IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 381 An Instantaneous Reactive Volt–Ampere Compensator and Harmonic Suppressor System Kishore Chatterjee, B. G. Fernandes, and Gopal K. Dubey, Senior Member, IEEE Abstract—A novel control method for a reactive volt–ampere compensator and harmonic suppressor system is proposed. It operates without sensing the reactive volt–ampere demand and nonlinearities present in the load. The compensation process is instantaneous, which is achieved without employing any complicated and involved control logic. The compensator is operated in cycle-by-cycle reference-current-controlled mode to achieve the instantaneous compensating feature. A mathematical model of the scheme is developed. Detailed analysis and simulation results are presented. A laboratory prototype of the compensator is developed to validate the results. Index Terms—Active power filter, instantaneous compensation, load compensation, power factor correction, SCSVC, SVC. I. INTRODUCTION O VER THE YEARS, there has been a continuous proliferation of nonlinear type of loads due to the intensive use of power electronic control in all branches of industry as well as by the general consumers of electric energy. As a result, the utility supplying these loads has to provide large reactive volt amperes. Also, it gets polluted by the harmonics generated by the load. The punitive tariffs levied by utilities against excessive vars and the threat of stricter harmonic standards have led to extensive research in the field of load compensation. The basic requirements of the compensation process involve precise and continuous reactive volt–ampere control with fast response time, reduced inrush currents, avoidance of resonances created by peripheral low-frequency current sources, and the on-line elimination of the effect of the load harmonics. To satisfy the above criteria, the traditional methods of compensation consisting of switched capacitor or fixed capacitor and phase-controlled reactor coupled with passive filters have been increasingly replaced by new approaches utilizing the concept of synchronous link converters [1]. This new class of compensators, which has generated tremendous interest among the researchers, is known by several terminologies such as var generators [2], advanced static var generators [3], synchronous solid-state var compensators [4], pulsewidth modulation (PWM) inverter var compensators [5], etc. The Manuscript received November 7, 1996; revised August 25, 1997. Recommended by Associate Editor, P. Enjeti. K. Chatterjee and B. G. Fernandes are with the Department of Electrical Engineering, Indian Institute of Technology, Bombay, India. G. K. Dubey is with the Department of Electrical Engineering, Indian Institute of Technology, Kanpur 208016, India (e-mail: gdubey@iitk.ernet.in). Publisher Item Identifier S 0885-8993(99)01839-6. authors here will call this class of var compensators as selfcommutated static var compensators (SCSVC). When SCSVC is utilized for harmonic compensation, it is known as an active power filter [6]–[10] or power line conditioner [21]. Several topologies of SCSVC and active power filters are reported in the literature, but most of them have noninstantaneous transient response [3]–[14]. The schemes based on indirect current control technique have a poor transient response [4], [5], [13]. Schemes utilizing current control principle either use: 1) a reactive volt–ampere calculator to set the compensator current reference or 2) error between the dc-link voltage reference and the sensed dc-link capacitor voltage to set the amplitude of the source current reference. In type 1), the presence of the reactive volt–ampere calculator generates a delay in the compensation process. In type 2), a low-pass filter is required to eliminate ripple from the sensed dc-link voltage. Inclusion of this filter introduces finite delay in the control structure. This coupled with the inertia presented by the dc-link capacitor while absorbing or releasing energy introduces a cumulative delay of at least two–three cycles in the dc-link capacitor voltage response. As a result, the amplitude of the source current reference has a low-frequency distortion and a dc component as long as the transient persists. Hence, the current drawn from the source during transients is not in phase with the utility voltage and not free from low-order harmonics. Other schemes having instantaneous compensation feature employ complicated and an involved control strategy [15], [16]. But these schemes can only be applied for three-phase case. The present paper proposes a new technique of compensation of var and load harmonics for low- and medium-power applications using an insulated gate bipolar transistor (IGBT) as the switching device. The novel features of the present technique are as follows. 1) The compensation process is instantaneous. 2) The control logic and the associated hardware are simple, thereby enhancing the system reliability. 3) The compensation is achieved without sensing either the load reactive volt–ampere demand or the load harmonics. case 4) Unlike [15] and [16], it can be used for the as well. The scheme is developed both for single- and three-phase systems, and the performance is found to be satisfactory. A mathematical model of the proposed compensation process is developed and analyzed. A detailed simulation program of the scheme is developed to predict its performance for 0885–8993/99$10.00 1999 IEEE Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 382 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 or (3) where From Fig. 1, amplitude of the inphase component of the load current; amplitude of the quadrature component of the load current. , therefore (a) (4) where (4), if is the amplitude of the current reference. Now, in is made equal to , is obtained as (5) (b) Fig. 1. (a) 1 0 and (b) 3 0 compensator. different operating conditions. To demonstrate the viability of the scheme, a laboratory prototype is developed, and experimental results are presented. II. OPERATING PRINCIPLE The power circuit configurations for the single- and threephase compensators are shown in Fig. 1. It is operated in a controlled current boost-type converter mode. The current is made to follow a sinusoidal drawn from the utility within a fixed hysteresis band. The reference current width of the hysteresis window determines source current profile, its harmonic spectrum, and switching frequency of the devices. The dc-link capacitor voltage is kept constant throughout the operating range of the compensator. In the and will increase case of single phase, turning on , whereas turning on and will decrease it [17]. For the three-phase case, three current references inphase with the respective phase to neutral voltages are taken, and each phase of the compensator is controlled independently [18]. To increase the current of a particular phase, the lower switch of the compensator associated with that particular phase, i.e., or is turned on while to decrease the current the upper or of the respective compensator phase switch, i.e., is turned on. A. Estimation of the Reference Current The technique to determine the reference current is explained for the single-phase compensator. The same approach is applicable for the three-phase case. be given by Let the utility voltage (1) Consider a linear load drawing a current utility voltage by an angle . Therefore , which lags the (2) From the above development, it can be inferred that if the source current is made to follow a current reference which is equal to the inphase component of load current and inphase with the utility voltage, the compensator current is equal and opposite to that of the quadrature component of the load current. As in the present scheme, the reactive volt–ampere requirement of the load is not sensed, the magnitude of the inphase component of the load current is to be determined indirectly. Since the average power consumed by the compensator is zero, the average dc-link capacitor voltage remains constant. However, there will be losses taking place in the compensator which will be replenished at the expense of the stored energy of the capacitor. This results in reduction of the capacitor voltage. To maintain the capacitor voltage, the losses of the compensator has to be supplied from the utility. This . Moreover, if is achieved by choosing a proper value of the load reactive volt–ampere increases, the compensator loss increases and the capacitor voltage drops further. A similar situation arises if there is an increase in the real component of the load current. When there is a decrease in the reactive and/or real component of the load current, the capacitor voltage rises. Thus, by monitoring the average capacitor voltage a suitable can be chosen. value of As the source current is made to follow the sinusoidal reference current within a small hysteresis band, the improvement in the harmonic spectrum of is significant. This improvement is again achieved without sensing or estimating 49 , which the load harmonics. The higher order harmonics are present in the source current, will get eliminated by the short circuit impedance of the utility. III. CONTROL STRATEGY It is well known that in the case of synchronous link converters, the dc-link capacitor voltage is superimposed case, although with second harmonic ripple [1]. In the the magnitude of sixth harmonic dc-link voltage ripple is insignificant while compensating linear loads, it increases while compensating nonlinear loads. If the dc-link voltage is sensed and compared with the reference dc voltage to control the amplitude of the reference current, then source current will also have second or sixth harmonic distortion. To Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. CHATTERJEE et al.: VOLT–AMPERE COMPENSATOR AND HARMONIC SUPPRESSOR SYSTEM Fig. 2. DC-link voltage profile for 1 383 0 and 3 0 topology. Fig. 4. Control block diagram of the current reference generator. Fig. 3. Control block diagram of the 1 0 topology. overcome this difficulty, the dc-link voltage is sensed and the harmonics present in it are filtered out. The inclusion of the filter introduces a delay in the compensation process and the transient response becomes poor. Here, a novel control strategy is proposed to make the compensation process instantaneous. Fig. 2 shows the steady-state voltage profile of the dc-link capacitor along with the source voltage waveform for both single- and three-phase topologies. It can be noted from the figure that the magnitude of the capacitor voltage remains constant at all zero-crossing instants of the source voltage. Instead of continuous monitoring, if the dc-link voltage is can be avoided sampled only at these instants, distortion in without employing the filter. The basic control block diagram of the proposed scheme for single-phase case is shown in Fig. 3. Latch-1 and Latch-2 are made transparent only at the positive going zero crossings of the source voltage. This ensures that the error information which is to be passed to the proportional–integral (PI) controller and the processed error to be passed to the reference current generator block is made available only at the positive going zero-crossing instants. This implies that the set at the beginning of a cycle reference current level is maintained constant throughout the cycle. The reference produces current generator based on the information of which is inphase with the the required reference current and based utility voltage. The comparator compares with on this error information switching pattern of the compensator is decided so that is made to follow within a hysteresis band. is maintained constant throughout Since the amplitude of a sampled cycle of the utility voltage, the source current is maintained distortion free and inphase with the utility voltage both during steady state and transient operation. Hence, the compensation process is instantaneous. The dc-link capacitor is specially designed for this purpose so that the dc-link voltage does not fall below the source current controllability limit. However, as the source current is forced to follow the reference within a hysteresis band some finite delay is still expected. The authors have found through extensive simulation studies that even in the worst case of transients this delay comes out to be less than 50 s, i.e., less than 1 of the power cycle, which is insignificant for all practical purpose. The fact that this insignificant delay does not affect the instantaneous compensating feature is corroborated in [15], where the compensator current is made to track the synthesized reference current by bang–bang control. For the three-phase case, the positive zero-going instant of any one of the phases is taken as the sampling instant. The current reference generator produces three current references and which are inphase with the respective . phase to neutral voltages and having an equal amplitude The other features of the controller are same as that of the single-phase topology. A. Current Reference Generator The internal block diagram of the current reference gener8-b EPROM is used to ator is shown in Fig. 4. A 1024 store the sinusoidal current reference. It is being addressed by a 10-b counter. The counter counts the VCO pulse output of the PLL, the frequency of which is set to 1024 times the utility frequency. The output of the EPROM which is the digitized version of the sine wave is fed to the DAC for converting it to the analog sine wave. The amplitude of the sine wave is set Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 384 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 Similarly, rms compensator current is written as (9) where rms inphase component of the compensator current; rms quadrature component of the compensator current. The rms source current is then Fig. 5. Single line diagram of the compensator connected to the utility. by the AI input of the DAC which is connected to the output latch of the PI controller of Fig. 3. As the reference is synthesized from a previously programmed EPROM and not directly derived from the utility, the presence of any distortion in the utility voltage or occasional dips in it will not have any effect on the reference and, hence, on the source current wave shape. For three-phase cases, three such units are used. The AI inputs of the three units are together connected to the output latch of the PI controller. Outputs of the three DAC’s provide the reference currents for the three phases. But , therefore (10) Power input to the compensator is given by (11) where for single-phase topology and for three-phase topology. Power loss in the resistance is given by IV. MATHEMATICAL MODEL The rate at which the dc-link capacitor voltage responds to the changes in the reference source current is analyzed here. Although the dynamic response of the dc-link voltage has no effect on the instantaneous compensating feature of the scheme, a mathematical model is required for stability analysis and, hence, for determining the parameters of the PI controller. The principle of average power balance is used to determine the approximate model of the compensator. This is valid since the magnitude of the current reference does not change within a cycle of the utility voltage. The mathematical model is derived based on the following assumptions. 1) The utility voltages are balanced and contain no harmonics. 2) Only the fundamental components of currents are considered as the harmonic components do not affect the average power balance expressions. 3) All losses of the system are lumped and represented by an equivalent resistance connected in series with the line inductor . 4) Ripple in the dc-link capacitor voltage is neglected. From Fig. 5 (6) (7) The load current is assumed to be lagging the utility voltage can be written as by an angle . The rms load current (8) (12) Average rate of change of energy associated with the inductor Since is constant for a particular operating point (13) Average rate at which energy is being absorbed by the capacitor (14) is the instantaneous dc-link voltage. Equating where average rate of change of energy associated with ac link and and is obtained for a dc link, the relation between particular operating point, which is given by (15) is applied in the inphase comIf a small perturbation about a steady-state ponent of the compensator current, , the average dc-link voltage will also operating point about its steady-state get perturbed by a small amount . Putting operating point where rms inphase component of the load current; rms quadrature component of the load current. and Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. CHATTERJEE et al.: VOLT–AMPERE COMPENSATOR AND HARMONIC SUPPRESSOR SYSTEM 385 Fig. 6. Transfer function model of the open-loop plant. in (15), the small-signal perturbed equation neglecting the higher order differential terms is obtained as Fig. 7. Comparison of output response of the mathematical model to that of the actual model for single-phase topology. (16) The steady-state equation from (15) is (17) Subtracting (17) from (16), the linear relationship between and is obtained as (18) The transfer function model of the compensator for a particular operating point is obtained from (18) as Fig. 8. Comparison of output response of the mathematical model to that of the actual model for three-phase topology. For this case, and are obtained as (19) where The block diagram of the proposed open-loop compensator is shown in Fig. 6. The sampled data model of the compensator is obtained as (20) A realistic system is chosen to simulate the performance characteristics of the proposed compensating scheme. The system specifications are as follows: 230 V; 20 A (rated max); 20 A (rated max); 500 V; 2000 F; 0.5 ; 0.25 A (the chosen operating point). For a unit step input of , the response of derived from the mathematical model and that obtained by simulating the actual system for single- and three-phase cases are shown in Figs. 7 and 8, respectively. The closeness of the two responses shows that the mathematical model developed is in close agreement with that of the actual system. The closed-loop configuration of the scheme is shown in Fig. 9. The PI controller is designed to obtain acceptable gain margin of 5 dB and phase margin of 45 , respectively. The and are found to be parameters of the PI controller 0.37 and 6.0, respectively, for single-phase topology and 0.14 and 4.5, respectively, for three-phase topology. The openloop frequency response curves of the single- and three-phase compensators along with the above mentioned PI controllers are shown in Figs. 10 and 11, respectively. V. DESIGN OF DC-LINK CAPACITOR The value of the dc-link capacitor is chosen to restrict the ripple of the dc-link voltage within a permissible limit. The ripple is proportional to the magnitude of reactive volt ampere to be compensated. Therefore, the capacitor value is decided by the maximum var to be handled. In the present scheme, as the link voltage is controlled in a discrete mode, the capacitor may have to supply the real power demand of the load for Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 386 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 Fig. 9. Transfer function model of the compensated closed-loop plant. (a) (a) (b) (b) Fig. 10. Open-loop frequency response of the single-phase compensator with a PI controller in the feedforward path. (a) Gain versus frequency plot and (b) phase versus frequency plot. one cycle of the utility voltage in the worst case of transient. Hence, the capacitor design is based on the maximum real power rating of the load. The design equation based on this principle is derived as follows. W and the Let the peak power rating of the load be V. Therefore, the maximum energy rms utility voltage be that the capacitor has to supply in the worst case of transient is given by (21) Let the minimum allowable dc-link voltage be fore . There(22) is the set dc-link voltage and , the value of the where dc-link capacitor. Equating (21) and (22), is obtained as (23) where (24) The value of is judiciously chosen so that the source current controllability is ascertained at all operating points. Fig. 11. Open-loop frequency response of the three-phase compensator with a PI controller in the feedforward path. (a) Gain versus frequency plot and (b) phase versus frequency plot. VI. SIMULATED RESULTS Simulation studies are carried out to predict the performance of the proposed SCSVC. A dedicated computer program is employed for the purpose and simulated waveforms are presented next for the cases of linear and nonlinear load compensation. In all the cases studied, the width of the hysteresis window is maintained at 0.5 A and the upper limit of the average switch frequency is found to be 5 KHz. A. Simulated Waveforms for Linear Load Compensation 1) Single-Phase Topology: In order to validate the transient KVA as well as the steady-state behavior, a load is initially connected. At 61 ms, i.e., just after the commencement of the fourth cycle, the load is abruptly changed KVA. The waveforms of the source current, to load current, dc-link voltage along with the utility voltage are shown in Fig. 12. The source current is near sinusoidal and is inphase with the utility voltage. The displacement factor and power factor of the source current are found to be 0.999 985 and 0.999 907, respectively. The harmonic spectrum of the fifth cycle of the source current is shown in Fig. 13. Although the dc-link voltage transients take some time to settle down after the disturbance, the source power factor is maintained Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. CHATTERJEE et al.: VOLT–AMPERE COMPENSATOR AND HARMONIC SUPPRESSOR SYSTEM 387 (a) (a) (b) (b) (c) Fig. 12. Simulation waveforms of the single-phase topology for an increment in the real component of the load current. (a) DC-link voltage, (b) source voltage and source current, and (c) load current. Fig. 13. Fig. 12. Harmonic spectrum of the fifth cycle of the source current of unity throughout this entire period. This implies that the compensation process is instantaneous Similar waveforms for change of load from KVA to KVA are shown in Fig. 14. Displacement factor and power factor of the source current are found to be 0.999 97 and 0.999 192, respectively. 2) Three-Phase Topology: Similar tests are carried out with the three-phase compensator. At 61 ms, i.e., just after the (c) Fig. 14. Simulation waveforms of the single-phase topology for an increment in the reactive component of the load current. (a) DC-link voltage, (b) source voltage and source current, and (c) load current. beginning of the fourth cycle of the phase-A source voltage, KVA load is abruptly changed to a KVA. The waveforms of the utility voltages, source and load currents of the three phases and the dc-link capacitor voltage are shown in Fig. 15. The source currents are near sinusoidal and inphase with the respective phase voltages. The transient period in the dc-link voltage has no effect on the phase relationship between the source currents and the utility voltages; they are always maintained inphase with each other even during the transients. Similar waveforms for a change of KVA to KVA are load from shown in Fig. 16. B. Simulated Waveforms for Nonlinear Load Compensation The nonlinear load is simulated by a phase-controlled thyristorized converter operating at a phase delay of 45 and supplying 10 A of dc current. The waveforms of the compensation process for single-phase case is shown in Fig. 17. Although the load current is quasi-square wave having a Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 388 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 (a) (a) (b) (b) (c) (c) Fig. 16. Simulation waveforms of the three-phase topology for an increment in the reactive component of the load current. (a) DC-link voltage, (b) phase-A source voltage and source current, (c) phase-A load current. (d) the source current is shown in Fig. 19. The displacement factor and power factor of the source current is found to be 0.999 98 and 0.999 84, respectively. The waveforms of the three-phase compensation process is diode bridge supplying 10 shown in Fig. 20. Here, a A of dc current is taken as the load. The displacement factor and power factor of the load current are 0.9107 and 0.8783, respectively, whereas the displacement factor and power factor of the source current are found to be 0.9999 and 0.9988, respectively. VII. EXPERIMENTAL RESULTS (e) Fig. 15. Simulation waveforms of the three-phase topology for an increment in the real component of the load current. (a) DC-link voltage, (b) phase-A source voltage and source current, (c) phase-A load current, (d) phase-B source voltage and source current, and (e) phase-B load current. displacement factor of 0.586 60 and power factor of 0.544 52, the source current is found to be near sinusoidal. The harmonic spectrum of the load current is shown in Fig. 18 and that of A scaled-down laboratory prototype is developed to validate the simulation results of single- and three-phase topologies of the proposed compensation schemes. Oscillogram records of the various waveforms of the single-phase topology are shown in Figs. 21–25. Fig. 21 shows the steady-state performance of compensator while compensating a lagging load the A. The harmonic spectrum of the current of compensated source current is shown in Fig. 22. It can be inferred that low-order harmonics are not introduced and the magnitude of the higher order harmonics are less than 1% of the fundamental. This is achieved at a fairly low switching Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. CHATTERJEE et al.: VOLT–AMPERE COMPENSATOR AND HARMONIC SUPPRESSOR SYSTEM (a) 389 (a) (b) (b) (c) (c) Fig. 17. Simulation waveforms of the single-phase topology compensating a nonlinear load. (a) DC-link voltage, (b) source voltage and source current, and (c) load current. Fig. 18. Fig. 20. Simulation waveforms of the three-phase topology compensating a nonlinear load. (a) DC-link voltage, (b) phase-A source voltage and source current, and (c) phase-A load current. Harmonic spectrum of the nonlinear load current of Fig. 17. Fig. 21. Steady-state performance: Tr1: dc-link voltage (50 V/div); Tr2: utility voltage (60 V/div); Tr3: source current (4 A/div); and Tr4: load current (5 A/div) time scale = 5 ms/div. Fig. 19. Harmonic spectrum of the compensated source current of Fig. 17. frequency of 2 KHz. Fig. 23 shows the compensation of a nonlinear load. The load in this case is ac–dc fully controlled thyristor bridge having a mismatch of firing angle delay between the positive and negative half cycles so that the current drawn contains a dc component in addition to the harmonics. Fig. 24 shows the transient behavior when an Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 390 Fig. 22. KHz. IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 Harmonic spectrum of the source current. Frequency range: 0–2.5 Fig. 23. Steady-state performance: Tr1: dc-link voltage (50 V/div); Tr2: utility voltage (60 V/cm); Tr3: source current (4 A/div); and Tr4: nonlinear load current (1 A/div) time scale = 5 ms/div. Fig. 24. Transient performance for increment in load: Tr1: dc-link voltage (15 V/div) and Tr2: source current (4 A/div). Time scale = 0:1 s/div. incremental step change of to A is introduced in the load current, while Fig. 25 shows the utility voltage and source current along with the load current during the same condition. The source current is found to be inphase with the utility voltage even during the transients thereby validating the instantaneous compensation feature of the scheme. Oscillogram records of the three-phase topology are shown in Figs. 26–32. Figs. 26 shows the steady-state behavior of Fig. 25. Transient performance for increment in load: Tr1: utility voltage (30 V/div) and source current (4 A/div) and Tr2: load current (4 A/div). Time scale = 20 ms/div. Fig. 26. Steady-state performance: Tr1: phase-A utility voltage (120 V/div); Tr2: phase-A source current (10 A/div); Tr3: phase-A load current (10 A/div); and Tr4: phase-B source current (10 A/div); time scale = 5 ms/div. Fig. 27. Steady-state performance: Tr1: phase-A utility voltage (120 V/div); Tr2: phase-A source current (10 A/div); Tr3: phase-A nonlinear load current (10 A/div); and Tr4: phase-B source current (10 A/div); time scale = 5 ms/div. the compensator compensating a linear lagging load A/phase. Fig. 27 shows the waveforms current of of nonlinear load compensation. The load considered is a diode bridge rectifier supplying a resistive load. Fig. 28 shows the spectrum of the nonlinear load current while Fig. 29 shows the spectrum of the compensated phase-A source current. Steady-state behavior for compensating an unbalanced Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. CHATTERJEE et al.: VOLT–AMPERE COMPENSATOR AND HARMONIC SUPPRESSOR SYSTEM Fig. 28. Harmonic spectrum of the phase-A nonlinear load current. Frequency range: 0–5 KHz. 391 Fig. 31. Transient performance for increment in dc voltage reference: Tr1: dc-link voltage (44 V/div) and Tr2: phase-A source current (4 A/div). Time scale = 0:1 s/div. Fig. 29. Harmonic spectrum of the phase-A source current. Frequency range: 0–5 KHz. Fig. 32. Transient performance for increment in dc voltage reference: Tr1: phase-A utility voltage (30 V/div) and phase-A source current (10 A/div) and Tr2: phase-B utility voltage (30 V/div) and phase-B source current (10 A/div). Time scale = 20 ms/div. and source current of phase B for the same condition of transience. Here again the instantaneous compensation feature is observed. VIII. CONCLUSIONS Fig. 30. Compensating an unbalanced load: Tr1: phase-A source current (10 A/div); Tr2: phase-A load current (10 A/div); Tr3: phase-B source current (10 A/div); and Tr4: phase-B load current (10 A/div). Time scale = 5 ms/div. load is shown in Fig. 30. Here, the phase-A load current is reduced to 50% to that of the phase-B and phase-C load currents. It is observed that the source currents are balanced. compensator, For studying the transient behavior of the step change in the reference dc-link voltage is introduced instead of changing the load. Fig. 31 shows the dc-link voltage and phase-A source current when an incremental step change of 220–260 V is introduced. Fig. 32 depicts the utility voltage and source current of phase-A along with the utility voltage A new reactive volt–ampere compensator and harmonic suppressor system is proposed for low- and medium-power applications. The proposed technique makes the compensation process instantaneous. This feature is achieved using simplified control technique thereby enhancing the system reliability. Mathematical model of the scheme is derived. Simulation results supported by experimental validations are presented. REFERENCES [1] V. R. Kanetkar, M. S. Dawande, and G. K. Dubey, “Recent advances in synchronous link converters,” in Power Electronics and Drives, G. K. Dubey and C. R. Kasarbada, Eds. India: IETE, 1994. [2] L. Gyugi, “Reactive power generation and control by thyristor circuits,” IEEE Trans. Ind. Applicat., vol. IA-15, pp. 521–532, Sept./Oct. 1979. [3] C. W. Edwards, K. E. Mattern, E. J. Stacey, P. R. Nannery, and J. Gubernick, “Analysis and design of a advanced static var generator employing GTO thyristors,” IEEE Trans. Power Delivery, vol. 3, pp. 1622–1627, Oct. 1988. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply. 392 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 2, MARCH 1999 [4] L. T. Moran, P. D. Ziogas, and G. Joos, “Analysis and design of a three-phase synchronous solid-state var compensator,” IEEE Trans. Ind. Applicat., vol. 25, pp. 598–608, July/Aug. 1989. [5] G. Joos, L. T. Moran, and P. D. Ziogas, “Performance analysis of a PWM inverter VAR compensator,” IEEE Trans. Power Electron., vol. 6, pp. 380–391, July 1991. [6] J. Nastran, R. Cajhen, M. Seliger, and P. Jereb, “Active power filter for nonlinear ac loads,” IEEE Trans. Power Electron., vol. 9, pp. 92–96, Jan. 1994. [7] H. Akagi, A. Nabae, and S. Atoh, “Control strategy of active power filters using multiple voltage-source PWM converters,” IEEE Trans. Ind. Applicat., vol. IA-22, pp. 460–465, May/June 1986. [8] H. Akagi, Y. Tsukamoto, and A. Nabae, “Analysis and design of an active power filter using quad-series voltage source PWM converters,” IEEE Trans. Ind. Applicat., vol. 26, pp. 93–98, Jan./Feb. 1990. [9] F. J. Peng, H. Akagi, and A. Nabae, “A study of active power filters using quad-series voltage-source PWM converters for harmonic compensation,” IEEE Trans. Power Electron., vol. 5, pp. 9–15, Jan. 1990. [10] H. L. Jou, J. C. Wu, and H. Y. Chu, “New single phase active power filter,” Proc. Inst. Elect. Eng., vol. 141, no. 3, pp. 129–134, 1994. [11] S. Deb, B. W. Sherman, and R. Hoft, “Resonant converter power line conditioner: Design and evaluation,” IEEE Trans. Ind. Applicat., vol. 29, pp. 500–509, May/June 1993. [12] J. D. Van Wyk, D. A. Marshall, and S. Boshoff, “Simulation and experimental study of a reactively loaded PWM converter as fast source of reactive power,” IEEE Trans. Ind. Applicat., vol. IA-22, pp. 1082–1090, Nov./Dec. 1986. [13] L. T. Moran, P. D. Ziogas, and G. Joos, “Analysis and design of a novel 3 solid-state power factor compensator and harmonic suppressor system,” IEEE Trans. Ind. Applicat., vol. 25, pp. 609–619, July/Aug. 1991. [14] , “A solid-state high-performance reactive-power compensator,” IEEE Trans. Ind. Applicat., vol. 29, pp. 969–978, Sept./Oct. 1993. [15] H. Akagi, Y. Kanazawa, and A. Nabae, “Instantaneous reactive power compensators comprising switching devices without energy storage components,” IEEE Trans. Ind. Applicat., vol. IA-20, pp. 625–630, May/June 1984. [16] J. L. Willems, “A new interpretation of the Akagi-Nabae power components for nonsinusoidal three-phase situations,” IEEE Trans. Instrum. Meas., vol. 41, pp. 523–527, Aug. 1992. [17] O. Stihi and B. T. Ooi, “A single-phase controlled-current PWM rectifier,” IEEE Trans. Power Electron., vol. 3, pp. 453–459, Oct. 1988. [18] B. T. Ooi, J. C. Salmon, J. W. Dixon, and A. B. Kulkarni, “A threephase controlled-current PWM converter with leading power factor,” IEEE Trans. Ind. Applicat., vol. IA-23, pp. 78–84, Jan./Feb. 1987. 0 B. G. Fernandes was born in Mangalore, India, on May 17, 1962. He received the B.Tech. degree in 1984 from Mysore University, India, the M.Tech. degree in 1989 from the Indian Institute of Technology, Kharagpur, India, and the Ph.D. degree in 1993 from the Indian Institute of Technology, Bombay, India. He was with M/S Development Consultant Ltd. from 1984 to 1987. From 1993 to 1997, he was with the Department of Electrical Engineering, Indian Institute of Technology, Kanpur, as an Assistant Professor. Currently, he is with the Department of Electrical Engineering, Indian Institute of Technology, Bombay. His current research interests are in PMSM drives, vector-controlled drives, quasi-resonant dc-link converter topologies, modern var compensators, and active power filters. Gopal K. Dubey (SM’83) was born on November 17, 1939. He received the B.E. degree (with honors) from Jabalpur University, India, in 1963 and the M.Tech. degree in drives and controls and Ph.D. degree from the Indian Institute of Technology, Bombay, India, in 1965 and 1972, respectively. He was an Assistant Professor at the Indian Institute of Technology, Bombay, until 1977 and has been Professor at the Indian Institute of Technology, Kanpur, since 1978. He was an Honorary Visiting Research Fellow and Commonwealth Scholar at the University of Bradford, U.K., from 1974 to 1975 and a Visiting Professor at the University of British Columbia, Vancouver, Canada, from 1983 to 1984 and at the Virginia Polytechnic Institute and State University, Blacksburg, from 1984 to 1985. He was a Senior Visiting Fellow at the National University of Singapore in 1995. His fields of interest include electrical drives, power electronics, control systems, and engineering education. He has written several books including: Power Semiconductor Controlled Drives (Englewood Cliffs, NJ: Prentice-Hall, 1989), Thyristorized Power Controllers (New Delhi: Wiley Eastern, 1986), and Fundamentals of Electrical Drives (New Delhi: Narosa, 1994). He edited Power Electronics and Drives (New Delhi: Tata–McGrawHill, 1993) and has published 150 research papers. He is an Honorary Editor of the IETE Journal of Research. Dr. Dubey received the Bimal Bose Award of IETE in 1990 for excellence in power electronics. He is a Fellow of the IETE, Institution of Engineers, and Indian National Academy of Engineering. He was Chairman of the IEEE UP Subsection and then Section for five years (1989–1993). He is an Associate Editor of the IEEE TRANSACTIONS ON POWER ELECTRONICS. Kishore Chatterjee was born in Calcutta, India, on July 20, 1967. He received the B.E. and M.E. (power electronics) degrees from M.A.C.T., Bhopal, India, and Bengal Engineering College, India, in 1990 and 1992, respectively. In 1998, he received the Ph.D. degree in power electronics from the Indian Institute of Technology, Kanpur, India. From 1997 to 1998, he was a Senior Project Associate at the Indian Institute of Technology, Kanpur, where he was involved with a project on power factor correction and active power filtering, which was being sponsored by the Central Board of Irrigation and Power, India. Since December 1998, he has been an Assistant Professor in the Department of Electrical Engineering, Indian Institute of Technology, Bombay. His current research interests are modern var compensators, active power filters, utilityfriendly converter topologies, and S.R.M. drives. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 03:53 from IEEE Xplore. Restrictions apply.