Protection Relays 01 MiCOM P122C Time-Overcurrent Protection The Micom P122c is a compact unit for nondirectional time-overcurrent protection. It is designed for the selective short-circuit protection of high- and medium voltage networks as well as for the overload protection of transformers, overhead lines and cables. In addition to a wide spectrum of protection functions, a number of supervision functions are available, including circuit breaker supervision. Thanks to the provision of two setting groups, the P122C is readily adapted to varying conditions in system operation. Customer Benefits •1A/5A software setting •4 function keys •Compact unit for flush and wall-surface mounting •Comprehensive measurements •Disturbance and event recording The intuitive user interface together with the easily accessible PC interface allow straightforward yet comprehensive setting as well as access to readings from extensive recordings. Interfacing to substation control or the SCADA system is readily accomplished using the optional communication interface and a communication protocol selected to suit the application. Four function keys at the front panel provide user-friendly handling and rapid access to data and control operations such as manual closing and opening of the circuit breaker. For extra flexibility, the compact housing is suitable for either flush- or wall-surface mounting. Protection Relays MiCOM P122C 02 Application Global functions One of the major applications of the MiCOM P122C non-directional time-overcurrent protection unit is the selective short-circuit protection of radial networks with single-side infeed and of open ring systems. The following global functions are generally available in the P122C: Alternatively, the P122C provides back-up protection for differential protection units. Furthermore, the P122C offers preventative protection based on its thermal overload and unbalance protection functions. Applications of these functions to lines, cables, motors and transformers are fully supported for short-circuit, overload and unbalance protection. • • • • Setting groups Measured data acquisition Event counters (with trip statistic) Event recording (signal recording with real-time stamp) • Fault recording • Startings recording • Disturbance recording (CT inputs and binary events) Functions Overview P122C 50/51 Three-phase overcurrent protection • 50N/51N Earth fault overcurrent protection • 46 Unbalance protection • 49 37 50BF 50/27 86 Thermal overload protection Loss of load protection Circuit breaker failure protection Switch on to fault protection Output relay latching • • • • • Cold load pick up • Setting groups • Blocking logic • Logic selectivity Circuit breaker supervision • • Trip circuit supervision • Broken conductor / CT circuit supervision Self monitoring Measured data acquisition Peak and rolling values Event recording Fault recording Startings recording • • • • • • • Disturbance recording • 46BC Communication interface (RS 485 or fibre optics Protocol for communication interface: IEC 60870-5-103 or Modus RTU Function keys Binary inputs Output relays MiCOM P122C provides a wide range of protection functions option • 4 2 (opt. 7) 8 Protection Relays MiCOM P122C 03 Main functions The protection and supervision functions can be individually configured or disabled to suit a particular application. Settings of functions that are not required and have been disabled by the user are hidden (except for the selection parameter). Functional support is withdrawn from these hidden settings. This concept permits an extensive scope of functions and universal application of the device in a single design version, while at the same time providing for a clear and straight-forward setting procedure and adaptation to the protection and control task under consideration Simple function selection by mouse click Function diagram PC Interface Communication to setting program S1 Communication Interface to SCADA / Substation control... via RS485 or Fibre Optics using IEC 60870-5-103 or Modbus Further Functions Measurements Cold load pick-up Blocking logic Logik selectivity Circuit breaker supervision Trip circuit supervision Self monitoring Function keys ... Phase and residual currents Direct and Inverse currents Max. Phase current storaged Peak and Rolling values Frequency Thermal state CB operating times ... Recordings Event rec. Starting rec. . Fault rec. Disturbance rec. 50/51 50N/51N 46 49 37 50BF 50/27 46BC 86 I Always Available (Description of ANSI code No. see Functions Overview) Option Time-Overcurrent Protection P122C Protection Relays MiCOM P122C Three-phase overcurrent protection (50/51) The overcurrent protection for phase faults comprises three stages; each stage is provided with separate startings for the three phases. The first two stages can be operated as either inverse-time (IDMT) or definitetime (DTOC) stages. For the IDMT mode, a multitude of tripping characteristics is offered for selection. The third stage operates as a definite-time (DTOC) stage. For a detection of intermittent faults the first two stages are additionally equipped with hold-time logic (reset timer). 04 Nr. Tripping time char. Constants and formulas (t in s) ( k = 0.03...4.00) a b STI Short time inverse 0,05 0,04 SI Standard inverse 0,14 0,02 VI Very inverse 13,50 1,00 EI Extremely inverse 80,00 2,00 LTI Long time inverse 120,00 1,00 RC Rectifier protection 45900 5,60 1) c R t= a k b I I ref –1 (SI, VI, EI and LTI according to IEC 255-3) Earth fault overcurrent protection Tripping (50N/51N) The overcurrent protection for earth faults comprises three stages. The first two stages can be operated as either inverse-time (IDMT) or definite-time (DTOC) stages. For the IDMT mode, a multitude of tripping characteristics is offered for selection. The third stage operates as a definitetime (DTOC) stage. For a detection of intermittent faults the first two stages are additionally equipped with hold-time logic (reset timer). Additionally the first stage when in DTOC mode - is optionally provided with a second hold-time logic. This effects a pulse prolongation of the starting signal. For specific applications a high, standard or sensitive setting range can be ordered for the earth fault stages. The effect of the earth fault stages on the formation of the general starting signal can optionally be suppressed. This will then automatically inhibit the formation of the trip command by the earth fault stages. Unbalance protection (46) The current unbalance protection, based on the evaluation of the negative-sequence current, comprises two stages. The first stage can be operated as either an inverse-time (IDMT) or a definite-time (DTOC) stage. For the IDMT mode, a multitude of tripping characteristics is offered for selection. The second stage operates as a definite-time (DTOC) stage. MiCOM P122C for rapid and selective fault clearance in your power system Reset MI Moderately inverse 0,0515 0,02 0,1140 4,85 VI Very inverse 19,6100 2,00 0,4910 21,60 EI Extremely inverse 28,2000 2,00 0,1217 29,10 C02 Short time inverse 0,00342 0,02 0,00242 2,226 C08 Long time inverse 5,95 2,00 0,1800 5,98 t = k a b I I ref +c –1 t r= R k r 1 – I 2 I ref (MI, VI and EI according to ANSI/IEEE C37. 112) RI RI -type inverse t= 1 k 0,339 – 0,236 (k=0,05...10,00) I Iref For all the characteristic curves additionally a reset timer with a definite time characteristic is available t r = Reset - time 1) Available for Overcurrent Phase and Earth Tripping time characteristics For a detection of intermittent faults the first stage is additionally equipped with hold-time logic (reset timer). The effect of the negative-sequence current stages on the formation of the general starting signal can optionally be suppressed. This will then automatically inhibit the formation of the trip command by the negative-sequence current stages Protection Relays MiCOM P122C 05 Thermal overload protection(49) Cold load pick-up This function provides thermal overload protection for overhead lines, cables and transformers. The maximum value of the three phase currents is used to track a first-order thermal replica according to DIN IEC 255-8. The tripping time is determined with the help of the preset thermal constant t of the object to be protected, the preset tripping limit θ Trip and the preset overload factor k and is dependent on the accumulated thermal load θp: during cold load pick-up the current thresholds of the overcurrent and unbalance protection as well as the current threshold of the overload protection can be raised for a configurable period of time. The cold load pick-up function can be triggered optionally via a binary input signal or a settable current stage. This function can be used to avoid unwanted trips caused by shortterm increases in load e.g. when energizing a motor or a transformer. 1 0,339 – 0,236 I (k=0,05...10,00) Iref An initial warning can be issued when the preset threshold θWarning is exceeded Loss of load protection (37) a loss of load can be detected via a definite-time delayed undercurrent stage. The function is inhibited when the feeder is switched off. The recognition of the switched-off feeder takes place optionally via status of the CB auxiliary contact or a settable current criterion. Circuit breaker failure protection (50bf) a timer is started by the trip command. While the timer is running, the amplitudes of the three phase currents are monitored. Their values below a configurable threshold are used as a criterion for the detection of open circuit breaker poles. If the set condition is not met when the timer stage has elapsed, a signal is issued to indicate that the circuit breaker has failed to clear the fault. The receipt of this signal from a downstream relay at an appropriately configured logic input in combination with the persisting general starting leads to the generation of an instantaneous trip signal. Switch on to fault protection while switching on the circuit breaker it can happen that due to a remaining feeder earthing the circuit breaker erroneously switches on to a fault. This function provides an instantaneous protection trip during a settable time after the issue of the Manual-close command. According to the operating mode a trip command is issued either via a general starting signal or via one of the phase current stage startings. Blocking logic via two independent binary inputs various time stages e.g. for the individual overcurrent - and unbalance protection can be blocked externally. This is controlled via a matrix for the selection of the timers to be taken into account for blocking. This facilitates e.g. the implementation of a zone interlocking scheme. Current in % In t=k 400 300 200 NominalThreshold 100 0 1 2 3 4 5 6 Short-term increases in load following energization Time (s) Logic selectivity Via two independent binary inputs the time delays of the second and third overcurrent stages of the phase and earth can be replaced externally by the time delays of the logic selectivity. This takes place via individual selection as to which of the time stages shall be replaced with the presence of the external signal. This facilitates e.g. a reduction in grading time of the radial feeder or the implementation of a zone interlocking scheme without the application of blocking logic. Protection Relays MiCOM P122C 06 Setting group selection Function keys The protection settings can be stored in two independent groups for adaptation to various operating or system management conditions. Four function keys are available on the P122C relay. Function keys F1 or F2 automatically access the operating data or fault records respectively. Function keys F3 and F4 are user configurable and can be integrated into the trip command or can be configured to an output relay to facilitate control access e.g. manual operation of the circuit breaker. Trip circuit supervision The trip circuit supervision further increases the operational security. The trip circuit supervision recognizes the interruption of the trip circuit irrespective of whether the circuit breaker is open (OFF) or closed (ON). Circuit breaker supervision The preventative CB maintenance is provided by monitoring the breaking current accumulated over the service duration, the number of trip operations as well as by controlling the operating times. By reaching or exceeding the settable threshold value an appropriate signal is issued by this function. Broken conductor / CT circuit supervision The P122C includes facilities for monitoring the phase currents. Phase current monitoring is based on the principle of a maximum permissible ratio of the negative- and positive- sequence current components to detect broken conductor conditions. The function can be configured for phase current monitoring on a two-phase CT connection. This is based on the principle of a maximum permissible difference between the magnitudes of phase currents IA and IC. Event records the last 75 events are stored in a non-volatile memory with a 1ms resolution. Data recorded includes the state change of binary inputs and outputs, operating and alarm signals and any setting changes. Fault records the P122C logs the last 5 faults that generated a trip. Each log includes the following data: • • • • Date and time Active setting group Alarm signal that caused the trip Numerical fault data Disturbance records the internal disturbance recorder records the sampled values of the analog variables and relevant alarm signals. A total of 8 records each lasting up to max. of 3 seconds can be stored and read via the PC or optional communication interface. Latching of the output relays (86) All freely configurable output relays can be set to a latched operating mode. In addition, individual trip functions can be separately latched for the trip output relay. Proven protection, flush- or surfacemounted case, comprehensive local control, just one setting file. Disturbance record Protection Relays MiCOM P122C 07 Information interfaces Mechanical design information exchange is done via the local control panel, the PC interface and the optional communication interface. The communication interface (IEC 60870-5103 or Modbus) is intended for integration with substation control systems. the P122C consists of an aluminum case with reversible connector blocks and adjustable side brackets and can be used for wall surface or panel flush mounting. In either case the wiring connection is accomplished using screw terminals. Information interfaces HMI: Full access to settings, signals, measurands and function keys PC Interface: Local access by protection engineer Optional Communication Interface: SCADA/Substation control interface Protection Relays MiCOM P122C 08 Device Track Record • PS 431: First non-directional time overcurrent device in compact case design, more than 20 000 devices since 1992. Schneider Electric 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France Tel: +33 (0) 1 41 29 70 00 RCS Nanterre 954 503 439 Capital social 896 313 776 € www.schneider-electric.com EnergyAutomation-DS-P122C-0831-EN As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing: 10-2010 © 2010 Schneider Electric - All rights reserved • MiCOM P122C: MiCOM non-directional time-overcurrent device in compact case design with extended functionality, launched in 2003.