Applying Ultraviolet Germicidal Irradiation to HVAC Heat Exchangers to Reduce Biofouling and Improve Heat Transfer Capability Julia C Luongo and Shelly L Miller Department of Mechanical Engineering, University of Colorado, Boulder, CO Key words: UVC, UVGI, Coil fouling, Biofilm, Cooling coil Introduction Ultraviolet Germicidal Irradiation (UVGI) has a long history of being used for the disinfection of air streams, primarily in environments with higher risk of airborne pathogen transmission such as healthcare facilities, schools, and prisons (Reed, 2010). Using UVGI as a coil cleaning technology in air-handling units (AHUs) has recently gained popularity. While air disinfection may still occur as air passes by the UVGI system, the primary focus of UVGI on cooling coils is surface disinfection and, in turn, energy savings, maintenance cost savings, and increased or prolonged system capacity. The buildings sector accounted for about 41% of primary energy consumption in the US in 2010 (DOE, 2011). More than half of the energy used in buildings is for heating, ventilating and/or air-conditioning (HVAC) the indoor environment (EIA, 2003) so energy savings for HVAC systems could have large implications for total building energy consumption. Heat exchanger surfaces are an ideal site for biofilms due to the presence of adequate nutrients (debris inherent on coil surfaces) and moisture (Morey, 1988). High bacterial and fungal concentrations have been documented within AHUs, specifically on cooling coils and drain pans (Hugenholtz & Fuerst, 1992; Levetin et al., 2001; Menzies et al., 2003). Anecdotal evidence exists reporting energy savings from cooling coil UVGI (Keikavousi, 2004; ACHR News, 2007). An increase in energy efficiency of 10-15% from coil cleaning has also been reported, but not specifically using UVGI (Montgomery & Baker, 2006). To the author’s knowledge, few peer-reviewed studies have measured changes in heat transfer coefficients, flow resistance, or energy consumption resulting from UVGI coil cleaning. The objective of this study is to report detailed measurements of heat transfer and flow characteristics for an irradiated coil versus a non-irradiated coil in a laboratory setting. Biological samples of the air and coil surface were analysed using various techniques, including culturing and epifluorescent microscopy. Methodologies System Parameters An HVAC test apparatus was built in the Air Quality Laboratory at the University of Colorado, consisting of two parallel ducts, each with its own cooling coil, but supplied by the same temperature and relative humidity controlled airstream (Figure 1). The test apparatus is equipped with sensors to measure duct velocities, static pressure drops, entering and exiting water temperatures, and entering and exiting air temperatures and relative humidities for each branch. Fan Electric Heating Element Humidifier Length that allows appropriate mixing Tin Tout Damper Pitot Tube Tout , RHout ! Damper Pitot Tube Cooling Coil Tin , RHin Meshing to eliminate water droplets Static Pressure Taps Tout , RHout Cooling Coil UVC lamp Tin , RHin Static Pressure Taps Tin Tout Figure 1. Schematic of HVAC test apparatus. The test apparatus uses indoor air from the room as the inlet air. The room HVAC system supplies 100% outdoor air filtered with MERV 14 filters. Air enters each cooling coil, on average, at 72 oF and 45% relative humidity and chilled water enters at 45 oF, satisfying conditions for condensation onto the coils. These conditions, however, are mild compared to the condensing conditions of cooling coils in very humid climates. The system mimics a constant volume HVAC system, meaning the volumetric flow rate is held constant. The flow rates through each coil are held equal to one another using dampers since the static pressure drop across the coils may not be equal given equivalent flow rates. Air and water inlet temperatures, inlet relative humidity, and water flow rate are all held constant. The system ran undisturbed for 10 months without UV on either coil to ensure that both coils “fouled” at an equivalent rate and to establish a robust baseline dataset. After 10 months of operation, the UV lamp was turned on, irradiating the downstream side of one of the cooling coils (labeled “Top” coil). The control coil is labeled “Bottom” coil. The irradiance at the surface of the Top coil was 200 μW/cm2 at the center and 150 μW/cm2 at the corners. The UV lamp had been constantly irradiating the Top Coil for 3 weeks at the time of submittal of this paper. Assessment of Heat Exchanger Flow Characteristics and Effectiveness One of the main challenges in assessing changes in flow characteristics and effectiveness in two heat exchangers over time is that all variables affecting these qualities are never exactly the same and cannot be held completely constant. For this reason, small fluctuations in temperature, relative humidity, or flow rate will affect static pressure drop and the calculated value of heat transfer, making it difficult to compare. To remedy this, comparisons between the control and UV-treated coils were only made with dimensionless quantities, including heat exchanger effectiveness and normalized static pressure drop at a reference flow rate of 350 cubic feet per minute (CFM). Heat exchanger effectiveness is the ratio of the actual airside heat transfer to the maximum heat transfer theoretically possible. Equation 1 shows how the effectiveness is independent of the flow rate through the heat exchanger. , , , @ (1) , where is the mass flow rate through the heat exchanger, , is the enthalpy of the air entering the heat exchanger, , is the enthalpy of the air leaving the heat exchanger, and @ , is the saturation enthalpy at the temperature that the water enters the heat exchanger. Heat exchanger effectiveness was monitored throughout the entire experiment for both coils. The static pressure drop at a reference flow rate of 350 CFM was also monitored throughout the experiment for both coils. Since both control and treatment coils did not have identical static pressure drops at the start of the experiment, the static pressure drop throughout the experiment was normalized by the initial pressure drop. Biological Assessment Coil surface samples were taken with sterile BBL CultureSwabs (BD, Sparks, MD). A 10-cm2 area of the coil surface was swabbed and extracted into HPCL water. Both the upstream and downstream side of each coil was swabbed. Samples were stained using SYTO BC Green Fluorescence stain (Life Technologies, Carlsbad, CA) and deposited on a 0.2-μm black polycarbonate membrane (Millipore, Billerica, MA). SYTO BC is a nucleic acid stain that penetrates both Gram-negative and Gram-positive bacteria, yielding total cell counts. Samples were directly counted using an epifluorescent microscope (Nikon E600). Results and Discussion Assessment of Heat Exchanger Flow Characteristics and Effectiveness The effectiveness of both coils remained fairly constant for the first 6 months of operation and, in fact, rose slightly over the first 4 months. We hypothesize that a clean coil sees a slight increase in effectiveness in the early stages of cooling due to the condensed water slightly increasing the heat transfer coefficient. After the initial 5-6 months of operation, the effectiveness began to decrease rapidly, approximately 15% over 3-4 months. Figure 3 displays the effectiveness of both cooling coils over the 10-month period of “fouling” as well as 3 weeks of UV exposure for the treatment coil. The arrow indicates when the UV lamp was turned on for the treatment coil (Top coil). 1 Top Coil (UV) Bottom Coil 0.9 Coil Effectiveness (%) UV turned on (Top Coil) 0.8 0.7 0.6 0.5 0.4 10/01 01/01 04/01 07/01 10/01 Time Figure 3. Effectiveness of both cooling coils throughout the baseline data collection of 10 months plus 3 weeks of irradiating the Top coil. The vertical line indicates when the UV lamp was turned on for the treatment coil (Top Coil). Both coils began the experiment with a normalized static pressure drop of 1 (normalized by the initial static pressure drop of 0.167 inches of H2O for the Top coil and 0.158 inches of H2O for the Bottom coil) at the reference flow rate of 350 CFM. After 10 months, the normalized static pressure drops for the Top and Bottom coils were 1.11 and 1.18, respectively, meaning that static pressure drops at 350 CFM increased 11% and 18%, respectively. After 3 weeks of irradiating the downstream side of the Top coil, the normalized pressure drop was 1.06, a reduction of 5%. The UV-irradiated coil began looking visually cleaner after 1 week of irradiation. Biological Assessment Results from epifluorescent microscopy show higher total microbial counts on the downstream surface samples versus upstream surface samples on both coils prior to being exposed to UV (two sets of bars on the left side in Figure 4). This result is consistent with evidence of higher viable microbial loads on the downstream side of cooling coils when culturing surface samples (Hugenholtz & Fuerst, 1992). No change was observed in the total surface cell counts for the irradiated coil after 3 weeks even though the coil appeared visually cleaner. Previous studies on UVGI coil cleaning have seen drastic declines in viable bacterial counts when culturing coil surface samples from UV-irradiated coils (Moyer et al., 2010; Menzies et al., 2003). We experienced difficulty culturing bacteria from surface samples due to mild condensing conditions and low nutrient loads in the inlet air but preliminary results show lower viable bacterial counts on the irradiated coil. A larger dataset of culturable bacteria is being collected. Our preliminary results may indicate that while UVGI inactivates surface microbes and cleans the coil via oxidation, the inactive DNA of previously viable biofilms may still remain on the coil. 300 Microbial Counts per Field (410x330 um) Downstream Upstream 250 200 150 100 50 0 Bottom Coil Baseline Top Coil Baseline Top Coil (1 wk UV) Top Coil (2 wks UV) Top Coil (3 wks UV) Figure 4. Total microbial surface cell counts per field of view using epifluorescent microscopy. The two sets of bars on the left show average counts for both sides of both coils prior to UV irradiation (baseline). The following three sets of bars on the right show the UV-irradiated coil (Top Coil) cell counts for each week of the 3 weeks of UV exposure. No significant change was observed. Error bars represent the standard error. Conclusions After 10 months of baseline (“fouling”) operation, the effectiveness of both cooling coils dropped roughly 15% and the static pressure drop at the reference flow rate of 350 CFM increased between 11-18%. Microbial surface sampling indicates a higher degree of biofouling on the downstream side of the cooling coils prior to UV irradiation. While the UV-irradiated coil appeared visually cleaner after 1 week of irradiation and saw a 5% reduction in static pressure drop at 350 CFM after 3 weeks, the total surface cell counts from epifluorescent microscopy remained the same. Preliminary data from culturing surface samples, however, indicates higher counts of viable microbes on the non-irradiated coil but a more robust dataset is currently being collected. Data collection is ongoing and further results will be reported. References ACHR News, "UVC Lights Keep Hospital Cool , Efficient" The HVACR Contractor’s Weekly News Magazine, 1295–1296 (2007). DOE, Buildings Energy Data Book (2011). EIA, Commercial Buildings Energy Consumption Survey (CBECS) Data (2003). Hugenholtz, P. & Fuerst, J. a, "Heterotrophic bacteria in an air-handling system" Applied and environmental microbiology, 58(12):3914–20 (1992). Keikavousi, F., (2004) UVC : Florida Hospital Puts HVAC Maintenance Under a New Light. Engineered Systems, pp.60–66. Levetin, E., Shaughnessy, R., Rogers, C.A., et al., "Effectiveness of Germicidal UV Radiation for Reducing Fungal Contamination within Air-Handling Units" Applied and Environmental Microbiology, 67(8):3712–3715 (2001). Menzies, D., Popa, J., Hanley, J. a, et al., "Effect of ultraviolet germicidal lights installed in office ventilation systems on workers’ health and wellbeing: double-blind multiple crossover trial" Lancet, 362(9398):1785–91 (2003). Montgomery, R.D. & Baker, R., "Study Verifies Coil Cleaning Saves Energy" ASHRAE Journal, (November):34–37 (2006). Morey, P.R., "Microorganisms in buildings and HVAC systems: A summary of 21 environmental studies" In Proceedings of the ASHRAE Conference on Indoor Air Quality, American Society of Heating, Refrigeration, and Air-Conditioning Engineers. Atlanta, GA, pp. 10–24 (1988). Moyer, E.S., Miller, W.E., Commodore, M. a., et al., "Aerosol and Biological Sampling of a Ventilation Fan-bank Modified with Ultraviolet Germicidal Irradiation and Improved Filter Holders" Indoor and Built Environment, 19(2):230–238 (2010). Reed, N.G., "The history of ultraviolet germicidal irradiation for air disinfection" Public Health Reports, 125:15–27 (2010). Schmidt, M.G., Attaway, H.H., Terzieva, S., et al., "Characterization and control of the microbial community affiliated with copper or aluminum heat exchangers of HVAC systems" Current microbiology, 65(2):141–9 (2012).