Mini Tower
Liebert
Keeping Business in Business
ENVIRONMENTAL CONTROL
Technical Data
Manual
LPN: SLE MT TDM E.3_r1 (10/99)
HPN:
Table of Contents
System nomenclature
1
Introduction
2
Standard features - all models
3
Optional features - all models
10
Technical data - all models
14
Electrical data - all models
16
Sound data - all models
17
Dimensional drawings
18
Mini Tower - Technical Data Manual
System nomenclature
The nomenclature for Mini Tower packaged (compressor in the
indoor unit) and split (compressor located in a condensing unit)
systems is as follows:
TS/TSF
06 A U X
Humidifier:
M = Humidifier
X = No humidifier
Air pattern:
U = Upflow
D = Downflow
System type:
A = Air cooled
W = Water cooled
G = Glycol cooled
C = Chilled water
Model size:
Capacity in kW (Nominal)
TS = Mini Tower Packaged
TSF = Mini Tower Split (Air
Cooled only)
TS/TSF
Mini Tower
06
Model size
A
System type
U
Air pattern
M
Humidification
04
4kW nom. cap.
A
Air cooled
D
Downflow
M
Humidifier
06
6kW nom. cap.
W
Water cooled
U
Upflow
X
No humidifier
07
7kW nom. cap.
G
Glycol cooled
09
9kW nom. cap.
C
Chilled water
11
11kW nom. cap.
AIR (Packaged)
AIR (Split)
WATER
GLYCOL
CHILLED WATER
TS04AUX/ADX
TSF6AUX/ADX
TS04WUX/WDX
TS04GUX/GDX
TS07CUX/CDX
TS04AUM/ADM
TSF6AUM/ADM
TS04WUM/WDM
TS04GUM/GDM
TS07CUM/CDM
TS06AUX/ADX
TSF9AUX/ADX
TS06WUX/WDX
TS06GUX/GDX
TS11CUX/CDX
TS06AUM/ADM
TSF9AUM/ADM
TS11CUM/CDM
TS06WUM/WDM
TS06GUM/GDM
TS09AUX/ADX
TS09WUX/WDX
TS09GUX/GDX
TS09AUM/ADM
TS09WUM/WDM
TS09GUM/GDM
SLE MT TDM E.3_r1 (10/99)
1
Mini Tower - Technical Data Manual
Introduction
Precision environmental control may be defined as the
simultaneous control of air temperature, humidity,
distribution and cleanliness on a continual, around-the-clock
basis.
System types
The Mini Tower is available in a number of configurations:
Conventional building or ‘comfort’ systems, as they are
called, are not designed for this 24-hour, year-round usage;
they lack the ability to provide the precision and reliability or
‘close control‘ that is so critical to many applications.
Air cooled
All units are built in accordance with European directives
98/37/CE (89/392/CEE; 91/368/CEE; 93/68/CEE),
89/336/CEE; 73/23/CEE. The Liebert Air Conditioning
Quality System is approved by LRQA in accordance with the
standards UNI EN ISO 9001: 1994.
This comprises an indoor unit (consisting of an evaporator
coil, scroll compressor, direct driven fan, electric reheat and
filter section) and an outdoor air cooled condenser.
Two system types are available:
Packaged
Each unit is supplied complete with a Test Certificate and
Declaration of Conformity.
All Mini Tower units carry the “CE” mark and fully comply
with European Directives concerning mechanical, electrical
and electromagnetic safety.
Liebert technology and energy
efficiency
Liebert has become a world leader in precision environmental
control systems by providing maximum energy efficiency
without compromising precision and reliability.
Liebert takes a no-compromise approach to environmental
control system design. All enhancements to energy efficiency
are designed to reduce operating time of key components.
This is accomplished by taking advantage of alternate sources
of cooling when available or, by reducing compressor work
load when the heat load in the critical space is lower.
Applications
The Mini Tower unit is ideally suited for precision close
control of the following types of environment:
· Data centres
· Telecommunications
· Industrial applications
· Office environments
Indoor Unit
Matching Condenser*
TS04A
HCA07
TS06A
HCA10
TS09A
HCA14
*: Quoted at 32 oC outside ambient temperature. For other
ambients, consult the Condenser Technical Data Manual
(P/N SLE CD TDM).
Split
This comprises an indoor unit (consisting of an evaporator
coil, direct driven fan, electric reheat and filter section) and an
outdoor condensing unit (complete with scroll compressor).
Indoor Unit
Matching Condensing Unit*
TSF6A
MMC08
TSF9A
MMC10
o
*: 32 C outside ambient temperature.
Water/Glycol cooled
This comprises of an indoor unit (consisting of an evaporator
coil, scroll compressor, plate condenser, direct driven fan,
electric reheat and filter section) and an outdoor drycooler.
Note: This product may not be suitable for all open water
tower applications as good quality water is essential for
correct operation. Consult Liebert Hiross Applications
Engineering for further details.
Chilled Water
This comprises of an indoor unit only (consisting of a chilled
water coil, 3-way valve, direct driven fan, electric reheat and
filter section).
The unit is supplied with chilled water from a central building
chiller or other chilled water source.
2
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Standard features - all models
General
The Mini Tower series comprises both direct expansion units
and chilled water units. Cooling capacities range from 4 to 11
kW. Direct expansion units are equipped with compliant
scroll compressors. The design of the scroll compressor,
ensures a constant refrigerant pressure, thus improving
reliability, energy consumption and sound emission.
The Mini Towers compact design, facilitates a minimum unit
footprint, allowing the unit to be installed in very confined
areas, the unit is fully serviceable from the front.
Access/maintenance
Routine maintenance access to refrigerant circuit
components, the compressor, liquid reservoir, thermal
expansion valve, sight glass, filter dryer etc. is available
through the front panel of the unit. Service access to the air
filter is also through the unit front panel.
All other components of the machine, the fan, humidifier,
electric panel, electronic controller PCB, electric reheats etc.
are accessible through the front and grille panels.
Customer connections to the refrigerant circuit (hot gas and
liquid line), mains power supply, humidifier water supply and
condensate drain lines are located in the lower right-hand-side
of the unit.
Cabinet
The cabinet is manufactured from primed and treated steel, it
is then degreased and painted in RAL 9018 using dry powder
epoxy resin paint (the return air grille is finished in NCS 3502
coloured paint). The paint finish is easily cleaned and is hard
wearing to give maximum protection. The unit has removable
panels which give access to all internal components from the
front of the unit. The panels are insulated with 12mm, 30
kg/m3 density foam which reduces noise emission and heat
loss. The foam is a self-extinguishing material in compliance
with the following standards: ASTM D 1992, MVSS302,
UL94 Class 0.
A safety microswitch is fitted to the front panel of the unit.
The microswitch deactivates the unit if the front panel is
removed.
Filter section
The guaranteed efficiency is EU3, (Eurovent EU4/5 (30%
efficiency), equivalent to G3 - CEN Standard). An optional
EU4 filter (G4) is available on request.
The air filter is mounted on the face of the evaporator coil and
is easily accessed/replaced by removing the front panel. The
filter is made of open-cell foam and is designed to minimise
the air pressure drop while maintaining maximum filter
efficiency.
Fan and motor assembly
The unit is fitted with a direct-drive, double-inlet forwardcurved, galvanized-steel, centrifugal fan. The fan impeller is
statically and dynamically balanced and equipped with
sealed-for-life bearings. The fan is mounted on
vibration-absorbing rubber supports to reduce vibration
transmission between the fan and the unit frame. This
vibration attenuation helps to keep noise emission to a
minimum.
The fan motor is a single-phase, 5-speed motor complete with
thermal overload protection. Each speed of the motor
produces a different airflow through the unit, refer to the
Technical Data section for specific model/airflow data.
Each unit is wired for two different airflows, a cooling airflow
and a lower, dehumidification airflow. The controller will
switch the unit to the lower airflow during the
dehumidification cycle.
Electric reheat
The single-stage, three element reheats are of rigid,
fin-tubular design that have extended operational life. The
reheat has ample capacity to maintain room dry-bulb
conditions during a system call for dehumidification. The
low-watt density, phase balanced, electrically enclosed
elements are surrounded by the tube and fins, reducing sheath
temperatures and eliminating ionisation.
Reheat control is of the ON-OFF type. The reheat is provided
with a manual reset, reheat safety thermostat, to disable the
reheat in the event of high temperature.
The edges of the panels are fitted with seals to prevent air loss
and to keep noise levels to an absolute minimum.
SLE MT TDM E.3_r1 (10/99)
3
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Microprocessor controls
T h e M icroface environm ental control system i s
microprocessor based and can be programmed to match the
unique needs of any application. The processor integrates the
separate mechanical and electrical components into a
‘state-of-the-art’ conditioned space support system that
controls and monitors temperature, humidity, air flow and air
cleanliness.
The control system offers a tailored and well proven advance
in reliability and control flexibility allowing the unit to
modify its performance in response to changing critical space
conditions.
The controller allows local monitoring and programming of
the following room conditions:
· Temperature (oC)
· Temperature setpoint (5.0oC – 40.0oC in steps of 0.1 oC)
· Temperature sensitivity (1.0oC - 10oC in steps of 0.1 oC)
· Humidity (%RH)
· Humidity setpoint (20%RH - 80%RH in steps of 1%)
· Humidity sensitivity (5%RH - 20%RH in steps of 1%)
The parameters are enunciated using symbols and text on an
LCD display. Normal operating modes are indicated by
symbols on the display. Alarm conditions activate a visual
indicator.
The following alarms are standard:
· High temperature
· Low temperature
· Fan failure
Electrical panel
The electric panel is located at the top-front of the unit in an
airtight compartment. The electrical panel contains the
MCB’s, contactors, transformer, controller PCB and
overload relays etc. Each high voltage system component is
provided with a separate over-current protective device. All
high-voltage components are touch protected by means of a
plastic cover. Electrical design is in accordance with UNI /
EN 60204-1.
All models are supplied as standard for operation at
400V/3ph/50 Hz.
Models TS04A, TS06A, TSF6A, TS07C and TS11C can be
supplied for 230 V/1ph/50 Hz operation to special order.
Packaging
As standard, the units are wrapped in plastic film to protect
painted surfaces, enclosed in a cardboard box and mounted on
a wooden pallet.
On request, for sea transport etc., the units can be packed in
wooden crates or cases complete with silicon desiccant.
Warranty clauses
The warranty does not cover any damage or malfunction of
the unit which may occur during or as a result of operating the
unit outside of the specified application limits.
Liebert does not accept responsibility for any damage caused
by improper use of the product.
· High pressure alarm – (compressorised systems only)
· Low pressure alarm - (compressorised systems only)
· Electrical reheat high temperature
· Memory failure
· Common alarm
Other alarms are also available when the relevant option is
ordered with the unit (e.g. if a humidifier is ordered with the
unit, the High Humidity, Low Humidity etc. alarms are
enabled). For a full list of all the options and alarms available
with the Microface controller, refer to the Microface
Controller Operation Manual (P/N SLE MF OM).
The controller also incorporates a sequential auto-restart
timer, allowing field adjustable time delays to be applied to
unit restart after a power loss (or other shutdown). The timers
allow multiple units to be restarted while limiting
instantaneous inrush current.
4
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Refrigerant circuit - dx models
Each unit in the range has a single refrigerant circuit. The
circuit consists of a compressor, a thermal expansion valve, a
liquid line sight glass, a filter dryer, an evaporator coil and
high and low pressure switches.
Liebert recommends the installation of a non-return valve
(supplied as an option, on request) on the liquid line from the
condenser, to protect the compressor from unexpected
refrigerant migration. All low temperature parts of the
refrigerant circuit are insulated as standard.
Compressors
The fully hermetic compliant scroll compressor incorporates
several safety features for protection during normal and the
occasional abnormal operating conditions. They are:
· Self resetting overloads to sense excessive currents and
temperatures.
· Rubber mounting to ensure reduced compressor noise and
vibration.
Schraeder connections are fitted to the unit for service access.
Refrigerant
R22 HCFC is the standard refrigerant used in the Mini Tower
range. An optional “Green” refrigerant, R407C is available to
special order. In this case the compressor is supplied with
ester oil instead of mineral oil. Air cooled units are shipped
with a nitrogen holding charge.
Evaporator coil
The evaporator coil is constructed from copper tubes with
aluminium fins to ensure maximum heat transfer. It is
designed to maximise the available surface area resulting in
low face velocities, low internal air pressure drops and the
high sensible heat ratios. A corrosion resistant drain pan is
provided on all models.
· An internal pressure relief valve which limits discharge
pressure to protect mechanical parts.
· Motor insulation that is resistant to chemical attack.
Air Cooled
Condenser
Condensing
Unit
Outdoor
Outdoor
Indoor
Indoor
Packaged air cooled systems
SLE MT TDM E.3_r1 (10/99)
Split air cooled systems
5
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Sight glass
Refrigerant line sight glasses serve as a means of quick visual
inspection to determine if there is moisture in the system and
if the system is properly charged.
Filter-dryer
Liquid line filter-dryers ensure a clean, moisture-free
refrigerant system for extended component life. The filter
drier is suitable for use with standard R22 and optional “Zero
ODP” refrigerant R407C.
Expansion valve
The externally equalised, adjustable, thermostatic expansion
valve smoothly controls refrigerant flow during varying
indoor heat loads and outdoor ambient temperatures by
controlling evaporator superheat.
Safety controls
Each compressor has a manual-reset high pressure switch for
high pressure protection and a high pressure alarm circuit to
warn of high system pressures, allowing corrective action to
be taken before a significant loss of temperature control
occurs.
The low pressure switch is auto-resetting and detects low
pressure conditions such as loss of refrigerant charge.
The pressure switch calibration values are shown in the
Installation, Operation & Maintenance Manual supplied with
the machine.
Packaged air-cooled models
Water/glycol cooled models
Water/glycol-cooled Mini Tower units are fitted with a high
pressure plate heat exchanger and a 2-way water regulating
valve (rated at 1030kPa (150psi)) to maintain head pressure.
Plate heat exchanger
The compact brazed plate heat exchanger consists of a
number of parallel stainless steel pressed plates, the pressing
pattern being inverted on alternate plates. In this way, the
ridges on adjoining plates form contact points and the
refrigerant and fluid move in contra-flow through alternate
channels. The plate heat exchanger is designed to operate at a
maximum working pressure of 30 bar (3000 kPa)
(factory-tested to 40 bar (4000 kPa)).
The units operate with mains water, cooling tower water or
water in a closed circuit with an external drycooler.
When operating in a closed circuit, it may be necessary
(depending on outside temperatures) to add mono-ethylene
glycol to prevent the water freezing in winter, refer to the unit
Installation Manual for applicable percentages.
A pump is used to circulate water (water/glycol) through the
unit (not supplied by Liebert).
If mains water or tower water is used, it is recommended to fit
a mechanical filter on the water line to protect the plate heat
exchanger against possible impurities contained in the water
(for plate heat exchanger cleaning, refer to the Installation
Manual).
Note: Water cooled units may not be suitable for some open
cooling tower applications as good water quality is essential.
Contact Liebert Applications Engineering for details.
Air cooled condensers
Water regulating valve
A matching Liebert air cooled condenser with fan speed
control should be ordered with the unit. The range includes
condensers with axial fans and centrifugal fans. Details of
standard condenser selections for 32oC ambient are provided
in this manual, full technical details of all condensers for all
outdoor ambients are available in the Condenser Technical
Data Manual, (P/N SLE CD TDM).
A 2-way water regulating valve is fitted as standard and is
designed to operate with fluid working pressures of 10.1 bar
(1010 kPa). The valve operates with a maximum fluid
temperature of 77 oC.
Note: Condenser selections/performances for each outdoor
ambient are based on calculated data. The actual selection of
a condenser should always be verified on the basis of the
specific working conditions on each site.
Drycooler
A matched Liebert drycooler should be ordered with the unit.
The range includes condensers with axial fans and centrifugal
fans. Details of standard drycooler selections for 32oC
ambient are provided in this manual, full technical details of
all drycoolers for all outdoor ambients are available in the
Drycooler Technical Data Manual, (P/N SLE DC TDM).
Note: Drycooler selections/performances for each outdoor
ambient are based on calculated data. The actual selection of
a drycooler should always be verified on the basis of the
specific working conditions on each site.
6
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Split air-cooled models
Condensing unit
Cabinet
The cabinet is manufactured from zinc coated steel, it is then
de-greased and painted in “Pearl White” (RAL7032) dry
powder epoxy resin paint. The paint finish is easily cleaned
and is hard wearing. The cabinet has been designed
specifically for outdoor applications, all materials, fittings
and components have been selected to provide maximum
weather protection, durability and security (vandal-proof
cabinet). The unit has removable panels (a special key is
required) which give access to all internal components. The
condenser air inlet is through the rear of the unit and
discharges through the front. A metal safety grid prevents
accidental contact with the fan and the coil. The compressor is
located in the side of the Condensing unit, separated from the
airstream.
· Rubber mounting to ensure reduced compressor noise and
vibration.
The compressor is fitted with a crankcase heater as standard.
They maintain minimum refrigerant temperature and are
energised while the unit is powered and the compressor is off.
Schraeder valves are fitted to the compressor for service
access.
Refrigerant
R22 HCFC is the standard refrigerant used in this range.
Condensing units suitable for use with an optional “Zero
ODP” refrigerant, R407C are available to special order.
Controls
Pre-wired, factory installed electrical and control
components include:
· Mains and low voltage terminals.
· Compressor and fan contactor.
Condenser coil
· Factory pre-wired high pressure switch.
The condenser coil is manufactured from refrigeration quality
copper tubes with mechanically bonded aluminium fins, and
is vertically mounted.
Electrical design is in accordance with UNI / EN 60204-1.
Fan/motor assembly
The condensing unit is equipped with a single axial fan with
integral motor, it is statically and dynamically balanced. The
fan impeller and casing are made from zinc-coated steel to
protect against corrosion. The direct drive motor includes
sealed-for-life bearings. The fan motor is IP54 rated and
complete with internal thermal protection. The fan motor is
controlled by a pressure switch to maintain a steady
condensing temperature.
Fan speed control
A factory fitted solid state fan speed controller is installed to
maintain the refrigerant condensing pressure. The controller
varies airflow through the condenser to maintain a constant
pressure. The advantages of fan speed control are two-fold.
Higher reliability of the system due to less starts/stops of the
compressor and a lower noise level because the fan is running
at a lower speed, mainly during night-time.
Compressor
The fully hermetic compliant scroll compressor incorporates
several safety features for protection during normal and the
occasional abnormal operating conditions. They are:
Sight glass
Refrigerant line sight glasses serve as a means of quick visual
inspection to determine if there is moisture in the system
and/or if the system is properly charged.
Filter-dryer
Liquid line filter-dryers ensure a clean, moisture-free
refrigerant system for extended component life. The filter
drier is suitable for use with standard R22 and optional “Zero
ODP” refrigerant R407C.
Liquid receiver in indoor unit
In split air-cooled models, a welded steel liquid receiver is
provided to maintain constant and even refrigerant flow to the
expansion valve, under all circumstances. It is installed in the
indoor unit. Shut-off valves are fitted as standard on the inlet
and outlet of the receiver to assist maintenance of the circuit,
if required.
A suitably rated pressure relief valve is installed on the liquid
receiver. The valve is equipped with a threaded connection to
allow the refrigerant to be discharged outside of the
conditioned space, if required.
· Self resetting overloads to sense excessive currents and
temperatures.
· An internal pressure relief valve which limits discharge
pressure to protect mechanical parts.
· Motor insulation that is resistant to chemical attack.
SLE MT TDM E.3_r1 (10/99)
7
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Chilled water systems
Cooling coil
The chilled water coil is manufactured from refrigeration
quality copper tubes with mechanically bonded aluminium
fins. Coils are circuited from a header to ensure low water
pressure drops. It is designed to maximise the available
surface area resulting in low face velocities, low internal air
pressure drops and the high sensible heat ratios. A corrosion
resistant drain pan is provided on all models.
3-way control valve
The chilled water valve provides on/off control action in
response to room temperature and humidity as sensed by the
microprocessor. This is a slow acting, motorised ball-valve
offering on/off control without water-hammer. The valve is
rated to 862 kPa (125 psi).
Operating limits - dx models
Mini Tower dx units are designed for operation within the
following working limits (the limits are applicable to newly
commissioned machines which have been correctly installed
and maintained).
Indoor operating range
TS04A/W/G from 18.0°C, 45% R.H. to 30.0°C, 55% R.H.
Air flow
The minimum and maximum air flows and available external
static pressure are given in the Technical Data section of this
manual. The fan motor thermal overload protects the unit
from any damage which could result from operating outside
the specified values.
Voltage tolerance
All models: 400 V ± 10%
Frequency tolerance
All models: 50 Hz ± 2 Hz.
Condenser installation (packaged air cooled)
Condenser above indoor unit
Maximum distance between indoor unit and external air
condenser: 30 meters equivalent length.
Condenser below indoor unit
Maximum geodetic height difference between condenser and
unit: 3 meters.
Condensing unit installation (split air cooled)
Maximum distance between indoor unit and condensing unit:
15 meters equivalent length. Refer to the unit Installation,
Operation and Maintenance for further details.
TS06A/W/G from 18.0°C, 35% R.H. to 30.0°C, 70% R.H.
TS09A/W/G from 18.0°C, 35% R.H. to 27.0°C, 70% R.H.
To minimise the possibility of water carry-over, (i.e. too much
condensate on the evaporator coil leading to the formation of
water droplets), it is critical to ensure that the latent load
(difference between total and sensible load) does not exceed
the following values:
TS04A/W/G 1.4 kW
TS06A/W/G 2.0 kW
TS09A/W/G 2.8 kW
Outdoor operating range
Lower limit
-25°C (with fan speed control in the condenser).
Upper limit
This is determined by the capacity of the condenser coupled to
the unit (at the relevant outdoor ambient). If the limit is
exceeded, the High Pressure Switch will shut the compressor
down. The switch must then be manually reset after the
problem has been rectified.
8
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Standard features - all models (continued)
Operating limits - chilled water
models
Mini Tower chilled water units are designed for operation
within the following working limits (the limits are applicable
to newly commissioned machines which have been correctly
installed and maintained).
Indoor operating range
TS07C from 18.0°C, 45% R.H. to 27.0°C, 55% R.H.
TS11C from 18.0°C, 35% R.H. to 30.0°C, 70% R.H.
Note: Consult Liebert Applications Engineers for use of the
units outside this range.
To minimise the possibility of water carry-over, (i.e. too much
condensate on the evaporator coil leading to the formation of
water droplets), it is critical to ensure that the latent load
(difference between total and sensible load) does not exceed
the following values:
TS07C 1.4 kW
TS11C 2.0 kW
Outdoor operating range
The entering chilled water temperature to the cooling coil
should normally be at least 5oC lower than the return air
temperature to the cooling coil.
Chilled water temperatures below 6oC require careful unit
selections.
Maximum recommended water pressure: 16 bar
Air flow
The minimum and maximum air flows and available external
static pressure are given in the Technical Data Section of this
manual. The fan motor thermal overload protects the unit
from any damage which could result from operating outside
the specified values.
Voltage tolerance
All models: 400 V ± 10%
Frequency tolerance
All models: 50 Hz ± 2 Hz.
SLE MT TDM E.3_r1 (10/99)
9
Mini Tower - Technical Data Manual
Optional features - all models
Electrode boiler steam humidifier
Provides humidification control and consists of a steam
generator, steam distribution tube, fill valve, drain pump and
electronic controls, located within the evaporator module.
The 2.4 kW (at 380V) humidifier produces a maximum steam
output of 3 kg/hr (adjustable).
Note: These humidifiers should only be used where the supply
water has a conductivity between 80 and 1000 mS/cm and a
water pressure of 0.3 to 8 bar (Max. supply water temperature
30 oC).
Modulating chilled water valve
Optional fully modulating (2 or 3-way) chilled water valve for
close control applications. The valve body is rated for 27.5 bar
(2750 kPa) operating pressure for closed systems. For high
pressure open systems, consult Applications Engineering for
valve and actuator selections.
Plenum
They maintain minimum refrigerant temperature and are
energised while the unit is powered and the compressor is off.
Condensate pump ( units with
humidifier)
The condensate pump is provided for mounting either under
the raised floor or local to the unit and is complete with sump,
motor, pump and automatic control. The pump has a capacity
of 548 l/hr at a head of 6 meters of water. (max. water
temperature 82 oC).
Condensate pump (units without
humidifier)
The condensate pump is provided for mounting within the
unit and is complete with an internal sump which will switch
the pump motor on when water is detected. When water has
been removed from the sump, the pump will automatically
stop.
A 400mm high top discharge plenum, with insulated side
panels and painted to match the unit colour, is available for
applications where the supply air side of the unit is to be
connected to a ceiling void. Plenums with discharge grilles
(both fixed and adjustable) are available to special order.
10
Fresh air kit
A fresh air supply kit is available comprising a spigot
connection for 100mm I.D. duct hose (hose not supplied by
Liebert) and a cylindrical intake filter.
3-way water regulating valve
A 3-way water regulating valve can be fitted and is designed
to operate with fluid working pressures of 10.1 bar (1010
kPa). The valve is rated for a maximum fluid temperature of
77 oC.
Note: This valve is supplied loose for fitting externally to the
machine and comes complete a 1m capillary line.
9
Flow Rate
Ltrs/Hour
8
7
0
Lift in
metres
1
6
2
3
5
0
10
20
30
Horizontal Distance Pumped in metres
Crankcase heaters
Crankcase heaters are available as an option with all
compressorised models (standard on split air-cooled models).
10
Figure 1 - Condensate pump capacity chart (units
without humidifier)
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Optional features - all models (continued)
Refrigerant non-return valves
Refrigerant non-return valves for air-cooled units are
available as an option.
The valve is installed on the liquid line, close to the condenser
and mounted vertically.
High efficiency filters
Optional high efficiency filters are available for all models.
The high efficiency filters are interchangeable with the
standard filters. The filters are EU4 (Eurovent 4/5), filtration
class G4 (CEN standards).
Filter clog switch
An adjustable diaphragm-type, differential pressure switch
can be fitted to initiate a change filter alarm when a
pre-selected pressure drop across the filter bank is exceeded.
Hot water reheat
The economical hot water reheaters have the capacity to
maintain dry bulb conditions when the system is calling for
dehumidification. The reheats are controlled by a 3-way
(on/off) valve from the microprocessor control panel. The
system is completely pre-piped and includes an air bleed
valve. The reheat coil is single row, constructed of copper
tubes with aluminium fins. The coil is tested to a pressure of
30 bar.
A hot water thermostat (provided by the customer) is used in
the valve control sequence to determine the availability of
reheat capacity.
Water detection options
The water detection sensor LT410 contains an isolated switch
that closes when water (or other conductive liquid) is detected
by the sensor probes. The sensor is hermetically sealed,
robust and should be fitted in the location where water
problems might occur.
The LT460 is a water detection cable. The cable is placed on
the floor around the base of the unit. It will generate an alarm
(via contact closure) if water (or other conductive liquid)
comes in contact with the cable.
Smoke alarm
The smoke detector will activate an audible alarm and stop the
unit if smoke is detected in the return air. The sensor is an
optic smoke detector (Tyndall effect) which is insensitive to
light or air movement.
Firestat
The firestat deactivates the unit when the return air
temperature is too high. The firestat can be mounted in the
unit or remotely, consult Liebert Applications Engineers for
further details.
Environmental Alarm Package
The Electronic Environmental Alarm Package (EEAP) is a
remote temperature and relative humidity sensor (additional
to the internal sensor) connected to the unit controller.
The sensor can be installed up to 20m from the unit and
generates an alarm if the temperature or the relative humidity
exceeds one of the 4 user-set limits:
· High Temperature Limit
(Adjustable from 10°C to 50°C)
· Low Temperature Limit
(Adjustable from 0°C to 30°C)
· High Humidity Limit
(Adjustable from 30% to 99%)
· Low Humidity Limit
(Adjustable from 10% to 70%).
Floorstand
Floorstands are available in a range of heights: 230mm,
305mm, 380mm, 460mm, 530mm and 610mm. Each height
of floorstand is adjustable over a ± 38mm range. The
floorstands permit installation and connection of the unit
prior to installation of the raised floor.
Turning vane
A factory installed turning vane may be specified to direct the
air as required within the floorstand.
Full details are available from your Liebert representative.
SLE MT TDM E.3_r1 (10/99)
11
Mini Tower - Technical Data Manual
Optional features - all systems (continued)
Hiromatic graphic*
*: The Hiromatic Graphic is supplied in a wall-mounted box
for remote installation.
The Hiromatic Graphic sets even higher standards in
p u r pos e-des igned control system s for preci s i on
air-conditioning. It simultaneously monitors the critical space
and signals alarms either locally or remotely. The graphics
screen displays all the major parameters, including symbolic
representation of unit functions, such as heating, cooling etc.;
in addition temperature and humidity variations with time can
be presented graphically on the screen. All diagnostic
procedures, including the checking and calibration of input
and output signals, and of the microprocessor itself, can be run
from the front panel
BEMS Interface
Features
Note: For full details of the controller, refer to the Hiromatic
Graphics Controller Manual, (P/N SLE HG OM).
· Backlit LCD graphics display
· User interface via pushkeys
· Battery-backed clock for date/time and real time functions
· Password control for setpoints, unit/control setup and
service functions
· Graphics display of temperature and humidity over a 24
hour period
The Hiromatic Graphic is specifically designed for group
management of a number of individual units although it can
be used in stand-alone applications. Due to its large graphical
display area, combined with exceptional contrast, it allows
the user to move around easily within the network of
connected unit controllers (up to max. 16). It is possible to
control/adjust each connected units operations from a single
point.
The controller is menu-driven and user menu’s are available
in 10 languages. The controller records the last 120 “events”
(Alarms, Warnings etc.) occurring in the system along with a
“Graphic Data Record” for each connected unit. The Graphic
Data Record displays the temperature and humidity readings
from each unit for the last 24 hours (stored since the last
start-up of the unit).
The Hiromatic Graphic allows units on a network to be
integrated with the Hirolink Communications Bus when an
RS422 card is installed at the back of Hiromatic. Hiromatic
can control up to 8 Microface units in this configuration and
communicate the relevant data to Hirolink.
Hirolink works as a communications manager between the
Hiromatic Graphic and Microface units and industry standard
field busses and protocols used in Building Management
Systems such as Mod-Bus, J-Bus, Satchwell, etc.
Special packaging
Where the unit is to be transported by sea or in other cases
where heavy duty packaging is required, special crating is
available.
This can consist of either a wooden crate over the standard
carboard/bubble wrap packaging or the entire unit can be
encased in a wooden box.
Alternative refrigerant R407C
An optional “green” refrigerant, R407C can be supplied with
all compressorised models.
The compressor is filled with a special ester oil required for
R407C. Air cooled units are filled ex-factory with a holding
charge of dry nitrogen. Water and glycol units are charged
with R407C.
The Hiromatic Graphic controls date and time functions using
them as operating information for the customer and as a
reference whenever a status change occurs, logging the status
change in the “Status Report”. Details of the event which
occurred, the date and time at which the event occurred are
also stored. Using buffered RAM, the Hiromatic also stores
the operating hours of each component (compressor, fan,
electric heaters, humidifier etc.) for each connected unit.
A feature uniquely available with the Hiromatic controller is
“Sleep Mode” Sleep Mode allows units to be programmed to
switch on and off at different times of the day, and on different
days of the week.
12
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Optional features - all systems (continued)
Special colour
Where required by the installation, the unit can be supplied in
any RAL colour. Minimum order quantities may apply,
consult Liebert Applications Engineering.
Extended warranty
The standard, parts-only, warranty is 15 months from the unit
ship date. This can be extended to 21, 27 or 39 months as an
option.
Flow switch
The flow switch is available as an option with chilled water
units. It is fitted as standard on the chilled water inlet line but
can be fitted on the bypass-leg (3-way valves) or between the
valve and the coil, if required by the application.
The switch is of the paddle type and is complete with volt-free
contacts. It can be wired to activate an alarm and/or shut down
the unit should the chilled water supply be interrupted.
Epoxy coated fins
- condensing unit
If the condensing unit is to be installed in a potentially
corrosive environment or close to salt water, epoxy/acrylic
coated fins are available to maximise the operating life of the
condenser coil. Capacity will be derated, contact Liebert
Applications Engineering for specific details.
SLE MT TDM E.3_r1 (10/99)
13
Mini Tower - Technical Data Manual
Technical data - all models
Gross Cooling1 Capacities Data in kW
Water2
Cooled
Air
Cooled
TS04
TS06/
TSF6
TS09/
TSF9
TS04
TS06
TS09
TS04
TS06
TS09
TS07
TS11
Total
5.5
7.2
9.5
5.9
7.5
10.4
6.0
7.4
9.4
8.3
11.9
Sensible
4.8
6.2
8.4
4.9
6.3
8.7
5.7
6.6
8.3
6.8
9.4
Total
5.3
6.9
9.1
5.6
7.1
9.8
6.0
7.0
9.1
6.8
9.7
Sensible
4.7
6.1
8.2
4.8
6.2
8.5
6.0
6.5
8.2
6.1
8.5
Total
5.3
7.2
9.4
5.4
7.4
9.6
6.0
7.3
9.4
6.3
8.9
Sensible
4.7
7.2
9.4
5.1
7.4
9.1
6.0
7.3
9.4
6.3
8.9
Total
5.0
6.6
8.7
5.3
6.7
9.3
5.8
6.7
8.7
5.5
7.8
Sensible
4.6
6.0
8.0
4.7
6.0
8.3
5.8
6.3
8.0
5.5
7.8
MODEL
26 ºC DB,
50% RH
24 ºC DB,
50% RH
24 ºC DB,
45% RH
22 ºC DB,
50% RH
Chilled3
Water
Glycol
Cooled
: Capacity data is based on gross cooling capacity. To obtain nett figures, deduct the fan motor kW.
: 24 C Entering Water Temperature and 43 C Condensing Temperature
7.2 C Entering Water Temperature and 5.5 C Temperature Rise
: Air cooled capacities, packaged/split, are stated at 32 C outside ambient.
1
2
o
3:
o
o
o
4
o
Fan Section - Single Fan, Direct Drive
Air Flow m /h
(m3/s)
1600
(0.44)
1800
(0.5)
2300
(0.64)
1600
(0.44)
1800
(0.5)
2300
(0.64)
1600
(0.44)
1800
(0.5)
2300
(0.64)
1800
(0.5)
2300
(0.64)
Ext. Static Press. Pa
25
25
25
25
25
25
25
25
25
25
25
3
Evaporator Coil - Copper Tube/Aluminium Fin
Face Area m
Chilled
Water Coil
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
Rows of Coil
2
3
4
2
3
4
2
3
4
3
4
Face Velocity m/s
1.2
1.34
1.72
1.2
1.34
1.72
1.2
1.34
1.72
1.34
1.72
2
Flowrate/Pressure Drop
Water Cooled Condensers
Chilled
Water Coil
Flowrate (l/s)
--
--
--
0.1
0.2
0.3
0.1
0.2
0.3
0.4
0.5
Pressure Drop (kPa)
--
--
--
0.7
2.6
5.6
0.7
2.6
5.6
15.7
29.9
14
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Technical data - all models (continued)
Pipe Connections
Model
Chilled
Water
Return
Chilled
Water
Supply
TS04 A
-
-
1
2
in.
TS06 /TSF6 A
-
-
1
2
in.
TS09 /TSF9 A
-
-
1
2
in.
TS 04 W/G
-
-
-
-
3
TS 06 W/G
-
-
-
-
3
TS 09 W/G
-
-
-
3
-
-
TS 07 C
3
TS 11 C
3
Hot
Gas
Line
-
4
in. BSP
4
in. BSP
1
3
1
3
4
in. BSP
4
in. BSP
1
Liquid
Line
3
3
3
-
1
8
in.
8
in.
8
in
3
3
3
-
-
10mm
18mm
-
-
12mm
18mm
4
Humidifier
& Coil
Drain
1 in.
4
Male
Flared
3 "
4
Female
BSP
-
-
-
-
-
.3
MMC10
Steam
Distributor
Drain
-
3
MMC08
Humidifier
Supply
-
3
4 in. BSP
in. BSP
4
2
in. BSP
4
2
in. OD
1
4
2
-
4
Water
Connections
4
4
-
-
-
-
BSP = British Standard Pipe; : Male Thread Connections; : Female Thread Connections; : Male flare connector, : O.D. Copper
1
2
3
4
Condensing Unit Section
MMC08
MMC10
Air Volume m3/h (m3/s)
5510 (1.53)
5510 (1.53)
Face Area m2
0.60
0.60
Face Velocity m/s
2.5
2.5
Rows of Coil
4
4
Weight kg
87
90
Weight (unpacked) - indoor unit
Model
TS04/6/9A1
TSF6/9A
TS04/6/9W & G
TS07/11C
Weight kg
164.3
136.8
170.5
136.8
: For air cooled condenser weights and pipe sizes, refer to the Condenser Technical Data Manual P/N SLE CD TDM.
1
Reheat/Humidifier section - all models
Electric Reheat - Single Stage, Fin Tubular
Total reheat capacity at 400V
3kW (3 number 1kW (400V) elements)
Electrode Boiler Steam Humidifier
Max. Capacity
3.0 kg/h
Cleanable, open cell foam EU3 Filter
1 no.
Filter - all models
SLE MT TDM E.3_r1 (10/99)
15
Mini Tower - Technical Data Manual
Electrical data - all models
Mini Tower Electrical Ratings
Model
Compressor*
FLA
Fan Motor
kW
OA
Electric
Reheat
FLA
Steam
Humidifier
kW
FLA
kW
FLA
230/1/50
400/3/50
Nom.
230/1/50
230/1/50
400/3/50
Nom.
400/3/50
Nom.
400/3/50
TS04A/W/G
9.7
—
0.40
2.43
3.6
—
3.0
4.3
2.5
7.0
TS06A/W/G
12.3
—
0.40
2.70
3.6
—
3.0
4.3
2.5
7.0
TS09A/W/G
—
6.2
0.40
3.10
3.6
—
3.0
4.3
2.5
7.0
TS07C
—
—
0.40
2.70
3.6
—
3.0
4.3
2.5
7.0
TS11C
—
—
0.40
3.10
3.6
—
3.0
4.3
2.5
7.0
TSF6A
—
—
0.40
2.70
3.6
—
3.0
4.3
2.5
7.0
TSF9A
—
—
0.40
3.10
3.6
—
3.0
4.3
2.5
7.0
MMC08
—
4.8
0.40
—
—
3.5
—
—
—
—
MMC10
—
6.6
0.40
—
—
3.5
—
—
—
—
Electrical Ratings - Other Matching Equipment
Air Cooled
Condenser
Drycooler
Indoor Model
Model
FLA
Model
TS04A
HCA07
1.0
—
—
TS06A
HCA10
2.0
—
—
TS09A
HCA14
1.25
—
—
TS04G
—
—
DSL009
3.0
TS06G
—
—
DSL009
3.0
TS09G
—
—
DSL009
3.0
230/1/50
FLA
230/1/50
*: Quoted for R22
Note 1 : FLA = Full Load Amps
Note 2: OA = Operating Amps
Note 3 : Nom. = Nominal
Note 4 : All units require a Neutral.
Note 5: Condenser/Drycooler selection based on an ambient temperature of 32 C. For other ambient temperatures, consult the
Drycooler or Condenser Technical Data Manuals (P/N’s SLE DC TDM & SLE CD TDM).
o
16
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Sound data - all models
Sound Pressure Levels dB(A)
TS04/6/9 A/W/G
TSF6/9 A & TS07/11C
TS06A/W/G
TS09A/W/G
Standard Air Volumes TSF6A & TS07C
Sound Pressure Level dB(A)
Sound Pressure Level dB(A)
Standard Air Volumes TS/04A/W/G
At 1.5m
Free
Field
At 1.5m
Free
Field
Air Volume m3/h (thousands)
Air Volume m3/h (thousands)
Notes:
1.
2.
3.
4.
5.
6.
TSF9A & TS11C
3
Sound pressure levels (at 1.5m) were measured in a room with a reverberation time of 0.476 seconds and a net volume of 270m .
For unit standard air volumes and capacities, refer to the unit capacity section of this manual.
For more information on air volumes other than standard, consult the Liebert Applications Engineering Department.
The above graphs are for a constant 25 Pascals external static pressure, all figures are quoted at standard operating conditions.
Free field sound pressure levels are calculated from the dBX & dBY/ dBZ Sound Power components.
General Tolerance 1.5 dB(A)
Sound Power Levels dB (re: 1 pW)
Model
TS04A/W/G
TS06A/W/G
TS09A/W/G
TSF6A &
TS07C
TSF9A &
TS11C
Hz
31.5
63
125
250
500
1k
2k
4k
dBx
68.8
60.8
65.5
58.8
54.2
49.3
43.2
36.8
dBy
79.9
72.1
60.8
56.9
57.5
50.9
44.4
35.1
dBz
80.8
72.5
61.2
57.2
57.9
51.3
44.8
35.5
dBx
72.8
64.1
68.9
62.8
57.3
52.6
46.8
40.1
dBy
83.2
75.4
64.5
60.2
60.8
54.2
47.8
38.4
dBz
83.6
75.8
64.5
60.5
61.2
54.6
48.1
38.2
dBx
75.9
68.8
72.2
66.3
61.2
56.5
50.8
44.3
dBy
87.3
79.2
68.1
64.2
64.7
58.0
51.6
42.5
dBz
87.5
79.7
68.4
64.4
65.1
58.8
52.0
42.8
dBx
69
61.1
65.9
59.2
54.3
49.6
43.8
37.1
dBy
80.2
72.4
61.8
57.2
57.8
51.2
44.7
35.4
dBz
80.6
72.7
61.5
57.5
58.2
51.6
45.1
35.8
dBx
72.3
65.8
69.3
63.5
58.9
53.6
47.1
41.0
dBy
84.1
76.0
65.2
61.8
61.5
55.0
48.2
39.5
dBz
84.5
76.7
65.4
61.4
62.1
55.5
49.9
37.9
Figure 3 - Measurement
directions for noise data
Condensing units - MMC08/10
Sound Pressure level at 2m in the Free Field: MMC08: 56dB(A). MMC10: 57 dB(A).
Note: For condenser sound data - refer to the Condenser Technical Data Manual.
SLE MT TDM E.3_r1 (10/99)
17
DX
WATER
DX
AIR
35
LIQUID
LINE
3/8"
FLARE
WATER
OUTLET
3/4" BSP
FEMALE
HOT
GAS
1/2"
FLARE
WATER
INLET
3/4" BSP
FEMALE
HUMIDIFIER SUPPLY
HOT GAS / WATER INLET
LIQUID LINE / WATER OUTLET
431
3/4" ID
DRAIN
1/4" OD
3/4" ID
1/4" OD
DRAIN
110
HUMIDIFIER
SUPPLY
HUMIDIFIER
SUPPLY
DETAIL 'A'
END VIEW
LEFT
205
55
REMOVABLE
1749
205
10
PIPING ENTRIES
(SEE DETAIL 'A')
ALTERNATIVE
PIPING ENTRIES
(REFER TO DETAIL 'A')
165
REAR PANEL
A
188
95
179
(DIM'NS INCLUDE PANELS)
95
(SEE DETAIL 'B')
CABLE ENTRIES &
FAN DISCHARGE OPE.
(DOWNFLOW UNITS ONLY)
SECTION A-A
392
FRONT ELEVATION
690
A
RETURN AIR
REMOVABLE
END VIEW
RIGHT
DETAIL 'B'
ALTERNATIVE
CABLE ENTRIES
(REFER TO DETAIL 'B')
FRONT PANELS
50
CONTROL DISPLAY
150
RETURN AIR
236
608
100
750
45
COMPRESSOR
30
18
170
470
GRILLE DIM
694
FRONT VIEW
(PANELS REMOVED)
SHOWING MAJOR COMPONENTS
DIRECT
DRIVE
BLOWER
AIR FILTER
ELECTRIC PANEL
HUMIDIFIER
28
DISCHARGE GRILLE
(UPFLOW UNITS ONLY)
MAINS SUPPLY INPUT
& ALARM TERMINALS
CONDENSER
(WATER, GLYCOL)
(OPTIONAL)
Mini Tower - Technical Data Manual
Dimensional data - air, water/glycol cooled (packaged)
SLE MT TDM E.3_r1 (10/99)
25
CW
3/4" BSPT
MALE
WATER
OUTLET
HUMIDIFIER SUPPLY
CHILLED WATER OUTLET
CHILLED WATER INLET
DETAIL 'A'
WATER
INLET
25
3/4" BSPT
MALE
CONDENSATE DRAIN
431
END VIEW
LEFT
236
1/4" OD
HUMIDIFIER
SUPPLY
55
REMOVABLE
110
REAR PANEL
1749
165
3/4" ID
DRAIN
205
10
1/4" SAE
FLARE CONN
HUMIDIFIER
STEAM DRAIN
PIPING ENTRIES
(SEE DETAIL 'A')
ALTERNATIVE
PIPING ENTRIES
(REFER TO DETAIL 'A')
A
188
95
179
(DIM'NS INCLUDE PANELS)
SECTION A-A
392
FRONT ELEVATION
690
95
FAN DISCHARGE OPE.
(DOWNFLOW UNITS ONLY)
A
RETURN AIR
CABLE ENTRIES &
HUMIDIFIER STEAM DRAIN
(SEE DETAIL 'B')
REMOVABLE
END VIEW
RIGHT
DETAIL 'B'
ALTERNATIVE
CABLE ENTRIES
(REFER TO DETAIL 'B')
FRONT PANELS
50
CONTROL DISPLAY
150
RETURN AIR
236
608
100
750
45
HOT WATER
VALVE
(OPTIONAL)
CHILLED WATER
VALVE
30
SLE MT TDM E.3_r1 (10/99)
170
470
GRILLE DIM
694
FRONT VIEW
(PANELS REMOVED)
SHOWING MAJOR COMPONENTS
DIRECT
DRIVE
BLOWER
AIR FILTER
ELECTRIC PANEL
HUMIDIFIER
28
DISCHARGE GRILLE
(UPFLOW UNITS ONLY)
MAINS SUPPLY INPUT
& ALARM TERMINALS
(OPTIONAL)
Mini Tower - Technical Data Manual
Dimensional data - chilled water
19
25
Mini Tower - Technical Data Manual
Dimensional data - air cooled (split)
20
SLE MT TDM E.3_r1 (10/99)
Mini Tower - Technical Data Manual
Dimensional data - air cooled condensing unit (split)
690
690
500
1050
SIDE VIEW
FRONT VIEW
REAR VIEW
AIR FLOW
4 no. ø8 mm Mounting Holes
AIR FLOW
526
AIR FLOW
=
887
=
AIR FLOW
TOP VIEW
SLE MT TDM E.3_r1 (10/99)
21
A World Leader in
Computer Support
Systems.
Environmental Control
Power Protection
Site Monitoring
Liebert Corporation designs,
manufactures and markets complete
systems for improved uptime and
performance
of
electronic
equipment, including computer
rooms, networks, medical, industrial,
and other critical systems. The result
is improved business operations,
increased productivity and higher
return on the customer's electronic
equipment investment. Liebert
Systems provide dependable
environmental control and electrical
power protection, combined with
centralised monitoring. This
approach represents a single-source
integrated support network. Based on
over two decades of experience and
over
100,000
installations
worldwide, Liebert is committed to
offering the highest quality products
and services for critical electronics.
Liebert
European Headquarters
While every precaution has been taken to ensure accuracy and completeness
in this manual, Liebert assumes no responsibility and disclaims all liability for
Liebert Europe
Zona Industriale Tognana,
Via Leonardo da Vinci, 8,
damages resulting from the use of the information contained herein or any
35028 Piove di Sacco (PD), Italy.
errors or omissions.
Tel: +39-049-9719111
Fax: +39-049-9719455
Internet: http://www.liebert.com
International Headquarters
Liebert Corporation
1050 Dearborn Drive, P.O. Box 29186
© Liebert Corporation
® All rights reserved throughout the world. Specifications
subject to change without notice. Liebert and the logo, are
registered trademarks of Liebert Corporation.