Three-phase squirrel cage induction motors in flameproof enclosure Ex de IIC T4 type K8UR frame size 132S-4 Page 1/2 DATA SHEET o Type…………………………………………………………………K8UR 132S-4 o Reference standard……………………………………………… IEC 60034-1 EN 60079-0 EN 60079-1 EN 60079-7 o Rated output…………………………………………………….… 6,6 kW o Rated stator voltage……………………………………………….440V / Y o Stator current at 100% load …………………………………….. 12,0 A o Number of poles…………………………………………………….4 o Rated speed/Rated frequency…………………………………. 1735 rpm / 60Hz o Rated duty ………………………………………………………… S1 o Efficiency at 100% load……………………………………………87% o Power factor at 100% load………………………………………. 0.83 o Break-down torque……………………………………………… 2,7 x Mn o Locked rotor torque………………………………………………..2,5 x Mn o Locked rotor current……………………………………………….6.0 x In o Insulation class…………………………………………………… F o Direction of rotation……………………………………………… Both o Protection degree………………………………………………. IP55 o Mounting………………………………………………………….. IMB3 o Cooling method………………………………………………….. IC 411 o Max. ambient temperature………………………………………. 40°C o Altitude……………………………………………………………. 1000m o PTC thermistor …………………………………………….. 1 set (triple connected in series) o Bearing type…………………………………………………….. 6308 ZZ DE 6308 ZZ NDE o Weight…………………………………………………………….. 90Kg o Vibration level :………………………………………………….. A (acc.IEC 60034-14 ) o Noise level ……………………………………………………….. acc.IEC 60034-9 o Cable entries……………………………………………………....1 x M32x1.5 o Min and max admissible supply cable diameter………………15.5-20.5mm o Paint system……………………………………………………… RAL7031 Three-phase squirrel cage induction motors in flameproof enclosure Ex de IIC T4 type K8UR frame size 132S-4 Page 2/2 The overall and mounting dimensions IM B3 Dimensions (mm) Frame size 132S Foot mounting A B C D E F GA d HD AC L a b c BB BC HA 216 140 89 132 12 60 264 200 69 19 38 k6 80 10h9 41 M12 400 263 523 200 175 160 H-0,5 K AA AB Shaft extension Three-phase squirrel cage induction motors in flameproof enclosure Ex de II CT4 type K8UR frame size 160Mb-2 Page 1/2 DATA SHEET o Type………………………………………………………………………K8UR 160Mb-2 o Reference standard………………………………………………….… IEC 60034-1 EN 60079-0 EN 60079-1 EN 60079-7 o Rated output………………………………………………………….… 15 kW o Rated stator voltage…………………………………………………….440V/ Y o Stator current at 100% load ………..…………………………………25.4 A o Number of poles………………………………………………………….2 o Rated speed /Rated frequency………………………….…………….3510 rpm / 60Hz o Rated duty……………………………………………………………… S1 o Efficiency at 100% load………………………………………………… 89.8% o Power factor at 100% load……………………………………………...0.86 o Break-down torque………………………………………………………2.4 x Mn o Locked rotor torque……………………………………………………...2.2 x Mn o Locked rotor current……………………………………………………..7 x In o Rotor inertia ………………………………………………………………0.04155 kgm2 o Insulation class……………………………………………………………F o Direction of rotation………………………………………………………Both o Protection degree………………………………………………………...IP55 o Mounting…………………………………………………………………..IMB3 o Cooling method…………………………………………………………...IC 411 o Max. ambient temperature …………………………………………… 40°C o Altitude…………………………………………………………………….1000m o PTC thermistor …………………………………………….. 1 set (triple connected in series) o Bearing type……………………………………………………………..6310 ZZ DE 6310 ZZ NDE o Weight……………………………………………………………………150Kg o Vibration level :…………………………………………………………..A (acc.IEC 60034-14 ) o Noise level ………………………………………………………..……..acc.IEC 60034-9 o Cable entries…………………………………………….….. …………..1 x M40x1.5 o Color Paint system ……………………………………………………... RAL 7031 Three-phase squirrel cage induction motors in flameproof enclosure Ex de II CT4 type K8UR frame size 160Mb-2 Page 2/2 The overall and mounting dimensions IMB3 Dimensions (mm) Frame size 160 Mb-2 Foot mounting A B C H-0,5 K Shaft extension D E F GA d HD AC L a b c AA AB BB BC HA 254 210 108 160 14.5 80 320 300 63 20 42k6 110 12h9 45 M16 471 317 660 245 210 195 Three-phase squirrel cage induction motors in flameproof enclosure Ex de IICT4 type K8UR frame size 225M-2 Page 1/2 DATA SHEET o Type……………………………………………………………………………K8UR 225M-2 o Reference standard………………………………………………………… IEC 60034-1 EN 60079-0 EN 60079-1 EN 60079-7 o Rated output………………………………………………………………… .45 kW o Rated stator voltage………………………………………………………….440V / Y o Stator current at 100% load………………………………………………….71.4 A o Number of poles……………………………………………………………….2 o Rated speed/Rated frequency……………………………………………….3510 rpm / 60Hz o Rated duty …………………………………………………………………… S1 o Efficiency at 100% load………………………………………………………92.85% o Power factor at 100% load………………………………………………… 0.89 o Break-down torque………………………………………………………… 2.5 x Mn o Locked rotor torque………………………………………………………… 2.0x Mn o Locked rotor current…………………………………………………………. 7.0 x In o Rotor inertia …………………………………………………………………. 0.24606 kgm2 o Insulation class ……………………………………………………………… F o Direction of rotation………………………………………………………… Both o Protection degree…………………………………………………………… IP55 o Mounting…………………………………………………………… ………… B3 o Cooling method……………………………………………………………… IC 411 o Max. ambient temperature………………………………………………… . 40°C o Altitude……………………………………………………………………….. 1000m o PTC thermistor …………………………………………….. 1 set (triple connected in series) o Bearing type…………………………………………………………………. 6313 2Z DE 6313 2Z NDE o Weight……………………………………………………………….……… 330 kg o Vibration level :…………………………………………………………. A (acc.IEC 60034-14 ) o Noise level ……………………………………………………………… .acc.IEC 60034-9 o Cable entries………………………………………………………..……… 1 x M50x1.5 o Min. and max. supply cable dia. …………………………………..…… 23.4 – 35 mm o Color Paint system………… ……………………………………………… RAL 7031 Three-phase squirrel cage induction motors in flameproof enclosure Ex de IICT4 type K8UR frame size 225M-2 Page 2/2 The overall and mounting dimensions IMB3 Dimensions (mm) Frame size 225M-2 Foot mounting Shaft extension A B C AA AB BB 356 311 149 100 440 430 H 225 0 -0.5 K D E F GA 18.5 55m6 110 16h9 59 L H 885 63 Data sheet 11.02.2015 MADE WITH VERSION: 7.70 Manufacturer Customer VEM motors GmbH Carl-Friedrich-Gauß-Straße 1 38855 WERNIGERODE Deutschland Three-phase motors with squirrel cage rotor, standard motors Housing grey cast iron Type Duty type Design output Efficiency determination Design frequency Design speed Voltage Connection Current Relative pull-in current Relative starting torque Relative pull-up torque Relative pull-out torque Power factor Efficiency Th. cl. Coolant temperature Altitude above sea level Degree of protection Moment of inertia Motor weight Bearing, D-side Bearing, N-side Relubrication interval Grease type Grease amount A-sound pressure level Special details to bearings 1 Special details to bearings 2 Bearing monitoring Winding protection Winding protection 2 Anti-condensation heating Special versions 1 Special versions 2 Special versions 3 Special versions 4 Limit values to vibration velocity Balancing with half key Colour system Colour shade Layer thickness K21R 225 M2 TPM HW S1 ( kW ) 45 (-) EN 60034-2 ( Hz ) 60 [rpm] 3535 (V) 440 (-) Y (A) 70.0 (-) 7,5 (-) 1,8 (-) 1,4 (-) 2,7 (-) 0,9 (%) 93,7 155(F) ( °C ) -30…+45 (m) 1000m IP55 2 0,22 ( kgm ) ( kg ) 290 6312 C3 6312 C3 (h) ASONIC GHY 72 (g) ( dB ) 78 none Fixed bearing, N-side none 1 set ptc resistors (triple connected in series) none none none none none none Class A 01 Moderate (KK C2) RAL 7031 blue-grey 70 µm Delivery conditions and/or official regulations: IEC / EN 60034-1 This document was produced electronically, all specifications are valid only after confirmation of the manufacturer © VEM motors GmbH, Carl-Friedrich-Gauß-Straße 1, D-38855 Wernigerode, Postfach-Nr. 101252, D-38842 Wernigerode E-Mail: motors@vem-group.com Internet: www.vem-group.com Seite 1/2 Data sheet 11.02.2015 MADE WITH VERSION: 7.70 Three-phase motors with squirrel cage rotor, standard motors Housing grey cast iron K21R 225 M2 TPM HW Type of mounting: IM B3 Flange: Position of terminal box: on the top Mounting position Motor A AA 356 75 AB 413 AC 390 AD - B 311 B' - L 767 H 225 HA 25 HD 525 HH 168 Bl 40 LC - BA 75 Terminal box: KK 100 A Cable gland O: 1 xSealing plug BA' - Flange P - C CA 149 Terminal box K 19 K' 25 AG 213 LL 207 BE - AH - N h6 D m6 DA m6 Tolerances N - LA - M - T - S - Shaft-DS D 55 BB 368 E 110 H -0,5 Shaft-NS GA 59 F 16 DB DIN 332-DS M20 DA - EA - GC - FA - DB...Centre hole Delivery conditions and/or official regulations: IEC / EN 60034-1 This document was produced electronically, all specifications are valid only after confirmation of the manufacturer © VEM motors GmbH, Carl-Friedrich-Gauß-Straße 1, D-38855 Wernigerode, Postfach-Nr. 101252, D-38842 Wernigerode E-Mail: motors@vem-group.com Internet: www.vem-group.com Seite 2/2