Cherry Valley Solar Application

March 23, 2016
Mrs. Michelle Buck, AICP
Town of Leicester Planning Department
3 Washburn Square
Leicester, MA 01524
Re:
Site Plan Review
Cherry Valley 1.0MW PV Array
148 Henshaw Street
Town Assessor’s Map 24, Lot A2 0
Leicester, Massachusetts
Dear Mrs. Buck:
Fuss & O’Neill has prepared the enclosed Site Plan Review Application on behalf of ZPT Energy
Solutions, LLC for the construction of a 1.0 MW photovoltaic array at the above-referenced site.
The attached application and supporting documents were prepared in accordance with the Town’s
Site Plan Review Rules and Regulations, and Zoning By-Laws.
The project site is approximately 8.0 acres and is located on the western side of Henshaw Street.
The site is part of a 149-acre property owned by Cherry Valley and Rochdale Water District that
includes Henshaw Pond. Currently, the site is wooded and has a dirt road from Henshaw Street
along the northern site boundary. The entire site is sloped to the north and drains to Henshaw
Pond.
An intermittent stream on the site conveys stormwater from a portion of the site towards the north
across the dirt access road. The wetland resource boundaries were delineated by National Resource
Services and were field surveyed by National Land Surveyors-Developers. The wetland delineation
methods are identified in the Report of Findings, 148 Henshaw Street, dated March 7, 2011.
317 Iron Horse Way
Suite 204
Providence, RI
02908
t 401.861.3070
800.286.2469
f 401.861.3076
www.fando.com
Connecticut
Massachusetts
Rhode Island
South Carolina
Work associated with the proposed facility includes installing the PV panels, electrical
infrastructure, perimeter fencing, landscaping, and the necessary land clearing and grubbing for
construction and operation of the array. Construction activities are proposed within the 100-foot
buffer zone, but no work will occur within the 25-foot buffer zone (No Disturb Zone). The
existing dirt road will also be improved with gravel, but will not require widening or significant
grading. Site grading is proposed only as required to accommodate turnaround area and to
construct a culvert to convey the existing intermittent stream under the gravel access road.
Soil erosion and sediment control practices will be implemented to prevent impact to wetland
resources and abutters. The controls will be installed prior to the commencement of work and any
disturbed areas will be stabilized prior to the removal of the controls. Controls include silt fence
F:\P2015\1249\A10\Deliverables\Site Plan Review\Site Plan Review Cover Letter.docx
Corres. (RI)
309 East County Road
Rutland, MA 01543
P: 508-210-6367
ZP-101 Cherry Valley
Mwac Photovoltaic Solar Electricity Generation Facility
E: pforte@zpeenergy.com
System Size =
Total Site=
Development Footprint=
Remaining Site Area=
MW AC
AC
AC
AC
Unit
Estimated
Quantity
Labor
Cost
CONTRACTOR FEES
Mobilization
Supervision/Management
Silt Fence
Rock Entrance
Permitting Fees
Subtotal Contractor Fees
LS
LS
LF
EA
LS
1
1
1700
1
1
$5,000.00
$5,000.00
$2.50
$3,000.00
$7,500.00
SITEWORK REMOVALS
Interior Site Gravel access drive & interconnection access drive
Restoration seeding from site activities
Fence removal & recycling
Residual site waste and cleanup
Subtotal Sitework Removal
SF
AC
LF
LS
8500
3.5
1580
1
$0.50
$3,000.00
$1.50
$3,833.33
RACKING REMOVAL
Remove and recycle racking system
Subtotal racking removal
LF
7500
$0.45
SOLAR MODULE REMOVAL
Remove Trina TSM-PD14 module
Subtotal solar module removal
EA
4500
$4.00
DECOMISSIONING BID TABULATION
1
5.7
3.5
2.2
Material Recycle
Value/(Cost)
Net
Cost
$5,000.00
$5,000.00
$4,250.00
$3,000.00
$7,500.00
$24,750.00
$4,250.00
$10,500.00
$2,370.00
$3,833.33
$70,453.33
$14,293.18
-$10,918.18
-$10,918.18
$18,000.00
$18,000.00
Notes
AC & DC WIRING REMOVAL
DC/AC direct burial wire removal
Interconnection pole removal
AC overhead wire removal
Central inverter removal
Subtotal AC & DC wiring removal
LF
LS
LF
EA
1333
7
440
1
$6.00
$400.00
$0.66
$4,000.00
Central communications pad removal
Remove and dismantle central equipment pad and transformer
Subtotal central communications pad removal
LS
1
$9,600.00
DECOMISSIONING SUBTOTAL
CONTRACTOR PROFIT-Markup 10% of overall contractor costs (excludes recycling value)
TOTAL DECOMISSIONING
$16,566.23
-$8,568.23
$2,800.00
$290.40
$4,000.00
-$1,477.83
$9,600.00
$9,600.00
$110,407.33
$11,040.73
$121,448.06
309 East County Road
Rutland, MA 01543
P: 508-210-6367
ZP-101 Cherry Valley
Mwac Photovoltaic Solar Electricity Generation Facility
Structural steel - structural racking
total weight
Racking weight Project size
lbs/per MW DC mw dc
lbs
tons
102350
1.47 150454.5 75.22725
E: pforte@zpeenergy.com
recycle val
per ton
190
total
$
$14,293.18
Wire
gauge
material
awg/kcmil
element
#12 awg
cu
#10 awg
cu
3/4" dia ground rodscu
500 kcmil
al
350 kcmil
al
300 kcmil
al
250 kcmil
al
#3/0 awg
al
#4 awg
al
#1 awg mv-90
al
length
deliver weight install weig recycle value
per ton
ft
lb
lb
3360
900
34666.67
810
3360
9000
200000
8100
190
26.66667 83.3333333
75
1833.333 1046.667
942 600
2266.667 933.3333
840 600
4000 1433.333
1290 600
3866.667 1183.333
1065 600
3466.667
700
630 600
7600 483.3333
435 600
366.6667
110
99 600
total
total
$
$1,360.80
$13,608.00
$7.13
$282.60
$252.00
$387.00
$319.50
$189.00
$130.50
$29.70
$16,566.23
1
2
1
2
3
3
4
6
7
13 per comb for yingli 310 max
200amp 600VDC
Final layout TBD
String A1 - A14
5
14 per comb for renesola 305
String Combiner A1
-
200amp 600VDC
A
A
+
String A15 -A28
+
200amp 600VDC
String Combiner A2
String A29 - A42
200amp 600VDC
+
String Combiner A3
-
200amp 600VDC
String A43 - A56
+
String Combiner A4
-
200amp 600VDC
B
+
200amp 600VDC
String Combiner A5
-
24VDC to Combiners
String A71 - A84
NC contact from Protective relay
200amp 600VDC
+
to Inverter remote shutdown
String Combiner A6
-
4
Inverter "A"
200amp 600VDC
String A85 - A98
+
Internal control contactor
String Combiner A7
-
200amp 600VDC
DC -
String A99 - A112
Service
Disconnect
AC Disconnect
DC CT
+
200amp 600VDC
String Combiner A8
-
C
C
and lockable
DC -
To Transformer
B
String A57 - A70
5A
String A113 - A126
String Combiner A9
-
GND
200amp 600VDC
String A127 - A140
+
String Combiner A10
-
200amp 600VDC
SGI 500XT
SEE INVERTER TABLE
600VDC max operating
FOR GRID PROTECTION
1705amps DC MAX
SETTINGS. PAGE 3
208 AC Delta
String A141 - A154
1387 Amps AC current limit
+
200amp 600VDC
String Combiner A11
-
5
200amp 600VDC
+
500kw power limit
UL1741
D
D
String A155 - A168
+
Weather station Mounted near inverters
String Combiner A12
String A169 - A182
TCP Modbus to site controller
+
String Combiner A13
-
Inverter A combiner
with load break disconnect
String A183 - A196
and contactor
+
String Combiner A14
-
+
Title
String Combiner A15
-
NOTICE: THIS DOCUMENT IS THE PROPERTY OF ZERO POINT ENGINEERING INC AND IS
ZP-101 148 henshaw street Leicester, MA
E
E
PRELIMINARY
NOT FOR CONSTRUCTION
PROFESSIONAL STAMP
String A197 - A204
DELIVERED ON THE EXPRESS CONDITION THAT IT IS NOT TO BE DISCLOSED, REPRODUCED
Author
IN WHOLE, OR IN PART, OR USED FOR ANYONE OTHER THAN ZERO POINT ENGINEERING
Zero Point Engineering
WITHOUT ITS WRITTEN CONSENT, AND THAT NO RIGHT IS GRANTED TO DISCLOSE OR SO
USE ANY INFORMATION CONTAINED IN SAID DOCUMENT. THIS RESTRICTION DOES NOT
LIMIT THE RIGHT TO USE INFORMATION FURNISHED BY VENDORS OR OTHERS OUTSIDE
Revision
1.0
ZERO POINT ENGINEERING INC.
1
2
3
4
5
6
Sheets
1 of 3
7
1
2
3
4
5
6
7
14 per comb for renesola 305
1
2
3
13 per comb for yingli 310 max
Final layout TBD
200amp 600VDC
String B1 - B14
A
A
+
String Combiner B1
-
200amp 600VDC
String B15 -B28
+
200amp 600VDC
String Combiner B2
String B29 - B42
200amp 600VDC
+
String Combiner B3
-
200amp 600VDC
String B43 - B56
+
String Combiner B4
B
200amp 600VDC
String B57 - B70
+
200amp 600VDC
String Combiner B5
-
24VDC to Combiners
String B71 - B84
NC contact from Protective relay
200amp 600VDC
+
to Inverter remote shutdown
String Combiner B6
-
200amp 600VDC
String B85 - B98
4
Inverter "B"
+
Internal control contactor
String Combiner B7
-
200amp 600VDC
DC -
String B99 - B112
Service
Disconnect
AC Disconnect
DC CT
200amp 600VDC
String Combiner B8
-
C
C
+
5A
String B113 - B126
String Combiner B9
-
GND
200amp 600VDC
String B127 - B140
+
String Combiner B10
-
200amp 600VDC
SGI 500XT
SEE INVERTER TABLE
600VDC max operating
FOR GRID PROTECTION
1705amps DC MAX
SETTINGS. PAGE 3
208 AC Delta
String B141 - B154
1387 Amps AC current limit
+
200amp 600VDC
String Combiner B11
500kw power limit
UL1741
D
-
5
200amp 600VDC
+
D
and lockable
DC -
To Transformer
B
-
String B155 - B168
+
Inverter B combiner
String Combiner B12
-
with load break disconnect
and contactor
String B169 - B182
TCP Modbus to site controller
+
String Combiner B13
String B183 - B196
+
String Combiner B14
-
PRELIMINARY
NOT FOR CONSTRUCTION
PROFESSIONAL STAMP
String A197 - A204
Title
NOTICE: THIS DOCUMENT IS THE PROPERTY OF ZERO POINT ENGINEERING INC AND IS
E
ZP-101 148 henshaw street Leicester, MA
E
+
String Combiner A15
-
DELIVERED ON THE EXPRESS CONDITION THAT IT IS NOT TO BE DISCLOSED, REPRODUCED
Author
IN WHOLE, OR IN PART, OR USED FOR ANYONE OTHER THAN ZERO POINT ENGINEERING
Zero Point Engineering
WITHOUT ITS WRITTEN CONSENT, AND THAT NO RIGHT IS GRANTED TO DISCLOSE OR SO
USE ANY INFORMATION CONTAINED IN SAID DOCUMENT. THIS RESTRICTION DOES NOT
LIMIT THE RIGHT TO USE INFORMATION FURNISHED BY VENDORS OR OTHERS OUTSIDE
Revision
1.0
ZERO POINT ENGINEERING INC.
1
2
3
4
5
6
Sheets
2 of 3
7
2
3
4
connection to item 8
Mforce Gang operated switch
8
12.7kV
VFI
Class 2
VB
Pad mounted tamper proof
BAY PRCL
VB
S
T
DISTRIBUTION
3-PHASE
PT's
FEEDER
CT's
UTILITY INSTALLED
LIGHTNING ARRESTORS
PAD MOUNTED SWITCHGEAR
Revenue Grade Meter.
MODBUS
Edison Idea iDP-210 relay
SCADA, Advanced functions
Wh
Remote
data
unit
UTILITY-OWNED AND INSTALLED
iDP-210 (10,12,14)
Phases connected separately to iDP-120 (13,11,9)
Protection Relay output to inverters
for system shutdown
RECLOSER AND PRIMARY
iDP-210 (2,4,6)
Utility Supplied Communication
METERING OVERHEAD
STRUCTURES
CT's 1000:1, 1%
PT's 70:1
PRIMARY VOLTAGE EQUIPMENT SHALL BE RATED TO
B
BATT
WITHSTAND PRIMARY UTILITY FAULT CURRENT
SEE PROPOSED SETTINGS CHART
Communications from inverters
TRIP
and protection relay
GROUNDING CONDUCTORS TO BE INSTALLED PER
PV STRING INFORMATION
INVERTER INFORMATION
SITE CONTROLLER
MODBUS TCP
COOPER EDISON IDEA iDP210
PROTECTIVE RELAY PROPOSED SETTINGS
27-1
0.5pu
0.1 SEC
Number of Module In Series
11
Module Manufacturer
Renesola
27-2
0.85pu
1.9 SEC
Manufacturer
EATON
STC Power per String
3,300.00 W
Module Model Number
JC300M-24
51N
0.75A
0.9 SEC
Main Device
CUTLER-HAMMER TYPE "CRD" 100% RATED VISA TYPE BRKR
MEC ARTICLE 250 AND 690
PV MODULE AND ARRAY INFORMATION
SERVICE DISCONNECTS
Solectria
STC VOC at -20C
559.3
Max Power
300W
51-phase
1.5pu
2.2 SEC U.S. TCC U4
Frame
1600A 3P #CRD316T32SW MOFM (VISA)
Model Number
SGI 500XT
Vmpp at 39C
344.9
VOC at -20C
50.85
59-1
1.1pu
0.6 SEC
Trip Unit
DIGITRIP RMS310 LSI
Operating Voltage
330 - 600
Impp STC
8.20
Vmpp
36.6
59-2
1.2pu
0.1 SEC
Fuse Provision
NONE
Mpp Voltage Range
300 - 600
Isc STC
8.69
Impp
8.20
81U-1
57
0.1 SEC
Rating Plug
1600A
Max Continuous Power
500kW
Isc
8.69
81U-2
58.5
1.6 SEC
Main Bus Rating
1600 amp, 240 volts, 60 hz
Max VOC
600
Max Series Fuse
20 amp
81O
60.5
0.1SEC
Grounding
Remote Upstream
Max Operating Input Current
1,705
Total Array DC STC
1346.4 kWp
51C
50
2.0 SEC U.S. TCC U4
SWBD CCT RATING
50 KA SYM
AC Nominal Voltage
208 L-L
59N
100V
1.9 SEC
BUS Bracing
50 KA SYM
Operatin AC Voltage Range
+10% -12%
Ground Fault Protection
NONE
Max Rated Output Current
1,387 amps
Cooper K-SEC 926 gang operated M-force disconnect switch.
Suitable for Service Use
YES
Total Harmonic Distortion
< 3%
Type "USE-2" 90C outdoor rated.
15kv distribution class with ice shields.
Enclosure Type
3R (NONWALK-IN)
Power Factor
> 99%
Max length 1000ft. Minimum length 10ft
Max Voltage 17kv
Certifications
UL / CSA
CEC Efficiency
98%
Grid Protection
UL 1741
Strrings Per Inverter
189
Combiner Inputs
15
Combiner Fuses
400amps
Max Strings Per Fuse
24
NUMBERED DRAWING ITEMS
10awg with MC4 connectors per string from panels to string combiner.
2
60.05hz
under frequency
55hz
over current
110%
voltage imbalance
10%
over voltage instantaneous
140%
over voltage fast
120%
over voltage slow
110%
under voltage instantaneous
10%
under voltage fast
50%
under voltage slow
85%
gnd fault current trip
5 amps
2). INSTALLATION SHALL BE PERFORMED IN ACCORDANCE WITH
3 SECOND, 25 kA Sym. rms
Home runs based on 152amp max current. 300kcmil per pole, based on 3
detail 2. Type UF 90C in under ground plastic conduit, SCH 80 PVC, 28% fill
including ground conductor. 1200ft max length
THE LATEST REVISION OF THE NATIONAL ELECTRIC CODE
FAULT CLOSE (ASYM) 1 @ 20 kA, 3 @ 15 kA
9
NEC2014 AND MASSACHUSETTS AMENDMENTS
15 Ohm Neutral reactor
3). USE IRREVERSIBLE COMPRESSION CONNECTORS TO BOND
PQI Global Services / RMCLARK assoc.
GROUND WIRES
Voltage Class 15kV
4
See Service Disconnects Table
5
Cables from inverter to transformer LV. 6 x 700kcmil per phase. 90C
4). LABEL EQUIPMENT AND CONDUCTORS PER MEC REQUIREMENTS
BIL 95kV
Continuous Current 10amps
NOTICE: THIS DOCUMENT IS THE PROPERTY OF ZERO POINT ENGINEERING INC AND IS
Bracing 2000amps for 2 seconds
DELIVERED ON THE EXPRESS CONDITION THAT IT IS NOT TO BE DISCLOSED, REPRODUCED
Aluminum Windings
IN WHOLE, OR IN PART, OR USED FOR ANYONE OTHER THAN ZERO POINT ENGINEERING
Distribution type pad-mounted transformer. Tamper proof. Designed for
Max rise 150C
WITHOUT ITS WRITTEN CONSENT, AND THAT NO RIGHT IS GRANTED TO DISCLOSE OR SO
Step-up operation. 1000kva, 3-winding, LHL, 5 leg core. KNAN cooling
NEMA 3R enclosure
USE ANY INFORMATION CONTAINED IN SAID DOCUMENT. THIS RESTRICTION DOES NOT
class. 60C rise. ANSI C57.12.34 and C57.12.28. NEMA TR-1 sound level
Bottom feed
LIMIT THE RIGHT TO USE INFORMATION FURNISHED BY VENDORS OR OTHERS OUTSIDE
LV BIL 30KV. MV BIL 95KV. UL listed. Guages, sample port and visible
Pad Mounted
ZERO POINT ENGINEERING INC.
600vac.
6
UNLESS NOTED OTHERWISE.
MOMENTARY 40 kA Asy. rms
Integrated arc fault detection and shutdown.
conduit buried electrical duct bank per MEC 2014 figure B.310.15 (B)(2)(2)
65hz
1). CONDUCTOR SIZES SHOWN ARE FOR COPPER CONDUCTORS
LOAD BREAK, 50@600A, 10@900A
Max current 192amps. Load break rated lockable disconnect.
3
NOTES
CONTINUOUS CURRENT 600A
Input wire range 14 to 6 awg. NEMA 4. Output wire range (2) 1awg - 600kcmil
59.95hz
over frequency
BIL 110kv
Field combiner. 16 input, 15 amp fuses Solectria ARCCOM 24. UL1741 rated
PROTECTION SETTINGS
Reconnect High Frequency
8
D
1
C
Manufacturer
load break disconnect accessible without opening termination cabinet.
Minimum impedance H-X and H-Y 3.5% at 500kva. Target impedance
4%. Efficiency >99% CEC weighted. Dead-Front Loop fed. Fault current
limited to 20kA by PRCL "Zero Forcing" Fuse in transformer. Has fully rated
E
Insulated neutral bushing and 15ohm neutral reactor
7
ESB 756 C 5.5.3.1
PRELIMINARY
NOT FOR CONSTRUCTION
PROFESSIONAL STAMP
NEUTRAL REACTOR IS A PLACE HOLDER.
NATIONAL GRID WILL DETERMINE IF THIS
IS A REQUIREMENT AND WILL SPECIFY
THE REQUIRED PARAMETERS.
Title
ZP-101 148 henshaw street Leicester, MA
E
C
UTILITY
iDP-210 (13)
Primary Side
Reconnect Low Frequency
LINE
4-WIRE
VFI
Connection
D
PROPERTY
DISCONNECT
RECLOSER
iDP-210 (11)
supplied as
OEM equipment
Battery Back-up
GANG OPERATED
UTILITY INSTALLED
DEMARCATION
S
CT's and PT's
N
9
VB
T
13.2kv Ygnd
CUSTOMER
CT's
VFI
VB
From Inverter "B"
208D
7
UTILITY INSTALLED
PT's
From Inverter "A"
208D
PCC
S
T
iDP-210 (9)
A
Transformer
6
UTILITY METERING
B
6
5
Utility to make
7
Author
15 kV 3 Phase Vacuum Fault Interrupter (VFI) Pad-Mounted Switchgear.
Zero Point Engineering
Cooper Model 5 - 2 Way Part Number KP00610L01S09M. Single sided
dead-front. Front-mounted front-operated switch, trip-free operation.
Housing protective relay and all associated PT's, CT's, communication
Revision
1.0
and power supply transformers. Visible break window on all tap ways.
1
A
1
2
3
4
5
6
Sheets
3 of 3
7
Mono
Multi
T+E
Solutions
8tility
02'8/E
72 CELL
MULTICRYSTALLINE MODULE
P'1
300-315W
Ideal for large scale installations
POWER OUTPUT RANGE
‡ +igh powerful footprint reduces installation time and %2S costs
‡ 10009 8/10009 ,E& certiÀed
16.2%
MAXIMUM EFFICIENCY
One of the industry’s most trusted modules
‡ )ield proven performance
0~+3%
POWER OUTPUT GUARANTEE
Highly reliable due to stringent quality control
‡ 2ver 0 inhouse tests 89, T&, +), and many more
‡ ,nhouse testing goes well beyond certiÀcation reTuirements
‡ P,' resistant
As a leading global manufacturer
of next generation photovoltaic
products, we believe close
cooperation with our partners
is critical to success. With local
presence around the globe, Trina is
able to provide exceptional service
to each customer in each market
and supplement our innovative,
reliable products with the backing
of Trina as a strong, bankable
partner. We are committed
to building strategic, mutually
beneÀcial collaboration with
installers, developers, distributors
and other partners as the
backbone of our shared success in
driving Smart Energy Together.
‡ 200 Pa wind load
‡ 500 Pa snow load
‡ 25 mm hail stones at 82 kmh
LINEAR PERFORMANCE WARRANTY
Year ProdXFt Warrant\ ‡ Year Linear PoZer Warrant\
100%
Guaranteed Power
Trina Solar Limited
www.trinasolar.com
CertiÀed to Zithstand challenging enYironmental
conditions
Additio
nal Ya
lXe Iro
m
90%
Trina S
o
lar·V li
near Z
a
rrant\
80%
Years
5
10
Trina standard
15
20
Industry standard
25
THE Utility MODULE TSM-PD14
DIMENSIONS OF PV MODULE
unit:mm
ELECTRICAL DATA (STC)
Peak Power WattsPMAX Wp
941
00
05
Power Output TolerancePMAX %
180
JUNCTION
BOX
160
NAMEPLATE
G = 1200±10
4-Ø 9×12
INSTALLING HOLE
10
15
0 a Maximum Power 9oltage9MPP 9
.2
.
.0
.1
Maximum Power CurrentI MPP A
8.28
8.
8.8
8.51
Open Circuit 9oltage9OC 9
5.
5.5
5.5
5.
Short Circuit CurrentI SC A
8.
8.81
8.85
9.00
Module EfÀciency ηm %
15.5
15.
1.0
1.2
1276
1956
STC: Irradiance 1000 Wmò, Cell Temperature 25ƒC, Air Mass AM1.5 according to EN 090.
Typical efÀciency reduction of .5% at 200 Wm 2 according to EN 0901.
ELECTRICAL DATA (NOCT)
6-Ø 4.3 GROUNDING HOLE
12-DRAIN HOLE
A
A
Maximum PowerPMAX Wp
22
22
21
25
Maximum Power 9oltage9MPP 9
.5
.8
.1
.1
Maximum Power CurrentI MPP A
.
.2
.
.88
Open Circuit 9oltage9OC 9
2.1
2.2
2.2
2.
Short Circuit CurrentI SC A
.08
.11
.15
.2
NOCT: Irradiance at 800 Wmò, Ambient Temperature 20ƒC, Wind Speed 1 ms.
812
Back 9iew
MECHANICAL DATA
AA
I-V CURVES OF PV MODULE(315W)
8.00
800W/m2
195 ð 992 ð 0 mmð 9.05 ð 1.5 inches
Weight
2. kg 0.8lb
Glass
.0 mm,High Transmission, AR Coated Tempered Glass
Backsheet
White
Frame
Silver Anodi]ed Aluminium Alloy
-Box
IP 5 or IP rated
Cables
Photovoltaic Technology cable .0mmò 0.00 inchesò,
1200mm .2 inches
Connector
MC or MC Compatible
600W/m2
5.00
ƒC “2ƒC
Operational Temperature
0a85ƒC
10009DC IEC
10009DCUL
15A
Temperature CoefÀcient of PMAX
0.1%ƒC
Maximum System
9oltage
Temperature CoefÀcient of 9OC
0.2%ƒC
Max Series Fuse Rating
Temperature CoefÀcient of I SC
4.00
MAXIMUM RATINGS
0.05%ƒC
400W/m2
3.00
200W/m2
2.00
1.00
WARRANTY
0.00
10 year Product Workmanship Warranty
Voltage(V)
25 year Linear Power Warranty
Please refer to product warranty for details
CERTIFICATION
PACKAGING CONFIGURATION
Modules per box: 2 pieces
Modules per 0· container: 52 pieces
TSM_EN_Mar_2015_A
Current(A)
6.00
2 cells ð 12
Module dimensions
Nominal Operating Cell
Temperature NOCT
1000W/m2
7.00
Multicrystalline 15 ð 15 mm inches
Cell orientation
TEMPERATURE RATINGS
10.00
9.00
Solar cells
Recyclable
packaging
CAUTION: READ SAFETY AND INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT.
‹ 2015 Trina Solar Limited. All rights reserved. SpeciÀcations included in this datasheet are subMect to change without notice.
dĞƌƌĂ&ĂƌŵĂƚĂ^ŚĞĞƚ
dĞƌƌĂ&Ăƌŵ'ƌŽƵŶĚDŽƵŶƚͲ>ĂŶĚƐĐĂƉĞ
ƉƉůŝĐĂƚŝŽŶ͗
'ƌŽƵŶĚŝŶŐ͗
WĂŶĞůKƌŝĞŶƚĂƚŝŽŶ͗
ƌƌĂLJŽŶĨŝŐƵƌĂƚŝŽŶƐ͗
dŝůƚŶŐůĞ͗
>ŽǁĞƌWĂŶĞůůĞĂƌĂŶĐĞ͗
>ŽĂĚŝŶŐŽŶĚŝƚŝŽŶƐ͗
tĂƌƌĂŶƚLJ͗
ŶŐŝŶĞĞƌŝŶŐ͗
DĂƚĞƌŝĂů͗
ĂƐƚͲtĞƐƚ^ůŽƉĞ͗
EŽƌƚŚͲ^ŽƵƚŚ^ůŽƉĞ͗
DĂdž&ƵƐĞZĂƚŝŶŐ͗
ŽŵŵĞƌĐŝĂůƚŽhƚŝůŝƚLJ^ĐĂůĞ
d>ůŝƐƚĞĚ͕ůĞĐƚƌŝĐĂůůLJďŽŶĚĞĚƐLJƐƚĞŵ͕ǀĞƌŝĨŝĞĚtŝůĞLJ
>ĂŶĚƐĐĂƉĞ
hƉƚŽϳƉĂŶĞůƐŚŝŐŚĂŶĚƵƉƚŽϭϮƉĂŶĞůƐůŽŶŐ
ϱʹϰϱĚĞŐƌĞĞƐ
hƉƚŽϰϴŝŶĐŚĞƐ͕ƐƚĂŶĚĂƌĚ
hƉƚŽϭϲϬŵƉŚǁŝŶĚƐƉĞĞĚ͕ϴϬƉƐĨƐŶŽǁůŽĂĚ͕džƉŽƐƵƌĞ
ϮϬͲLJĞĂƌůŝŵŝƚĞĚǁĂƌƌĂŶƚLJ
WƌŽĨĞƐƐŝŽŶĂůŶŐŝŶĞĞƌ^ƚĂŵƉĞĚƌĂǁŝŶŐƐǀĂŝůĂďůĞŝŶϱϬ^ƚĂƚĞƐ
ƵƐƚŽŵŶŐŝŶĞĞƌĞĚƚŽdžĐĞĞĚƉƉůŝĐĂďůĞ^͕/͕ĂŶĚh>^ƚĂŶĚĂƌĚƐ͘
'ĂůǀĂŶŝnjĞĚƐƚĞĞů;'ϵϬŽƌĞƚƚĞƌͿ
ϮϬйŵĂdžŝŵƵŵ
ϲϬйŵĂdžŝŵƵŵ͕ůŝŵŝƚĞĚďLJŝŶƐƚĂůůĂƚŝŽŶĞƋƵŝƉŵĞŶƚ
ϯϬŵƉ&ƵƐĞZĂƚŝŶŐ
DĂdžĂƉĂĐŝƚLJŽĨWsŵŽĚƵůĞƐ͗
ϭϮ,ŝŐŚdžϭϮtŝĚĞ;ϭϰϰWĂŶĞůƐͿ͗
ϳ,ŝŐŚdžϭϬtŝĚĞ;ϳϬWĂŶĞůƐͿ͗
ϳ,ŝŐŚdžϵtŝĚĞ;ϲϯWĂŶĞůƐͿ͗
ϳ,ŝŐŚdžϴtŝĚĞ;ϱϲWĂŶĞůƐͿ͗
>ŝƐƚĞĚ&ƌĂŵĞůĞƐƐ;dŚŝŶ&ŝůŵͿWsDŽĚƵůĞ;Ϯϭ͟ͲϮϲ͟džϰϳ͟Ͳϱϭ͟Ϳ
ϱϰĞůů>ŝƐƚĞĚůƵŵŝŶƵŵ&ƌĂŵĞĚWsDŽĚƵůĞ;ϯϳ͟Ͳϰϭ͟džϱϲ͟ͲϲϬ͟Ϳ
ϲϬĞůů>ŝƐƚĞĚůƵŵŝŶƵŵ&ƌĂŵĞĚDŽĚƵůĞ;ϯϳ͟Ͳϰϭ͟džϲϯ͟Ͳϲϳ͟Ϳ
ϳϮĞůů>ŝƐƚĞĚůƵŵŝŶƵŵ&ƌĂŵĞĚDŽĚƵůĞ;ϯϳ͟Ͳϰϭ͟džϳϱ͟džϳϵ͟Ϳ
W,͗Ϯϯϵ͘ϯϲϮ͘ϬϮϭϭ&͗Ϯϯϵ͘ϯϲϮ͘Ϭϱϴϲ
sŝƐŝƚƵƐŽŶůŝŶĞĂƚǁǁǁ͘ƚ Ğ ƌ ƌ Ă Ɛ ŵ Ă ƌ ƚ ͘ĐŽŵ
ĞŶĞĨŝƚƐ
DŝŶŝŵĂůŚĂƌĚǁĂƌĞƚŽĂƐƐĞŵďůĞ
EŽŝŶͲĨŝĞůĚĚƌŝůůŝŶŐ͕ĐƵƚƚŝŶŐ͕ŽƌǁĞůĚŝŶŐ
^ŝŐŶŝĨŝĐĂŶƚůLJƌĞĚƵĐĞƐŝŶƐƚĂůůĞĚůĂďŽƌĐŽƐƚƐ
/ŶƚĞŐƌĂƚĞĚĨŽƵŶĚĂƚŝŽŶƐŽůƵƚŝŽŶ
dƵƌŶͲŬĞLJŝŶƐƚĂůůĂƚŝŽŶƐĞƌǀŝĐĞĂǀĂŝůĂďůĞ͕&ŽƵŶĚĂƚŝŽŶƚŽWĂŶĞůƐ
WƌĞͲĂƐƐĞŵďůLJŽƉƚŝŽŶƐĂǀĂŝůĂďůĞ
DĂdžŝŵƵŵĂĚũƵƐƚĂďŝůŝƚLJĨŽƌĨŽůůŽǁŝŶŐŐƌĂĚĞ
W,͗Ϯϯϵ͘ϯϲϮ͘ϬϮϭϭ&͗Ϯϯϵ͘ϯϲϮ͘Ϭϱϴϲ
sŝƐŝƚƵƐŽŶůŝŶĞĂƚǁǁǁ͘ƚ Ğ ƌ ƌ Ă Ɛ ŵ Ă ƌ ƚ ͘ĐŽŵ
W,͗Ϯϯϵ͘ϯϲϮ͘ϬϮϭϭ&͗Ϯϯϵ͘ϯϲϮ͘Ϭϱϴϲ
sŝƐŝƚƵƐŽŶůŝŶĞĂƚǁǁǁ͘ƚ Ğ ƌ ƌ Ă Ɛ ŵ Ă ƌ ƚ ͘ĐŽŵ
U T IL I T Y-SC A L E IN V ER T ER S
SGI 500XT
features
ü Compliant with NEC 2014
690.11 & 690.12 arc
fault and rapid shutdown
requirements when
coupled with ARCCOM
combiner
ü &(&HŐFLHQF\
ü Parallel power stages
ü Fuse and breaker
subcombiner options
ü Modbus communications
ü User-interactive LCD
options
ü Uptime guarantee
ü Stainless steel enclosure
ü Web-based monitoring
ü Built-in cellular connectivity
ü AC breaker with shunt trip
ü Revenue grade metering
ü $LUŎOWHUV
utility-scale inverters
options for utilities
Solectria’s SMARTGRID 500XT is compliant with NEC 2014 690.11 & 690.12 arc fault
ü Real power curtailment
DQGUDSLGVKXWGRZQUHTXLUHPHQWV7KH6*,;7LVWKHPRVWUHOLDEOHDQGHŐFLHQW
ü Reactive power control
ulility-scale inverter in its class. Optimized for direct coupling to an external transformer,
ü Voltage ride through
the SGI 500XT is the best choice for large commercial and utility-scale applications that
ü Frequency ride through
ü Controlled ramp rates
ü DMS tie-in
demand the highest performance and reliability. The SGI 500XT’s unique inverter design
contains all critical components in a compact and easy to install enclosure ensuring
maximum uptime, energy production, and return on investment (ROI) for large PV systems.
Standout features include a wide range of DC subcombiner (fuses or breakers), optional AC
disconnect or AC breaker, and ample room inside the cabinet for easy wiring and service.
The SGI 500XT supports advanced grid management for power plants, including real power
curtailment, reactive power control, controlled ramp rates, and voltage and frequency ride
through.
Copyright © Solectria - A Yaskawa Company. All information subject to change without notice. April 2015 DOCR-070244-G
SPECIFICATIONS
SGI 500XT
DC Input
Absolute Maximum Input Voltage
600 VDC
Max Power Input Voltage Range (MPPT)*
300-500 VDC
Maximum Operating Input Current
1750 A
Strike Voltage
390 V
AC Output
Native Output Voltage
208 VAC, 3-Ph
AC Voltage Range
-12%/+10%
Continuous Output Power
500 kW
Continuous Output Current
1387 A
Maximum Backfeed Current
0A
Nominal Output Frequency
60 Hz
Output Frequency Range
57-60.5 Hz
Power Factor
Adjustable - 0.9 to +0.9, factory set at 1
Total Harmonic Distortion (THD) @ Rated Load
<3%
(ŐFLHQF\
3HDN(ŐFLHQF\
98.1%
&(&(ŐFLHQF\
98.0%
Tare Loss
41 W
6XEFRPELQHU2SWLRQV
8 positions, 225-400 A
Fuses or Breakers
16 positions, 110-200 A
Fuses Only
32 positions, 70-100 A
7HPSHUDWXUH
Ambient Temperature Range (full power)
-40°F to +122°F (-40°C to +50°C)
Storage Temperature Range
-40°F to +122°F (-40°C to +50°C)
Relative Humidity (non-condensing)
5-95%
'DWD0RQLWRULQJ
Optional SolrenView Web-based Monitoring
Integrated
Optional Revenue Grade Monitoring (Integrated)
1600 A
Optional SolZoneTM Sub-Array Monitoring (DC Current)
8 zones
Optional Cellular Communication
SolrenView AIR
External Communication Interface
RS-485 SunSpec Modbus RTU
7HVWLQJ&HUWLŎFDWLRQV
6DIHW\/LVWLQJV&HUWLŎFDWLRQV
Testing Agency
UL 1741/IEEE 1547, CSA C22.2#107.1
ETL
:DUUDQW\
Standard
5 year
Optional
10, 15, 20 year; extended service agreement; uptime guarantee
'HGLFDWHG([WHUQDO7UDQVIRUPHU
Dedicated External Transformer
Transformer Type
Output Voltage
5HTXLUHGSURYLGHGE\FXVWRPHUWR6ROHFWULDõVVSHFLŎFDWLRQ
Self cooled, step up, pad mount
Typical: 2.4-36.0 kV, 3-Ph
(QFORVXUH
dBA (Decibel) Rating
DC Disconnect (integrated)
AC Disconnect/Breaker (integrated)
Dimensions (H x W x D)
Shading Set Back
Weight
58 dBA @ 3m
Standard
Optional disconnect, breaker or breaker with shunt trip
82 in. x 109 in. x 41 in. (2083 mm x 2769 mm x 1042 mm)
øPPDWÖVRODUHOHYDWLRQ
3410 lbs (1547 kg)
Enclosure Rating
Type 3R
Enclosure Finish
Polyester powder coated steel; Optional 316 stainless steel
*At nominal AC voltage
www.solectria.com | inverters@solectria.com | 978.683.9700
M ADE IN T HE USA
DATE (MM/DD/YYYY)
CERTIFICATE OF LIABILITY INSURANCE
3/23/2016
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS
CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES
BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED
REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER.
IMPORTANT: If the certificate holder is an ADDITIONAL INSURED, the policy(ies) must be endorsed. If SUBROGATION IS WAIVED, subject to
the terms and conditions of the policy, certain policies may require an endorsement. A statement on this certificate does not confer rights to the
certificate holder in lieu of such endorsement(s).
CONTACT
Michael Knight
NAME:
PHONE
(484)324-2794
(A/C, No, Ext):
E-MAIL
ADDRESS: mknight@securitasins.com
PRODUCER
Securitas Insurance Partners, LLC
7 Great Valley Parkway
Suite 100
Malvern
PA 19355
FAX
(A/C, No):
INSURER(S) AFFORDING COVERAGE
NAIC #
INSURER A :Hartford
Fire Insurance Company
INSURER B :ACE Property & Casualty Insurance
INSURER C :Rated by Multiple Hartford
INSURER D :Crum & Forster
INSURED
ProTech Energy Solutions, LLC
215 Executive Drive
19682
20699
00914
44520
INSURER E :
Moorestown
NJ
08057
INSURER F :
CERTIFICATE NUMBER:CL155500216
COVERAGES
REVISION NUMBER:
THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD
INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS
CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS,
EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS.
INSR
LTR
A
TYPE OF INSURANCE
X
ADDL SUBR
INSD WVD
COMMERCIAL GENERAL LIABILITY
CLAIMS-MADE
X
POLICY NUMBER
44UENQI0006
POLICY EFF
POLICY EXP
(MM/DD/YYYY) (MM/DD/YYYY)
4/30/2015
4/30/2016
OCCUR
GEN'L AGGREGATE LIMIT APPLIES PER:
` POLICY X PROLOC
JECT
OTHER:
A
AUTOMOBILE LIABILITY
X
ANY AUTO
ALL OWNED
AUTOS
HIRED AUTOS
B
X
UMBRELLA LIAB
EXCESS LIAB
C
D
44UENQI0007
4/30/2015
4/30/2016
SCHEDULED
AUTOS
NON-OWNED
AUTOS
X
LIMITS
EACH OCCURRENCE
DAMAGE TO RENTED
PREMISES (Ea occurrence)
$
MED EXP (Any one person)
$
$
PERSONAL & ADV INJURY
$
GENERAL AGGREGATE
$
PRODUCTS - COMP/OP AGG
$
Employee Benefits - Each
$
COMBINED SINGLE LIMIT
(Ea accident)
BODILY INJURY (Per person)
$
1,000,000
300,000
10,000
1,000,000
2,000,000
2,000,000
1,000,000
1,000,000
$
BODILY INJURY (Per accident) $
PROPERTY DAMAGE
(Per accident)
G27833196
OCCUR
4/30/2015
4/30/2016
CLAIMS-MADE
$
Uninsured motorist combined
$
1,000,000
EACH OCCURRENCE
$
10,000,000
10,000,000
AGGREGATE
X RETENTION $
10,000
DED
WORKERS COMPENSATION
AND EMPLOYERS' LIABILITY
Y/N
ANY PROPRIETOR/PARTNER/EXECUTIVE
N/A
OFFICER/MEMBER EXCLUDED?
(Mandatory in NH)
If yes, describe under
DESCRIPTION OF OPERATIONS below
Professional Liability &
Pollution Liability
$
$
44WEQI0005
4/30/2015
4/30/2016
X
PER
STATUTE
OTHER
E.L. EACH ACCIDENT
$
E.L. DISEASE - EA EMPLOYEE $
E.L. DISEASE - POLICY LIMIT
PKC100535
7/30/2015
7/30/2016
$5,000,000 Aggregate Limit
$5,000,000 Per Occurrence
$
1,000,000
1,000,000
1,000,000
$25,000 Deduc.
$25,000 Deduc.
DESCRIPTION OF OPERATIONS / LOCATIONS / VEHICLES (ACORD 101, Additional Remarks Schedule, may be attached if more space is required)
Evidence of Insurance.
CERTIFICATE HOLDER
CANCELLATION
Town of Leicester
90 S. Main Street
Leicester, MA 01524-1402
SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE
THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN
ACCORDANCE WITH THE POLICY PROVISIONS.
AUTHORIZED REPRESENTATIVE
Michael Knight/MJK
ACORD 25 (2014/01)
INS025 (201401)
© 1988-2014 ACORD CORPORATION. All rights reserved.
The ACORD name and logo are registered marks of ACORD
Pro-Tech Solutions, LLC
Leicester, MA
Cherry Valley 1.0 MW PV ARRAY
March 2016