDUCTORS FOR 1-POLE 15AND 20-AMP CIRCUITS TO REDUCE VOLTAGE DROP. OVERSIZED CONDUCTORS FOR VOLTAGE DROP ON OTHER
CIRCUITS ARE INDICATED IN THE PANEL SCHEDULES.
DESCRIPTION
AUGUSTA COUNTY PUBLIC SCHOOLS
4.
SYMBOL
WILSON MIDDLE SCHOOL ADDITIONS
WHERE MULTIPLE CIRCUITS ARE COMBINED IN A SINGLE CONDUIT, DERATE CONDUCTORS PER THE NEC.
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
INITIAL
JUNCTION BOX
THOUSAND CIRCULAR MILS
KNOCKOUT
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT-HOUR
LIGHTNING ARRESTER
LIGHT EMITTING DIODE
LOW PRESSURE SODIUM
LIGHTING RELAY PANEL
LIGHTING
LUMENS OR LUMINAIRE
MAGNETIC
MANUAL
MASTER ANTENNA TELEVISION
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
THOUSAND CIRCULAR MILS
MOTOR/GENERATOR
METAL HALIDE OR MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MANUAL MOTOR STARTER
MASS NOTIFICATION SYSTEM
MOTOR OPERATED DAMPER
MOTOR
MAGNETIC STARTER
MOUNTED OR MOUNTING
METER
MERCURY VAPOR
NORMAL
NATIONAL ELECTRICAL CODE
NEUTRAL
NON-FUSIBLE SAFETY SWITCH
NIGHT LIGHT
NUMBER
OVERHEAD
POLE
PULL BOX OR PUSHBUTTON
PUSHBUTTON STATION
PHASE
PANEL OR PANELBOARD
PANELBOARD
PRIMARY
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
POWER
QUANTITY
RELAY BASE
RECEPTACLE
REFRIGERATOR
RIGID GALVANIZED STEEL CONDUIT
SPACE ONLY
SOUNDER BASE
SHORT CIRCUIT CURRENT RATING
MOTOR OPERATED SMOKE DAMPER
SECONDARY
SINGLE STATION
SURFACE METAL RACEWAY
SOLID NEUTRAL
SPECIAL PURPOSE
SURGE PROTECTIVE DEVICE
SPEAKER
SURFACE RACEWAY
SURGE SUPPRESSOR
STARTER
SWITCH
SWITCHBOARD
SWITCHGEAR
SYMMETRICAL
TIME CLOCK
TELEPHONE
TAMPER RESISTANT
TELEVISION
TYPICAL
UNDERCOUNTER
UNDERFLOOR
UNDERGROUND
UNDERWRITERS' LABORATORIES
UNLESS NOTED OTHERWISE
VOLT
VOLT-AMPERE
VOLT-AMPERE REACTIVE
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLTMETER
WATT OR WIRE
WEATHERPROOF
TRANSFER
TRANSFORMER
www.cra-architects.com
3.
IMC
INC
INIT
JB
KCMIL
KO
KV
KVA
KVAR
KW
KWH
LA
LED
LPS
LRP
LTG
LUM
MAG
MAN
MATV
MCB
MCC
MCM
M/G
MH
MIN
MLO
MMS
MNS
MOD
MOT
MS
MTG
MTR
MV
N OR NORM
NEC
NEUT
NFSS
NL
NO
OH
P
PB
PBS
PH
PNL
PNLBRD
PRI
PT
PVC
PWR
QTY
RB
REC
REFRIG
RGS
S/O
SB
SCCR
SDR
SEC
SL
SMR
SN
SP
SPD
SPKR
SR
SS
STR
SW
SWBD
SWGR
SYM
TC
TEL
TR
TV
TYP
UC
UF
UG
UL
UNO
V
VA
VAR
VERT
VFD
VM
W
WP
XFER
XFMR
MECHANICSBURG PA 17055
717-458-0272 FAX 717-458-0047
CAREFULLY COORDINATE ALL ELECTRICAL EQUIPMENT LOCATIONS WITH DUCTWORK, PIPING AND MECHANICAL
EQUIPMENT. MAINTAIN ALL CLEARANCES AND SPACES REQUIRED BY THE NEC.
AMPERE
ABANDONED
ABOVE
ALTERNATING CURRENT
ABOVE COUNTER BACKSPLASH
ARC FAULT INTERRUPTER
ADJUSTABLE FREQUENCY DRIVE
ABOVE FINISHED FLOOR
AMPERES INTERRUPTING CAPACITY
ABANDONED IN PLACE
ALUMINUM
AMMETER
AMPLIFIER
ASYMMETRICAL
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAGE
BUILDING AUTOMATION SYSTEM
BELOW
BUS DUCT
BOTTOM
BREAKER
COUNTERTOP
CABLE
CABINET
CABLE TV
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
COMPACT FLUORESCENT
CIRCUIT
CEILING
CONDUIT
CENTER
COMBINATION
CONDUCTOR
CONNECTION
CONTACTOR
CORROSION RESISTANT
CURRENT TRANSFORMER
CONTROL
COPPER
COLD WATER
DOOR BELL
DIRECT CURRENT
DIMENSION
DISCONNECT
DOOR RELEASE SERVICE
DOOR SWITCH
DRAWING
EMERGENCY
EXIST CND AND NEW CONDS
EXIST RELOCATED TO THIS LOCATION
ELECTRIC OR ELECTRICAL
ELEVATOR
EXIST REMOVED
EXIST REMOVED AND RELOCATED
EXIST REMOVED AND NEW INSTALLED
ELECTRICAL METALLIC TUBING
ENCLOSURE
ENGINE
EXPLOSIONPROOF
EQUIPMENT
EXIST TO REMAIN
ELEVATOR RECALL
ELECTRIC WATER COOLER
EXISTING
EXTERIOR
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIRE ALARM CONTROL UNIT
FEEDER
FOOTCANDLE
FLUORESCENT
FIRE/SMOKE DAMPER
FUSIBLE SAFETY SWITCH
FIXTURE
GARAGE DOOR
GENERATOR
GROUND FAULT INTERRUPTER
GROUND FAULT PROTECTION/PROTECTED
GROUND
GENERATOR TRANSFER DEVICE
HORIZONTAL
HOSPITAL GRADE
HEIGHT
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSEPOWER OR HEAT PUMP
HIGH POWER FACTOR
HIGH PRESSURE SODIUM
HEATER
HOT WATER
HERTZ
INTERCOM OR INTERRUPTING CAPACITY
ISOLATED GROUND
CHARLOTTESVILLE VA 22902
434-975-7262 FAX 434-975-7263
2.
MTG. HGT.
A OR AMP
ABD
ABV
AC
ACB
AF OR AFI
AFD
AFF
AIC
AIP
AL
AM
AMPL
ASYM
ATS
AWG
BAS
BEL
BD
BOT
BRKR
C
CA
CAB
CATV
CB
CCTV
CF
CKT
CLG
CND
CNTR
COMB
COND
CONN
CONT
CR
CT
CTRL
CU
CW
DB
DC
DIM
DISC
DR
DS
DWG
E OR EMER
ECNC
EL
ELEC
ELEV
EM
EML
EMN
EMT
ENCL
ENG
EP
EQUIP
ER
ERC
EWC
EXIST
EXT
FA
FACP
FACU
FDR
FC
FLUOR
FSD
FSS
FXTR
GD
GEN
GF OR GFI
GFP
GND
GTD
H OR HOR
HG
HGT
HID
HOA
HP
HPF
HPS
HTR
HW
HZ
IC
IG
09.28.15
401 EAST WINDING HILL ROAD
LOAD SIDE CONDUCTOR AND CONDUIT SIZES FROM DISCONNECT SWITCHES AND STARTERS TO EQUIPMENT SHALL BE
THE SAME AS LINE SIDE CONDUCTORS AND CONDUIT.
250 WEST MAIN STREET, SUITE 200
1.
ELECTRICAL LEGEND
ELECTRICAL ABBREVIATIONS
CRABTREE ROHRBAUGH & ASSOCIATES - ARCHITECTS
GENERAL NOTES :
2"
TW = TEACHING WALL
TW
DETAIL
ELECTRICAL LEGEND,
ABBREVIATIONS, GENERAL
NOTES AND DETAILS
PROJECT
2846
PLOT SCALE:
NO SCALE
FILENAME:
E0.1
DATE:
SEPTEMBER 28, 2015
VDOE: 008-47-00-101
09.28.15
LIGHTING LEVEL SUMMARY
SPACE
ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS
PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.
CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND
OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION
OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF
CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE
UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.
© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2015, 2016
AVERAGE FOOT-CANDLE LEVEL
CLASSROOM, LAB, PREP
50-60
CORRIDOR, STORAGE
15-20
PANEL 2LAA1
EWC RECEPTACLE
20/1
RECEPTACLES
#12
#12
1/2"
1.44
#12
#12
#12
1/2"
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
DEMO BENCH RECEPTACLE
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
FUME HOOD
20/1
#12
#12
#12
1/2"
GOGGLE CABINET RECEPTACLE
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
EF-A8 & A9
20/1
#12
#12
#12
1/2"
EF-A10 & MOD
15/1
#12
#12
#12
1/2"
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
L3
.7
1.44
1.44
.9
.18
.72
.72
.54
.54
.3
.18
.9
.54
.36
1.39
.53
-
GND
COND
L1
#12
#12
1/2"
1.44
#12
#12
#12
1/2"
20/1
#12
#12
#12
1/2"
RECEPTACLE
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
DEMO BENCH RECEPTACLE
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
REF-SCI1 RECEPTACLE
20/1
#12
#12
#12
1/2"
GOGGLE CABINET RECEPTACLE
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPACE ONLY
-
-
-
-
-
SPACE ONLY
-
-
-
-
-
SPACE ONLY
-
-
-
-
-
CKT
LOAD SERVED
BKR
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
RECEPTACLES
20/1
#12
EWC RECEPTACLE
20/1
RECEPTACLES
PHASE NEUT
PHASE LOAD TOTALS
LOADS ( KVA)
0
10
9.08
0
0
DEMAND
FACTOR
1.25
1.0
0.5
0.0
1.0
3.32
.7
0
1.0
0.25
1.0
CONNECTED
LIGHTING
REC TO 10 KVA
REC REMAINING
SPACE HEATING
AIR CONDITIONING
NON-SEASONAL MOTORS
LARGEST MOTOR
WATER HEATING
DEMAND
LOADS (KVA)
CONNECTED
0
10
4.54
0
0
KITCHEN EQUIPMENT
CONTINUOUS
NON-CONTINUOUS
DEMAND
3.32
.17
0
TOTAL CONNECTED LOAD
MIN. FEEDER / PANEL CAPACITY
OVERALL DEMAND FACTOR
0
0
.3
0
DEMAND
FACTOR
1.0
1.25
1.0
1.0
22.7
18.3
0.81
L2
L3
.7
1.44
.72
.9
FXTR TYPE
A1
A2
B1
C1
D1
MOUNTING
RECESSED
RECESSED
RECESSED
SUSPENDED
WALL
X1
X2
CEILING
CEILING
LAMP (NO.) TYPE
(3) F32T8
(2) F32T8
(3) F32T8
(2) F32T8
APPROX. 3600
LUMEN LED
LED
LED
MANUFACTURER & CATALOG NUMBER (BASIS OF DESIGN)
COLUMBIA P424-332G-MA38-S-3EPU
COLUMBIA P424-232G-MA28-S-EPU
COLUMBIA 4PS24-332G-FSA12125-EPU
COLUMBIA CSR4-232-U-EPU-CSRWG-CSHC
SPAULDING TRP-30L4K-035-3-U-BZ
REMARKS
PROVIDE ONE 3-LAMP BALLAST
PROVIDE DUAL BALLASTS
PROVIDE WIRE GUARD AND CHAIN HANGER
BOTTOM OF FIXTURE SHALL BE 11'-6" ABOVE
FINISHED GRADE, U.N.O.
MAIN: 100A MLO
BUS RATING: 100A
GROUND BUS: YES
.18
.72
A
.72
.54
.54
HOT NEUTRAL
.18
.18
PROJECT
NORTH
.54
.54
.54
-
24VDC
OCCUPANCY
SENSOR
(TYPE 'O1')
CONTROL
COMMON
BLACK
+24VDC
RED
LOCAL SW
ORANGE
MANUAL ON
BLUE
COMMON
BLACK
POWER
PACK
THIS DIAGRAM APPLIES TO ALL ROOMS SHOWN WITH SWITCH THAT HAS
SUBSCRIPT "L1", IN ORDER TO ACHIEVE VACANCY SENSOR OPERATION
PER THE 2012 VIRGINIA ENERGY CONSERVATION CODE. ROOMS WITH A
SWITCH THAT HAS A SUBSCRIPT "L1" WITH NO DUAL-BALLAST FIXTURES
HAVE A SEPARATELY CONTROLLED DAYLIGHT ZONE PER THE 2012
VIRGINIA ENERGY CONSERVATION CODE. 24VDC WIRE SIZES SHALL BE AS
RECOMMENDED BY THE MANUFACTURER; DEPENDING ON THE
MANUFACTURER, THERE MAY BE VARIATIONS IN THE REQUIRED WIRING
SCHEME. SEE SPECIFICATION SECTION 26 09 23.
RED
RED
LOAD a
10.39
6.73
5.58
2-BUTTON MOMENTARY
CONTACT SWITCH (SWITCH
WITH "L1" SUBSCRIPT) - EACH
BUTTON FOR TOGGLING A LOAD
WHITE
POWER
PACK
COND
L1
#12
#12
1/2"
2.02
#12
#12
#12
1/2"
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
LOAD SERVED
BKR
1
3
5
7
9
11
NEW ADDITION LIGHTING
20/1
#12
NEW ADDITION LIGHTING
20/1
SPARE
PHASE NEUT
L2
L3
2.4
-
+24VDC
RED
BLACK
LOCAL SW
ORANGE
RED
MANUAL ON
BLUE
RED
4.42
9.74
0
0
0
DEMAND
FACTOR
1.25
1.0
0.5
0.0
1.0
2.15
.92
0
1.0
0.25
1.0
CONNECTED
0
0
.3
0
SCALE: NONE
63.1
50.9
KVA
KVA
AMPS
AMPS
PRIMARY
A
CKT
LOAD SERVED
BKR
2
4
6
8
10
12
XFMR T-2LBB
25/3
#10
''
-
''
GND
COND
L1
-
#10
1/2"
5.04
#10
-
-
-
-
#10
-
-
-
EF-B5
15/3
#12
-
#12
1/2"
''
-
#12
-
-
-
''
-
#12
-
-
-
LIGHTING
REC TO 10 KVA
REC REMAINING
SPACE HEATING
AIR CONDITIONING
NON-SEASONAL MOTORS
LARGEST MOTOR
WATER HEATING
LOADS (KVA)
CONNECTED
5.53
9.74
0
0
0
KITCHEN EQUIPMENT
CONTINUOUS
NON-CONTINUOUS
DEMAND
2.15
.23
0
TOTAL CONNECTED LOAD
MIN. FEEDER / PANEL CAPACITY
OVERALL DEMAND FACTOR
0
0
0
0
PHASE NEUT
DEMAND
FACTOR
1.0
1.25
1.0
1.0
16.3
17.7
1.08
L2
MAIN: 60A MCB
BUS RATING: 100A
GROUND BUS: YES
CKT
LOAD SERVED
BKR
1
3
5
7
9
11
13
15
17
19
21
23
RECEPTACLES
20/1
#12
RECEPTACLES
20/1
GOGGLE CABINET RECEPTACLE
COND
L1
#12
#12
1/2"
1.44
#12
#12
#12
1/2"
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
DEMO BENCH RECEPTACLE
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
COUNTERTOP RECEPTACLES
20/1
#12
#12
#12
1/2"
L2
L3
1.44
.2
.9
.18
.72
.72
.54
.54
.54
.54
.54
LIGHTING
REC TO 10 KVA
REC REMAINING
SPACE HEATING
AIR CONDITIONING
NON-SEASONAL MOTORS
LARGEST MOTOR
WATER HEATING
0
9.74
0
0
0
DEMAND
FACTOR
1.25
1.0
0.5
0.0
1.0
1.22
.7
0
1.0
0.25
1.0
CONNECTED
DEMAND
2
.31
N
.31
.31
7.37
6.63
A
AMPS
AMPS
SECONDARY
GROUNDING ELECTRODE CONDUCTOR
GND
COND
L1
#12
#12
1/2"
1.44
#12
#12
#12
1/2"
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPARE
20/1
-
-
-
-
SPACE ONLY
-
-
-
-
-
SPACE ONLY
-
-
-
-
-
SPACE ONLY
-
-
-
-
-
2
4
6
8
10
12
14
16
18
20
22
24
RECEPTACLES
20/1
#12
EF-B10 & B11
20/1
SPARE
1.22
.17
0
TOTAL CONNECTED LOAD
MIN. FEEDER / PANEL CAPACITY
OVERALL DEMAND FACTOR
C
CONNECTED
0
0
0
0
11
11.1
1.02
BONDING JUMPERS AND
GROUNDING ELECTRODE
CONDUCTORS SHALL BE
#8 COPPER
NEAREST GROUNDING ELECTRODE
PER 2011 NEC 250.30(A)(4),
INCLUDING EXCEPTION NO. 1
BKR
KITCHEN EQUIPMENT
CONTINUOUS
NON-CONTINUOUS
DEMAND
B
SUPPLY-SIDE BONDING JUMPER
19.6
21.2
KVA
KVA
LOAD SERVED
0
9.74
0
0
0
TRANSFORMER
ENCLOSURE
2.31
0
0
0
0
CKT
LOADS (KVA)
EQUIPMENT GROUNDING CONDUCTOR
FROM PRIMARY FEEDER
DEMAND
PHASE NEUT
PHASE LOAD TOTALS
LOADS ( KVA)
C
3.92
INTEGRAL SPD: NO
MOUNTING: SURFACE
INTERRUPT RATING: 10,000 AIC
GND
PHASE NEUT
B
L3
PANEL 2LBB1
VOLTAGE: 208Y/120V
SYSTEM: 3PH, 4W
SOLID NEUTRAL: YES
DEMAND
FACTOR
1.0
1.25
1.0
1.0
KVA
KVA
MM-DD-YR
NAME
DESCRIPTION OF CHANGES
LOAD b
TYPICAL MULTI-LEVEL CEILING VACANCY SENSOR WIRING DIAGRAM
PHASE LOAD TOTALS
DEMAND
01
DEMAND
NOTE 1. PROVIDE LOCKABLE BREAKER(S) FOR CIRCUIT(S) 2
LOADS ( KVA)
REVISIONS
BLACK
-
CONST.
NORTH
WHITE
-
INTEGRAL SPD: YES
MOUNTING: SURFACE
INTERRUPT RATING: 18,000 AIC
GND
CKT
C
DUAL-LITE SE S R W
DUAL-LITE SE D R W
PANEL 2HB2
VOLTAGE: 480Y/277V
SYSTEM: 3PH, 4W
SOLID NEUTRAL: YES
B
L2
GROUND
L3
NEUTRAL
1.22
SYSTEM BONDING JUMPER
-
SUPPLY-SIDE BONDING JUMPER
-
DRY-TYPE TRANSFORMER CONNECTION SCHEMATIC
SCALE: NONE
5.04
3.92
FOR POSSIBLE FUTURE PROJECTOR
(NO CABLING INSTALLED AT THIS TIME)
2
1
RG6 COAXIAL CABLE FROM CORRIDOR
INDICATED ON FLOOR PLANS
DEMAND
0
0
0
0
30.4
30.9
FIRST SECONDARY
DISCONNECTING
MEANS ENCLOSURE
TW (UPPER A/V BOX)
AMPS
AMPS
A/V RUNNER CABLES: LEGRAND RAPIDRUN 2212-6000X-LLL MULTI-FORMAT AND
2212-60XXX-LLL OPTICAL
EMPTY CONDUIT
VGA, HDMI, RCA AUDIO/VIDEO, 3.5MM STEREO
IN DESK: LEGRAND RAPID-RUN 2212-60080-001 WITH
KEYSTONE PORT AND DECORA OPENING; 2212-60151-001
HDMI DECORA-STYLE TX WITH KEYSTONE PORT; BLANK
INSTALLED IN EACH KEYSTONE PORT
IN SURFACE RACEWAY: LEGRAND RAPID-RUN 2212-60039-001
WITH 2601-03345-ADT HDMI KEYSTONE INSERT AND 221260130-001 HDMI TX FLYING LEAD; BLANK INSTALLED IN EACH
KEYSTONE PORT IN SEPARATE FACEPLATE IN RACEWAY
3 (A/V BOX)
VGA, HDMI, RCA AUDIO/VIDEO, 3.5MM STEREO, USB.
LEGRAND RAPID-RUN 2212-60080-001 WITH KEYSTONE PORT AND DECORA
OPENING; 2601-60160-001 HDMI PASS-THRU DECORA WALLPLATE WITH 2
KEYSTONE PORTS, WITH ONE KEYSTONE PORT TAKEN BY 2601-28751-ADT
USB INSERT; 2212-60131-001 OPTICAL RX FLYING LEAD.
TWO KEYSTONE PORTS REMAIN - PROVIDE A COAXIAL RG6 TERMINATION
IN ONE KEYSTONE PORT, AND THE OWNER'S SEPARATE VENDOR WILL
PROVIDE A DATA CABLE TERMINATION IN THE OTHER KEYSTONE PORT.
INSTALL OWNER-FURNISHED TV (65"-72") AND MOUNTING BRACKET AT
HEIGHT DIRECTED BY OWNER.
232 HORNET ROAD, FISHERSVILLE , VA 22939
#12
L2
AUGUSTA COUNTY PUBLIC SCHOOLS
20/1
L1
WILSON MIDDLE SCHOOL ADDITIONS
RECEPTACLES
COND
www.cra-architects.com
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
GND
PHASE NEUT
MECHANICSBURG PA 17055
717-458-0272 FAX 717-458-0047
BKR
CHARLOTTESVILLE VA 22902
434-975-7262 FAX 434-975-7263
LOAD SERVED
LIGHTING FIXTURE SCHEDULE
401 EAST WINDING HILL ROAD
CKT
KEY PLAN
INTEGRAL SPD: NO
MOUNTING: SURFACE
INTERRUPT RATING: 10,000 AIC
250 WEST MAIN STREET, SUITE 200
MAIN: 100A MCB
BUS RATING: 100A
GROUND BUS: YES
CRABTREE ROHRBAUGH & ASSOCIATES - ARCHITECTS
VOLTAGE: 208Y/120V
SYSTEM: 3PH, 4W
SOLID NEUTRAL: YES
TW (LOWER A/V BOX)
INSTALL BLANK FACEPLATE
(NO CABLING TO THIS BOX)
THIS SETUP APPLIES TO ALL 12 NEW CLASSROOMS/LABS. PROVIDE SUFFICIENT SLACK IN CABLES FROM TEACHER'S DESK TO TV SUCH
THAT THE CABLES COULD BE RE-ROUTED TO THE PROJECTOR LOCATION IN THE FUTURE. PROVIDE SUFFICIENT SLACK IN RG6 CABLE
TO TV SUCH THAT IT COULD BE RE-ROUTED TO THE TEACHER'S DESK IN THE FUTURE.
ALL CABLE LENGTHS SHALL BE DETERMINED BY CONTRACTOR. COORDINATE ALL FACEPLATE AND DEVICE COLORS WITH ARCHITECT.
FOR SURFACE RACEWAY APPLICATIONS, CONTRACTOR SHALL ENSURE COMPATIBILITY OF FACEPLATES WITH RACEWAY. CONTRACTOR
SHALL MOCK-UP ONE ROOM FOR OWNER'S APPROVAL BEFORE DOING THE A/V INSTALLATION IN THE REST OF THE ROOMS.
A/V ROOM SETUP DIAGRAM
NO SCALE
SCHEDULES, LIGHTING
CONTROLS, TRANSFORMER
SCHEMATIC AND A/V DIAGRAM
PROJECT
2846
PLOT SCALE:
NO SCALE
FILENAME:
E0.2
DATE:
SEPTEMBER 28, 2015
VDOE: 008-47-00-101
09.28.15
ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS
PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.
CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND
OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION
OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF
CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE
UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.
© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2015, 2016
KEY PLAN
B
B
C
A
A
PROJECT
NORTH
CONST.
NORTH
REVISIONS
01
b
b
b
a
a
a
MM-DD-YR
NAME
DESCRIPTION OF CHANGES
O2 2HA2-21
CONNECT TO EXISTING EXIT SIGN CIRCUIT WITH
2 #12 AND 1 #12 GROUND IN 1/2" CONDUIT
S O1
2HA2-21
S L1
a
a
CONNECT IN SERIES WITH NON-EMERGENCY
TYPE A2 FIXTURES IN THIS CORRIDOR
C1
a
A1 TYP
STORAGE
A105
A
SS
B1 TYP
O1 2HA2-21
a
a
a
PREP
A107
O2 2HA2-21
SCIENCE LAB
A106
b
CIRCUITS 2HA2-19 AND 21 ARE CURRENTLY EMPTY SPACES. ADD
NEW 20A/1P BREAKERS IN THESE SPACES (AIC TO MATCH EXISTING),
AND CONNECT WITH 2 #12 AND 1 #12 GROUND IN 1/2" CONDUIT.
REMOVE AND REPLACE EXISTING
EXIT SIGN IN THIS VICINITY, AND
RECONNECT TO EXISTING CIRCUIT
X2
CONNECT TO EXISTING EXIT SIGN CIRCUIT WITH
2 #12 AND 1 #12 GROUND IN 1/2" CONDUIT
A1 TYP
A1 TYP
S L1
b
S L1
b
A2 TYP
b
a
a
a
2HA2-19
a
b
CONNECT IN SERIES WITH NON-EMERGENCY
TYPE A2 FIXTURES IN THIS CORRIDOR
O2
O1 2HA2-19
b
a
2HA2-19 O1
a
a
CORRIDOR
A101
b
a
D1
CLASSROOM
A103
a
SCALE: 1/8" = 1'-0"
b
CONNECT TO EXISTING CORRIDOR EMERGENCY LIGHTING
CIRCUIT WITH 2 #12 AND 1 #12 GROUND IN 1/2" CONDUIT
CLASSROOM
A102
a
a
D1
a
D1
REMOVE 3 LIGHTING BOLLARDS NEAR THIS ADDITION'S FOOTPRINT. PROVIDE 6" QUAZITE BOXES IN THE GROUND TO
SPLICE EXISTING CONDUCTORS TO MAINTAIN CIRCUIT CONTINUITY. EXTEND EXISTING BOLLARD LIGHT CIRCUIT TO
THE 4 NEW TYPE D1 FIXTURES (MATCH EXISTING WIRING) IN 3/4" CONDUIT CONCEALED IN EXTERIOR WALL.
FIRST FLOOR PLAN - UNIT A - LIGHTING
C
232 HORNET ROAD, FISHERSVILLE , VA 22939
CORRIDOR
A104
AUGUSTA COUNTY PUBLIC SCHOOLS
CONNECT TO EXISTING CORRIDOR
EMERGENCY LIGHTING CIRCUIT WITH 2 #
12 AND 1 #12 GROUND IN 1/2" CONDUIT
A2 TYP
REMOVE AND REPLACE EXISTING
EXIT SIGN IN THIS VICINITY, AND
X2
RECONNECT TO EXISTING CIRCUIT
WILSON MIDDLE SCHOOL ADDITIONS
S L1
www.cra-architects.com
a
MECHANICSBURG PA 17055
717-458-0272 FAX 717-458-0047
a
CHARLOTTESVILLE VA 22902
434-975-7262 FAX 434-975-7263
a
401 EAST WINDING HILL ROAD
A1 TYP
250 WEST MAIN STREET, SUITE 200
CLASSROOM
A108
CRABTREE ROHRBAUGH & ASSOCIATES - ARCHITECTS
O1 2HA2-21
b
D1
FIRST FLOOR PLAN - UNIT A LIGHTING
PROJECT
2846
PLOT SCALE:
1/8" = 1'-0"
FILENAME:
E1.1
DATE:
SEPTEMBER 28, 2015
VDOE: 008-47-00-101
09.28.15
ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS
PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.
CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND
OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION
OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF
CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE
UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.
© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2015, 2016
EL
INSTALL NEW FIXTURE ABOVE WINDOWS AND
BELOW SECOND FLOOR ADDITION. FEED FROM
SAME CIRCUIT AS EXISTING FIXTURE SHOWN,
WITH 2 #12 AND 1 #12 GROUND IN 1/2" CONDUIT
(RUN AS INCONSPICUOUSLY AS POSSIBLE)
KEY PLAN
D1
EXISTING LIGHTING FIXTURE IN THIS LOCATION
(BESIDE DOOR) TO BE RELOCATED TO NEW
COLUMN INDICATED, AT SAME HEIGHT AS
EXISTING LOCATION. EXTEND EXISTING
CONDUIT AND WIRE (MATCH EXISTING WIRING)
AS INCONSPICUOUSLY AS POSSIBLE.
B
C
A
PROJECT
NORTH
CONST.
NORTH
REVISIONS
232 HORNET ROAD, FISHERSVILLE , VA 22939
AUGUSTA COUNTY PUBLIC SCHOOLS
WILSON MIDDLE SCHOOL ADDITIONS
MECHANICSBURG PA 17055
717-458-0272 FAX 717-458-0047
CHARLOTTESVILLE VA 22902
434-975-7262 FAX 434-975-7263
www.cra-architects.com
DESCRIPTION OF CHANGES
401 EAST WINDING HILL ROAD
C
NAME
250 WEST MAIN STREET, SUITE 200
B
MM-DD-YR
CRABTREE ROHRBAUGH & ASSOCIATES - ARCHITECTS
01
B
A
FIRST FLOOR PLAN - UNIT B LIGHTING
FIRST FLOOR PLAN - UNIT B - LIGHTING
SCALE: 1/8" = 1'-0"
PROJECT
2846
PLOT SCALE:
1/8" = 1'-0"
FILENAME:
E1.2
DATE:
SEPTEMBER 28, 2015
VDOE: 008-47-00-101