FLAME-X 950 (N)HXCH FE180/E90 0,6/1kV - TELE

advertisement
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
Halogen- free low smoke fire resistant security power cables
with copper concentric conductor
CONSTRUCTION
Conductors:
Insulation:
Inner covering:
Concentric conductor:
Separator:
Sheath:
Colour of sheath:
Core identification:
bare copper conductor, circular solid class 1 (RE) or stranded circular or circular
compacted class 2 (RM) according to EN 60228
special cross-linked halogen-free fire resistant silicone compound
special flame-retardant and halogen-free compound
inner layer - round copper wires, outer layer - copper tape
tape
thermoplastic halogen- free compound type HM4 according to DIN VDE 0276-604
orange
according to DIN VDE 0293-308, HD 308 S2 or EN 50334
2-core:
blue, brown
3-core:
brown, black, grey
3-core:*
blue, brown, black
4-core:
blue, brown, black, grey
5-core:
blue, brown, black, grey, black
more 5-core:
black with numbering
*For certain applications only.
CHARACTERISTIC
Maximum conductor operating temperature:
+90oC
Lowest ambient temperature for fixed installation:
-30oC
Lowest installation temperature:
-5oC
Maximum short-circuit conductor temperature:
+250oC
Minimum bending radius:
12D - for multicore cable (D - overall cable diameter)
Maximum permissible tensile stress with cable grip for Cu: 50 N/mm2
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
FIRE PERFORMANCE
Insulation integrity FE 180:
DIN VDE 0472-814 (800°C, 180 min.), IEC 60331-21
System integrity E90:
DIN 4102-12 (90 min.)
Flame propagation:
DIN EN 50266-2-2, VDE 0482-266-2-2, IEC 60332-3-22
Smoke density:
DIN EN 61034-2, VDE 0482-1034-2, IEC 61034-2
Gases evolved during combustion: DIN EN 50267-2-2, VDE 0482-267-2-2, IEC 60754-2: pH 4,3;
conductivity 10 Smm-1
APPLICATIONS
Fire resistant security cables for installation everywhere where high safety requirements have a special significance
e.g., in industrial complexes, power stations, public buildings, hotels, underground railway systems, hospitals etc.
Standard length cable packing
500 or 1000m on drums.
Other forms of packing and delivery are available on request
APPROVALS
SIQ, GOST, VDE, CNBOP
Approximate overall diameter
Approximate net weight
of cables
Maximum conductor
resistance
o
at temperature 20 C
mm
kg/km
Ω/km
2x1,5RE/1,5
2x2,5RE/2,5
2x4RE/4
2x6RE/6
2x10RE/10
2x16RE/16
2x16RM/16
2x25RM/16
13,8
14,6
15,9
17,2
18,9
21,2
22,0
25,4
261
302
378
462
623
850
891
1154
12,1/12,1
7,41/7,41
4,61/4,61
3,08/3,08
1,83/1,83
1,15/1,15
1,15/115
0,727/1,15
3x1,5RE/1,5
3x2,5RE/2,5
3x4RE/4
3x6RE/6
3x10RE/10
3x16RE/16
3x16RM/16
3x25RM/16
3x35RM/16
3x50RM/25
3x70RM/35
3x95RM/50
14,4
15,2
16,6
17,9
19,7
22,2
23,1
26,7
29,0
32,9
36,5
42,4
287
336
425
526
720
999
1044
1393
1739
2339
3172
4364
12,1/12,1
7,41/7,41
4,61/4,61
3,08/3,08
1,83/1,83
1,15/1,15
1,15/115
0,727/1,15
0,524/1,15
0,387/0,727
0,268/0,524
0,193/0,387
Number and cross-sectional
area of conductor
n x mm
2
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
3x120RM/70
3x150RM/70
3x185RM/95
3x240RM/120
46,3
51,3
55,8
63,7
5404
6513
8071
10423
0,153/0,268
0,124/0,268
0,0991/0,193
0,0754/0,153
4x1,5RE/1,5
4x2,5RE/2,5
4x4RE/4
4x6RE/6
4x10RE/10
4x16RE/16
4x16RM/16
4x25RM/16
4x35RM/16
4x50RM/25
4x70RM/35
4x95RM/50
4x120RM/70
4x150RM/70
4x185RM/95
4x240RM/120
15,3
16,2
17,7
19,2
21,2
23,9
24,9
29,0
31,5
36,4
40,0
46,6
51,2
56,6
62,0
70,3
325
384
489
611
848
1183
1232
1682
2136
2924
3933
5415
6744
8135
10132
13013
12,1/12,1
7,41/7,41
4,61/4,61
3,08/3,08
1,83/1,83
1,15/1,15
1,15/115
0,727/1,15
0,524/1,15
0,387/0,727
0,268/0,524
0,193/0,387
0,153/0,268
0,124/0,268
0,0991/0,193
0,0754/0,153
5x1,5RE/1,5
5x2,5RE/2,5
5x4RE/4
5x6RE/6
5x10RE/10
5x16RE/16
5x16RM/16
5x25RM/16
5x35RM/16
5x50RM/25
5x70RM/35
5x95RM/50
5x120RM/70
5x150RM/70
5x185RM/95
5x240RM/120
16,3
17,3
19,0
20,6
22,8
25,8
26,9
31,5
33,9
39,9
43,9
51,5
56,4
62,8
68,1
77,4
371
445
570
716
1000
1397
1461
2026
2581
3531
4760
6600
8174
9953
12273
15810
12,1/12,1
7,41/7,41
4,61/4,61
3,08/3,08
1,83/1,83
1,15/1,15
1,15/115
0,727/1,15
0,524/1,15
0,387/0,727
0,268/0,524
0,193/0,387
0,153/0,268
0,124/0,268
0,0991/0,193
0,0754/0,153
7x1,5RE/2,5
7x2,5RE/2,5
7x4RE/4
7x4RM/4
17,4
18,5
20,3
21,2
431
523
679
720
12,1/7,41
7,41/7,41
4,61/4,61
4,61/4,61
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
Approximate overall diameter
Approximate net weight
of cables
Maximum conductor
resistance
o
at temperature 20 C
mm
kg/km
Ω/km
10x1,5RE/2,5
10x1,5RM/2,5
10x2,5RE/4
10x2,5RM/4
20,9
21,7
22,8
23,8
578
617
739
781
12,1/7,41
12,1/7,41
7,41/4,61
7,41/4,61
12x1,5RE/2,5
12x1,5RM/2,5
12x2,5RE/4
12x2,5RM/4
21,5
22,3
23,4
24,4
637
672
810
854
12,1/7,41
12,1/7,41
7,41/4,61
7,41/4,61
14x1,5RE/2,5
14x1,5RM/2,5
14x2,5RE/6
14x2,5RM/6
22,4
23,3
24,5
25,6
699
738
903
955
12,1/7,41
12,1/7,41
7,41/3,08
7,41/3,08
16x1,5RE/4
16x1,5RM/4
16x2,5RE/6
16x2,5RM/6
23,7
24,7
25,6
26,8
789
830
998
1057
12,1/4,61
12,1/4,61
7,41/3,08
7,41/3,08
19x1,5RE/4
19x1,5RM/4
19x2,5RE/6
19x2,5RM/6
24,8
25,8
26,8
28,1
870
917
1112
1178
12,1/4,61
12,1/4,61
7,41/3,08
7,41/3,08
20x1,5RE/6
20x1,5RM/6
26,0
27,0
960
1014
12,1/3,08
12,1/3,08
24x1,5RE/6
24x1,5RM/6
24x2,5RE/10
24x2,5RM/10
28,5
29,7
31,3
32,4
1078
1138
1423
1513
12,1/3,08
12,1/3,08
7,41/1,83
7,41/1,83
30x1,5RE/6
30x1,5RM/6
30x2,5RE/10
30x2,5RM/10
29,9
31,2
32,6
34,2
1240
1310
1655
1752
12,1/3,08
12,1/3,08
7,41/1,83
7,41/1,83
37x1,5RE/10
37x1,5RM/10
32,2
33,6
1506
1588
12,1/1,83
12,1/1,83
Number and cross-sectional
area of conductor
n x mm
2
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
Current ratings as defined in DIN VDE 0276-604, HD 604 S1-5G and DIN VDE 0276-627, HD 627 S1-7H
Operating temperature at conductor 90oC
Ambient air temperature 30oC
Installation: single multicore cable and three single core cables
Installation
3
Number of loaded cores
3
laying in air*
Cross-section, mm
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
2
Current ratings in Ampere (A)
25
33
43
54
75
100
136
165
201
255
314
364
416
480
565
-
27
36
47
59
81
109
146
179
218
275
336
388
438
501
580
654
Current ratings for control cables – DIN VDE 0276-627, HD 627 S1-7H:
Conversion factors for multicore cable ( 5 cores)
The conversion factors are to be used for laying the cables in air (col. 3), to the values given in above tables
Number of loaded cores
5
7
10
14
19
24
40
61
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
Laying in air
0,75
0,65
0,55
0,50
0,45
0,40
0,35
0,30
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
Current ratings - DIN VDE 0298-4 and IEC 60364-5-523
Ambient temperature: 30 C
Conductor operating temperature: 90 C
Installation: in free air for fixed installation within buildings: in walls, on wall, ladder or cable trays
Installation
method1
A2
B2
C
E
≥ 0,3 D
Number of
loaded cores
Crosssection mm2
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
Table
Multicore cables
in insulating tubes,
in thermally insulated
walls
2
3
Multicore cables
in insulating tubes
on a wall
2
3
Single- or multicore
cables
on a wall
2
≥ 0,3 D
Multicore cables
with a space of minimum
0,3 x diameter d to wall
3
2
3
Current ratings in Ampere (A)
18,5
25
33
42
57
76
99
121
145
183
220
253
290
329
16,5
22
30
38
51
68
89
109
130
164
197
227
259
295
22
30
40
51
69
91
119
146
175
221
265
305
—
—
19,5
26
35
44
60
80
105
128
154
194
233
268
—
—
24
33
45
58
80
107
138
171
209
269
328
382
441
506
22
30
40
52
71
96
119
147
179
229
278
322
371
424
26
36
49
63
86
115
149
185
225
289
352
410
473
542
23
32
42
54
75
100
127
158
192
246
298
346
399
456
386
52-C2
346
52-C4
—
52-C2
—
52-C4
599
52-C2
500
52-C4
641
52-C11
538
52-C11
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
FLAME-X 950
(N)HXCH FE180/E90
0,6/1kV
DIN VDE 0266, DIN 4102-12
Current ratings for single core sheathed cables in free air.
Ambient temperature 30 C, conductor operating temperature 90 C
Single core sheathed cables with a space of minimum 1 x diameter (D) to wall.
F
G
Installation method
Touching
Spaced
≥D
≥D
Number of loaded cores
2
Cross-section /mm /
25
35
50
70
95
120
150
185
240
300
Table
2
≥D
3
≥D
3
Current ratings in Ampere (A)
161
141
135
200
176
169
242
216
207
310
279
268
377
342
328
437
400
383
504
464
444
575
533
510
679
634
607
783
736
703
52-C11
52-C11
52-C11
≥D
≥D
3
≥D
3
182
226
275
353
430
500
577
661
781
902
52-C11
161
201
246
318
389
454
527
605
719
833
52-C11
All the information contained in this document - including tables and diagrams - is given in good faith and believed to be correct at
the time of publication. The information does not constitute a warranty nor representation for which TELE-FONIKA Kable assumes
legal responsibility. TELE-FONIKA Kable reserves rights to introduce changes to the document at any time.
TELE-FONIKA Kable Sp. z o.o. S.K.A.
www.tfkable.com
Download