Lansdowne HS Assessment Details

advertisement
LANSDOWNE HS FUNCTIONAL ASSESSMENT
GYM
AREA
MEASURED AREA
HEIGHT
PANIC HARDWARE
LOCKER ROOM
AUXILIARY GYM
AUX GYM MEASURED AREA
AUX GYM HEIGHT
CONDITION
COMMENTS
CAFETERIA
AREA
MEASURED AREA
HEIGHT
PANIC HARDWARE
KITCHEN
CONDITION
COMMENTS
MEDIA CENTER
AREA
MEASURED AREA
HEIGHT
PANIC HARDWARE
ADA CASEWORK
CONDITION
COMMENTS
12928
11220 22
PARTIAL
YES
NO
3
clerestory lets in good diffused daylight, ok acoustics
8464
7088
11
NO
FULL
3
little daylight, open space with good adjacency but no visual access to serving line, odd odor
6040
4673
11.7
NO
NON‐ADA
3
good daylight, open space, no adjacent computer lab, AUDITORIUM
AREA
MEASURED AREA
HEIGHT
PANIC HARDWARE
STAGE STAGE AREA
CONDITION
COMMENTS
CLASSROOMS
MEASURED AREA (TYP)
HEIGHT (TYP)
ADA CASEWORK
CONDITION
COMMENTS
ADDITIONAL SPACES
CONFERENCE ROOMS
CONF RM AREA
HEALTH SUITE AREA
GUIDANCE SUITE AREA
SPECIALTY SPACES
SPECIAL EDUCATION
SPECIAL ED # OF ROOMS
CTE PROGRAMS
SPECIALTY PROGRAMS
OPEN SPACE CLASSROOMS
RELOCATABLES
RELOC_COMMENTS
15403
10020
25.8
YES
NO
982
2
seating capacity is ok, but rear seating configuration is inefficient
689
10.3
ADA ACCESSIBLE
3
good daylight, small rooms, lack of casework, bland;
science‐ 1268 sf, 9.2 ft
no ada lab stations
2
296
102
193
Activity Room 4859 SF
YES
5
FINE ARTS
HEALTH PROFESSIONS
SCIENCE
FINANCE
ART
MUSIC
SCIENCE
NO
1
unused
ADA FACILITIES
SINKS
TOILETS
CLEARANCES
DRINKING FOUNTAINS
STAIRS
STAIR WIDTH
RAMPS
ELEVATOR COUNT
DOOR CLEARANCE
DOOR HARDWARE
CORRIDOR WIDTH
CORRIDOR HEIGHT
CORRIDOR PROTRUSIONS
HEALTH SUITE
DEAD END CORRIDORS
BUILDING ENTRANCE
EXITS
GYM
AUDITORIUM
CAFETERIA
MEDIA CENTER
NO
NO
NO
NO
YES
5.6
N/A
PARTIAL
PARTIAL
10
9.5
ELEVATION CHANGES
PIPES
DISPLAY CASES
YES
NO
ELEVATION CHANGES
6
12
8
2
OVERALL CONDITION
OVERALL NOTES
2
elevation changes in many areas with no ramp access, core spaces have good locations, with dedicated lobbies for each; multiple access points could be a security concern, non ada gym entrance
SITE NOTES
Topography creates elaborate site entry and exit, site at busy intersection, play fields are very distant from building, large pond adjacent to site.
Good visual access to admin, but entry is somewhat hidden, multiple entry points take away from centrality, hierarchy.
LANSDOWNE HS PHYSICAL ASSESSMENT
LOCATION
AUDITORIUM
ASSEMBLY TYPE
CEILING
AUDITORIUM CORRIDORS
SCIENCE ROOM
CLASSROOMS
MEDIA CENTER
CAFETERIA
CEILING
CEILING
CEILING
CEILING
CEILING
CEILING
GYM
CEILING
STOREFRONT
EXTER BLDG
EXTERIOR OPENING
EXTERIOR OPENING
EXTERIOR OPENING
EXTERIOR WALL
EXTER BLDG
STOREFRONT
LOUVER
MATERIAL
FINISH
GYP BD
ALUM
COMMENTS
3 large water stain, acoustic treatment in some areas
1 in rear seating area, patching
1 patching in many areas
2 bowing
2
1 patching everywhere
1 leaking, staining, bowing, bulkhead denotes entry from main space 3 acoustic panels hung along depths of concrete beams
2 breezeway to cafeteria and gym wing, in poor shape
4 at main entrance
ALUM
3
ACT
ACT
ACT
ACT
ACT
ACT
EXPOSED STRUCTURE
ALUM
INSULATED METAL PANEL
BRICK
METAL PANEL
EXTERIOR WALL
ALUM
INSULATED METAL PANEL
EXTER BLDG
EXTERIOR WALL
METAL
CERAMIC TILE
SITE WALLS
AUDITORIUM
AUDITORIUM STAGE
CORRIDORS
STAIRS
SCIENCE ROOM
CLASSROOMS
MEDIA CENTER
CAFETERIA
GYM
ADMIN
CONCRETE
CONCRETE
CONCRETE
WOOD
CONCRETE
STEEL
CONCRETE
CONCRETE
CONCRETE
CONCRETE
WOOD
HM
AUDITORIUM
CORRIDORS
EXTERIOR WALL
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
FLOOR
INTERIOR OPENING
INTERIOR OPENING
INTERIOR OPENING
INTERIOR OPENING
INTERIOR OPENING
INTERIOR WALL
INTERIOR WALL
CMU
CMU
GYP BD
CERAMIC TILE
STAIRS
SCIENCE ROOM
CLASSROOMS
MEDIA CENTER
INTERIOR WALL
INTERIOR WALL
INTERIOR WALL
INTERIOR WALL
CMU
CMU
CMU
CERAMIC TILE
PAINT
GLAZED BLOCK
GYP BD
CLASSROOMS
MEDIA CENTER
CAFETERIA
GYM
HM
VCT
VAT
TERRAZZO
TERRAZZO
VCT
VAT
CARPET
TERRAZZO
WOOD
ALUM
CONDITION
4 corrugated metal wrap for upper half of auditorium 2 window bay system, some panels have been replaced, others in horrible shape, oil canning pamels
2 cracking tiles, storefront in poor shape at cafeteria
2
1
2
4
2
2
4
2
3
2
3
3
patching, cracking at seams, damaged, raw in rear seating area, patching
worn, cracking
terrazzo treads, terr tile landing steel pan stair
furniture marks, cracking
significant wear, poor thresholds
4 wired glass lites
HM
3 provide views into corridor and other served spaces within 3 doors with transom band at serving line
CONCRETE
1 broken panes in gym clerestories
3 some wear, wood panelling along stage
3 ceramic tile walls jut out between locker bays, worn at base
3 side walls have typ corridor ct, rear wall has 2x2
4
2 glazed block in bad shape
3 mostly storefront and built in casework
LOCATION
CAFETERIA
GYM
CANOPY
ASSEMBLY TYPE
MATERIAL
INTERIOR WALL
INTERIOR WALL
CMU
ROOF
STEEL
SOFFIT
ROOF
CONCRETE
GENERAL NOTES:
leaking is a major problem
nearly all ceiling are in need of replacement
poor finishes in most areas
raw concrete floors in art wing
OVERALL PHYSICAL CONDITION: 1
FINISH
CERAMIC TILE
GLAZED BLOCK
CONDITION
COMMENTS
2 dirty grout, gyp board partition at serving line
3 stack bond, some patching around bleachers
3 bus canopy at main entry, stone panel and square tube column supports
2 water damage at main entry
LANSDOWNE HS BUILDING SYSTEMS ASSESSMENT
MECHANICAL
AUTOMATIC TEMPERATURE CONTROLS
ATC MANUFACTURER
JOHNSON CONTROLS
ATC SYSTEM TYPE
D.D.C.
ATC COMPRESSOR
YES
ATC COMPRESSOR CONDITION
4
CONDITION
4
NOTES
‐ The 1963 portion of the building has pneumatic controls and the condition rating is one. The 1998 Addition has DDC controlls and the condition rating is as indicated above.
HEATING HEATING SYSTEM
DUAL TEMP IN 1998 ADDITION, 2 PIPE HEATING ONLY IN ORIGINAL 1963 BUILDING.
PIPE INSULATION CONDITION
1
HOT WATER PIPE CONDITION
1
VALVING CONDITION
1
CHEMICAL TREATMENT CONDITION 2
CHEMICAL TREATMENT?
YES
BOILER FUEL TYPE
GAS
OVERALL CONDITION
2
HEATING NOTES
‐ No Heating System Chemical treatment in 1963 original building Boiler room.
‐ Piping, Valving and pipe insulation condition values are for the 1963 building system.
AHU NOTES
‐ The majority of the split system condensing units serving unit ventilators in the 1998 Addition's classrooms are disconnected.
COOLING
MAIN SYSTEM TYPE
DUAL TEMP
PIPE INSULATION CONDITION
3
CONDENSER CONDITION
3
VALVING CONDITION
3
CHILLER CONDITION
3
CHEMICAL TREATMENT CONDITION 3
CHEMICAL TREATMENT?
YES
OVERALL CONDITION
3
NOTES
PLUMBING/FP
FIRE PROTECTION
BUILDING COVERAGE
SYSTEM CONDITION
FIRE PUMP?
FIRE PUMP TYPE
FIRE PUMP CONDITION
SYSTEM TYPE
SYSTEM CONDITION
STANDPIPE
STANDPIPE CONDITION
NOTES
OVERALL CONDITION
DOMESTIC WATER
INCOMING DOMESTIC WATER
CITY/COUNTY WATER
BOOSTER PUMP
BOOSTER MANUFACTURER DATE
BOOSTER CONDITION
DOM WATER HEATERS
DOM WATER COND
DW FUEL SOURCE
BFP
BFP CONDITION
PLUMBING FIXTURES
PIPING CONDITION
PIPING INSULATION CONDITION
VALVING CONDITION
OVERALL CONDITION
PLUMBING SYSTEM NOTES
no sprinklers
DOMESTIC ONLY
PUBLIC
NO
VERT. TANK
4
GAS
NO
2
4
3
4
3
ELECTRICAL
SERVICE
MANUFACTURER
VOLTAGE
AMPERAGE
MAINS
MAIN DISC QTY
COMMENTS
YEAR INSTALLED
CONDITION
NOTES
DISTIBUTION
TRANSFORMERS
PANEL BOARDS
MOTOR CONTROL CENTER
CONDITION
NOTES
GENERATOR
MANUFACTURER
FUEL TYPE
LOCATION
RATING
KW
COMMENTS
CONDITION
NOTES
LIGHTING
CONDITION
NOTES
SQUARE D
277/480V, 3Ø
3000A
CKT BRKR
1
DAMAGE
LACKS CODE CLEARANCE
2
Panel covers appear to be corroded. Please consider upgrading this SWBD to accommodate future development and to ensure the safety of the facility's equipment.
AVERAGE CONDITION
CIRCUIT BREAKERS
IN CORRIDORS
ACCESSIBLE TO STUDENTS
DAMAGED
MISSING COVERS
CIRCUIT BREAKERS
AVERAGE CONDITION
3
Throughout bldg power distribution is conducted with federal pacific panels. Please consider upgrading these panels to ensure the safety of the facility's equipment and property. Also, please consider replacing panels without covers to ensure the safety of equipment and occupants in bldg.
N/A
FIRE ALARM
MANUFACTURER
TYPE
ALARM
MOTIFICATION
COMMENTS
CONDITION
NOTES
SECURITY
ACCESS CONTROL
DEVICES
CONDITION
NOTES
CCTV
CAMERAS
RECORDING
CONDITION
NOTES
IT/DATA
CLASSROOMS
CONDITION
NOTES
EDWARDS SYSTEM TECH
ADDRESSABLE
PULL STATIONS
SMOKE DETECTORS
SPEAKERS/VOICE
STROBES (ADA)
FULL COVERAGE
5
MAIN ENTRY INTERCOM
MAIN ENTRY DOOR RELEASE
CARD READERS
MOTION SENSORS
3
Motion sensors are not in 2nd floor classrooms. Please consider adding these systems to ensure the safety of property.
BOTH
YES
5
HARDWIRED NETWORK OUTLETS
MEETS MSDE (3 PER RM)
SMART BOARDS
3
Some classrooms have smart boards, while most every other classroom does not.
LANSDOWNE HS MEP EQUIPMENT
CATEGORY
COOLING
HEATING
HEATING
HEATING
HEATING
AIR HANDLING UNITS
AIR HANDLING UNITS
ROOM TYPE/EQUIP TYPE
WINDOW AC
BOILERS
BOILER CIRCULATION HEATING WATER PUMPS
BASEBOARDS
ADMIN
GYM
AIR HANDLING UNITS
AUX. GYM
AIR HANDLING UNITS
CAFETERIA
AIR HANDLING UNITS
ADDITION
AIR HANDLING UNITS
LOCKER ROOM
AIR HANDLING UNITS
CLASSROOMS
AIR HANDLING UNITS
AIR HANDLING UNITS
AIR HANDLING UNITS
AIR HANDLING UNITS
CLASSROOMS
CLASSROOMS
COMPUTER ROOM
CLASSROOMS
AIR HANDLING UNITS
AUDITORIUM
TYPE
QUANTITY
HYDRONIC
IN‐LINE
BASE MOUNTED
CONDITION
2
2
6
0
WINDOW AC UNITS
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
WINDOW AC UNITS
SELF CONTAINED
SPLIT SYSTEM AHU
HEATING & VENTILATION UNIT
HEATING & VENTILATION UNIT
5
4
4
2
2
3
2
2
3
1
2
1
3
3
2
0
2
0
12
4
3
3
5
4
4
3
LANSDOWNE HS LIGHT FIXTURES
ROOM TYPE
CAFETERIA
KITCHEN
GYM
CLASSROOMS
LIBRARY
CORRIDORS
COMPUTER ROOM
AUDITORIUM HALL
CLASSROOMS
CORRIDORS
HEALTH SUITE
OFFICES
STAIRS
ADMIN
CONFERENCE ROOMS
EXTER BLDG
EXTER CANOPY
PARKING LOT
FIXTURE TYPE
RECESSED
RECESSED
SUSPENDED
SUSPENDED
RECESSED
RECESSED
RECESSED
RECESSED
RECESSED
RECESSED
RECESSED
RECESSED
SURFACE MTD
RECESSED
SUSPENDED
SURFACE MTD
SURFACE MTD
POLE LIGHTS
LAMPING
T8/T12
T8/T12
METAL HALIDE
T8/T12
T8/T12
T8/T12
T8 FLUOR
T8 FLUOR
T8/T12
T8 FLUOR
T8/T12
T8/T12
T8/T12
T8/T12
HID
HID
HPS
CONDITION
1
3
3
1
2
3
5
1
5
1
3
3
3
2
1
2
3
3
COMMENTS
PAST LIFE EXPECTANCY
AVERAGE CONDITION
AVERAGE CONDITION
PAST LIFE EXPECTANCY
PAST LIFE EXPECTANCY
AVERAGE CONDITION
GOOD CONDITION
NONE PRESENT
GOOD CONDITION
POOR CONDITION
AVERAGE CONDITION
AVERAGE CONDITION
AVERAGE CONDITION
POOR CONDITION
PAST LIFE EXPECTANCY
PAST LIFE EXPECTANCY
AVERAGE CONDITION
AVERAGE CONDITION