XS Fan Module

advertisement
XS Fan Module
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
Supply/Extract Units
Installation and Maintenance
E
Introduction
General
The Nuaire XS Fan Module is available in 6, 9 and 12 inch
impeller sizes suitable for supply or extract.
An internal grille assembly is included for use if required.
Ensure adequate air replacement for the fan and any fuel
burning appliance in the room.
The external rotor motor makes for simple removal of the
push-on impeller for easy cleaning. The fan is IP24 splash proof
approved with the motor rated at IP44.
Fig 1 Fan module and internal grille.
Removing the Grille
All external components are made in soft grey colours from
ultra violet stable ABS material so they will blend with most
decors and will not fade in sunlight.
The Fan Module is supplied complete with an inlet grille.
To remove the grille, remove the two lower grille fixings. The
grille can now be lifted upwards to clear the top lip retainer and
removed.] Re-fitting the grille is the reverse of this procedure.
Fan Module
Internal grille
Coding for Fan Modules
Description
6 inch Fan Module
9 inch Fan Module
12 inch Fan Module
6 inch Refurb Kit
9 inch Refurb Kit
12 inch Refurb Kit
Code
XS6
XS9
XS12
XS6RE
XS9RE
XS12RE
General Applications
Switching
The Nuaire XS Fan Module can be used as a direct replacement spare for any of the XS Fan Installation Kits available
from Nuaire. Remember to specify fan size 6, 9 or 12inch.
Operated via a separately wired 3 amp fused spur (by others)
or operated via the optional XS-MFC remote controller allowing
supply or extract, variable speed and automatic or manual
switching of several fans if desired.
The XS Fan Installation Kits available are as follows:
XS Window Fan Kit
XS Wall Fan Kit
XS Ceiling Fan Kit
XS Roof Fan Kit
Sensors
Sensors are available as remote units or integral ‘plug in’ units.
They are able to control multiple fans, depending on sensor and
fan types. Integral sensors are quick and easy to install and
are aesthetically pleasing, whilst remote sensors give the
benefit of location close to the pollutant source.
Remote sensors can be fitted with an optional security strap to
prevent unwanted tampering.
Other applications
1). In Line installation (using Duct Kit from Nuaire
Code: XS-IDK) See page 7 for details.
2). Plate Installation fixing the Fan Module face direct
to a wall.
3). Retro fit into an existing wall aperture/outlet louvre.
Page 5.
Dimensions of Fan Module (mm) Fig 2.
A
C
Fixing
Holes
XS6 Fan Module
XS9 Fan Module
XS12 Fan Module
B
FRONT VIEW
(Leaflet 671050)
(Leaflet 671051)
(Leaflet 671052)
(Leaflet 671053)
A
269
342
420
B
272
342
420
C
140
150
170
SIDE VIEW
Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk
1
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Electrical wiring instructions
Electrical work should be undertaken by a qualified electrician
in accordance with the wiring regulations.
1
2
Release the electrical panel from the fan plate.
Remove the terminal cover.
3
4
Clamp the cable and complete the connections.
Refit terminal cover before replacing the electrical panel.
Wiring
Isolation - Before commencing work make sure
that the unit is electrically isolated from the mains supply.
2
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
XS6 Consumption and weight
Electrical Wiring cont.
Input Power
Watts
Model
Max.
Weight
kg
Economy
XS6 supply + extract
38
Note figures are for extract only.
20
4.1
Electrical Specification
230V ~ 50Hz Class I. Motor thermally protected by overload
device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from
a 5A lighting circuit, no local fuse is required).
XS9 Consumption and weight
Input Power
Watts
Model
Max.
XS9 supply + extract
Weight
kg
Economy
50
37
5.7
Note figures are for extract only
Electrical Specification
230V ~ 50Hz Class I. Motor thermally protected by overload
device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from
a 5A lighting circuit, no local fuse is required).
XS12 Consumption and weight
Model
Input Power
Watts
Weight
kg
Max. Economy
XS12 supply + extract
100
Note figures are for extract only
70
8.6
Electrical Specification
230V ~ 50Hz Class I. Motor thermally protected by overload
device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from
a 5A lighting circuit, no local fuse is required).
(Shutter Operation XS fans)
There will be a short delay on startup and shutdown of
approximately 40 seconds. This is normal.
3
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Fitting Remote Controller XS-MFC
or Remote Sensors (optional)
1
The XS-MFC Multi Fan Control provides supply or extract,
variable speed and automatic or manual switching of several
fans if desired, (see note below).
The control is best mounted approx 1.5m above the floor.
Remote Sensors are available for Humidity, Air Quality and
Passive Infra Red control.
Remote Sensors should be positioned at least 1.5m above the
floor and away from direct heat sources e.g. radiators.
Note: Up to 5 fans (size 6 / 9 inch) can be controlled by one
XS-MFC. Up to 3 fans (size 12 inch) can be controlled by one
XS-MFC. Do not mix different fan sizes on the same controller.
Lift up panel and remove two screws to dismantle unit.
2
3
1.5m
Spot through backplate box and drill and plug the wall.
Push out backplate box cable entry using a screwdriver.
4
5
200mm
Fix backplate box to the prepared wall.
Feed approx. 200mm of supply cable into the box
6
7
Connect the end of the cable into the control block.
Fit the control into the backplate box and secure.
Test the installation.
4
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Fitting Integral Sensors (optional)
1
Note: Before following the pictorial sequence shown- first
remove the fans front cover grille (2 screws). Release the four
main corner screws and lift out the motor/fan plate assembly.
Remove the electrical cover plate opposite the sensor plate.
Follow the pictorial sequence on this page.
Unscrew the module plate from motor plate assy.
2
3
Remove the module plate.
Lift out the sensor module wiring connector.
4
5
Plug the connector into the required sensor module.
Screw the sensor module into position.
Typical Application
This shows an XS Fan Module
being retro fitted into an existing
wall aperture. The two internal
wall battens are used to support
the fan and should be arranged
to match the fan fixing centres as
listed in the table.
XS6
XS9
XS12
X
237
310
390
Y
8
8
8
5
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Refurbishment Installation
Complete Kits XS12RE,
XS9RE and XS6RE
Replacing existing Nuaire XS Fans
The fan is fixed as the previous fan into the
existing channels on the wall liner. The picture
frame can be used if desired, however the
metal brackets are not required.
Replacing existing T-Series Fans
The brackets supplied with the kit can be
aligned with the screw fixing holes of the
previous fan. This then positions the receiving
nut on the bracket in the correct location to
allow fixing of the Nuaire refurbishment
fan.
Wiring details – T-Series Fans
A Nuaire XS fan can be used to replace a
Vent Axia ‘T’ Series fan, retaining the original
controller, providing the controller is of the
‘Ecotronic 130’, ‘Rangemaster’ or ‘T’ Series
Controller type.
This arrangement will give the
following operating features:
■
■
■
■
■
Adjustable speed
Adjustable minimum speed
Extract/intake
Fan off – shutter open
Fan off – shutter closed.
Limitations are:
Control of single fan only
Integral sensors not possible
Automatic ECO setting not available
■
■
■
This arrangement will give the
following operating features:
■
■
■
Single speed
Extract/intake
On/off.
Limitations are:
■
■
■
Control of single fan only
Integral sensors not possible
Automatic ECO setting not available
Fans should be installed in line with the IEE
wiring regulations.
6
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Dimensions (mm) In Duct Kit
Ancillaries
In Duct Kit
For use in In Duct applications when using flexible ducting.
Comprising of one In Duct Kit. Manufactured from HIPS.
The Fan is mounted within the two halves of the housing and
the ducting is connected both sides.
Order Code: XS-IDK6
Order Code: XS-IDK9
Order Code: XS-IDK12
For use with 6 inch fans.
For use with 9 inch fans.
For use with 12 inch fans.
A
B
C
D
E
XS-IDK6
268
268
197
240
25
XS-IDK-9
348
348
247
250
25
XS-IDK12
420
420
347
268
25
Maintenance
Terms
Periodically, at least once a year, or more frequently in case of
heavy use, remove the dirt and encrustation from the grille(s)
fan impeller and motor casing.
Ensure the impeller is not cracked or deformed and is able to
rotate freely and without oscillation. Do not use any solvents
to clean this product.
This warranty applies to units installed and used in the United
Kingdom.
The equipment will be repaired or replaced at Nuaire’s cost
provided that the appliance:
1. Has been installed and used in accordance with the fitting
and wiring instructions supplied with each unit.
2. Has not been connected to an unsuitable electrical supply.
(The correct supply voltage is shown on the appliance rating
label attached to the unit).
Replacement of Parts
As a manufacturer Nuaire is aware that time is important. In
the event of a breakdown of this equipment, it should be
adequately packaged and returned to Nuaire. IMPORTANT!
Please telephone Nuaire before posting your unit. We will give
you a returns number to identify your package.
We will endeavour to repair or replace it within five working
days of receipt. See our warranty terms.
3. Has not been modified or repaired by persons not authorised
by Nuaire.
4. A unit returned to Nuaire should be suitably protectively
packaged and clearly marked with the ‘returns number’
obtained from Nuaire prior to posting.
Warranty
Service Enquiries
The 3 year warranty starts from the day of delivery and
includes parts and labour for the first year.
The remaining period covers replacement parts only.
This warranty is conditional on planned maintenance being
undertaken.
Nuaire can assist you in all aspects of service. Our service
department will be happy to provide any assistance required,
initially by telephone and If necessary arrange for an engineer
to call within 48 hours if possible.
Telephone 029 2085 8585
Fax 029 2085 8586
Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and
dimensions of equipment and the right is reserved to make such changes without prior notice.
7
Leaflet Number 671067 January 2012
Installation and Maintenance
XS Fan Module
Western Industrial Estate
Caerphilly United Kingdom
CF83 1NA
T: 029 2088 5911
F: 029 2088 7033
E: info@nuaire.co.uk
W: www.nuaire.co.uk
8
Leaflet Number 671067 January 2012