1. 2. 3. 4. 5. ALL FLOOR DRAINS AND FLOOR SINKS MUST HAVE TRAP PRIMERS. PROVIDE INVERTED TEE CONNECTION FROM SINK TAILPIECE OR FLUSH VALVE TYPE TRAP PRIMER CONNECTION TO ALL FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS. AS LAST RESORT PROVIDE MECHANICAL TYPE TRAP PRIMER (PPP INC. "OREGON #1" TYPE). CONNECT TO NEAREST WATER SERVING THAT AREA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. IN JURISDICTIONS WHERE PRESSURE ACTIVATED MECHANICAL PRIMERS ARE NOT ALLOWED, USE ELECTRONIC TRAP PRIMERS. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR. PROSET "TRAP GUARD" DEVICE MAY BE USED IN LIEU OF TRAP PRIMERS WHEN ALLOWED BY LOCAL CODE AUTHORITY HAVING JURISDICTION. BEFORE USING PROSET "TRAP GUARD" CONTRACTOR MUST OBTAIN WRITTEN APPROVAL FROM LOCAL CODE AUTHORITY HAVING JURISDICTION AND PROVIDE COPIES TO ARCHITECT AND ENGINEER. A. B. C. PIPING SIZE FOR WATER MAIN DROPS AND MANIFOLD IN CHASE OR WALL TO REMAIN FULL SIZE OF DROP INDICATED. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL LINE SIZE TO EACH FIXTURE. COORDINATE ALL WASTEWATER FLOOR PENETRATIONS AND PIPING PENETRATIONS WITH STRUCTURAL PRIOR TO INSTALLATION. PIPING MAY BE OFFSET SLIGHTLY TO AVOID STRUCTURAL CONFLICTS. ROUTE VENT FROM EACH FIXTURE TO HORIZONTAL VENT HEADER IN CHASE/WALL OR TO NEAREST COMMON VTR ABOVE CEILING. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL FIXTURE VENT SIZES. VENT HEADERS IN CHASE TO BE SIZED ACCORDINGLY: 1 1/2" VENT UP TO 6 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 60 FEET (EXCEPT FOR WATER CLOSETS), 2" VENT UP TO 20 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 120 FEET, 3" VENT UP TO 84 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 212 FEET AND 4" VENT UP TO 256 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 300 FEET. BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH ARE TO BE INCREASED BY ONE PIPE SIZE. NO MORE THAN 1/3 OF THE CODE PERMITTED DEVELOPED LENGTH SHALL BE IN HORIZONTAL POSITION. EXTEND COMMON VENT UP THROUGH ROOF. ROUTE ALL VENTS TO NEAREST COMMON VENT THRU ROOF (VTR) TO MINIMIZE ROOF PENETRATIONS. VTR TO BE MINIMUM 15 FEET AWAY FROM OUTSIDE AIR INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. D. E. CONTRACTORS TO REVIEW AND COMPARE ALL DRAWINGS SO ALL WORK IN THEIR RESPECTIVE TRADE IS INCLUDED IN BID. EACH CONTRACTOR SHALL INCLUDE ALL MATERIALS AND INSTALLATION REQUIRED FOR HIS PARTICULAR TRADE AFTER COMPLETE REVIEW OF ALL CONTRACT DRAWINGS AND SPECIFICATIONS. ALL WORK SHALL COMPLY WITH THE APPLICABLE LOCAL, STATE AND FEDERAL CODES AND ORDINANCES. FOLLOW RECOMMENDED PRACTICES AS SET DOWN BY ASME, SMACNA, ASHRAE, NFPA, APPLICABLE BUILDING CODE, APPLICABLE MECHANICAL CODE, APPLICABLE PLUMBING CODE, NATIONAL ELECTRICAL CODE, AGA, ADA AND OSHA, AS THEY APPLY TO THIS PROJECT EXCEPT IN CASES WHERE LOCAL STATUTES GOVERN. THE CONTRACTOR SHALL VERIFY WITH AUTHORITY HAVING JURISDICTION THE LATEST ADOPTED LOCAL CODES, ORDINANCES AND AMENDMENTS THAT APPLY TO THIS PROJECT. PROVIDE CONDENSATE DISPOSAL POINT FOR ALL MECHANICAL EQUIPMENT TO CODE APPROVED DISPOSAL. COORDINATE WITH MECHANICAL CONTRACTOR. ABSOLUTELY NO PIPING OR DUCTWORK CAN BE ROUTED ABOVE ELECTRICAL PANELS, GEAR OR TRANSFORMERS. THE ONLY HVAC, PLUMBING, SPRINKLER OR DUCTWORK THAT CAN ENTER AN ELECTRIC ROOM ARE THOSE SPECIFICALLY SERVING THAT ROOM. THESE SERVICES CAN ONLY ENTER INTO ELECTRIC ROOM ABOVE ENTRY DOOR. F. PROVIDE VALVE TAGS FOR ALL VALVES. PROVIDE CEILING ACCESS MARKERS FOR VALVES LOCATED ABOVE CEILING OR BEHIND WALL MOUNTED PANEL. G. PLUMBING PIPING SHALL NOT BLOCK ACCESS TO EQUIPMENT, JUNCTION BOXES, DISCONNECTS, ACCESS DOORS, ETC. H. ALL VALVES ARE TO BE ACCESSIBLE AND SHALL NOT BE LOCATED MORE THAN FOUR FEET ABOVE THE CEILING. I. CONTRACTOR TO CONNECT COLD WATER, TEMPERED WATER, WASTE WATER AND VENT PIPING TO ALL FIXTURES PER MANUFACTURER'S RECOMMENDATIONS, UNLESS OTHERWISE NOTED ON DRAWINGS. J. BEFORE ANY CUTTING OR TRENCHING OPERATIONS BEGIN, VERIFY WITH OWNER'S REPRESENTATIVE, UTILITY COMPANIES AND OTHER INTERESTED PARTIES THAT ALL AVAILABLE INFORMATION HAS BEEN PROVIDED CONCERNING EXISTING UTILITY LOCATION. VERIFY LOCATIONS GIVEN. CONTACT ARCHITECT IMMEDIATELY UPON UNCOVERING UNKNOWN UTILITIES FOR FURTHER DIRECTION. INDICATE ALL UNCOVERED UTILITIES ON RECORD DRAWINGS. K. INSTALL ROOF JACK AS REQUIRED AT ALL GAS PIPING ROOF PENETRATIONS. L. FIRE SEAL AROUND ALL PIPING AT PENETRATIONS THROUGH RATED WALLS, CEILINGS AND TUNNELS PER UL LISTED MATERIAL FOR ACTUAL SEALANT BEING USED. COORDINATE WITH ARCHITECTURAL PLANS FOR RATED WALL LOCATION. M. PROVIDE ALL APPROPRIATE TOOLS, WRENCHES, KEYS, ETC. AS REQUIRED FOR ACCESS AND OPERATION OF VALVES, COVERS, ETC. N. DO NOT ROUTE PIPING UNDER EQUIPMENT LOCATED ABOVE CEILING. ROUTE PIPING AROUND EQUIPMENT TO ALLOW FOR ACCESS AROUND EQUIPMENT AND FOR FUTURE REMOVAL OF EQUIPMENT. O. P. HOT (TEMPERED) AND COLD WATER REQUIRED UNLESS NOTED OTHERWISE ON PLUMBING FIXTURE SCHEDULE. PROVIDE TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. THE CONTRACTOR IS TO VISIT THE SITE PRIOR TO BID TO FAMILIARIZE HIMSELF WITH ALL CONDITIONS AS THEY EXIST. SUBMISSION OF BID INDICATES THE CONTRACTOR'S UNDERSTANDING OF EXISTING CONDITIONS AND HIS WILLINGNESS TO WORK WITH THESE CONDITIONS. NO ADDITIONAL TIME OR MONEY WILL BE ALLOTTED DUE TO LACK OF COORDINATION WITH EXISTING CONDITIONS OR OTHER TRADES. Q. PLUMBING CONTRACTOR IS RESPONSIBLE FOR PROVIDING FLUES AND COMBUSTION AIR PIPING TO EXTERIOR FOR GAS FIRED WATER HEATERS AND BOILERS. PROVIDE HEAT TRAPS ON INCOMING AND DISCHARGE LINES FROM WATER HEATERS WHICH DO NOT HAVE THEM FACTORY INSTALLED OR ARE NOT CONNECTED TO A RECIRCULATING SYSTEM. GAS PIPING: 1. IF HORIZONTAL VENT LENGTH EXCEEDS 20 FEET, INCREASE VENT SIZE TO TWO INCHES. COMMERCIAL KITCHEN SINKS GET HOT WATER, REMAINDER TO BE PROVIDED WITH TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. SHOWER VALVES TO BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION BALANCED-PRESSURE/THERMOSTATIC CONFORMING TO ASSE 1016. 2. 3. G:\2015\THRALL ISD - HIGH SCHOOL.084\84P1.01.dwg, 1/27/2016 3:29:37 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 Q. SUPPORT ALL GAS PIPING ON ROOF WITH PIPE STANDS/ROLLER EQUAL TO MIRO INDUSTRIES MODEL 4-RAH-PC OR PORTABLE PIPE HANGERS, INC. (PPH), TYPE PP10 WITH ROLLER. FOR PIPING 2-1/2", UP TO AND INCLUDING 8" USE MIRO INDUSTRIES MODEL 6-RAH-PC OR PORTABLE PIPE HANGER, INC. (PPH) TYPE PS-1-2. ALL PIPE STANDS TO SIT ON WALK BOARD (COORDINATE TYPE AND METHODS OF SUPPORT WITH ROOFING CONTRACTOR). WALK BOARD TO BE A MINIMUM OF 3" LARGER ON EACH SIDE THAN SUPPORT. PROVIDE MINIMUM PIPE HEIGHT ABOVE ROOF DECK AS REQUIRED BY JURISDICTION HAVING AUTHORITY (AT LEAST 6"). PROVIDE SUPPORTS FOR PIPING UNDER 2" AT SIX FEET ON CENTER. PROVIDE SUPPORTS FOR PIPING 2" AND OVER AT EIGHT FEET ON CENTER. ROUTE PIPING DOWN MINIMUM TWELVE INCHES (12") UNDERGROUND AND STUB UP FOR NEW GAS METER TO BE INSTALLED BY LOCAL GAS COMPANY. VERIFY GAS SERVICE LOCATION WITH CIVIL DRAWINGS AND LOCAL GAS COMPANY BEFORE INSTALLATION OF GAS PIPING. PAINT GAS RISER ON BUILDING TO MATCH BUILDING EXTERIOR. PIPING UNDERGROUND TO BE WRAPPED FOR PROTECTION. PROTECT ROOF DURING INSTALLATION. TEST PIPING USING COMPRESSED AIR AT 60 PSI. SOAP ALL JOINTS. RUN EQUIPMENT INLET LINE SIZE FROM REGULATOR TO EQUIPMENT. PAINT ALL THE EXPOSED GAS PIPING. INSTALL COMPRESSED AIR MAIN AS SHOWN ON PLANS. PIPING TO BE SCHEDULE 40 BLACK STEEL PIPE WITH CAPPED TEES AT EACH JOINT FOR FUTURE CONNECTION OF COMPRESSED AIR LINES. CAPPED TEE TO FACE UP FOR CONNECTION OFF TOP OF MAIN. MAKE DROPS SHOWN ON PLANS. NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9. REFERENCE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. ALL WALL HUNG FIXTURES TO BE INSTALLED WITH WALL CARRIERS, VERIFY CONFIGURATION TYPE. PROVIDE VANDAL RESISTANT SCREWS AT ALL FIXTURES. INSTALL STAINLESS STEEL CAPS AT ALL UNUSED LAVATORY FAUCET HOLES. NO OFFSET FLANGES WILL BE ALLOWED FOR WATER CLOSET INSTALLATIONS. GROUT FOR LEVELING WATER CLOSETS SHALL NOT EXTEND UP ON SIDE OF WATER CLOSET BASES. TAKE GROUT BACK TO MINIMUM 1/8" UNDER BASE AND CAULK FOR FINAL FINISH. VERIFY CAULK COLOR AND TYPE WITH ARCHITECT. REFERENCE ARCHITECTURAL CONTRACT DOCUMENTS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES. CONTACT ARCHITECT FOR ADDITIONAL INFORMATION AS REQUIRED. PROVIDE INVERTED TEE CONNECTION FROM SINK TAILPIECE OR FLUSH VALVE TYPE TRAP PRIMER CONNECTION TO ALL FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS. AS LAST RESORT PROVIDE MECHANICAL TYPE TRAP PRIMER (PPP INC. "OREGON #1" TYPE). CONNECT TO NEAREST WATER SERVING THAT AREA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL PLUMBING FIXTURES TO BE "LEAD FREE" AB1953 COMPLIANT (.25% OR LESS AVERAGE LEAD CONTENT). PROVIDE DOCUMENTATION IN SUBMITTALS THAT THIS REQUIREMENT IS MET FOR EACH APPLICABLE FIXTURE. WC WATER CLOSET: AMERICAN STANDARD FLOWISE MODEL 2234.001, FLOOR MOUNTED, VITREOUS CHINA, 1 1/2" TOP SPUD, 15" HIGH ELONGATED BOWL. EXPOSED FLUSH VALVE: SLOAN ROYAL #111 WITH EBV-550-A SFSM, SIDE MOUNT BATTERY PACK AUTO FLUSH, 1.28 GALLON FLUSH. SEAT: CHURCH MODEL 295CT, STA-TITE FASTENER, OPEN FRONT LESS COVER (WHITE). WCAH WATER CLOSET (ADULT ADA): AMERICAN STANDARD FLOWISE MODEL 3042.001, FLOOR MOUNTED, VITREOUS CHINA, 1-1/2" TOP SPUD, 17-1/4" HIGH ELONGATED BOWL. EXPOSED FLUSH VALVE: SLOAN ROYAL #111 WITH EBV-550-A SFSM, SIDE MOUNT BATTERY PACK AUTO FLUSH, 1.28 GALLON FLUSH. SEAT: CHURCH MODEL 295CT, STA-TITE FASTENER, OPEN FRONT LESS COVER (WHITE). UR URINAL: SLOAN #SU-1009-A, VITREOUS CHINA, WASH DOWN ACTION 3/4" TOP SPUD. EXPOSED FLUSH VALVE: SLOAN ROYAL #186 WITH EBV-550-A SFSM, SIDE MOUNT BATTERY PACK AUTO FLUSH, 0.125 GALLON FLUSH. REFERENCE ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT. URH URINAL: SLOAN #SU-1009-A, VITREOUS CHINA, WASH DOWN ACTION 3/4" TOP SPUD. EXPOSED FLUSH VALVE: SLOAN ROYAL #186 WITH EBV-550-A SFSM, SIDE MOUNT BATTERY PACK AUTO FLUSH, 0.125 GALLON FLUSH. REFERENCE ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT. LH LAVATORY (ADA): AMERICAN STANDARD 0356.015, 20" x 18" VITREOUS CHINA, WALL HUNG, 8" FAUCET CENTERS AND GRID STRAINER. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P e480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 psi DROP. FAUCET: CHICAGO #404-HZ317CP, TEMPERED AND COLD WATER, 4" WRIST BLADE HANDLES, E-12 AERATOR. WF3 WASH FOUNTAIN (ADA): BRADLEY MODEL NO. SS - 3N/AST4-TMA, CONTINUOUS POLYESTER RESIN BOWL FOR 3 USERS, 3 SPAY HEADS WITH INDEPENDENT PUSHBUTTON AIR METERING ACTIVATION. ACRYLIC LAMINATE PEDESTAL, WALL HUNG FRAME, THERMOSTATIC MIXING VALVE (ASSE 1070). SKH SINK (ADA): ELKAY #LRAD-2219-55 (OFF-CENTER DRAIN), 18 GAUGE STAINLESS STEEL, SELF-RIM, 18" x 14" x 5.5" DEEP BOWL, THREE (3) FAUCET HOLES WITH STAINLESS STEEL BASKET STRAINER. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P e480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 psi DROP. FAUCET: ELKAY #LK-2423BH, SWING GOOSENECK, WRIST BLADE HANDLES. SKART ART ROOM DEEP SINK: JUST #SLXD-1921-A-GR, 18 GAUGE STAINLESS STEEL, SELF-RIM, 18" x 14" x 12" DEEP BOWL, THREE (3) FAUCET HOLES WITH STAINLESS STEEL BASKET STRAINER. FAUCET: ELKAY #LK2432BH, SWING GOOSENECK, WRIST BLADE HANDLES. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P e480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 psi DROP. SKART1 ART ROOM ADA SINK: JUST #SL-ADA-1921-A-GR, 18 GAUGE STAINLESS STEEL, SELF-RIM, 18" x 14" x 5.5" DEEP BOWL, THREE (3) FAUCET HOLES WITH STAINLESS STEEL BASKET STRAINER. FAUCET: ELKAY #LK2432BH, SWING GOOSENECK, WRIST BLADE HANDLES. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P e480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 psi DROP. KSH KITCHEN SINK (ADA): ELKAY #LRAD-3319 (OFF-CENTER DRAIN), 18 GAUGE STAINLESS STEEL, SELF-RIM, TWO (2) 14" x 14" x 5.5" DEEP BOWLS, FOUR (4) FAUCET HOLES WITH TWO (2) STAINLESS STEEL BASKET STRAINERS. FAUCET: ELKAY #LKD2443, SWING GOOSENECK, METAL WING HANDLES, HOSE SPRAYER. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P e480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 psi DROP. SS2 LAUNDRY ROOM FREE STANDING DEEP SINK: ELKAY #WNSF81362, 14 GAUGE STAINLESS STEEL, 1/4" RADIUS COVED CORNER CONSTRUCTION, 36" x 24" x 14" DEEP BOWL, 8" HIGH FULL LENGTH BACKSPLASH , STAINLESS STEEL TUBULAR LEGS WITH ADJUSTABLE BULLET SHAPED FEET. FAUCET: ELKAY #LK907BR07L2H, LEVER HANDLES, BUCKET HOOK, VACUUM BREAKER. US4 UTILITY SINK: 96" GRIFFIN PRODUCTS, INC. MODEL MS-496, 16 GA., TYPE 304 STAINLESS STEEL SINK AND TUBULAR BRACES, 9" BACK SPLASH, FLAT STRAINER DRAIN. FAUCETS: FOUR (4) MODEL FG-105, GOOSENECK FAUCETS WITH 4" WRIST BLADE HANDLES. PROVIDE WITH TEMPERATURE MIXING VALVE EQUAL TO POWERS HYDROGUARD T/P E480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 PSI DROP. EWCH ELECTRIC WATER COOLER (ADA): ELKAY #LVRCGRNTL8SC, HIGH EFFICIENCY, FILTERED, VANDAL RESISTANT, TWO (2) STATION, VANDAL RESISTANT PUSH BUTTON IN FRONT, VANDAL RESISTANT BUBBLERS, STAINLESS STEEL FINISH, CANE APRON. 120V-1PH. SHH SHOWER (ADA): PROVIDE WHITE FREEDOM MODEL APFQ3698BF625 ADA FIBERGLASS SHOWER STALL WITH COLLAPSIBLE WATER RETAINER, FOLDING SHOWER SEAT, CAULKLESS DRAIN, GRAB BARS, SHOWER CURTAIN AND ROD, MOEN PRESSURE BALANCE SHOWER VALVE AND HAND HELD SHOWER WITH 69" CHROME METAL COVERED HOSE AND SLIDE BAR. LEFT OR RIGHT HANDED AS REQUIRED. SH SHOWER: PROVIDE WHITE AQUARIUS MODEL G3679SH FIBERGLASS SHOWER STALL WITH COLLAPSIBLE WATER RETAINER, CAULKLESS DRAIN, SHOWER CURTAIN AND ROD, MOEN MODEL 8375EP15 PRESSURE BALANCE SHOWER VALVE AND 1.5 GPM WALL MOUNT SHOWER HEAD. LEFT OR RIGHT HANDED AS REQUIRED. HB HOSE BIBB: WOODFORD MODEL B67 SERIES, IN FLUSH MOUNTING WALL BOX, ASSE 1052 OR 1101 BACKFLOW PROTECTED AUTOMATIC DRAINING, FREEZELESS, NO SPRAYBACK. PROVIDE SHUT-OFF VALVE INSIDE BUILDING IN ACCESSIBLE LOCATION. SLOPE LINE FROM SHUT-OFF VALVE TO WALL HYDRANT TO ALLOW DRAINING OF LINE FOR FREEZE PROTECTION. HB2 HOSE BIBB: WOODFORD MODEL 26, TEE KEY OPERATOR, ASSE 1052 OR 1101 BACKFLOW PREVENTER, CLOSE COUPLED, NO SPRAYBACK. PROVIDE SHUT-OFF VALVE INSIDE BUILDING IN ACCESSIBLE LOCATION. SLOPE LINE FROM SHUT-OFF VALVE TO WALL HYDRANT TO ALLOW DRAINING OF LINE FOR FREEZE PROTECTION. HWRP1B, 2B, 1C, 1E HOT WATER RECIRCULATION PUMP: GRUNDFOS UPS15-55, 4 GPM AT TEN FEET (10') OF HEAD. 1/12 HP-120V-1PH. WH 1A WATER HEATER: A.O.SMITH MODEL DEL-20, 20 GALLON STORAGE, 3KW-208V-1PH NON-SIMULTANEOUS ELEMENTS, 15 GPH RECOVERY AT 80 DEGREES RISE. WH 1B, 2B, 3B WATER HEATER: A.O.SMITH MODEL MXiBTH199, 95%, 100 GALLON STORAGE, 199 MBH INPUT, ASSEMBLY. WH 1C WATER HEATER: A.O.SMITH MODEL DEL-30, 30 GALLON STORAGE, 6KW-208V-1PH NON-SIMULTANEOUS ELEMENTS, 30 GPH RECOVERY AT 80 DEGREES RISE. WH 1E WATER HEATER: A.O.SMITH MODEL DEN-40, 40 GALLON STORAGE, 3KW-208V-1PH NON-SIMULTANEOUS ELEMENTS, 15 GPH RECOVERY AT 80 DEGREES RISE ANT ACID NEUTRALIZATION TANK: ORION STYLE 8, POLYETHYLENE, POINT OF USE, 1.5 GALLONS, TOP INLET/OUTLET/CLEANOUT. FILL WITH LIMESTONE CHIPS FOR ACID NEUTRALIZATION. SI SOLIDS INTERCEPTOR: JAY R. SMITH #8710 WHITE DUCO COATED STEEL BODY AND REMOVABLE STAINLESS STEEL SCREEN AND CAST IRON COVER, 2" PIPE SIZE. RE: ARCHITECTURAL FOR LOCATION. ROUGH-IN SO IT WILL SET ON THE VERY BOTTOM SHELF. WB WALL BOX FOR CONNECTION TO REFRIGERATOR WATER AND/OR ICE MAKER EQUAL TO SOUIX CHIEF 696 SERIES WITH ABS OUTLET BOX, 1/4 TURN VALVE AND ASSE 1010 WATER HAMMER ARRESTOR. WM WASHING MACHINE SUPPLY AND DRAIN: GUY GRAY 20 GAUGE POWDER COATED BOX AND FACEPLATE, 2" DRAIN PIPE, TOP OR BOTTOM SUPPLY, 1/4 TURN BALL VALVES AND WATER HAMMER ARRESTERS. FD FLOOR DRAIN (GENERAL PURPOSE): C.I. BODY, FLASHING COLLAR, WEEPHOLES, ADJUSTABLE STAINLESS STEEL OR NICKEL BRONZE ROUND TOP (6" DIAMETER). MIFAB F1100 CS-3 SERIES. FD4 FLOOR DRAIN (SINGLE STALL SHOWER): C.I. BODY, ADJUSTABLE CLAMPING COLLAR, WEEPHOLES, ADJUSTABLE STAINLESS STEEL OR NICKEL BRONZE STRAINER (6" DIAMETER), AND STAINLESS STEEL SEDIMENT BASKET. MIFAB F1100 C 5-3 SERIES. THERMOSTATIC MIXING VALVE (ASSE 1070). FD7 FLOOR DRAIN (KITCHEN): C.I. BODY, FLASHING COLLAR, WEEPHOLES, SECURED AND ADJUSTABLE STAINLESS STEEL OR NICKEL BRONZE SQUARE TOP (6" x 6") MINIMUM WITH COPPER SEDIMENT BASKET. TOP SIZE TO MATCH TILE SIZE AS CLOSE AS POSSIBLE, VERIFY TOP SIZE. MIFAB F1100 CS-3-5 SERIES. SS SERVICE SINK: FIAT #MSB-2424, ONE-PIECE MOLDED STONE WITH #832-AA HOSE AND HOSE BRACKET #E-77-AA VINYL BUMPER GUARD, MSG-2424 STAINLESS STEEL WALL GUARD AND #830-AA FAUCET. FD8 KETTLE DRAIN: C.I. BODY, WEEPHOLES, FLASHING COLLAR, ADJUSTABLE SATIN NICKEL BRONZE STRAINER (7" DIAMETER) 4" DIAMETER FUNNEL EXTENSION. MIFAB F1100 C N7-F4 SERIES. SS1 TUBA SINK: GRIFFIN JUMBO SINK MODELJS-423, 36"T x 42"W x 33.5"D, 16 GA., TYPE 304 FS FLOOR SINK: 6" DEEP WITH ACID-RESISTING PORCELAIN ENAMEL INTERIOR, ALUMINUM INTERNAL DOME STRAINER, and STAINLESS STEEL GRATE (1/2 GRATE TYPE). MIFAB FS1720-3 SERIES. HS KITCHEN HAND SINK (ADA): ELKAY #ELVW02219, 304 STAINLESS STEEL, NSF, COMPLETE WITH WALL HANGER, INTEGRAL STAINLESS STEEL SUPPORT BRACKETS, INTEGRAL OVERFLOW. BACKSPLASH. VALVE EQUAL TO POWERS HYDROGUARD T/P E480 SERIES, .5 GPM MINIMUM FLOW, ASSE 1070, INTEGRAL CHECKS, 1.9 GPM AT 10 PSI DROP. YH YARD HYDRANT: WOODFORD MODEL Y2, AUTOMATIC DRAINING, FREEZELESS, NO SPRAYBACK,ASSE 1052 OR 1101 BACKFLOW PREVENTER. PROVIDE DRYWELL ADJACENT TO HYDRANT. INSTALL PER MANUFACTURERS INSTALLATION DETAILS/REQUIREMENTS. DBP DOMESTIC BOOSTER PUMP SYSTEM: "LITTLE GIANT INLINE CP WATER BOOSTER SYSTEM" TO INCLUDE FOUR (4) PUMPS (208V-1PH), TWO (2) SUB DRIVE DUPLEX ALTERNATORS, FOUR (4) 2.5 GALLON EXPANSION TANKS, PRESSURE SENSOR FITTINGS, ADJUSTABLE PRESSURE VALVE (NORMALLY SET AT MAINTAINING 55 PSI FROM THE FACTORY). AR AIR REEL: COXREELS "P" SERIES MODEL P-LP-130, SPRING RETURN, 300 psi MAX PRESSURE, 30 FOOT, 1/2" O.D. HOSE, 1" SOLID STEEL AXLE AND LUBRICATED BEARINGS, ONE PIECE HEAVY GAUGE 1/4" STEEL BASE AND SUPPORT POST, NITRILE SEIVEL SEALS, ADJUSTABLE GUIDE ARM, HEAVY DUTY STEEL CONSTRUCTION. INSTALL PER MANUFACTURERS INSTALLATION REQUIREMENTS. WATER PIPING: WATER PIPING TO BE COPPER PER SPECIFICATIONS WITH THE FOLLOWING EXCEPTION. PROVIDE PEX-a PIPING FOR DOMESTIC HOT AND COLD WATER PIPING THAT IS 2" AND SMALLER ONLY. DOMESTIC WATER PIPING TO BE INSULATED PER SPECIFICATIONS. PEX-a DOMESTIC COLD WATER PIPING CAN BE UNINSULATED. ALL DOMESTIC HOT WATER PIPNG ( COPPER AND PEX-a) IS TO BE INSULATED PER SPECIFICATIONS. ALL PEX-a PIPING MUST BE PROVIDED WITH PEX-a PIPE SUPPORT INSTALLED PER PIPING MANUFACTURER'S INSTALLATION INSTRUCTIONS TO MEET 25/50 SMOKE RATING AND TO ALLOW FOR HANGERS/SUPPORTS TO BE SPACED THE SAME AS COPPER PIPING. SCHEDULES, NOTES, & LEGENDS - PLUMBING P1.01 1 OF 8 G:\2015\THRALL ISD - HIGH SCHOOL.084\84P1.02.dwg, 1/27/2016 3:29:44 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 ALL VALVE LOCATIONS AND NUMBERS TO BE RECORDED ON RECORD DRAWINGS. DETAILS - PLUMBING P1.02 2 OF 8 1 DO NOT ROUTE ANY PIPING ABOVE THIS AREA. 2 CONNECT TO WASTEWATER (WW) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. 3 RE: DOUBLE CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 4 RE: EXTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 5 RE: INTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 6 RE: TYPICAL CONDENSATE STUB DETAIL ON PLUMBING DETAIL SHEET(S). 401 VEST 452 FEC VEST 455 STAGE CONTROL & STORAGE 212 456 LRC OFFICE 208 GYMNASIUM 400 COMMONS 209 STAGE 457 LEARNING RESOURCE CENTER 207 REFER TO X1.01 FOR STAGE THEATRICAL EQUIPMENT LAYOUT CONCESSION 458 CM OFFICE 204 ENGLISH CLASSROOM 201 VEST 459 ENGLISH CLASSROOM LEARNING RESOURCE ANNEX 202 CONTENT MASTERY 206 FEC 203 CUST TABLE STORAGE 461 460 IDF 205 W/D VEST SHOWERS 420 434 ELECTRICAL PANEL 432 STORAGE LAUNDRY & CUST FEC 433 RR 421 RR SHOWERS 423 431 CORRIDOR 424 200 BOOK ROOM COACH'S LOCKER RR 428 GIRLS JV LOCKERS WALL OF HONOR G:\2015\THRALL ISD - HIGH SCHOOL.084\84P2.01.dwg, 1/27/2016 3:29:52 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 VEST STORAGE 463 462 427 GIRLS VARSITY LOCKERS 422 RR RR 115 114 430 CORRIDOR 119 CLASSROOM 118 VEST 425 COACH'S OFFICE 426 VEST TEACHER'S WORKROOM & BREAK ROOM 429 CLASSROOM CLASSROOM 116 117 113 CORRIDOR SUPPLY 100 112 FEC FEC TEST STORAGE SECURE VESTIBULE CLASSROOM 101 CLASSROOM CLASSROOM 102 103 CLASSROOM RECEPTION 106 CONFERENCE 111 110 105 104 HALL 107 PRINCIPAL 109 COUNSELOR 108 FLOOR PLAN - AREA A - PLUMBING - WASTEWATER P2.01 3 OF 8 1. 2. 3. 4. HOT (TEMPERED) AND COLD WATER REQUIRED UNLESS NOTED OTHERWISE ON PLUMBING FIXTURE SCHEDULE. PROVIDE TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. IF HORIZONTAL VENT LENGTH EXCEEDS 20 FEET, INCREASE VENT SIZE TO TWO INCHES. COMMERCIAL KITCHEN SINKS GET HOT WATER, REMAINDER TO BE PROVIDED WITH TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. SHOWER VALVES TO BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION BALANCED-PRESSURE/THERMOSTATIC CONFORMING TO ASSE 1016. 5. ALL FLOOR DRAINS AND FLOOR SINKS MUST HAVE TRAP PRIMERS. PROVIDE INVERTED TEE CONNECTION FROM SINK TAILPIECE OR FLUSH VALVE TYPE TRAP PRIMER CONNECTION TO ALL FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS. AS LAST RESORT PROVIDE MECHANICAL TYPE TRAP PRIMER (PPP INC. "OREGON #1" TYPE). CONNECT TO NEAREST WATER SERVING THAT AREA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. IN JURISDICTIONS WHERE PRESSURE ACTIVATED MECHANICAL PRIMERS ARE NOT ALLOWED, USE ELECTRONIC TRAP PRIMERS. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR. PROSET "TRAP GUARD" DEVICE MAY BE USED IN LIEU OF TRAP PRIMERS WHEN ALLOWED BY LOCAL CODE AUTHORITY HAVING JURISDICTION. BEFORE USING PROSET "TRAP GUARD" CONTRACTOR MUST OBTAIN WRITTEN APPROVAL FROM LOCAL CODE AUTHORITY HAVING JURISDICTION AND PROVIDE COPIES TO ARCHITECT AND ENGINEER. MANUFACTURERS: ISIMET UTILITY CONTROLLER AND E-SERIES ENCLOSURE - (210) 654-8015 or LAB SAFETY SYSTEMS UTILITY CONTROLLERS - (512-845-3528) 1 DO NOT ROUTE ANY PIPING ABOVE THIS AREA. 1. 2 CONNECT TO WASTEWATER (WW) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. 3 RE: DOUBLE CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 4 RE: EXTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 5 RE: INTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 6 RE: TYPICAL CONDENSATE STUB DETAIL ON PLUMBING DETAIL SHEET(S). 7 TWO WAY SINGLE RISER CLEANOUT TO ACT AS SAMPLING PORT. 8 CONNECT TO STORM SEWER STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. PIPING SIZE FOR WATER MAIN DROPS AND MANIFOLD IN CHASE OR WALL TO REMAIN FULL SIZE OF DROP INDICATED. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL LINE SIZE TO EACH FIXTURE. COORDINATE ALL WASTEWATER FLOOR PENETRATIONS AND PIPING PENETRATIONS WITH STRUCTURAL PRIOR TO INSTALLATION. PIPING MAY BE OFFSET SLIGHTLY TO AVOID STRUCTURAL CONFLICTS. ROUTE VENT FROM EACH FIXTURE TO HORIZONTAL VENT HEADER IN CHASE/WALL OR TO NEAREST COMMON VTR ABOVE CEILING. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL FIXTURE VENT SIZES. VENT HEADERS IN CHASE TO BE SIZED ACCORDINGLY: 1 1/2" VENT UP TO 6 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 60 FEET (EXCEPT FOR WATER CLOSETS), 2" VENT UP TO 20 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 120 FEET, 3" VENT UP TO 84 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 212 FEET AND 4" VENT UP TO 256 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 300 FEET. BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH ARE TO BE INCREASED BY ONE PIPE SIZE. NO MORE THAN 1/3 OF THE CODE PERMITTED DEVELOPED LENGTH SHALL BE IN HORIZONTAL POSITION. EXTEND COMMON VENT UP THROUGH ROOF. ROUTE ALL VENTS TO NEAREST COMMON VENT THRU ROOF (VTR) TO MINIMIZE ROOF PENETRATIONS. VTR TO BE MINIMUM 15 FEET AWAY FROM OUTSIDE AIR INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. 2. ELECTRICAL CONTRACTOR: PROVIDE A UTILITY CONTROLLER (1000 SERIES 12X9) AND E-SERIES (E3112-EX) CONTACTOR ENCLOSURE FOR EMERGENCY SHUT-OFF OF POWER (RECEPTACLES), COLD WATER, TEMPERED WATER AND GAS AS REQUIRED (VERIFY EXACT UTILITIES REQUIRED IN EACH INDIVIDUAL ROOM WITH PLUMBING CONTRACTOR). PROVIDE INDIVIDUAL CONTROL SWITCH FOR CW/HW/GAS/RECEPTACLES. EXHAUST FANS FOR HOODS TO BE CONTROLLED FROM UTILITY CONTROLLER WITH KEY SWITCH TO ENABLE FAN SWITCH ON HOOD. CONTACTOR ENCLOSURES TO BE MOUNTED ABOVE CEILING. ELECTRICAL CONTRACTOR TO FURNISH AND INSTALL UTILITY CONTROLLER AND E-SERIES CONTACTOR ENCLOSURE AND PROVIDE ALL 120 VOLT WIRING AND 24V WIRING BETWEEN CONTROLLER, CONTACTOR ENCLOSURE AND EQUIPMENT. PROVIDE CONTACTOR ENCLOSURES FOR (12) TWELVE CIRCUITS. ELECTRICAL CONTRACTOR TO ALSO PROVIDE 24 VOLT CONTROL WIRING BETWEEN UTILITY CONTROLLER AND S-SERIES SOLENOID ENCLOSURE. INNER CONNECT WITH FACP TO SHUT DOWN SERVICES. COORDINATE WITH FIRE ALARM CONTRACTOR. PLUMBING CONTRACTOR: PROVIDE PRE-ASSEMBLED S-SERIES (S-3113-24VAC-X-K-F-R-A-U) SOLENOID ENCLOSURE WITH ALL CONTACTS RESET SOLENOID AND INTERFACE RELAYS FOR EACH SCIENCE ROOM FOR EMERGENCY SHUT-OFF OF COLD WATER, TEMPERED WATER AND GAS. EACH SOLENOID TO BE ASSEMBLED WITH THREADED BALL VALVE, UNIONS, "Y" STRAINERS, SHOCK ARRESTOR, AND CAPPED ENDS FOR FIELD INSTALLATION. ENCLOSURE SHALL BE NEMA 1, SURFACE MOUNT ABOVE CEILING. FIELD VERIFY EXACT MOUNTING ARRANGEMENT. VERIFY EXACT UTILITIES REQUIRED IN EACH INDIVIDUAL ROOM . 9 ISLAND SINK. RE: ISLAND SINK DETAIL ON DETAIL SHEET(S). 10 SOLIDS INTERCEPTOR EQUAL TO PARK MODEL STSC-150, 150 CALLUN CAPACITY, 15 GPM (REQUIRED BECAUSE DISPOSERS ARE UTILIZED). 3. ELECTRICAL AND PLUMBING CONTRACTOR TO COORDINATE ALL REQUIREMENTS TO PROVIDE A COMPLETE AND WORKABLE SYSTEM. 11 4. PROVIDE FACTORY START-UP WITH PLUMBING AND ELECTRICAL CONTRACTOR PRESENT AND SIGNED START-UP CERTIFICATE. SOLIDS INTERCEPTOR TO BE SET IN ADJACENT CABINET SPACE TO ALLOW FOR CLEAR ADA SPACE BENEATH SINK. INSTALL SO THAT TOP CAN BE REMOVED AND INTERCEPTOR CAN BE CLEANED PER MANUFACTURERS INSTRUCTIONS 5. WHEN EMERGENCY BUTTON IS DEPRESSED, POWER IS SHUT OFF TO ALL ANCILLARY DEVICES. 6. ROOM EXHAUST CONTROLLED SEPARATELY BY TIMER SWITCH ON WALL PROVIDED BY ELECTRICAL CONTRACTOR. 7. COORDINATE WITH BUILDING B.M.S. SYSTEM AS REQUIRED FOR DAILY SHUT-DOWN SIGNAL. ALL SCIENCE ROOM AND SCIENCE PREP ROOM EMERGENCY SHOWERS, SINKS AND FAUCETS ARE TO BE PROVIDED BY SCIENCE CASEWORK CONTRACTOR. PLUMBING CONTRACTOR TO PROVIDE ROUGH-IN AND CONNECTION TO SUPPLIES AND WASTE. FAUCETS TO HAVE INTEGRAL VACUUM BREAKER OR OTHER MEANS OF BACKFLOW PROTECTION. FEC W/D FEC FEC FEC FEC F ICE FEC FEC FEC FEC DW G:\2015\THRALL ISD - HIGH SCHOOL.084\84P2.02.dwg, 1/27/2016 3:30:03 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 DW FEC FLOOR PLAN - AREA B - PLUMBING - WASTEWATER P2.02 4 OF 8 B.1 B.2 B.3 1 DO NOT ROUTE ANY PIPING ABOVE THIS AREA. 2 CONNECT TO WASTEWATER (WW) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. 3 CONNECT TO COLD WATER (CW) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. 4 RE: CW BUILDING ENTRY DETAIL ON PLUMBING DETAIL SHEET(S). 5 RE: DOUBLE CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 6 RE: EXTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 7 RE: INTERIOR CLEANOUT DETAIL ON PLUMBING DETAIL SHEET(S). 8 WATER HEATER ON MEZZANINE. RE: WATER HEATER DETAIL ON PLUMBING DETAIL SHEET(S) FOR WATER HEATER PIPING. 9 RE: TYPICAL CONDENSATE STUB DETAIL ON PLUMBING DETAIL SHEET(S). 10 CONNECT TO GAS STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. PROVIDE ADAPTER AS REQUIRED TO MAKE SIZE AND/OR MATERIAL TRANSITION. PROVIDE SHUTOFF VALVE, PRESSURE REGULATOR AND TEST CONNECTION IN RISER. REFERENCE GAS RISER DETAIL ON DETAIL SHEETS. PAINT RISER TO MATCH BUILDING. 11 LOW PRESSURE GAS ABOVE CEILING OR EXPOSED IN SHOP. 12 SOLENOID VALVE TO BE OPERATED BY EMERGENCY SHUT-OFF BUTTON IN ROOM. VERIFY EXACT LOCATION OF BUTTON WITH OWNER PRIOR TO ROUGH-IN. 13 COMPRESSED AIR MAIN TO CONNECT TO OWNER PROVIDED AIR COMPRESSOR. 14 3/4" COMPRESSED AIR DOWN ON WALL TO WALL MOUNTED AIR REEL. COORDINATE EXACT HEIGHT AND LOCATION WITH OWNER PRIOR TO ROUGH-IN. 15 3/4" COMPRESSED AIR TO CONNECT TO AIR REEL MOUNTED TO STRUCTURE. COORDINATE EXACT HEIGHT AND LOCATION WITH OWNER PRIOR TO ROUGH-IN. 16 LOW PRESSURE GAS DOWN TO SERVE B.5 B.4 B.A B.A AR WALL B.B B.B B.C B.C GAS DEMAND DEMAND = 780 MBH LENGTH = 200 FEET FEC B.D F F F B.D B.E B.E FEC B.F G:\2015\THRALL ISD - HIGH SCHOOL.084\84P2.03.dwg, 1/27/2016 3:30:13 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 W/D B.F FEC RG RG RG RG B.G B.G B.H B.H B.1 B.2 B.3 B.4 B.5 FLOOR PLAN - AREA C - PLUMBING P2.03 5 OF 8 WATER PIPING: WATER PIPING TO BE COPPER PER SPECIFICATIONS WITH THE FOLLOWING EXCEPTION. PROVIDE PEX-a PIPING FOR DOMESTIC HOT AND COLD WATER PIPING THAT IS 2" AND SMALLER ONLY. DOMESTIC WATER PIPING TO BE INSULATED PER SPECIFICATIONS. PEX-a DOMESTIC COLD WATER PIPING CAN BE UNINSULATED. ALL DOMESTIC HOT WATER PIPNG ( COPPER AND PEX-a) IS TO BE INSULATED PER SPECIFICATIONS. ALL PEX-a PIPING MUST BE PROVIDED WITH PEX-a PIPE SUPPORT INSTALLED PER PIPING MANUFACTURER'S INSTALLATION INSTRUCTIONS TO MEET 25/50 SMOKE RATING AND TO ALLOW FOR HANGERS/SUPPORTS TO BE SPACED THE SAME AS COPPER PIPING. 1 DO NOT ROUTE ANY PIPING ABOVE THIS AREA. 2 ROUTE GAS TIGHT TO WALL IN GYM. 3 ROUTE LOW PRESSURE GAS LOW ON WALL. 4 RE: WATER HEATER DETAIL ON PLUMBING DETAIL SHEET(S) FOR WATER HEATER AND HOT WATER RECIRCULATION PUMP PIPING. 5 INSURE ADEQUATE SPACE (48" MIN.) IS LEFT FOR LADDER ACCESS TO MEZZANINE. 6 CONNECT TO GAS STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION. 7 PROVIDE SHUT-OFF VALVE, GAS REGULATOR AND TEST CONNECTION IN GAS RISER PER GAS RISER DETAIL ON DETAIL SHEET(S). 401 VEST 452 FEC VEST 455 STAGE CONTROL & STORAGE 212 456 LRC OFFICE 208 GYMNASIUM 400 COMMONS 209 STAGE 457 LEARNING RESOURCE CENTER 207 REFER TO X1.01 FOR STAGE THEATRICAL EQUIPMENT LAYOUT CONCESSION 458 CM OFFICE 204 ENGLISH CLASSROOM 201 VEST 459 ENGLISH CLASSROOM LEARNING RESOURCE ANNEX 202 CONTENT MASTERY 206 FEC 203 CUST TABLE STORAGE 461 460 IDF 205 W/D VEST SHOWERS 420 434 ELECTRICAL PANEL 432 STORAGE LAUNDRY & CUST FEC 433 RR 421 RR SHOWERS 423 431 CORRIDOR 424 200 BOOK ROOM COACH'S LOCKER RR 428 GIRLS JV LOCKERS WALL OF HONOR G:\2015\THRALL ISD - HIGH SCHOOL.084\84P3.01.dwg, 1/27/2016 3:30:27 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 VEST STORAGE 463 462 427 GIRLS VARSITY LOCKERS 422 RR RR 115 114 430 CORRIDOR 119 CLASSROOM 118 VEST 425 COACH'S OFFICE 426 VEST TEACHER'S WORKROOM & BREAK ROOM 429 CLASSROOM CLASSROOM 116 117 113 CORRIDOR SUPPLY 100 112 FEC FEC TEST STORAGE SECURE VESTIBULE CLASSROOM 101 CLASSROOM CLASSROOM 102 103 CLASSROOM RECEPTION 106 CONFERENCE 111 110 105 104 HALL 107 PRINCIPAL 109 COUNSELOR 108 FLOOR PLAN - AREA A - PLUMBING - SUPPLY P3.01 7 OF 8 1. ALL FLOOR DRAINS AND FLOOR SINKS MUST HAVE TRAP PRIMERS. PROVIDE INVERTED TEE CONNECTION FROM SINK TAILPIECE OR FLUSH VALVE TYPE TRAP PRIMER CONNECTION TO ALL FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS. AS LAST RESORT PROVIDE MECHANICAL TYPE TRAP PRIMER (PPP INC. "OREGON #1" TYPE). CONNECT TO NEAREST WATER SERVING THAT AREA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. IN JURISDICTIONS WHERE PRESSURE ACTIVATED MECHANICAL PRIMERS ARE NOT ALLOWED, USE ELECTRONIC TRAP PRIMERS. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR. PROSET "TRAP GUARD" DEVICE MAY BE USED IN LIEU OF TRAP PRIMERS WHEN ALLOWED BY LOCAL CODE AUTHORITY HAVING JURISDICTION. BEFORE USING PROSET "TRAP GUARD" CONTRACTOR MUST OBTAIN WRITTEN APPROVAL FROM LOCAL CODE AUTHORITY HAVING JURISDICTION AND PROVIDE COPIES TO ARCHITECT AND ENGINEER. 2. MANUFACTURERS: ISIMET UTILITY CONTROLLER AND E-SERIES ENCLOSURE - (210) 654-8015 or LAB SAFETY SYSTEMS UTILITY CONTROLLERS - (512-845-3528) 1 DO NOT ROUTE ANY PIPING ABOVE THIS AREA. 1. 2 CONNECT TO COLD WATER (CW) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION. 3 RE: CW BUILDING ENTRY DETAIL ON PLUMBING DETAIL SHEET(S). 4 RE: WATER HEATER DETAIL ON PLUMBING DETAIL SHEET(S) FOR WATER HEATER AND HOT WATER RECIRCULATION PUMP PIPING. 5 CONNECT TO FIRE LINE (F) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. 6 RE: FIRE LINE RISER SUPPORT DETAIL ON PLUMBING DETAIL SHEET(S). 7 SCIENCE ROOM UTILITY CONTROLLER ABOVE CEILING. REFERENCE NOTES ON THIS SHEET. 8 CW DOWN TO IN-LINE RPZ BACKFLOW PREVENTOR ON WALL IN ACCESSIBLE LOCATION. COORDINATE EXACT LOCATION WITH ARCHITECT AND EQUIPMENT. ROUTE RELIEF FROM RPZ TO FLOOR SINK FOR ICEMAKER. ELECTRICAL CONTRACTOR: PROVIDE A UTILITY CONTROLLER (1000 SERIES 12X9) AND E-SERIES (E3112-EX) CONTACTOR ENCLOSURE FOR EMERGENCY SHUT-OFF OF POWER (RECEPTACLES), COLD WATER, TEMPERED WATER AND GAS AS REQUIRED (VERIFY EXACT UTILITIES REQUIRED IN EACH INDIVIDUAL ROOM WITH PLUMBING CONTRACTOR). PROVIDE INDIVIDUAL CONTROL SWITCH FOR CW/HW/GAS/RECEPTACLES. EXHAUST FANS FOR HOODS TO BE CONTROLLED FROM UTILITY CONTROLLER WITH KEY SWITCH TO ENABLE FAN SWITCH ON HOOD. CONTACTOR ENCLOSURES TO BE MOUNTED ABOVE CEILING. ELECTRICAL CONTRACTOR TO FURNISH AND INSTALL UTILITY CONTROLLER AND E-SERIES CONTACTOR ENCLOSURE AND PROVIDE ALL 120 VOLT WIRING AND 24V WIRING BETWEEN CONTROLLER, CONTACTOR ENCLOSURE AND EQUIPMENT. PROVIDE CONTACTOR ENCLOSURES FOR (12) TWELVE CIRCUITS. ELECTRICAL CONTRACTOR TO ALSO PROVIDE 24 VOLT CONTROL WIRING BETWEEN UTILITY CONTROLLER AND S-SERIES SOLENOID ENCLOSURE. INNER CONNECT WITH FACP TO SHUT DOWN SERVICES. COORDINATE WITH FIRE ALARM CONTRACTOR. PIPING SIZE FOR WATER MAIN DROPS AND MANIFOLD IN CHASE OR WALL TO REMAIN FULL SIZE OF DROP INDICATED. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL LINE SIZE TO EACH FIXTURE. 3. COORDINATE ALL WASTEWATER FLOOR PENETRATIONS AND PIPING PENETRATIONS WITH STRUCTURAL PRIOR TO INSTALLATION. PIPING MAY BE OFFSET SLIGHTLY TO AVOID STRUCTURAL CONFLICTS. 4. 2. ROUTE VENT FROM EACH FIXTURE TO HORIZONTAL VENT HEADER IN CHASE/WALL OR TO NEAREST COMMON VTR ABOVE CEILING. REFERENCE FIXTURE CONNECTION SCHEDULE FOR INDIVIDUAL FIXTURE VENT SIZES. VENT HEADERS IN CHASE TO BE SIZED ACCORDINGLY: 1 1/2" VENT UP TO 6 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 60 FEET (EXCEPT FOR WATER CLOSETS), 2" VENT UP TO 20 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 120 FEET, 3" VENT UP TO 84 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 212 FEET AND 4" VENT UP TO 256 DRAIN FIXTURE UNITS MAXIMUM DEVELOPED LENGTH OF 300 FEET. BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH ARE TO BE INCREASED BY ONE PIPE SIZE. NO MORE THAN 1/3 OF THE CODE PERMITTED DEVELOPED LENGTH SHALL BE IN HORIZONTAL POSITION. EXTEND COMMON VENT UP THROUGH ROOF. HOT (TEMPERED) AND COLD WATER REQUIRED UNLESS NOTED OTHERWISE ON PLUMBING FIXTURE SCHEDULE. PROVIDE TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. IF HORIZONTAL VENT LENGTH EXCEEDS 20 FEET, INCREASE VENT SIZE TO TWO INCHES. COMMERCIAL KITCHEN SINKS GET HOT WATER, REMAINDER TO BE PROVIDED WITH TEMPERATURE MIXING VALVE (ASSE 1070) AT THE FIXTURE. SHOWER VALVES TO BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION BALANCED-PRESSURE/THERMOSTATIC CONFORMING TO ASSE 1016. 5. ROUTE ALL VENTS TO NEAREST COMMON VENT THRU ROOF (VTR) TO MINIMIZE ROOF PENETRATIONS. VTR TO BE MINIMUM 15 FEET AWAY FROM OUTSIDE AIR INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. PLUMBING CONTRACTOR: PROVIDE PRE-ASSEMBLED S-SERIES (S-3113-24VAC-X-K-F-R-A-U) SOLENOID ENCLOSURE WITH ALL CONTACTS RESET SOLENOID AND INTERFACE RELAYS FOR EACH SCIENCE ROOM FOR EMERGENCY SHUT-OFF OF COLD WATER, TEMPERED WATER AND GAS. EACH SOLENOID TO BE ASSEMBLED WITH THREADED BALL VALVE, UNIONS, "Y" STRAINERS, SHOCK ARRESTOR, AND CAPPED ENDS FOR FIELD INSTALLATION. ENCLOSURE SHALL BE NEMA 1, SURFACE MOUNT ABOVE CEILING. FIELD VERIFY EXACT MOUNTING ARRANGEMENT. VERIFY EXACT UTILITIES REQUIRED IN EACH INDIVIDUAL ROOM . 9 SHUT-OFF VALVE FOR EMERGENCY SHOWER / EYEWASH. LEAVE VALVE IN OPEN POSITION. REMOVE HANDLE AND TURN OVER TO OWNER. 3. ELECTRICAL AND PLUMBING CONTRACTOR TO COORDINATE ALL REQUIREMENTS TO PROVIDE A COMPLETE AND WORKABLE SYSTEM. 10 FIRE LINE OUT TO FIRE DEPARTMENT CONNECTION (FDC). CONNECT TO FIRE LINE (F) STUB PROVIDED BY CIVIL. FIELD VERIFY EXACT LOCATION AND INVERT. 4. PROVIDE FACTORY START-UP WITH PLUMBING AND ELECTRICAL CONTRACTOR PRESENT AND SIGNED START-UP CERTIFICATE. 11 5. WHEN EMERGENCY BUTTON IS DEPRESSED, POWER IS SHUT OFF TO ALL ANCILLARY DEVICES. ALL VALVES ABOVE CEILING TO BE LOCATED AS NEAR TO LIGHT FIXTURES AS POSSIBLE. LIGHT FIXTURES ARE REMOVABLE AND THIS WILL BE UTILIZED AS ABOVE CEILING ACCESS POINTS. 12 INSURE ADEQUATE SPACE (48" MIN.) IS LEFT FOR LADDER ACCESS TO MEZZANINE. 13 LOW PRESSURE GAS ROUTED ABOVE CEILING. 6. ROOM EXHAUST CONTROLLED SEPARATELY BY TIMER SWITCH ON WALL PROVIDED BY ELECTRICAL CONTRACTOR. 7. COORDINATE WITH BUILDING B.M.S. SYSTEM AS REQUIRED FOR DAILY SHUT-DOWN SIGNAL. ALL SCIENCE ROOM AND SCIENCE PREP ROOM EMERGENCY SHOWERS, SINKS AND FAUCETS ARE TO BE PROVIDED BY SCIENCE CASEWORK CONTRACTOR. PLUMBING CONTRACTOR TO PROVIDE ROUGH-IN AND CONNECTION TO SUPPLIES AND WASTE. FAUCETS TO HAVE INTEGRAL VACUUM BREAKER OR OTHER MEANS OF BACKFLOW PROTECTION. FEC ENSEMBLE UNIFORM STORAGE 307 305 MECH / FIRE 306 W/D RR OFFICE 226 229 CUST 227 BAND HALL 304 RECEIVING 228 FEC ELEC 230 PRACTICE ROOM PRACTICE ROOM BAND OFFICE 308 309 302 WAREWASH 225 COOLER LIBRARY & REPAIR PRACTICE ROOM SOUND VEST. PRACTICE ROOM 222 CORRIDOR 218A 303 COOKING 301 310 311 224 FREEZER PREP FEC 221 223 FEC CORRIDOR 300 SCIENCE PREP WH VEST VEST 410 406 MECH WH 453 BOYS VARSITY LOCKERS COACH'S OFFICE 411 MDF 214 220 SERVING 454 BIOLOGY 215 DRY STOR WH 219 DW WH 407 BOYS JV LOCKERS 403 COACH'S LOCKER RR 408 CUST 216 409 FEC GIRLS RR F ICE TRAINING 402 SHOWERS RESTROOMS 404 405 SHOWERS 450 412 RESTROOMS 413 CORRIDOR STORAGE BOYS RR 414 217 FEC 451 VEST 401 VEST 415 CORRIDOR FEC 218 FEC FEC PHYS / ART SCIENCE PREP 213 CHEMISTRY 210 211 DW G:\2015\THRALL ISD - HIGH SCHOOL.084\84P3.02.dwg, 1/27/2016 3:30:39 PM, JESUS, DWG To PDF.pc3, ARCH full bleed E1 (30.00 x 42.00 Inches), 0.125:12 FEC CHEM STOR 212 FLOOR PLAN - AREA B - PLUMBING P3.02 8 OF 8