UFO-RP2 FLUORESCENT BATTERY PACK IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. CAUTION - To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power is supplied to the unit. 2. CAUTION - This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the A.C. Branch circuit and by disconnecting the unit connector. 3. The battery is sealed, non-maintenance, and is not replaceable in the field. Please contact manufacturer for information on service. Do not attempt to service the battery please. 4. DO NOT USE OUTDOORS. The product is for use with grounded, UL Listed, indoor fixtures except in heated air outlets or hazardous locations. 5. The product requires an unswitched A.C. Power source of either 120 or 277 volts. Properly cap the unused A.C. Lead. 6. Do not mount near gas or electric heaters. 7. The product should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. 8. This product is for use with 14 W through 54W(2'-4')T5 and T8 single pin or bipin for one lamp,Instant Start and Rapid Start,14W through 39W(2'-4')T5 and T8 single pin or bipin for two lamp, Instant Start and Rapid Start,18 W through 50 W (4-pin) long compact Rapid Start, or 32 W (4-pin) compact, 24W through 32W U-Bend FBT8 fluorescent lamps from Philips,Osram and GE or equivalent manufacture. 9. The product is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with one lamp operating in the emergency mode. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 11. Do not use this equipment for other than intended use. 12. Install in accordance with the National Electrical Code and local regulations. 13. Installation and servicing should be performed by qualified personnel. 14. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility before final installation. 15. The battery is sealed,non-maintenance,and is not replaceable in the field. Please contact manufacturer for information on service. Do not attempt to service the battery please. 16. The rated operating time in the emergency mode with battery is 1-1/2 hours and the recharge time shall not be less than 24 hours. SAVE THESE INSTRUCTIONS Warning-This product contains chemicals known to the State of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product. CONTAINS NICKEL-CADMIUM UL LISTED R RECHARGEABLE BATTERY. MUST BE RECYCLED OR DISPOSED OF PROPERLY. Ni - Cd Hubbell lighting, Inc,• 701 Millennium Blvd.Greenville SC 29607•864 678-1000•FAX (864) 678-1415•www.dual-lite.com 93039242-A Page 1 INSTALLATION INSTRUCTIONS NOTE: All the branch circuit wiring has to be ready as well as an unswitched source of power before the fixture is installed. Both AC and Emergency Ballasts must be Fed From the same branch circuit. CAUTION Battery connector has to be opened to prevent high voltage on output leads (Red and Yellow). Wait until all the installation process is completed and AC is supplying power to the emergency ballast before joining the battery connector. 1. AC power has to be off before installation. 2. Choose the right wiring diagram to connect the emergency ballast to AC ballast and lamp. 3. Please ensure the electrical connections conform to the National Electrical Code and local regulations if applicable. 4. Follow the diagram 1&2 to install the emergency ballast in the ballast channel. DIAGRAM 1 DIAGRAM 2 Emergency Ballast Test Button,Indicator Light(TBIL) Emergency Ballast Ballast Channel Cover Test Button,Indicator Light(TBIL) 5. Wall switch has to be connected properly (Check diagram 3), Match the violet and brown leads to connect the TBIL to the emergency ballast(Check diagram 4). The TBIL would be on after the fixture is installed properly. DIAGRAM 3 SWITCHED FIXTURE UNSWITCHED FIXTURE WHITE BLACK WHITE A.C. BALLAST BLACK WHT/BLK (277V) ORG 1 HOT A.C. LINE TBIL WHT/BLK WHT/RED WHITE COMMON 1 BROWN + RED VIOLET WHT/RED WHITE COMMON UFO-RP2 (120V) BLK WHT A.C. BALLAST Select proper voltage lead. Cap unused lead. (277V) ORG 1 HOT A.C. LINE TBIL 1 UFO-RP2 (120V) BLK WHT BROWN + RED VIOLET Select proper voltage lead. Cap unused lead. 6.Please search in readily visible location and stick the label with “CAUTION: This Unit Has More Than One Power Supply Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing.” 7. Do not join the inverter connector until the fixture is completely installed and AC power is supplied to the emergency ballast. 8. The battery needs to be charged for one hour in order to have short-term testing on the emergency function. Before having a long-term emergency function testing, the battery in emergency ballast has to be charged for 24 hours. NOTE: MARK AN APPROPRIATE LABEL ON INDICATOR LIGHT AND TEST SWITCH AFTE INSTALLATION. Page 2 OPERATION THE CHARGING INDICATOR LIGHT WOULD BE ON TO INDICATE THE BATTERY IS BEING CHARGED WHEN AC POWER IS APPLIED. THIS EMERGENCY BALLAST WOULD FUNCTION AND OPERATE ONE OR TWO LAMPS AT LEAST 90 MINUTES WHEN THE AC POWER IS FAILED. THE EMERGENCY BALLAST WILL OPERATE 14WATT TO 54WATT LAMPS AT LEAST 90 MINUTES. Illustration 1 Illustration 2 Recessed Troffer Fixture FIXTURE Strip Fixture TBIL FIXTURE BALLAST CHANNEL COVER UFO-RP2 UFO-RP2 PLASTIC TUBE 7/8 BUSHING TBIL FIXTURE LENS OBSERVE PROPER POLARITY NOTE: MARK AN APPROPRIATE LABEL ON INDICATOR LIGHT AND TEST SWITCH AFTER INSTALLATION. MAINTENANCE NOTE: SERVICES SHOULD ONLY PERFORMED BY QUALIFIED PERSONNEL. THE EMERGENCY BALLAST SHOULD BE CHECKED PERIODICALLY TO CONFIRM FUNCTIONING AND THE FOLLOWING SCHEDULE IS RECOMMENDED. 1) INSPECT THE CHARGING INDICATOR EVERY MONTH AND CONFIRM THAT IS ILLUMINATED. 2) PUSH THE TEST SWITCH FOR 30 SECONDS TO ENSURE THE EMERGENCY BALLAST IS FUNCTIONING. PERFORM THIS TEST EVERY 30 DAYS. 3) PERFORMING A LONG-TERM TEST (90 MINUTE BATTERY DISCHARGE) ONCE IN EVERY YEAR. ONE OR TWO LAMPS SHOULD BE OPERATED FOR NO LESS THAN 90 MINUTES. TABLE 1 (FOR BROWN CONNETOR) LAMP DIAMETER T5 ,T8 SINGLE OR BIPIN BASE TYPE POWER (LENGTH) NUMBER OF LAMPS EMER. BROWN CONNECTOR 14W-39W 1 CLOSE 2 OPEN 40W-54W 1 CLOSE LONG COMPACT COMPACT U-Bend FBT8 4 PIN(2G11) 4-PIN 4 PIN 32W 24-32W 18W-39W 1 CLOSE 2 OPEN 40W-50W 1 1 CLOSE CLOSE Page 3 1 CLOSE 2 OPEN EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT Typical schematics only may be used other ballast, consult the factory wiring diagram WIRING DIAGRAM For One Lamp Emergency Operation(14-54W) B. TWO (2) LAMP INSTANT START BALLAST A. ONE (1) LAMP INSTANT START BALLAST BROWN UFO-RP2 RED TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD BROWN WARNING WARNING UFO-RP2 RED WHT RED TBIL Refer to Table 1 before connecting WHITE COM ORANGE BLACK UFO-RP2 RED WHT SWITCHED OR UNSWITCHED LINE WHT/BLK UFO-RP2 RED WHT TBIL BROWN UFO-RP2 RED TBIL WHT WHITE ORANGE BLACK WHT/RED SWITCHED OR UNSWITCHED LINE Refer to Table 1 before connecting WHT/BLK BROWN WARNING COM WHITE ORANGE BLACK BROWN BLUE TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD BLUE/WHITE Refer to Diagram 3 before connecting BLUE/WHITE WHITE RED RED VIOLET(+) BROWN(-) AC BALLAST RED RED BLUE BLUE BLUE/WHITE YELL/BLK YELLOW YELLOW YELLOW RED TBIL WHT VIOLET(+) BROWN(-) UFO-RP2 WHT/RED WHITE RED TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting RED LAMP 1 LAMP 2 LAMP 3(EMERGENCY) I.FOUR (4) LAMP RAPID START BALLAST SWITCHED OR UNSWITCHED LINE Refer to Table 1 before connecting WARNING BROWN WHT/BLK BROWN WHITE ORANGE BLACK COM YELLOW YELLOW AC BALLAST RED RED BLUE/WHITE YELLOW BLUE/WHITE BLUE BLUE BROWN BROWN BLUE BLUE/WHITE YELL/BLK RED TBIL WHT VIOLET(+) BROWN(-) UFO-RP2 WHT/RED WHITE RED Refer to Diagram 3 before connecting WHT/RED WHITE RED RED VIOLET(+) BROWN(-) COM BROWN WARNING SWITCHED OR UNSWITCHED LINE WHT/BLK TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD H.THREE (3) LAMP RAPID START BALLAST G. TWO (2) LAMP RAPID START BALLAST Refer to Table 1 before connecting WHITE ORANGE BLACK BROWN WHITE RED VIOLET(+) BROWN(-) COM BROWN WARNING SWITCHED OR UNSWITCHED LINE WHT/BLK Refer to Table 1 before connecting TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting WHT/RED Refer to Diagram 3 before connecting WHT/RED WHITE RED RED VIOLET(+) BROWN(-) WHT TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD F. TWO (2) LAMP RAPID START BALLAST E. ONE (1) LAMP RAPID START BALLAST TBIL UFO-RP2 Refer to Diagram 3 before connecting WHT/RED COM WHITE ORANGE BLACK BROWN TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD SWITCHED OR UNSWITCHED LINE WHT/BLK BROWN WARNING WHITE RED RED VIOLET(+) BROWN(-) WHITE RED RED Refer to Table 1 before connecting COM WHITE ORANGE BLACK BROWN BROWN TBIL SWITCHED OR UNSWITCHED LINE WHT/BLK Refer to Diagram 3 before connecting D. FOUR (4) LAMP INSTANT START BALLAST C. THREE (3) LAMP INSTANT START BALLAST Refer to Table 1 before connecting WHT/RED VIOLET(+) BROWN(-) WHT TBIL TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD ORANGE BLACK UFO-RP2 RED COM WHITE BROWN Refer to Diagram 3 before connecting WHT/RED WHT/BLK Refer to Table 1 before connecting WHITE RED RED VIOLET(+) BROWN(-) WHT TBIL SWITCHED OR UNSWITCHED LINE COM WHITE ORANGE BLACK BROWN WARNING SWITCHED OR UNSWITCHED LINE WHT/BLK Refer to Table 1 before connecting TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting RED LAMP 1 LAMP 2 LAMP 3 LAMP 4(EMERGENCY) NOTE: Use the proper input voltage lead, cap unused lead Page 4 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT Typical schematics only may be used other ballast, consult the factory wiring diagram WIRING DIAGRAM For Two Lamps Emergency Operation (14-54W) A. TWO (2) LAMP INSTANT START BALLAST SWITCHED OR UNSWITCHED LINE Refer to Table 1 before connecting WHT/BLK BROWN WARNING WHITE ORANGE BLACK BROWN UFO-RP2 RED TBIL BROWN UFO-RP2 Refer to Diagram 3 before connecting WHITE RED RED RED WHITE ORANGE BLACK BROWN UFO-RP2 RED WHT TBIL Refer to Table 1 before connecting COM WARNING TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD BROWN UFO-RP2 WHITE RED RED RED TBIL WARNING WHT/BLK BROWN BROWN UFO-RP2 RED TBIL WHT Refer to Table 1 before connecting SWITCHED OR UNSWITCHED LINE WHT/RED TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting BLUE TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD BLUE YELLOW/BLACK YELLOW BLUE/WHITE Refer to Diagram 3 before connecting BLUE/WHITE AC BALLAST RED RED BLUE BLUE/WHITE YELLOW YELLOW RED TBIL WHT SWITCHED OR UNSWITCHED LINE COM WHITE ORANGE BLACK BROWN WHITE RED RED VIOLET(+) BROWN(-) WHT/BLK BROWN WARNING COM WHITE ORANGE BLACK WHT/RED WHITE RED RED VIOLET(+) BROWN(-) WHT SWITCHED OR UNSWITCHED LINE COM WHITE ORANGE BLACK F.THREE (3) LAMP RAPID START BALLAST E. TWO (2)LAMP RAPID START BALLAST Refer to Table 1 before connecting WHT/BLK BROWN Refer to Diagram 3 before connecting WHT/RED VIOLET(+) BROWN(-) WHITE RED RED SWITCHED OR UNSWITCHED LINE WHT/BLK BROWN TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting D. TWO (2)LAMP RAPID START BALLAST C. FOUR (4) LAMP INSTANT START BALLAST WARNING COM WHT/RED VIOLET(+) BROWN(-) WHT TBIL Refer to Table 1 before connecting WHITE ORANGE BLACK BROWN WARNING TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD SWITCHED OR UNSWITCHED LINE WHT/BLK Refer to Table 1 before connecting COM WHT/RED VIOLET(+) BROWN(-) WHT B. THREE (3) LAMP INSTANT START BALLAST UFO-RP2 VIOLET(+) BROWN(-) WHT/RED TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting WHITE RED RED LAMP 1 LAMP 2(EMERGENCY) LAMP 3(EMERGENCY) G.FOUR (4) LAMP RAPID START BALLAST Refer to Table 1 before connecting WARNING WHT/BLK BROWN WHITE ORANGE BLACK BROWN RED RED YELLOW AC BALLAST BLUE BLUE/WHITE YELLOW/BLACK BLUE/WHITE YELLOW UFO-RP2 BLUE/WHITE YELLOW BLUE BLUE BROWN BROWN RED TBIL WHT VIOLET(+) BROWN(-) WHT/RED SWITCHED OR UNSWITCHED LINE COM TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD Refer to Diagram 3 before connecting WHITE RED RED LAMP 1 LAMP 2 LAMP 3(EMERGENCY) LAMP 4(EMERGENCY) Emergency only Operation A. ONE (1) LAMP WITHOUT AC BALLAST (14-54W) B. TWO (2) LAMP WITHOUT BALLAST (14-54W) WHITE/RED Refer to Table 1 before connecting WARNING WARNING BROWN BROWN UFO-RP2 RED TBIL WHT VIOLET(+) BROWN(-) BROWN WHITE/RED Refer to Table 1 before connecting ORANGE BLACK WHITE WHT/BLK WHITE RED RED BROWN TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD UFO-RP2 RED TBIL Page 5 WHT VIOLET(+) BROWN(-) ORANGE BLACK WHITE WHT/BLK WHITE RED RED TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD