Instruction Bulletin
63249-420-379A2
02/2013
Emergency Lighting Control Panel
ELCP
63249-420-379A2
UL NOTIFICATIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including
the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

Do not mount near gas or electric heaters.

Equipment should be mounted in locations and at heights where it will not be subjected to tampering
by unauthorized personnel.

The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition.

Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
INTRODUCTION
This bulletin contains instructions for installing and wiring an Emergency Lighting Control Panel (ELCP).
The ELCP is specifically designed to contain UL924-listed Automatic Load Control Relays (ALCR) for
use with emergency lighting control in accordance with NEC.
The ELCP is positioned between emergency and regular power panelboards. The regular panelboard
provides power to the ELCP for monitoring a building's voltage, while the emergency panelboard
provides power through a relay contact and controls egress lighting. The design of the ALCR and ELCP
maintains isolation between emergency and regular building power.
When a building's power is in a regular power state, the egress lighting turns ON and OFF with the
regular lighting in the facility. In an emergency state, the ELCP controlling the egress lighting turns ON
automatically and waits for back-up power from a generator or emergency source.
BEFORE YOU BEGIN
ELCPs are ordered based on the enclosure mounting location (surface or flush), the number of ALCRs,
and the voltage used by the panel mounted devices (120V or 277V).
Figure 1: Panel Number Explanation
KEY:
A. Emergency Panel
B. X = the number of panel
mounted devices
C. S = Surface Mount,
F = Flush Mount
D. 1 = 120V, 2 = 277V
Each shipment contains one enclosure with 6 to 24 panel mounted devices (SLSEPMC 120 or
SLSEPMC277) and this instruction bulletin.
NOTE: ELCPs are available for order with an even number of ALCRs, ranging from 6 to 24 ALCRs.
© 2013 Schneider Electric. All Rights Reserved.
Emergency Lighting Control Panel
Instruction Bulletin
63249-420-379A2
02/2013
DIMENSIONS
Figure 2: Surface Mounted Panel (32 inches)
Figure 3: Surface Mounted Panel (44 inches)
NOTE: The 32 in. ELCPs contain 6-16 ALCRs.
NOTE: The 44 in. ELCPs contain 18 to 24 ALCRs
Figure 4: Flush Mounted Panel (32 inches)
Figure 5: Flush Mounted Panel (44 inches)
NOTE: The 32 in. ELCPs contain 6-16 ALCRs.
NOTE: The 44 in. ELCPs contain 18 to 24 ALCRs
2
© 2013 Schneider Electric. All Rights Reserved.
63249-420-379A2
02/2013
Emergency Lighting Control Panel
Instruction Bulletin
SAFETY PRECAUTIONS
This section contains important safety precautions that must be followed before attempting to install or
maintain electrical equipment. Carefully read and follow the safety precautions below.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH






Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E.
This equipment must be installed and serviced by qualified electrical personnel.
This unit has more than one power supply connection point. To reduce the risk of electric shock,
disconnect the branch circuit breakers or fuses and the emergency power supplies before servicing
this unit.
Turn off all electrical power supplying this equipment before working on or inside the equipment.
Always use a properly rated voltage sensing device to confirm that power is off.
Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
ENCLOSURE AND INTERIOR MOUNTING FOR THE EMERGENCY LIGHTING CONTROL PANEL
HAZARD OF EQUIPMENT DAMAGE


Ensure all connections are properly tightened.
Refer to the torque information label provided on the panelboard before tightening the connections.
Failure to follow these instructions can result in equipment damage.
To properly mount and install the ELCP, follow the instructions below for either "Surface Mounting" or
"Flush Mounting" the panel.
Surface Mounting
1.
2.
3.
4.
Remove the interior trim and dead front from the enclosure.
Remove the four hex nuts holding the interior in place.
Remove the interior back pan containing the ALCRs from the enclosure studs.
Secure the enclosure to the wall with the appropriate mounting hardware.
NOTE: Mounting hardware is not supplied with the enclosure.
5. Install the interior as described in the steps below:
a. Set the interior on the enclosure studs. An elevating screw is not required.
b. Tighten the hex nuts against the interior rails until the rails are against the back of the
enclosure.
c. Remount the interior trim and dead front after wiring.
NOTE: Follow all state and national codes for mounting and wiring the ELCP.
© 2013 Schneider Electric. All Rights Reserved.
3
Emergency Lighting Control Panel
Instruction Bulletin
63249-420-379A2
02/2013
Flush Mounting
1.
2.
3.
4.
Remove the interior trim and dead front from the enclosure.
Remove the four hex nuts holding the interior in place.
Remove the interior back pan containing the ALCRs from the enclosure studs.
Secure the enclosure to the wall or studs with the appropriate mounting hardware.
NOTE: Mounting hardware is not supplied with the enclosure.
5. Install the interior as described below:
a. Set the interior on the enclosure studs. Place the hex nuts onto the enclosure studs, but do not
tighten.
b. Adjust the elevating screws so the lip of the interior trim is approximately 0.25 inches (6.35 mm)
from the wall line.
c. Tighten the hex nuts against the side rails.
d. Remount the interior trim after wiring.
NOTE: Follow all state and national codes for mounting and wiring the ELCP.
Figure 6: Interior Mounting
KEY:
A.
B.
C.
D.
E.
4
ELCP Deadfront
Screw (10-32 x 0.875 in.)
Hexnut
Mounting stud
Elevating Screw
© 2013 Schneider Electric. All Rights Reserved.
63249-420-379A2
02/2013
Emergency Lighting Control Panel
Instruction Bulletin
WIRING
Figure 7: Typical Wiring Configuration
© 2013 Schneider Electric. All Rights Reserved.
5
Emergency Lighting Control Panel
Instruction Bulletin
63249-420-379A2
02/2013
SPECIFICATIONS
Panel Specification
Description
Model
SLPEPXS1/SLPEPXF1*
SLPEPXS2/SLPEPXF2*
Ballast
120VAC, 20A
277VAC, 20A
Tungsten
120VAC, 1800W
277VAC, 1500W
General Use
20A, 1 HP
20A, 1 HP
Short Circuit Current Rating
65KA @ 120VAC
18KA @ 277VAC
Terminal Wire Size
10 to 14 AWG
Maximum Terminal Torque
1.15 lb/ft (16 kg/cm)
Standards
UL /cUL listed; UL 924, UL 50
Enclosure
NEMA Type 1
Temperature
32°F to 140°F (0°C to 60°C)
®
*see Ordering Information for catalog number descriptions
6
© 2013 Schneider Electric. All Rights Reserved.
63249-420-379A2
02/2013
© 2013 Schneider Electric. All Rights Reserved.
Emergency Lighting Control Panel
Instruction Bulletin
7
Emergency Lighting Control Panel
Instruction Bulletin
Contact the Customer Information Center for technical support by phone at 1-888-778-2733 or e-mail at
lightingcontrol.support@us.schneider-electric.com.
Contact your local Schneider Electric service representative for repairs or service to your network.
You may also find helpful information on our web site at www.Schneider-Electric.us.
Schneider Electric, USA
320 Tech Park Drive, Suite 100
All trademarks are owned by Schneider Electric Industries SAS or its affiliated
companies.
La Vergne, TN, 37086
1-888-778-2733
www.schneider-electric.us
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this material.
© 2013 Schneider Electric. All Rights Reserved.
63249-420-379A2