Study Committee B5 Colloquium 2005 September 14-16 Calgary, CANADA 316 Zero Sequence Current Compensation for Distance Protection applied to Series Compensated Parallel Lines TAKAHIRO KASE* PHIL G BEAUMONT Toshiba International (Europe) Ltd. United Kingdom SUMMARY The effects of zero sequence mutual coupling on the performance of distance protection installed on parallel transmission lines can be significant. It is well understood and documented that the effects of mutual coupling can cause distance relays to over-reach or under-reach depending on the operational status of the adjacent line. In principle, this problem can be solved by introducing the zero sequence current from the parallel line to the relay on the faulted line. Nevertheless, manufacturers and users have adopted a variety of coping strategies in order to compensate for these effects in cases where the adjacent current is not available. However, recent experience has shown that there is another problem that must be considered when distance relays are applied to series compensated parallel lines. When a fault occurs on a series compensated transmission line, a transient oscillating current will flow between the L and C components. This oscillation has a sub-synchronous frequency. Generally speaking, it is difficult to remove the sub-synchronous frequency completely from the measured current and voltage, hence the sub-synchronous components will affect distance measurement. In this paper, the undesirable effect of mutual coupling on distance measurement is discussed theoretically together with practical simulation cases and the benefit of introducing zero sequence compensation on parallel transmission lines for distance calculation is also demonstrated using simulation studies. Keywords: Distance relay – Series capacitor – Zero sequence compensation – Parallel line – Mutual impedance – sub-synchronous frequency – EMTP – ATP 1. INTRODUCTION Series compensated lines provide significant advantages in terms of improvements in power system stability, an increase in the capacity of transmission lines etc. However, from a line protection perspective, series compensated lines can cause many difficulties, particularly for distance protection relays. In order to overcome problems numerous studies have been undertaken [1]-[4]. The main problems for distance protections applied to compensated lines are overreach, directional element errors and oscillation of impedance measurement. In previous studies, it has been recognized that problems occur in the case of faults beyond the series capacitor. Therefore studies have focused on phenomena which were apparent for *kaset@til.toshiba-global.com 316 - 1 faults occurring beyond the series capacitor and solutions have been proposed. In these studies, it would appear that distance protections were able to calculate the impedance correctly for faults up to the series capacitor. Meanwhile, many studies in the application of distance relays to parallel lines have also been undertaken [5], [6]. The main problem in the application of distance relays to parallel lines is the effect of the mutual impedance of the parallel line on the phase-to-ground impedance measurement for earth faults. Theoretically, it is apparent that the introduction of the residual current of the adjacent line is the easiest and the most effective way of overcoming this problem. Many alternative methods have been proposed because sometimes it is neither possible nor preferred to introduce the residual current of the adjacent line. Our studies have revealed that the combination of parallel lines and series capacitors has caused new problems for impedance measurement even when the fault occurs before the series capacitor. In this paper, the new problems are introduced both theoretically and by simulation. It is shown that the introduction of the residual current of the adjacent line is the solution to the problem. 2. MUTUAL ZERO SEQUENCE COMPENSATION Firstly, the principle of distance measurement when distance protection is applied to parallel lines with mutual impedance is shown in Fig.2.1 for a typical parallel line model with double end infeed. P term I0M Q term Z1, Z0 EP ~ EQ ZP VP Z0M IA ,I0 ZQ VTs CTs Z1F, Z0F ~ IF Relay Fig.2.1 Typical parallel line model with double end infeed In Fig.2.1 it is assumed that an A-phase-to-ground fault occurs. The A phase voltage at the relay can then be calculated as follows. V PA = Z 1F I A + ( Z 0 F − Z 1F ) I 0 + Z MF I 0 M = Z 1 ( I A + Z Z 0 F − Z 1F I 0 + 0 MF I 0 M ) Z 1F Z 1F (2.1) = Z 1F ( I A + k s I 0 + k m I 0 M ) where, VPA : A-phase voltage at P term, IA : A-phase current of faulted line I0 : zero sequence current of faulted line, I0M : zero sequence current of adjacent line Z1F : positive sequence impedance from relay to fault point Z0F : zero sequence impedance from relay to fault point Z0MF : zero sequence mutual impedance from relay to fault point k s = ( Z 0 − Z1 ) / Z1 , k m = Z 0 M / Z 1 Therefore the impedance to the fault point can be calculated as follows. Z 1F = V PA I A + k s I 0 + k m I 0M (2.2) If the zero-sequence current of the adjacent line is not available, distance relays must calculate the impedance as follows. Z '1F = V PA I A + ks I0 (2.3) Examining (2.2) and (2.3), it is apparent that Z’1F is larger than Z1F when I0m is positive (i.e. in the same 316 - 2 direction) and that Z’1F is smaller than Z1F when I0m is negative (i.e. opposite direction). When faults occur towards the far end of the line I0m is generally positive and distance relays may underreach. Overreach for near faults is not so serious a problem for distance protection. Therefore one possible solution to this problem is to use a larger value of ks than the calculated value. However, the direction of zero sequence current can vary with the operational condition of the adjacent line, for example, the adjacent line may be in operation or open or earthed. An alternative idea for adjusting the setting of ks is to introduce the status of the adjacent line to the relay. It is well known that the distance relay on the healthy line can overreach because of mutual zero sequence compensation, and one solution to this problem is to block the mutual zero sequence compensation for faults on the adjacent line. This can be detected by comparing the zero-sequence current of the protected line to the zero-sequence current of the adjacent line. This solution has been applied for many years in Japan. 3. SERIES COMPENSATED PARALLEL LINE It is well recognized that faults beyond the series capacitor, as shown in Fig.3.1 cause two main problems for distance measurement. The first problem is the overreach caused by the reduction in impedance by the insertion of the capacitor in the line. The other problem is that sub-synchronous frequencies are superimposed. This can be understood by solving the differential equation (3.1), and the fault current can be given by (3.2) generally:- E P sin ωt = Ri + L di 1 + idt dt C ∫ (3.1) I F = I m sin(ωt + φ ) + e −αt ( I m sin φ cosωC t + I n sin ωC t ) (3.2) where, ω : System angular velocity I m = EP / R 2 + (ωL − 1/ ωC ) 2 , α = R / 2L , 2 2 ωC = 1/ LC − ( R / 2L) 2 , φ = tan −1 ( ωL − 1 / ωC ) , I n = − α + ωC I m cosφ + α I m sin φ R ω ⋅ ωC ωC Therefore the sub-synchronous frequency component, which is expressed by ωC, is superimposed on the fundamental frequency component. Generally speaking, it is difficult to remove this frequency using a digital filter, because the long data window required will cause a delay in operation. Hence the algorithm for distance measurement must be immune to this lower frequency [7]. Fig.3.2 shows the parallel series compensated line model. In this model series capacitors are installed at one end. It is clear that the zero-sequence current of the adjacent line will flow to the fault point through the series capacitors for faults located up to the series capacitor. The influence of mutual impedance includes the sub-synchronous frequency caused by the series capacitor. Furthermore the zero sequence current of the adjacent line can be capacitive if the total capacitive reactance is larger than the line reactance. This phenomenon is more likely to happen when the fault point is close to the series capacitor. VTs CTs R, L P term C I0M Q term Z 1 , Z0 EP EP ~ Relay EQ IF ~ ~ EQ SC ZP VP Z0M IA ,I0 ZQ VTs CTs xZ1, xZ0 Relay IF (1-x)Z1, (1-x)Z0 ~ SC SC : series capacitance 0 ≤ x ≤1 Fig.3.1 Fault at series compensated line Fig.3.2 Parallel series compensated line 316 - 3 xZ1 (1-x)Z1 xZ1 (1-x)Z1 2ZP1 C1 EP C1 2ZQ1 EQ ~ ~ EQ positive-sequence 1st circuit ~ ~ C1 EP ZQ1 ZP1 (1-x)Z1 xZ1 xZ1 Relay (1-x)Z1 C1 positive-sequence circuit positive-sequence 2nd circuit (1-x)Z2 xZ2 2ZP2 C2 xZ2 (1-x)Z2 C2 2ZQ2 ZQ2 ZP2 xZ2 (1-x)Z2 C2 negative-sequence 1st circuit xZ2 Relay (1-x)Z2 C2 negative-sequence circuit negative-sequence 2nd circuit xZ0 (1-x)Z0 C0 ZP0 2ZP0 xZ01 (1-x)Z01 C0 2ZQ0 ZQ0 xZ0 Z0M (1-x)Z0 C0 zero-sequence 1st circuit xZ00 Relay (1-x)Z00 C0 zero-sequence circuit zero-sequence 2nd circuit Fig.3.3 Equivalent circuit using sequence components Fig.3.4 Equivalent circuit using sequence component by 2-phase component method Fig.3.3 shows the equivalent circuit using sequence components in the case of an A-phase-to-ground fault. In Fig.3.3, the mutual impedance in the zero-sequence circuit complicates the calculation. It is well known that by applying the 2-phase component method [8], the mutual impedance in the zero-sequence circuit can be decoupled. The calculation method of conversion to 2-phase components is shown in (3.3) and the method of re-conversion to normal sequence components is shown in (3.4). By means of the 2-phase component method, Fig.3.3 is modified to Fig.3.4. ⎡V k1 ⎤ 1 ⎡1 1 ⎤ ⎡ Vk ,1L ⎤ ⎡ I k 1 ⎤ 1 ⎡1 1 ⎤ ⎡ I k ,1L ⎤ ⎥, ⎢ ⎥ = ⎢ ⎥ ⎢V ⎥ = 2 ⎢1 − 1⎥ ⎢V ⎥⎢ ⎦ ⎣ k , 2 L ⎦ ⎣ I k 2 ⎦ 2 ⎣1 − 1⎦ ⎣ I k , 2 L ⎦ ⎣ ⎣ k2 ⎦ (3.3) ⎡V k ,1L ⎤ ⎡1 1 ⎤ ⎡ V k1 ⎤ ⎡ I k ,1L ⎤ ⎡1 1 ⎤ ⎡ I k1 ⎤ (3.4) ⎢V ⎥=⎢ ⎥=⎢ ⎥, ⎢ ⎥⎢ ⎥⎢ ⎥ ⎣ k , 2 L ⎦ ⎣1 − 1⎦ ⎣V k 2 ⎦ ⎣ I k , 2 L ⎦ ⎣1 − 1⎦ ⎣ I k 2 ⎦ where, k=1, 2, 0 (positive, negative, zero sequence component respectively) 1, 2 : converted value of first circuit and second circuit respectively 1L, 2L : measured value of Line 1 and Line 2 respectively For example, V02 is the zero sequence voltage of the second circuit shown in Fig.3.4 and I1,2L is the positive sequence current of Line 2. It should be noted that the mutual impedance is eliminated in Fig.3.4, and consequently it becomes easier to see how the fault current flows. In Fig.3.4, Z00 and Z01 can be calculated as follows using the conversion above. Z 00 = Z 0 + Z 0 M , Z 01 = Z 0 − Z 0 M (3.5) The fault current flows to P-term side and Q-term side dependent on the ratio of the impedances of both sides. The I0 of each line can be calculated as follows if If is assumed to be the total fault current, for example:(3.6) I 0,1L = I 01 + I 02 , I 0, 2 L = I 01 − I 02 where, 316 - 4 I 01 = (1 − x) Z 0 + 2Z Q 0 − j (1 / ωC0 ) Z 0 + 2Z P 0 + 2Z Q 0 − j (1 / ωC0 ) (1 − x) Z 0 − j (1 / ωC 0 ) I f , I 02 = If Z 0 − j (1 / ωC 0 ) (3.7) As described before, when the direction of I0,2L is different from the direction of I0,1L relays can overreach when using (2.3) instead of (2.2) for impedance calculation. It is apparent that the relay would cause overreach when the value of ‘x’ is close to 1, which means that the fault is near to the series capacitor. It can also be seen that the phase angles of I0,2L and I0,1L can be different, and this difference causes phase errors in the impedance measurement. In addition to the above, it is clear that the sub-frequency component can vary between I0,1L and I0,2L. Furthermore they can be different from Ia, which is calculated from I0+I1+I2. Therefore the sub-frequency component can vary between “Ia+ksI0” and “Ia+ksI0+kmI0m”, which are the denominators of (2.2) and (2.3) respectively, although their respective voltage is the same. 4. PRACTICAL SIMULATIONS AND ANALYSIS Problems predicted in the application of distance protection to series compensated parallel lines have been described theoretically in previous sections. In this section, simulations using EMTP/ATP have been undertaken in order to understand the influence of mutual impedance. The model system used in the simulation is shown in Fig.4.1. Parameters used in simulations are shown in Table 4.1. SC CTs P-term Z1,Z0 I0m ~ Q-term MOV ~ Z0M ZP1,ZP0 ZQ1,ZQ0 VTs CTs F0 F8 xZ1, xZ0 (1-x)Z1, (1-x)Z0 DZ SC ZC MOV SC : Series Capacitors MOV : Metal Oxide Varistors Fig. 4.1 Simulation model Table.4.1 Simulation parameters Line impedance [ohms] Term-P source Table.4.2 Fault points Name Value Line length [km] Voltage [kV] Frequency [Hz] 200 275 50 10 + j76 40 + j184 30 + J84 j136 2+j72 j47 j37 -j46 Positive sequence impedance (Z1) Zero sequence impedance (Z0) Mutual zero sequence impedance (Z0M) Positive sequence impedance (ZP1) impedance Zero sequence impedance (ZP0) Term-Q source Positive sequence impedance (ZQ1) impedance [ohms] Zero sequence impedance (ZQ0) Series capacitor (ZC) [ohms] Fault point Distance from A reactance x [%] [ohms] F0 0 0 F1 12.5 9.5 F2 25 19 F3 37.5 28.5 F4 50 38 F5 62.5 47.5 F6 75 57 F7 87.5 66.5 F8 100 76 Fault points checked in the simulations are shown in Table 4.2. From the results four cases have been shown in this paper, (Figs. 4.2 to 4.5 inc.) with wave forms of I0 and I0m (the respective zero-sequence currents of the protected and adjacent lines) together with the results of distance measurement. The figures show the comparison between two methods of zero sequence compensation, one in which only the self zero-sequence compensation is calculated using (2.3), and the other one in which the self and mutual zero-sequence compensation is calculated using (2.2). 316 - 5 3000 3I0 3I0m Current [A 2000 1000 0 0.10 -1000 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 -2000 -3000 Tim e [s] 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 -50.10 -10 Measured Reactance Actual Reactance Actual Resistance Measured Resistance 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 -50.10 -10 Actual Reactance Measured Reactance Actual Resistance Measured Resistance 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 Tim e [s] Tim e [s] Fig.4.2 Fault point F8(100%) (Upper: Waveform, Left: With mutual compensation, Right: Only self compensation) Current [A The following can be identified from Fig.4.2. - The phase difference between I0 and I0m is almost 150 degrees. - The impedance measurement using I0m and I0 is very stable and precise - A significant oscillation and overreach by about 15% of impedance measurement can be seen for the case where only I0 is used. 2000 1500 1000 500 0 -5000.10 -1000 -1500 -2000 -2500 3I0 3I0m 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 Tim e [s] 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 -50.10 -10 Reactance Resistance 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 -50.10 -10 Reactance Resistance 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 Tim e [s] Tim e [s] Fig.4.3 Fault point F6(75%) (Upper: Waveform, Left: With mutual compensation, Right: Only self compensation) The following observations can be made upon examining Fig.4.3. - The phase difference between I0 and I0m is almost 90 degrees. - The impedance measurement using I0m and I0 is very stable and precise - A significant oscillation whose amplitude is 10% of the theoretical impedance of impedance measurement can be seen for the case where only I0 is used. - Overreach of resistance measurement can be seen for the case using only I0, although the reactance measurement is close to the theoretical value. This is the phase error in the impedance measurement. 316 - 6 3000 3I0 3I0m Current [A 2000 1000 0 0.10 -1000 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 -2000 -3000 Tim e [s] 50 50 45 Reactance 45 Reactance 40 40 35 35 30 30 25 25 20 20 15 15 10 10 Resistance 5 0 0.10 -5 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 Resistance 5 0.30 0 0.10 -5 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 Tim e [s] Tim e [s] Fig.4.4 Fault point F4(50%) (Upper: Waveform, Left: With mutual compensation, Right: Only self compensation) Current [A The following can be identified from Fig.4.4. - The phase difference between I0 and I0m is almost 60 degrees. - The impedance measurement using I0m and I0 is very stable and precise - A significant oscillation of impedance measurement can be seen for the case where only I0 is used. - Underreach of reactance element and overreach of resistance measurement can be seen for the case where only I0 is used. 4000 3000 2000 1000 0 -10000.10 -2000 -3000 -4000 -5000 3I0 3I0m 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 0.30 Tim e [s] 30 30 25 25 Reactance 20 15 15 10 10 Resistance 5 0 0.10 0.12 0.14 0.16 0.18 0.20 0.22 0.24 0.26 0.28 Reactance 20 Resistance 5 0.30 0 0.10 0.12 0.14 0.16 Tim e [s] 0.18 0.20 Tim e [s] 0.22 0.24 0.26 0.28 0.30 Fig.4.5 Fault point F2(25%) (Upper: Waveform, Left: With mutual compensation, Right: Only self compensation) The following can be identified from Fig.4.5. - The magnitude of I0m is almost zero, 100ms after the fault. - The impedance measurement using I0m and I0 is very stable and precise - The impedance measurement using only I0 is stable and precise According to these results, it is expected that the following problems will be experienced in distance measurement if I0m is not used in the calculation. 316 - 7 - The sub-synchronous frequency component can cause significant oscillations in distance measurement. - Overreach for faults towards the far end of the line can occur due to the effect of mutual impedance, which is not seen by the relay unless compensation for the parallel line is applied. - The angular difference between I0 and I0m can be seen and can be considered as the reason for the error in distance measurement. - The effect of mutual impedance on distance measurement varies significantly with the fault point. In order to compare the frequency components of the zero-sequence current in the protected line and the adjacent line, the A-phase current, the denominator of (2.2) and (2.3) and the A-phase voltage, the results of the FFTs(Fast Fourier Transform) of these waveforms are shown below. The data window is 100 ms from fault inception. The fault point is F6, which is the same as that shown in Fig.4.3. The horizontal axis of the following graph is f/f0, (f0 is the system frequency), and the vertical axis is the contribution of each frequency component, in which the value of the basic frequency component is normalized to 1. 1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 2 4 6 8 0 10 0 Fig.4.6 Frequency diagram (I0) 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 2 4 6 2 4 6 8 10 Fig.4.7 Frequency diagram (I0m) 8 10 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 Fig.4.8 Frequency diagram (Ia) 2 4 6 8 10 Fig.4.9 Frequency diagram (Ia+ksI0) 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 2 4 6 8 10 Fig.4.10 Frequency diagram (Ia+ksI0+kmI0m) 0 2 4 6 8 10 Fig.4.11 Frequency diagram (Va) On examining Figs. 4.6 to 4.10 inc., it can be seen that a large sub-synchronous component exists in I0 and I0m, compared to the sub-synchronous component which is smallest in (Ia+ksI0+kmI0m), the compensated current. Hence, the introduction of the zero-sequence current of the adjacent line effectively reduced the sub-synchronous component. If it is considered that the DC component in the current can be 316 - 8 eliminated almost completely by using a digital filter, it can be said that the frequency component in “Ia+ksI0+kmI0m” is similar to that of the voltage. This fact can be considered as the main reason why the introduction of the zero-sequence current of the adjacent line enables stable and precise distance measurement. 5. CONCLUSION This paper describes the problems associated with distance measurement when distance protection is applied to series compensated parallel lines. The following points are confirmed both theoretically and by practical simulation. - Faults up to the series capacitor can cause problems such as oscillation, overreach for remote end faults and phase error in distance measurement. - These problems are caused by the mutual zero-sequence impedance. Sub-synchronous frequency components in the zero-sequence current of the adjacent line cause oscillation in the measurement. The angular difference between the zero-sequence current of the protected line and the zero-sequence current of the adjacent line can cause overreach, underreach and phase error in the impedance measurement. - The relationship between I0 and I0m varies with the fault point. This means that the effect of mutual zero sequence impedance on distance measurement also varies with fault point. - These problems can be solved completely by using mutual zero-sequence compensation by the introduction of the zero-sequence current of the adjacent line. 6. REFERENCES [1] T.Maekawa, Y.Obata, M.Yamaura, Y.Kurosawa and H.Takani “Fault location for series compensated parallel lines,” IEEE/PES Transmission and Distribution Conference and Exhibition 2002, Conference Proceedings,2,pp.824-829 [2] M.M.Saha, B.Kasztenny, E.Rosolowski and J.Izykowski “First zone algorithm for protection of series compensated lines,” IEEE Trans. on Power Delivery Vol.16, No.2, pp.200-207 Apr.2001. [3] “Application guide on protection of complex transmission network configuration,” CIGRE materials, CIGRE SC-34 WG-04, Aug. 1990 [4] D.Novosel, A.Phadke, M.M.Saha and S.Lindahl “Problems and solutions for microprocessor protection of series compensated lines,” Sixth International Conference on Developments in Power System Protection, Conference Publication no.434, pp.18-23 [5] Yi Hu, D.Novosel, M.M.Saha and V.Leitloff “An adaptive scheme for parallel-line distance protection,” IEEE Trans. on Power Delivery Vol.17, No.1, pp.105-110 Jan.2002. [6] A.G.Jongepier and L.van der Sluis “The behavior of distance relays applied to double-circuit lines in practice and the need for adaptive protection,” CIGRE SC34 –205 Stockholm June,1995 [7] Y.Ohura, T.Matsuda, M.Suzuki, M.Yamaura, Y,Kurosawa and T.Yokoyama,”Digital distance relay with improved characteristics against distorted transient waveforms,” IEEE Trans. on Power Delivery Vol.4, No.4, pp.2025-2031 Oct.1989. [8] Y.Hase “Practical theory hand book for power system techniques”, MARUZEN, 2004 (in Japanese) 316 - 9