1 On-site Low Voltage Determination of Zero Sequence Impedances for Station Auxiliary Transformers Mariana Kamel, Haytham Saeed, Abdelrahman Karrar, Ahmed Eltom, Mark Bowman, Tamatha Womack, Preston Cooper University of Tennessee at Chattanooga & TVA 2 Background • Motivation for this research was the incident of January 30, 2012 at Byron Station NPP which involved an open-phase condition on the primary of two SATs. – This research describes a new method for finding the zero sequence parameters for typical SATs. – The method cuts the costs of prevailing methods, particularly for on-site measurements. – Initial simulations were promising. Method was then validated using actual measurements. 3 Background - 2 • In the standard IEEE/ANSI method, at least one measurement must be carried out from the high voltage side. This measurement is shown in figure as Z1No • The usual setting for this test would be a high voltage laboratory, where suitable test voltages are available. Z1Ns or Z2Ns Zp-0 Z1No Zm-0 Zt-0 Zs-0 Z2No 4 Background - 3 • Onsite measurements however would require renting high voltage mobile laboratories at a high cost. • Our method eliminates the high voltage test, and replaces it with the low voltage test shown below. • Only a low voltage (230 – 400 V) three phase supply is required. primary phase A opened Ia Ib Ic primary phase B and C shortcircuited A Vab V A Vbc V A secondary neutral point disconnected Three-phase low voltage source V Vca 5 Background - 4 • Our test configuration requires application of a three phase voltage to the secondary under the following conditions: 1. Secondary neutral is disconnected. 2. Two primary (high voltage) terminals are shorted to the neutral, with the remaining terminal left open. • This connection creates conditions involving all three sequence component voltages and currents. 6 Methods • Our method exploits the primary open phase sequence model. • Two methods were proposed. A simplified “approximate “ method and an iterative based “exact” method. I1 I2 I0 Zps-1 Zps-2 Zp-0 Zt-0//Zm-0 Zs-2 V2 Zs-1 V1 E1 7 Methods - 2 • The simplified method makes use of symmetry resulting from neglecting the transformer resistive components. • This assumed symmetry allows to calculate positive and negative sequence currents from line currents Ia, Ib and Ic . πΌπΌππΜ = πΌπΌππΜ = πΌπΌ πΌπΌ1 = −2 3 πΌπΌ cos(ππ + 30°) ππ = cos−1 πΌπΌ2 = 2 3 πΌπΌππΜ − 2πΌπΌ πΌπΌ cos(ππ − 30°) πΌπΌ0Μ + πΌπΌ1Μ + πΌπΌ2Μ = 0 Ic θ I2 -θ I1 Ia Ib Vc Vca V1 Vbc Va Vab Vb Ο V2 8 Methods - 3 • The exact method includes transformer resistive components and involves using the six current and voltage measurements Ia, Ib, Ic, Vab, Vbc and Vca in addition to the sequence network model to solve for real and imaginary values of I1, I2, V1 and V2 . From this solution Io is deduced and used to find the real and imaginary components of the zero sequence impedance. • The equations are non-linear and further overdetermined by one. Thus, a non-linear least square estimation method, for example the Newton-Gauss method is used for a solution. 9 Results • Summary of results for a test carried out on a TVA 18 MVA SAT at a test site in Virginia. 10 Conclusions • The test is expected to be valuable to those seeking to determine zero sequence parameters not available on many legacy SAT units with affordable costs. • Method is extendable to transmission type transformers – authors are developing model. • Field testing has confirmed the high accuracy offered by the method. 1 Paper No: 16PESGM1489 Analysis of Open Phase Fault Events Using ETAP Unbalanced Load Flow Module Preston O. Cooper III Tennessee Valley Authority pocooper@tva.gov 2 Background • Multiple events across the nuclear power industry • Existing schemes did not provide adequate protection • Need for greater understanding of what happens during an open phase fault (OPF) 3 Event • OPF above transformer • Magnetic circuits reconstruct missing phase • Configuration affects low side unbalance 4 Why Steady State? • Worst case V1 and V2 should not trip instantaneous motor protection (current) • I2 creates additional heating in motors • Motors have thermal mass 5 Methodology IEQ Equivalent Current I1 Positive Sequence Current I2 Negative Sequence Current IFL Motor Full Load Current ILR Motor Locked Rotor Current 6 7 8 Results • Greater transformer loading yields greater unbalances • Less impedance to ground yields greater unbalances • Lack of a stabilizing winding yields greater unbalances • Two different transformers in the same system yield equal maximum unbalances 9 Protective Devices • Possible – Transformer Phase Overcurrent – Transformer Neutral Overcurrent – Transmission Line Negative Sequence • Discounted – Transformer Differential – Degraded Voltage 10 Summary • Additional heating due to V2 and I2 is a significant consequence of an OPF • Transformer construction is crucial • Steadyβstate calculations are viable • Three dimensional surfaces – Visualize the effects of an open phase fault – Validate existing or develop new protection 1 Open-Phase Study in Nuclear Power Plant Presented by: Dr. Zia Salami Associate Professor, Electrical Engineering 2 Outline • • • • • • • Acknowledgment Introduction Equivalent 3-Phase Power System Model Open-Phase Scenarios Studied Sample of Results Notable Results & Conclusion Questions 3 Acknowledgment • Mr. Joel Mathewson, • Mr. Mario Poujol, • Mr. Volodymyr Habovda – Graduated in 2014, UNC Charlotte • Mr. Lee Easter, – PowerC, LLC Vice President 4 Introduction Equivalent 3-Phase Power System Model (in EMTP) Transformer Data/Model • 3 winding transformer (i.e. 3x1 phase) • Ratings: 345/6.9/4.16 kV, 40/35/5 MVA • Yg-Yg-Yg connected (primary solidly grounded, resistive ground on secondary 6.6 ohms, and tertiary 4.0 ohms, 600A) 7 Complete Equivalent 3-Phase Power System Model 8 Open-Phase Scenarios Studied Sample of Results 10 11 Sequence current (A), ES Bus, Normal Operation: • • • Scenario 1, Case 0 (base) Scenario 1, Case 1 (single) Scenario 1, Case 4 (double) 12 Sequence current (A), BOP Bus, 7000 hp starts: • • • Scenario 7, Case 0 (base) Scenario 7, Case 1 (single) Scenario 7, Case 4 (double) 13 Notable Results & Conclusion • I2/I1 are minimum in Cases 3 and 4 (i.e. solid grounded open-phase on the high voltage side of transformer and double open-phase). This value can be used to set open-phase pickup to be less than this minimum value. • I1 & I2 maximum are in case 2 (i.e. line to ground open-phase from the grid side). This value can be used for blocking the open-phase logic in case of any short-circuit fault in the system. • Longer motor acceleration times during double open- phase condition. • Bottom line, there is no single bullet to identify open-phase worst case scenario. It depends on system configurations, loadings, equipment, grid conditions, and more. I believe all possible plant’s permissible scenarios/ configurations should be studied and analyzed to identify the worst case open-phase condition. 14 QUESTIONS? 1 Influence of Zero Sequence Impedances of Station Auxiliary Transformers on Equipment Performance under Open-Phase Faults 2 AGENDA • • • • • Introduction Open Phase Fault Network Test Results Conclusion Questions 3 INTRODUCTION • Primary open-phase faults on SATs result in voltage imbalance at the auxiliary equipment level. • Primary to ground zero sequence impedance has a major role in balancing the secondary voltages during open phase faults. • This study investigates the impact of voltage imbalance on the performance of station auxiliaries. 4 OPEN PHASE FAULT NETWORK Single Line Diagram for System Studied with Primary Open Phase Fault Corresponding Sequence Network 5 SERVICE TRANSFORMER DATA SAT 1 Sequoyah 33 MVA (base) SAT 2 Sequoyah 18 MVA (base) SAT 3 J. M. Farley 26 MVA (base) Z1 P-S (%) 10.26 8.6 14.6 Z0 P-N (%) 8.75 10.37 32.41 6 TEST RESULTS • The analysis performed to answer: – Is the motor able to accelerate successfully to rated speed under open-phase conditions? – If yes, what is the acceleration time required? – What is the voltage unbalance ratio V2/V1 during and after attaining steady state operation? 7 TEST RESULTS V2/V1 (%) • Voltage imbalance was 8.6% at the instant of starting and 1.2% at steady state conditions 10 5 0 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 V1 (%) 200 100 0 V2 (%) 10 5 0 8 TEST RESULTS • Voltage imbalance increased the starting time to 17 s (3 seconds delay). Ia (%) 1000 500 0 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 0 2 4 6 8 10 Time (sec) 12 14 16 18 20 T (%) 500 0 wr (rad/sec) -500 500 0 -500 9 TEST RESULTS • Results for all three transformers under base (actual data) conditions SAT 1 Sequoyah 33 MVA SAT 2 Sequoyah 18 MVA SAT 3 J. M. Farley 26 MVA Start Run. Start. Run. Start. Run. Accel. time Normal (s) 14 - 15 - 17 - Accel. time Open –Phase (s) 17 - 24 - 45 - V2/V1 % 8.6 1.2 16 2.3 28.4 4.15 Ia current increase % -15.3 -8.64 -27.51 -16.13 -44.2 -28.36 Ib , Ic current increase % -4.3 5.6 -6.06 11 -9.03 20.87 Total heating increase % -15.1 2.16 -23.66 5.58 -34.5 14.5 10 TEST RESULTS • Results under unified MVA and positive sequence impedance conditions: SAT 1 Sequoyah 33 MVA SAT 2 Sequoyah 18 MVA SAT 3 J. M. Farley 26 MVA Start Run. Start. Run. Start. Run. Acceln. time (s) 17 - 18 - 28.5 - V2/V1 % 8.6 1.2 10 1.4 25.4 3.64 Ia current increase % -15.31 -8.64 -18.34 -10.04 -40.5 -25.49 Ib , Ic current increase % -4.31 5.6 -4.27 6.65 -8.56 18.43 Total heating increase % -15.05 2.16 -16.68 2.8 -32.46 12 11 TEST RESULTS • Results under base conditions with Two SATs in Parallel: SAT 1 Sequoyah 33 MVA SAT 2 Sequoyah 18 MVA SAT 3 J. M. Farley 26 MVA Start Run. Start. Run. Start. Run. Acceln. time (s) 15.5 - 19.6 - 28.5 - V2/V1 % 4.6 0.65 8.8 1.24 17 2.39 Ia current increase % -9 -4.6 -16 -8.8 -20.7 -16.65 Ib , Ic current increase % -2.3 2.96 -3.9 5.5 -10.9 11.17 Total heating increase % -8.77 1% -14.85 2 -26.1 5.56 12 CONCLUSION • lower values of primary to ground zero sequence impedance → better voltage imbalance → better starting and running performance. • A maximum voltage unbalance (V2/V1) of less than 10% during starting allowed adequate acceleration of RCP. • Delayed motor acceleration, or possibly failure to start could be expected if the voltage imbalance goes beyond 10%. 13 CONCLUSION • Accurate determination of zero sequence impedances is necessary to assess the response of substation auxiliaries and accordingly decide on the appropriate measures in the event of an open phase fault on the primary SAT level. 1 Open – Phase Detection Considerations for Nuclear Power Generating Station Electrical Systems Tony Sleva, LSM - IEEE Senior Engineering Consultant Altran 2 Typical Nuclear Generating Station One Line Diagram 3 Typical Nuclear Generating Station Positive Sequence Diagram 4 Typical Nuclear Generating Station Negative Sequence Diagram 5 Typical Nuclear Generating Station Zero Sequence Diagram 6 Typical Nuclear Generating Station Combined Sequence Diagram 7 Observations • Sequence Models are functions of Connected Load • Load Impedance is a function of Motor Speed • Positive Sequence Motor Impedance is different than Negative Sequence Motor Impedance • Positive Sequence Torque = Accelerating Torque • Negative Sequence Torque = Decelerating Torque • No Zero Sequence Torque 8 Observations • Sequence Voltage and Current are functions of Connected Load • When Zero Sequence Impedance is High, Zero Sequence considerations are minimal • When Zero Sequence Impedance is Low, Negative Sequence considerations are minimal 9 Observations • High Zero Sequence Impedance (Zero Sequence considerations are minimal.) • Motors Rotating during open phase conditions: o Positive sequence torque is reduced o Negative sequence torque is low o Motors will continue rotating o Motors will overheat (minutes) 10 Observations • High Zero Sequence Impedance (Zero Sequence considerations are minimal.) • Motor Acceleration during open phase conditions: o Positive sequence torque is reduced o Negative sequence torque is high o Motors will not accelerate to rated speed o Motors will overheat (seconds) 11 Observations • Low Zero Sequence Impedance (Negative Sequence considerations are minimal.) • Motors Rotating during open phase conditions: o Positive sequence torque is reduced o Negative sequence torque is minimal o Motors will continue rotating o Motors will not overheat 12 Observations • Low Zero Sequence Impedance (Negative Sequence considerations are minimal.) • Motor Acceleration during open phase conditions: o Positive sequence torque is reduced o Negative sequence torque is minimal o Motors will Accelerate o Motors will overheat slowly 13 Observations • Traditional Open Phase Detection Schemes are applied on a per Motor basis • Non-Nuclear Electrical Systems are designed for staged load increases • Nuclear Power Generating Station Electrical Systems are designed for Rapid Step Loading 14 Conclusions • Understanding Zero Sequence Impedance is KEY • Open Phase Detection with Microprocessor Based Protective Relays is achievable • Utilize Open Phase Watchdogs • Consider “Voting Logic” Applications 15 Conclusions Open Phase Watchdog Parameters ο§ Monitor for Negative Sequence Current ο§ Monitor Total Current ο§ Monitor Positive Sequence Phase Angle Negative Sequence Current, Large Phase Angle (~700), High Total Current Motor Acceleration – Quick Trip Negative Sequence Current, Moderate Phase Angle (~400), Moderate Total Current Motors Rotating – Slow Trip 1 Open-Phase Fault (OPF) Modeling and Analysis in ETAP Salman Kahrobaee Senior Electrical Engineer ETAP Tanuj Khandelwal Senior Principal Engineer ETAP 2 Agenda • • • • • • Unbalanced System OPF Study Objective & Requirements OPF Analysis and Related Indexes General Element Modeling Examples Conclusion 3 Real Unbalanced Power System • Distribution System – 3-phase, 2-phase, and single-phase network components – Unbalanced loads • Transmission System – Untransposed long transmission line – Unbalanced loads (e.g., electrical railway traction motors) • Abnormal condition with open-phase fault 4 Impact of System Unbalance • Overheating of equipment • Stalling of running motors • Longer motor acceleration times • Nuisance tripping of protective relays • Increased real power losses • Lifetime reduction 5 OPF Study Objectives • Identify the level of unbalance (voltage and current) throughout the plant • Analyze system performance during OPF • Determine whether existing protective systems will detect the OPF condition • Determine the protective device settings to avoid excessive heating 6 Unbalance Factors/Indexes • System unbalance is considered as a disturbance • Voltage/Current unbalance factors • Ratio of negative sequence to positive sequence • Ratio of zero sequence to positive sequence • Ratio of maximum deviation from average value to average value 7 OPF Study Requirements • Positive, negative and zero-Sequence Impedances • Mutual coupling of overhead lines • No-load losses for Buried delta windings for 2&3 winding transformers • Transformer winding connections • 3-phase, 2-phase and single-phase network components • Internal impedance of electric machines 8 OPF Study Method • The OPF analysis should consider – Operating scenarios (events/loading) – Configurations – Amount of potential voltage unbalance in the incoming plant power supplies (grid unbalance) • Overall analytical method is a steady-state load flow technique • Current Injection (CI) method 9 Buried Delta Winding • Assumption: – Symmetric – Linear – no saturation • 3 independent variables/impedances: 2-winding – 3 sets of test data • 6 independent variables/impedances: 3-winding – 6 sets of test data 10 Buried Delta Winding • Impedance modeling based on test data 11 3-Phase Machines • Sequence models 12 Loads • Single-Phase Loads – Different connection types: AB, BC, CA, AN, BN or CN • Three-Phase Loads – Connected in Delta, Wye or Wye-G • Lumped loads consisting of constant power, constant impedance and constant current components 13 OPF Analysis Software • ETAP NUUG began review of ETAP’s ability to perform OPFA shortly after the Byron open-phase event in early 2012 • ETAP is used throughout the world by nuclear plants, research laboratories, consulting firms, government agencies, and other organizations • Multiple OPF simulations can be performed considering different scenarios (transformer loading and open-phase grounding) 14 Steady State Simulation • Protective relaying settings will be based on steady state values in order to avoid nuisance tripping • Transient studies using EMTP requires considerable amount of time to model a complete power electrical system • Most of the electrical systems required are available and minimal data entry is need in order to expand the model to perform open phase fault simulation • Phase and sequence reporting 15 Sequence Network Connection • Open Phase Fault 16 Example Steady State vs. Transient • 3-phase Currents • 3-phase Voltages 17 Example Buried Delta & Motor Loading Scenario Revision Scenario 1 Scenario 2 Scenario 3 Scenario 4 Base Base Buried-Delta Buried-Delta Mtr1 Study Case ULF-100% ULF-50% ULF-100% ULF-50% Mtr2 25.00% 20.00% 15.00% 10.00% 5.00% 0.00% Scenario 1 Scenario 2 Scenario 3 Scenario 4 18 Example Double Open-Phase Fault • Heavily Loaded Motors • Ground path Study # Study 1 Study 2 Study 3 Study 4 Study Study 1 Study 2 Study 3 Study 4 Double Open-Phase Fault Study Case B-C open at T1 primary side B-C open at T1 primary side B-C open at T2 primary side B-C open at T2 primary side Mtr35 V1 L-L (%) 34.31 108.3 105.8 101.6 V2/V1 (%) 100 5.69 3.2 0.31 Summer Winter Summer Winter Mtr31 V1 L-L (%) 33.8 107.4 70.48 103.5 V2/V1 (%) 99.97 5.62 100 4.3 19 Conclusion • Data requirement including element connections, sequence impedance, unbalanced loads & sources • Application of a validated simulation software • OPF analysis on various scenarios • Protection scheme based on provided limits