UNIQLE – 5 Elements · 1 System

advertisement
V.
UNIQLE
Data centre and
Water-cooled server cabinet solutions
UNIQLE – 5 Elements · 1 System
With UNIQLE, SCHÄFER offers a system
platform to meet current and future
requirements.
n Scalable
n Modular design
n IP54 rating
n Variable connecting technology
n All-round 25 mm pitch pattern without
switch cabinet appearance
n Load-bearing capacity of up to 1000 kg
n 1 U taken up by RMS
n Demountable
n Cabinet dimensions for UNIQLE solutions:
50 U, front and rear, height: 2240 mm
inc. rollers and 54 U, front and rear,
height: 2440 mm inc. rollers
n Width: 800 mm
n Depth: 1200 mm
Type
UNIQLE, 4 – 21 kW usable cooling capacity with RMS and regulator
800 x 2400 x 1200 mm, 35 U horizontal/15 U vertical, black RAL 9005 – fine structure
UNIQLE, 4 – 21 kW usable cooling capacity with RMS and regulator
800 x 2440 x 1200 mm, 39 U horizontal/15 U vertical, black RAL 9005 – fine structure
UNIQLE, 4 bis 21 kW usable cooling capacity with RMS and regulator
n Weight with cooling unit: approx. 245 kg
lower section 800 x 600 x 1200 mm, black RAL 9005 – fine structure
n Weight without cooling unit:
optional
approx. 165 kg
Black RAL 9005
58
order no.
6420220
6420240
6420520
UNIQLE pipe set (VE/2 pipes) 2 m long
6420260
UNIQLE RMS emergency control
6420280
UNIQLE condensation pump
6420300
UNIQLE trays 2 U
6420360
UNIQLE trays 3 U
6420340
UNIQLE automatic door opening system, UNIQLE standard
6420500
The 5 Elements
n
n
n
n
n
SP54 Rack
Cooling System
Rack Control
Power Management
Partnership Management
Please note: Pipe work and a cold water generator are to be
provided by the customer. Air-intake temperature is regulated
by RMS with integrated control. operation and configuration
via SNMP or http.
n Full integration as a compact unit
n From 4 to 21 kW usable cooling capacity
n 100 % circulating air operation
n Thermally independent of the ambient air
n Parts carrying cooling water in separate housing
With UNIQLE, SCHÄFER is systematically implementing the principle of a
cooling system integrated in the server rack. The decision for integration
is a logical step.
Argument 1: Energy efficiency
n Low pressure loss, pump rating correspondingly lower
n Long fan lifetimes as fans are not mounted in heated sections
Argument 2: Space efficiency
Server space is not unlimited! And through the trend to higher and
higher computer performance accompanied by a greater packing density, server racks must guarantee a maximum of space efficiency.
This enables the maximum computer density per m² of floor space to
be achieved.
Comparison of floor space
n UNIQLE (integrated cooling system),
floor area in mm (W x H x D): 800 x 2240 x1200
n Server rack of 800 mm width with side cooling solution (300 mm),
floor space in mm (W x H x D): 1100 x 2200 x 1200
Floor space needed for 100 U
n UNIQLE
1.92 m²
n Server rack
3.96 m²
Cooling Unit Features
1 cooling unit (self-supporting, insulated housing) installed in lower
section of the UNIQLE unit, consisting of:
n 1 high-capacity heat exchanger
n 1 electrically actuated 3-way valve
n 2 fans (electronically controlled)
n 1 fuse box
Technical features
n Protective housing for heat exchanger
n Maintenance during operation
n Automatic circuit breaker operated from front
Cooling Unit technical data
Operating voltage
Power consumption
Input current
Spread chilled water
Max. air capacity
Water throughput rate
Air supply temperature to server
Dissipated heat
230 volts
1,04 kW
6A
12/18°
3500 m²/h
2,9 m3/h
21° C – 25° C
approx. 700 Watt (at 21 KW refrigeration
capacity/20° C ambient temperature)
approx. 300 Watt (at 7 KW refrigeration
capacity/23° C ambient temperature)
Water connection for heat exchanger 3/4“ external thread (from below)
Connection for condensate tray
5/8“ hose connection
Pressure loss (water-side)
1 bar max. (inc. 3-way valve)
Operating pressure heat exchanger 10 bar
Coolant
water (optional: glycol mixture)
59
V.
UNIQLE
Data centre and
Water-cooled server cabinet solutions
Water-cooled rack with heat exchanger
below the server
2200 mm
(46 U)
1800 mm
(37 U)
600 mm
The UNIQLE modular, water-cooled highdensity Rack solution, gives you the perfect
operating climate for your high-performance computers.
The heat exchanger at the bottom of the
rack is supplied with cold water and provides up to 21 kilowatts of usable cooling
capacity. The cooling-on-demand principle
will supply the servers with precisely the
cooling capacity needed to cover the
server’s thermal requirements by means of
air circulation. Compared to static cooling
systems, this leads to significant energy
savings.
Black RAL 9005
60
600 mm
The UNIQLE system using 37 U to 58 U can
be assembles on less than one square meter
of space, depending on what is available.
This is possible due to the separation of the
air-water heat exchanger and the SCHÄFER
server cabinets (available in heights of 1800
to 2200 mm) into two units.
This way, UNIQLE combines high userfriendly availability with extreme energy
efficiency.
l
tiona
Addi =
12 U
58 U
Article no. for lower section, see page 58
Benefits at a glance
n Effective cooling allows maximum
computer density
n Usable cooling capacity of up to
21 kilowatts
n Energy efficient due to reduced volume of
equipment to be cooled
n High availability
n Integrated rack management system for
permanent monitoring
n Increased fan service life, due to installation
outside hot zones
n Load bearing capacity of up to 1,000 kilos
n IP54 rating
n Air-water heat exchanger and server
cabinet as separate units › enables
quicker and easier replacement of
standard server cabinet (modular design)
n Low space requirement: footprint
800 x 1200 mm (space efficient)
61