ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Electrical Systems (ARUP) Electrical Codes & Regulations Design Load Estimates Normal Power Emergency Power Grounding System Lighting Lighting Control Fire Alarm System PV System Basis of Design Passive Daylighting Analysis Examples of Analysis ELECTRICAL SYSTEMS (CUPERTINO) Lighting Base Design Criteria Applicable Codes, Guidelines and Standards Load Calculation Criteria Equipment Sizing Criteria Lighting Systems 8 electrical systems DRAFT - 73 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Electrical The following content is based on preliminary program input received from Stanford University, Boora Architects, and CAS Architects. The load allowances provided herein reflect updated architectural programming requirements that have been revised since the issue of the SEQ2 Master Plan and Design Guideline. The load allowances for both chemical and computational (i.e. dry) laboratories are based on preliminary estimates provided as part of the initial Master Plan documents. These laboratory loads will be revised to reflect the updated lab loads as they are made availible for the inclusion in this report. The load allowances provided in this document represent predicted connected load per the National Electric Code (NEC) requirements and should not be used to validate LEED or sustainable criteria. Codes & Regulations 8 74 - DRAFT The electrical installation will comply with the following codes and standards, latest edition as adopted by Santa Clara County: •California Electrical Code (CEC) •California Administrative Code, Title 24 (Energy Conservation) •California Building Code for seismic bracing (CBC) •California Code of Regulations (CCR) •California Fire Code (CFC) • National Fire Protection Association Standards The electrical installation will comply with the following recommendations and design practices: • Illuminating Engineering Society of North America (IESNA) • Stanford’s Facility and Operations Design Standards, latest edition The electrical system will include: • Lighting (interior and exterior) • Power (normal, emergency & stand-by, 277/480V, 120/208V, 3‑phase, 4‑wire) • Signal systems: Fire alarm, telecommunication (voice/data) and security Estimated connected load for the Environment & Energy Building (E+E) Overall VA/ft2 Normal (kVA) Emergency VA/ft2 38,608 29 1,120 10 392 Laboratories - Dry 12,808 29 371 10 130 Offices 38,922 7 272 1 27 7 0 1 0 6 74 1 7 Special Use 10 0 1 0 Common Space 6 0 1 0 50 50 25 25 Programs Area (sqft) Assignable ft2 103,656 Laboratories - Wet Regional Assets Seminar/Conference Server Room 12,318 1,000 Emergency (kVA) Pumps & Fans - - 280 70 Design Load Estimates Plumbing - - 50 13 Elevators - - 108 54 The following is a summary of the preliminary load estimates for the Environment and Energy Building. It must be noted that these loads are based on schematic information from Boora Architects and CAS Architects. This information will be updated as additional input is received from Stanford University, Boora Architects and CAS Architects. The exact loads in the laboratory areas will have a significant effect on the sizing of the main systems. Fire Pump - - 35 35 Attria Exhaust - - 80 80 Sub Total 2,440 833 Allow 10% Margin 244 83 Total Demand 2,684 916 VA/ft 2 25.9 8.8 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Estimated connected load for the School of Engineering Building (SoE) Programs Assignable ft2 Area (sqft) Overall VA/ft2 Normal (kVA) Emergency VA/ft2 Emergency (kVA) 82,696 Laboratories - Wet 29 0 10 0 Laboratories - Dry 29 0 10 0 Offices 28,677 7 201 1 20 Regional Assets 25,999 7 182 1 18 Seminar/Conference 1,088 6 7 1 1 Special Use 18,520 10 185 1 19 Common Space 8,012 6 48 1 5 400 50 20 25 10 Server Room Pumps & Fans - - 200 50 Plumbing - - 35 9 Elevators - - 108 54 Fire Pump - - 35 35 Attria Exhaust - - 55 55 Sub Total 1,076 275 Allow 10% Margin 108 28 Total Demand 1,183 303 14.3 3.7 VA/ft 2 Note: The estimated connected load for the School of Engineering is based on Master Plan load estimates provided in August 2004 with revised areas updated in a later issue of SEQ 2 Master Plan and Design Guidelines. An allowance will be made for a total of two (2) outdoor pad mounted transformers with 12470(∆) volt primary service and a 277/480(Y) volt secondary building service. The building system ground will be provided at the buildings service entrance. The final size of the transformers serving the Environment and Energy Building will be determined by Stanford University and provided under a separate utility project. Two (2) additional transformer pads will be provided along the south side of the Science and Engineering Quad 2 for the future power requirements of the School of Engineering Building. This allowance includes the pad(s) and secondary conduits from the pad to the main electrical room. One diesel fuel generator will be located on grade. The generator will be an outdoor model with sufficient fuel for 8 hours at full rated current. The generator fuel storage tank will be a sub-base tank and will contain approximately 525 gallons of diesel fuel. The generator will be enclosed in a weather proof, acoustical enclosure. The generator size is currently estimated at 900 kW but will again depend on what equipment in the building will require generator back-up. The exact loads in the laboratory areas will have a significant effect on the sizing of the generator. The estimated generator size does not take into account the standby load that could be supplemented with a fuel cell. The economic payback and potential benefit of a 250 kW fuel cell is being reviewed by Stanford University. Power Distribution System Electrical service will be obtained from the 12kV campus distribution system supported by the Paulou Substation. The transformers will be arranged for loop feed. Stanford will confirm the exact point of service connection and whether the system has sufficient capacity to service the new buildings. Normal Power Two options for distributing power to the laboratory panelboards are being presented at the schematic design stage. • The first utilizes the traditional horizontal distribution that requires a distribution panel and transformer on each floor to serve the laboratory panels local to that floor. This method requires less space for distribution equipment in the basement electrical rooms but increases the requirements in the upper floor electrical rooms. • The second option utilizes vertical distribution and locates a main distribution panel and transformers to serve all laboratory panels in the basement electrical rooms. This reduces the space requirement for the electrical rooms on upper floors. The main electrical room will contain two (2) main switchboards and distribution boards for the Environmental and Energy Building. The main switchboards will be connected via a 1200A busway for redundancy with Kirk Key Interlocking devices. A space allowance will be provided within the main electrical room for future switchboards and distribution boards required by the School of Engineering Center. The building power distribution will be at 277/480V and 120/208V via cable feeders in conduits and will be distributed as follows: • 480V, 3‑phase, 3‑wire for all motor loads one horsepower and larger. • 277V, 1‑phase for fluorescent lighting and HID fixtures. • 208V, single phase or 3‑phase for special equipment. • 120V, single phase for receptacle outlets and motors 3/4‑horsepower or smaller. • No facility will be provided for power system other than 277/480V and 120/208V AC, 3‑phase, 4‑wire, 60 Hz. The two (2) main switchboards will be rated at a maximum of 2000A, 277/480V, 3‑phase, 4‑wire and will be located inside the building in a naturally ventilated, or conditioned, switchgear room. This main electrical room will be approximately 1750 ft2 in size and positioned at the basement level on the east side of the Environment and Energy Building. Each switchboard will include a digital Power Measurement Ltd meter per Stanford University Standards to monitor voltage, current, and energy usage. This monitoring system will be compatible with existing campus communication protocol (SCADA) and the building’s Energy Management Control System (EMCS). The branch electrical rooms of approximately 150 ft2 in size, with a minimum width of 8’-0”, shall be provided for in two (2) vertically stacked locations. The vertical stacks will be located central to the north-west the central to the building, and directly over the main electrical room. 277/480V distribution boards and feeders will be provided for service to the elevators, pump room, mechanical equipment and lighting panelboards. 120/208V distribution board will be provided to serve the general receptacles, any incandescent light fixtures, and all 120V and 208V equipment. One minimum 42-pole 120/208V, 3-phase, 4wire panelboard with main circuit breaker will be provided for each laboratory. Motor control centers and/or distribution boards for mechanical equipment will be provided for each mechanical room and roof mechanical platform. 8 electrical systems Distribution transformers will be K-13 for nonlinear loads and will be provided with 200% rated neutral terminals. Feeders for non-linear loads will include 200% rated neutral conductors. Distribution of power within the building laboraDRAFT - 75 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Fuel Cell (Continuous Operation) ~12' × 22' the Contractor in accordance with the recommendations and guidelines of the Illuminating Engineering Society (IESNA) and Stanford’s specification requirements. The lighting power density target will be confirmed by the Contractor. At present the lighting power density is expected to be between .7 and .9 W/ft2. This W/ft2 is below that mandated by California Code of Regulations (CCR), Title 24 - Energy Conservation Regulations. The following lighting levels will be provided in accordance with the above: Work Plane Lighting Levels Generator(s) at Via Palou Substation ~10' × 18' Proposed location for standby generator and fuel cell tory areas will be by a conduit and wire system and surface metal raceways. 8 Emergency Power A standby generator will be installed to provide emergency power to egress lighting, exit signs, fire alarm, and standby power for telecommunications, central exhaust and supply fans at 50% load for laboratories and a percentage of “emergency” outlets in the laboratories, electrical rooms and mechanical rooms. All smoke control fans will be on emergency power. In the laboratories a percentage of the refrigerators, freezers, incubators and all environmental chambers will be connected to standby power. Standby power will not be provided in office areas. Generator sizing will be based on more precise criteria to be determined during design. An Air Quality permit must be obtained and the appropriate fees paid for operating the emergency generator. The generator is presently being proposed at the following location in addition to a 250 kW fuel cell. The economic payback and potential benefit of a 250 kW fuel cell are currently being reviewed with Stanford University. 76 - DRAFT Two automatic transfer switches (ATS’s) will be provided one for “emergency” loads and the other for “standy-by” loads. Both ATS’s will be programmable delay transition type with four fully rated poles. The ATS’s will be configured for preferred source selection. The generator status will be monitored via the Campus SCADA sytem. Grounding System A central grounding system will be provided for the electrical service, all switchboards, and step-down transformers. A low impedance connection to earth will be obtained using ground rods, a concrete encased electrode and bonding to the building steel and main water piping. All grounded busses from switchboards, transformers, panelboards will be connected at a central ground bus in the electrical room. The telecommunications room grounds will also use the main building ground bus as the reference point. Lighting The lighting design will be further developed by Room Footcandles Offices 40 – 60 Laboratories 50 - 75 (to be verified with Stanford University) Lobby 15 - 30 Workrooms, Study Area 30 - 50 Corridors 10 - 20 Storage/Janitor's Rooms 15 - 25 Toilets 15 - 25 Telecommunications Rooms 50 - 60 Electrical/Mechanical Rooms 20 - 30 The following be followed: lighting specifications • All fluorescent fixtures will be provided with electronic ballasts and will generally be controlled by local wall mounted switches. • Exterior lighting will be high intensity discharge and will be controlled by a Lighting Control Panel. Fixtures will be selected to coordinate with existing site lighting in the area. Lighting Control A central lighting control system shall control a series of LCP’s throughout the building as follows: • The LCP’s will be controlled and monitored by the EMCS. • Open loop photocontrols controlled through LCPs, or remote relays throughout the building, will be provided for in all areas receiving natural daylighting. •Closed loop photocontrols not controlled thru the LCP will be acceptable in private offices. • LCP’s will be able to turn relay controlled groups ON/OFF per scheduled time function via astronomical time clock or EMCS input. Fire Alarm System will • Light fixtures in laboratories and offices will be fluorescent type with linear T8 or T5 lamps and electronic ballasts. • Dimming ballasts will be used in all areas receiving enough natural daylight to meet the above criteria without supplemental artificial lighting. • Light fixtures in offices, corridors and public toilets will be controlled by occupancy sensing devices. • Downlighting fixtures (compact fluorescent) will be used in selected areas. • Incandescent lamps will not be used except in special applications. • Exit signs will be LED type. • Indirect lighting should be investigated and used in appropriate areas. • Indirect lighting is highly recommended in all areas were light shelfs are used to bring daylight further into the building core. An addressable fire alarm system matching the Stanford standard specifications will be provided by Siemens or Notifier and will include the following: • Either: a) Full area smoke detector coverage in order to avoid the requirements for duct detectors. Certain areas with difficult environments may require heat detectors in lieu of smoke detectors. Fire/smoke dampers will be closed and air-handling units will be shut down using the full area coverage detectors in accordance with applicable codes and as required by the Santa Clara County Fire Marshal. b) Duct detectors located at all ducts passing thru fire separations, with the exception of the atria, to activate fire smoke dampers. The atria will utilize smoke detector coverage or another means of detection as deemed appropriate by the projects Code Consultant. Fire/smoke dampers will be closed and air-handling units will be shut down using the duct smoke detectors in accordance with applicable codes and as required by the Santa ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Clara County Fire Marshal. • A main fire alarm control panel located in the electrical room. •Heat and smoke detectors will be located in all elevator machine rooms, as required. • Audio alarms will be provided to be audible throughout the building. • Visual alarm stations will be provided along all egress routes, toilet areas, lobbies and other “common use” areas. • Pull stations will be provided along egress routes. • Remote annunciator at the Main entrance of the south side of the building. The fire alarm system will be linked with the elevators for return to a predetermined floor and mechanical air supply system for shut down in the event of fire alarm signal. The system will also be linked to the sprinkler flow switches and valve monitors. The system will transmit alarm and trouble signals, to the campus main fire alarm system through a telephone interface or the Campus SCADA system. All devices will be addressable. • Translucent PV film for exterior atrium glazing. This thin film provides benefits by limiting the light transmittance to a 10-30% range through the glazing, while harnessing 4-8% of the sun’s energy for electrical power. For example, etched amorphous silicon PV film incorporated into the glass. • Alternatively, translucent PV film for interior atrium glazing could be used instead of the film on the exterior glazing. This thin film provides the same benefits as the film on the exterior, located on the interior of the atrium space. Based on the allotted budget for a PV system installation, a preliminary system size estimate ranges between 80 and 100-kW peak output. A PV array providing a peak output of 80-kW would require approximately 7300 gross square feet (gsf) for the installation, while a 100-kW system would require approximately 9000 gsf on the surface of the building. Etched amorphous Silicon PV film – 10% Visible light transmittance, with approx 4.5W/ft2. The drawing below shows the application of the PV alternatives listed. Summer Sun Atria Ceilings Translucent PV Efficiency 4%–8% Winter Sun 8 electrical systems Roof Mounted PV System Basis of Design High Efficiency 11%–14% A building integrated photovoltaic (BIPV) system will be installed to supplement normal power to the Environment and Energy (E&E) building. Due to the climate and geography of the site, a BIPV system can perform effectively in any of several different installation alternatives. There are four primary installation alternatives for the placement of the BIPV system that should be considered, as follows: • A south-facing roof installation using high efficiency multi-crystalline or mono-crystalline PV modules, capable of harnessing 11-14% of the sun’s energy for usable electrical power. • South-face window shading devices to be installed with PV systems on the top face. This provides the dual benefit of shading interior spaces while harnessing energy. This application can use either opaque or translucent PV. Additional images of BIPV installations are shown below. Translucent Window Shade Multi-Crystalline PV Modules – Roof mounted with approx 11W/ft2. Efficiency 4%–8% Illustration showing utilization of different PV technologies throughout the E&E building. DRAFT - 77 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY The diagram below shows typical components for a PV installation. PHOTOVOLTAIC: LOCATED ON ROOF, AS A SHADING DEVICE, AS THE ATRIA CEILINGS POWER CONDITIONING SYSTEM WITH DC DISCONNECT & PROTECTION INVERTER SYSTEM WITH HIGH EFFICIENCY DC TO AC POWER CONVERSION INVERTER ISOLATION TRANSFORMER 8 FUSED DISCONNECT @ SERVICE ENTRANCE M METERING FOR STANFORD UNIVERSITY MAIN ELECT. DISTRIBUTION MAIN ELECT. DISTRIBUTION All PV power conditioning equipment and inverters should optimally be located in the fourth floor mechanical penthouse, to limit the DC distribution. The efficiency for the power conditioning equipment, including the inverter and isolation transformer, is around 90-95%. 78 - DRAFT Passive Daylighting Analysis The architecture of the Environment and Energy (E+E) Building is currently being refined to better utilize passive daylighting. The passive daylighting improvements being proposed will reduce the lighting load of the building while taking advantage of the psychological and health benefits associated with having naturally illluminated interiors that have views to the outside. As set forth by the SEQ2 Master Plan Design Guidelines, the E+E Building architecture will strive to exceed the standards as put forth in the LEED Green Building Rating System for New Construction Version 2.2 Credit 8.1. To achieve this credit a level of 25 footcandles (fc) must be achieved at 30 inches above finished floor (AFF) in 75% of all areas occupied for critical visual tasks under specific clear sky conditions. The design target of 75% has been increased to 80% of all areas occupied for critical tasks per the SEQ2 Master Plan Design Guidelines. • Reconfigured light-wells with light colored concrete to maximize the daylight entering the lowest level of the building. • Incorporation of photovoltaics into the atria ceiling to mitigate solar gains and unwanted glare. Ideally, these photovoltaics would retain a clear view to the sky and reduce the cost of an alternate photovoltaic installation location. • Various transmissivities of Low-E glass that will mitigate heat transfer and glare while maximizing daylight throughout the building perimeter and the building atria. • Incorporating a glass floor at the ground level of the atria to improve the transmission of visible daylight into the basement. Examples of Analysis Potential solar gains are being assessed prior to the incorporation of internal partitions to maximize the benefits of natural daylight throughout the building. The following is an example of the analysis taking place on the 2nd floor of the E+E building. The yellow areas demonstrate areas that can achieve 25 [fc] under the prerequisite sky conditions with the proposed partition configuration. The blue areas represent areas that cannot achieve the required 25 [fc]. The follow represent various studies that have been conducted to help the design team determine which daylighting strategies are most beneficial to our achieving the buildings daylighting design target. Various daylighting strategies are being analyzed in an effort to optimize the passive daylight elements adopted into the building architecture and achieve the 80% target. At present the daylighting strategies being reviewed are as follows: • Exterior shading devices for all south facing windows to mitigate unwanted solar gains and minimize glare in occupied spaces. • Integration of photovoltaics into shading devices over the south facing windows to mitigate unwanted solar gains and minimize glare in occupied spaces. • Raised and re-configured ceiling heights near the window wall to improve the penetration of daylight into the building. • Optimization of light shelf depths and orientations for all south facing interiors • Interior light shelfs that re-direct natural light in the atria to the northern core of the building interior. • Vertical fins at the East and West facing windows to minimize heat gains and glare, while increasing indirect illumination into the space. Example of horizantal illuminances provided on second floor of E+E Building for prerequisite clear sky conditions. ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Shading and glass transmittances are being reviewed to better understand the glare and the uniformity of daylight throughout the building interiors. The ray-traced rendering demonstrates the benefits of adding light shelfs to the windows receiving light from the basement level light wells. Model shows the daylight on the south-east corner of the building at noon on the fall equinox. 8 electrical systems Radiosity is used to model ceilings and light shelf orientations to identify improved daylight performance at the South window wall. The ray-traced rendering represents a revised ceiling and light shelf configuration that allows for a 45% improvement in daylighting over the initially proposed South window wall. 3-D Building model used to identify daylighting improvements and to review shadowing caused by architecture. Model shows the daylight on the south wall at 10AM on the spring equinox. DRAFT - 79 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY ELECTRICAL SYSTEMS (CUPERTINO ELECTRICAL INC.) 3. Equipment Sizing Criteria Lighting Base Design Criteria 1. Applicable Codes, Guidelines and Standards The latest edition of approved year of the following codes or combination codes and guidelines will govern the Electrical Systems and associated support system design. The systems will be designed to meet or exceed these standards. 8 a. Branch Circuit Load Calculations: Lighting - Actual installed wattage b. Demand Factors: Lighting - 125% of total wattage (continuous load) c. ADA Americans with Disabilities Act Accessibility Guidelines ANSI American National Standards Institute, Inc CAL/OSHACalifornia Occupational Safety Hazard Authority CCR Title 24 California Code of Regulations Energy Commission IEEE Institute of Electrical and Electronics Engineers IESNA Illuminating Engineering Society of North America NEC National Electrical Code with California Amendments NECA National Electrical Contractors Association NEMA National Electrical Manufacturers Association NESC National Electrical Safety Code NFPA National Fire Protection Association SFMCalifornia State and Local Fire Marshal UBC Uniform Building Code with Amendments UL Underwriters’ Laboratories, Inc. or equivalent testing lab by City of South San Francisco Minimum Bus Sizes 480Y/277V Panels: Normal Lighting Emergency Lighting 208Y/120V Panels Normal Lighting d. Design Lighting Levels (Non-Residential – Area Category Method). The target lighting power density as set by Boora Architect will be 20% below the standard. Standard LPD 2. Load Calculation Criteria Design Voltages Secondary Voltage Normal/Standby Emergency b. - - - - 480Y/277V, 3 phase, 4 wire 208Y/120V, 3 phase, 4 wire 480Y/277V, 3 phase, 4 wire 208Y/120V, 3 phase, 4 wire Design Loads Overall Connected Volt-Amperes (VA) per Square Foot. Lighting loads per 2005 California Building Energy Efficiency Standards (Non-Residential. Area category method. Office: Lighting Lab and Lab Support: Lighting Conference/Lobby: Lighting Circulation: Lighting Building Support: Lighting 80 - DRAFT - 100A The lighting power density (LPD) is based on the State of California Energy Commission 2005 Building Energy Efficiency Standards All other local and State codes and will be adhered to where applicable and available. a. - 100A - 100A - - - - - 1.2 watts/sq. ft. 1.3 watts/sq. ft. 1.4 watts/sq. ft. 0.6 watts/sq. ft. 0.6 watts/sq. ft. Offices less that 250 Sq. Ft, Laboratories Lobbies Workrooms, Study Areas Corridors Storage/Janitor Rooms Toilets Telecommunication Rooms Electrical/Mechanical Rooms Offices Larger Than 250 Sq. Ft. 20% Reduction 1.2 w/sq. ft. 1.3 w/sq. ft. 1.5 w/sq. ft. 1.4 w/sq. ft. 0.6 w/sq. ft. 0.6 w/sq. ft. 0.6 w/sq. ft. 1.0 w/sq. ft. 0.7 w/sq. ft. 1.2 w/sq. ft. 0.96 w/sq. ft. 1.04 w/sq. ft. 1.20 w/sq. ft. 1.12 w/sq. ft. 0.48 w/sq. ft. 0.48 w/sq. ft. 0.48 w/sq. ft. 0.80 w/sq. ft. 0.56 w/sq. ft. 0.96 w/sq. ft. * * 20% of lighting load to be added for task lighting. Typical footcandle levels. (Each room calculated to stand alone). ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY Offices 137 Sq. Ft. F32T8 Lamps 250 Sq. Ft. 400 Sq. Ft. 600 Sq. Ft. F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps Labs 1000 Sq. Ft. 3000 Sq. Ft. 5000 Sq. Ft. F32T8 Lamps F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps Standard LPD (1.2 W/Sq. Ft.) 20% Reduction 31 FC 30 FC D.N.C. * 32.6 FC 31.5 FC 32.6 FC 40 FC 34 FC 34 FC 44 FC 39 FC 37 FC 21 FC 20 FC D.N.C. * 26 FC 19 FC 22 FC 30 FC 29 FC 25 FC 37 FC 32 FC 31 FC Standard LPD (1.3 W/Sq. Ft.) 20% Reduction 52 FC 45 FC 43 FC 59 FC 53 FC 49 FC 62 FC 55 FC 53 FC 42 FC 36 FC 35 FC 48 FC 42 FC 40 FC 50 FC 44 FC 41 FC * Does Not Comply Lobby Standard LPD (1.5 W/Sq. Ft. 20% Reduction 62.8 FC 55.4 FC 52.3 FC 42 FC 37 FC 34 FC 1300 Sq. Ft. F32T8 Lamps F28T5 Lamps F54T5 HO Lamps Conference Rooms Standard LPD (1.4 W/Sq. Ft.) 43.8 FC 42.4 FC 36.5 FC 64.3 FC 58.0 FC 54.7 FC 256 Sq. Ft. 2000 Sq. Ft. F32T8 Lamps F28T5 Lamps F54T5 HO Lamps F32T8 Lamps F28T5 Lamps F54T5 HO Lamps 20% Reduction 32 FC 25 FC 22 FC 52 FC 46 FC 43 FC Footcandle levels in rooms are based on the 20% reduction in the LPD. Footcandle levels in rooms shall be verified by Stanford University. Footcandle levels as shown in the Stanford University Facilities Design Guidelines Section 16500, Part 1.02, systems description “A” illumination level needs to be revised to meet the adjusted lighting power density. Room Reflectance The following are minimum room reflectance levels: Ceiling Reflectance = 80 Wall Reflectance = 50 Floor Reflectance = 20 Note: Room furnishings should be as light as possible. Dark equipment (desks, tables, walls) equipment suspended from the ceiling or tall equipment will reduce the footcandle level in a room. 4. Lighting Systems a. System Description A complete lighting system for all indoor and site illumination will be provided. The indoor lighting system will consist primarily of energy-efficient fluorescent fixtures. Incandescent lighting will be used only as requested by the Owner or where aesthetics is of prime importance. In general, indoor lighting controls will consist of line voltage switches and occupancy sensors. Emergency/night lighting will be provided by unswitched branch circuits. These unswitched branch circuits will be fed from emergency lighting panel. 8 electrical systems Any seismic support wires for support of lighting fixtures will be furnished and installed by others. The electrical subcontractor will be responsible for tie off of seismic support wires at fixtures. All task lighting will be provided by others. b. Equipment and Materials (1) Lamps and Ballasts In general, fluorescent lamps will be T8, 4100 degrees Kelvin color temperature, with a color rendering index (CRI) of 75 or greater. Fluorescent ballasts will be high frequency electronic type with less than 10% total harmonic distortion. High intensity discharge ballasts will be high power factor, constant wattage type. (2) Lighting Control All lighting will be controlled to meet or exceed the requirements of California Title 24. Lighting control system with daylight harvesting utilizing dimmable electronic ballasts at the perimeter windows and atriums (where appropriate) lighting control system (LC & D) with Bacnet interface capabilities. DRAFT - 81 ENERGY + ENVIRONMENT BUILDING - BASIS OF DESIGN STANFORD UNIVERSITY 82 - DRAFT