Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips CONTROL OF A DOUBLY-FED INDUCTION MACHINE OPERATING AS A GENERATOR IN A WIND POWER PLANT IN THE EVENT OF VOLTAGE DIPS Krzysztof Blecharz / Gdańsk University of Technology 1. INTRODUCTION Modern generator units used currently in wind power plants make it possible to supply power to the power grid in a wide wind turbine changes range. The operation of a machine in a wide range of generator shaft rotational speed facilitates a decrease in mechanical stresses both on the shaft and mechanical transmission gear and an increase in wind turbine operating efficiency. In high-power wind power plants, slip-ring induction machines are used as generators where the rotor is powered by a power electronics converter facilitating a two-way flow of energy; however, the stator is connected directly to the power grid (fig. 1). In the literature, such solutions are referred to as generator units with a doubly-fed induction machine. � Power grid Pss Pr Psr is u dc ~ - Machine converter ips ~ Pm ir - Ps Grid converter Fig. 1. Wind power plant with a doubly-fed induction machine – propagation of energy with over-synchronous speed The main advantage differentiating such solutions from others is the power of the converter supplying the rotor being approximately 30% of the nominal power of the whole generator. This is crucial with regard to the costs of constructing the converter in the rotor circumference, taking into account the constantly increasing installed unit power in wind power plants. The sensitivity to voltage interferences on the stator side is a significant disadvantage of generator units with a doubly-fed induction machine. The rotor and stator are magnetically coupled, which results in voltage interferences originating in the power system being directly transformed to the rotor side. The voltage interferences have a significant influence on the operation of the converter supplying the generator’s rotor and may result in its being damaged. Summary The paper presents the problems related to the methods of regulating the power of a doubly-fed induction machine operating as a generator in a wind power plant. It touches upon the problem of generator operation when voltage interferences appear on the power system side in the form of a voltage dip. The paper presents power regulation systems based on asynchronous machine multi-scalar models enabling to extend the range of the generator’s continuous operation in the event of a voltage dip on the wind power plant terminal connecting it to the system. 5 Krzysztof Blecharz / Gdańsk University of Technology 6 A short-circuit is the most common disturbance in the operation of a power system. It directly results in voltage drops on the transmission grid elements and voltage dips in the system nodes. The characteristic feature of a doubly-fed induction machine is the poorly attenuated flux oscillation resulting from the voltage dip on the stator side. Flux oscillations result directly in the oscillation of power transmitted to the system. This is a disadvantageous phenomenon. The goal of a generator control system in standard operating conditions is to be able to independently regulate the active and reactive power constantly maintaining the generated energy quality parameters [1]. If there is voltage interference on the power grid side, the generator control system should function properly within the range of the construction limits of a converter in the rotor circumference and attenuate the oscillations of the output power transmitted to the system. This facilitates the active operation of a wind power plant in the direction of voltage stabilisation on the terminal connecting it to the power grid through supplying the reactive power. The regulations provided by transmission grid operators in different countries [2, 3] include guidelines for continuous wind power plant operation when a voltage dip is present. The fulfilment of conditions imposed by regulations provided by individual operators makes it possible to maintain a relatively large number of wind turbines in the system. Thus, the risk of generating an additional disturbance or system destabilisation is lower. The power regulation unit structures presented in the literature may be divided according to the type of control methods used. The largest group of regulation systems includes the solutions based on the Field Oriented Control (FOC) technique and systems using the direct torque control (DTC) method. The smaller group of regulation systems comprises solutions using the non-linear control technique with doubly-fed induction machine multi-scalar models developed at the Gdańsk University of Technology [4]. 2. MATHEMATICAL MODEL OF A WIND POWER PLANT SYSTEM In order to examine the dynamics doubly-fed induction machine control system operation and the generator unit reaction to symmetrical voltage dips on the power system side, a mathematical model of a wind power plant has been developed. � is L net G unet Rnet i net Cf idg Lg Rg Cd ig model of the power grid and filter on the wind power plant output idr Pgsc two-way converter model DFIM Pr DFIM model Fig. 2 Wind power plant model diagram The mathematical model comprises several elements: a simplified model of the power grid, filter model, functional model of a two-way converter in the rotor circumference and the model of a doubly-fed induction machine. In order to describe the dynamics of a doubly-fed induction machine model, vector equations for a mono-harmonic machine have been used – see below [4]: � dS u S R S iS ja S d (1) Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips � d r u R R R iR j(a m ) r d * � dm J Im S iS m o d (2) (3) � L iS L i R S S m (4) � L i R L iS R R m (5) where: – stator and rotor voltage space vectors, �u S , u R – stator and rotor current space vectors current, �u S , u R – stator and rotor voltage space vectors, R , R – stator and rotor windings resistance, S R τ – relative time; ωm – rotor angular velocity; ωu – angular speed of reference system rotations J – rotor moment of inertia; m0 – driving torque on the machine shaft. A detailed description of the remaining elements of the mathematical model has been presented, in the form of differential equations, in paper [5]. � S , R 3. DOUBLY-FED INDUCTION MACHINE MULTI-SCALAR MODEL For the purposes of a generator power control system, it is beneficial to use the slip-ring asynchronous machine multi-scalar model described in paper [6]. The type “z” multi-scalar model of a doubly-fed induction machine is obtained as a result of adopting the variables of state depending on the values of the stator stream and rotor current vectors and the angle between these vectors; the variables of state are, however, independent from the co-ordinate system. The variables look as follows: �z11 r (6) �z12 sx i ry syi rx (7) �z 21 S2 (8) �z 22 sx i rx syi ry (9) By determining the multi-scalar variable derivatives using the equations of the machine vector mathematical model equations (1)-(5), a non-linear differential equations system of the multi-scalar model is obtained [6]: �dz11 L m 1 z12 m 0 d JLS J (10) �dz12 (11) d 1 L L L z12 z11z 22 m z11z 21 s u r1 m u sf 1 u si1 TV w w w �dz 21 R R L 2 S z 21 2 S m z 22 2u sf 2 d LS LS (12) �dz 22 (13) d 2 1 R L R L z 2 z 22 L L z 22 S m z 21 S m 12 z11z12 S u r 2 m u sf 2 u si2 TV LS w LS z 21 w w where: �u r1 u ry sx u rx sy (14) 7 Krzysztof Blecharz / Gdańsk University of Technology 8 �u r 2 u rx sx u ry sy �u sf 1 u sy sx u sx sy �u sf 2 u sx sx u sy sy �u si1 u syi rx u sx i ry �u si2 u sx i rx u syi ry � TV LS w L2S R r L2m R S w R S (15) (16) (17) (18) (19) (20) where: � L PS m z12 Ls (21) � 1 Lm QS z 22 Ls Ls (22) The active and reactive power of a doubly-fed induction machine on the stator side in the generator’s fixed condition may be expressed as follows by means of adopted multi-scalar variables [6]: 4. DOUBLY-FED INDUCTION MACHINE POWER REGULATION SYSTEMS For the purposes of control system synthesis, the type “z” multi-scalar model of a doubly-fed induction machine has been used. Different types of controllers may be used in the generator power regulation system. In paper [4], the active and reactive power control has been achieved by means of four cascade-connected PI type controllers, two of which operate the active and reactive power control lane. If PI type controllers are used, it is necessary to ensure the linearization of the machine equations by using the decoupling block [4]. Unfortunately, this control system does not ensure attenuation of the oscillation of power transmitted to the system caused by the voltage dip on the power grid side [5]. In order to improve the control system operation, it has been suggested to provide, on the control loop, a non-linear sliding controller based on the sliding control technique. The control structure diagram is shown in fig. 3 [7]. Using the sliding controller results in low-amplitude and high-frequency oscillations in the regulated values ranges and it is likely that there will be a constant average error value present. This is a characteristic feature of systems featuring sliding controllers caused by the effect of rapid switchovers within the controller structure. One of the solutions making it possible to limit this phenomenon is to force a sliding movement in an additional auxiliary feedback loop whose operating rage includes the controlled variables observer. The generator power control system structure based on this algorithmic approach has been presented in fig. 4. The mathematical description of the multi-scalar variables dynamics observer has been presented in paper [9]. The synthesis method and the sliding controller internal structure have been shown in paper [7]. In both suggested control systems, the generator shaft speed has been estimated on the basis of the rotor current measurement in the rotor co-ordinate system, and next on the basis of the calculations related to the same current in the stator co-ordinate system [4]. Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips � power grid u r1 ur2 Sliding controller Grid control system Transformation u r�S u r�S u r�R (+) (+) Transformation � RSestK Correction (+) Pzad Qzad Correction u r�R � RSes t �s ��S z11, z12, z21, z22 (+) (-) usf 1, u sf2, u si1, u si2 (-) Vector controller Estimation of: rotor angle location, stator flux, multi-scalar model variables, power P and Q ir��R DFIM is ��S u s�� S ps qs Fig. 3. Diagram of the power control system structure for a doubly-fed induction machine with a sliding controller based on type “z” multi-scalar model dependencies � power grid ur1 ur2 Sliding controller u r�S z12 Pzad (-) Qzad (+) Multi-scalar variables observer (+) (-) u r �S u r�R Transformation, correction z22 z11, z12, z21, z22 Power grid inverter regulation system Transformation, correction ur�R � s��S Vector controller Estimation of: rotor angle location, stator flux, multi-scalar u sf1, u sf2, u si1, u si2 model variables, power P and Q ps qs ir��R DFIM i s�� S u s��S Fig. 4. Diagram of the power regulation system structure for a doubly-fed induction machine with a sliding controller and multi-scalar variables observer based on type “z” multi-scalar model dependencies 9 Krzysztof Blecharz / Gdańsk University of Technology 10 5. DFIM ACTIVE AND REACTIVE POWER CONTROL In the standard condition of a power grid operation where all its parameters are maintained within permissible ranges [10], the active power in a wind power plant which is transferred to the system is determined on the output of a supervisory power regulation system. The value of this power depends on the wind power and wind turbine parameters. From the point of view of wind power plant operation efficiency, maximisation of the power obtained from wind is significantly relevant. This issue is discussed in numerous publications [12, 13]. In order to ensure correct and stable operation of the power system, the transmission system operators (in the case of large generating units) require forecasting the active power value which may be transferred from a wind power plant to the system [3]. The Grid Code [10] contains also guidelines referring to the active power change speed on the power plant terminal. The Polish transmission system operator demands that the average active power change gradient during 1 minute does not exceed 30% of the wind farm nominal power and the regulation systems of individual generator units must ensure the active power decreases to the level of at least 20% of the nominal power in less than 2 seconds. As far as smaller generating units are concerned, these requirements are provided individually in connection agreements. The reactive power regulation on the stator side in the nominal power grid condition may be achieved using two different strategies. The first strategy entails the machine being magnetised by the rotor current magnetising component and the reactive power being generated by a machine inverter. A machine supplied in this way does not draw the inductive reactive power from the power grid. The generator operates with a power factor equal to unity. The reactive power value set in the regulation system is zero. The second strategy requires that the generator can operate by any power factor that is possible to obtain. The reactive power value on the wind power plant generator output is defined by the wind farm operator taking into account the present value of generated active power and the required voltage level at the point of connecting the wind power plant to the system, according to the following dependency [11]: �Q zad min Q max , Q S S PCC (23) where: ΔQPCC means the reactive power value on the generator terminal connecting it to the system in order to ensure the required voltage level. However, QSmax is the maximum reactive power value taking into account the nominal apparent power of the generator and the active power supplied to the system. It is determined as follows: � max QS S P max 2 MDZ zad 2 S (24) According to the transmission power grid operators’ requirements, in standard operating conditions, the wind power plant generator connected to the power system must be able to operate with a power factor in the range from 0.975 of the inductive type to 0.975 of the capacitive type [10], within the full load range. The change of active and reactive power on the generator output in the broad range of the cos(φ) power factor is related with changes of the generator’s rotor supply voltage. The voltage generated by the converter supplying the machine rotor is the function of active and reactive power set values and the generator shaft slip. The value of this voltage may be expressed by the dependency determined in the vector equation below: � R R jsL R R S jLS sL2m R R jsL R uR iS uS jL m jL m (25) The dependency (25) has been obtained on the basis of a generator’s vector equations (1) - (5) in the steady state for the synchronously rotating co-ordinate system. Fig. 5 and 6 show the rotor voltage amplitude value depending on the shaft rotational speed and generator’s operating point. The presented diagrams have been obtained on the basis of dependencies and expressions for active and reactive power on the stator side Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips 11 while properly parametrizing the active and reactive power values set in the power control system. The active power value Ps = –0,5 is equal to the generator’s nominal power. However, the reactive power value Qs = 0,7 is equal to the inductive reactive power drawn by the generator’s stator in the condition when the machine rotor is not powered. � � 0.5 0.5 Qs =-0.3 0.4 0.4 0.3 0.3 Ps= -0.2 |ur | |ur | 0.2 0.2 0.1 0.1 Qs=0.7 Qs =0.7 0 0.7 0.8 Ps = -0.5 Ps= -0.5 0.9 1 �� 1.1 1.2 1.3 Fig. 5. Amplitude of rotor voltage in the function of shaft rotational speed and active power Ps with the constant reactive power value Qs 0 0.7 0.8 0.9 1 �� 1.1 1.2 1.3 Fig. 6. Amplitude of rotor voltage in the function of shaft rotational speed and reactive power Qs with the constant active power value Ps The diagrams in fig. 5 and 6 show that it is possible to estimate the reserve of the rotor supply voltage value that can be generated by the machine converter depending on the generator operation point. This is particularly relevant taking into account the possibility of continuing constant generator operation during a power grid voltage dip. Reactive power control on the stator side is important taking into account the method of operation of a doubly-fed induction machine with power grid voltage fluctuations and in case a voltage dip on the power plant terminal occurs. Together with the decrease in the power grid voltage value, the area of the active and reactive power to be generated by the generator [8] also decreases. 6. RESULTS OF SIMULATIONS AND EXPERIMENTS In order to check the correct operation of suggested control systems and feasibility of the assumed mathematical model of a wind power plant system, simulations and experiments have been carried out. Simulations for operation of individual control systems and generator’s reaction to the symmetrical voltage dip on the power grid side have been carried out by a computer program written in C++, in the Borland C++ 4.5 programming package. In order to solve the differential equation, the fourth-order Runge–Kutta method has been used. The simulation program has taken into account the digital character of the control systems operation and the impulse width modulation algorithm, both on the machine and power grid inverter side. All values have been expressed in relative units [4]. The experiments on the wind power plant model have been carried out in a laboratory station whose structure is shown in fig. 7. The examinations included a 2 kW doubly-fed induction machine and a synchronous generator (apparent power 20 kVA). The power grid voltage dips have been forced by short-term activation of a symmetrical 3-phase rectifier little R3 resistance. This solution allowed achieving voltage dips in a broad range of depth and duration. During the tests, the constancy of the wind power plant shaft rotational speed was assumed. Krzysztof Blecharz / Gdańsk University of Technology 12 � R2 G M DFIM M thyristor controller R1 operator’s console R3 Fig. 7. Laboratory station structure The operation in the system shown in fig. 7 where the energy is exchanged between the doubly-fed induction machine transmitting the energy obtained on the shaft to a synchronous generator is not favourable, taking into account high power oscillations in the system. Thus, the synchronous generator was loaded with an external R1 3-phase receiver with resistance characteristics. This enabled equalizing the power balance in the system. The tests for the operation dynamics of the presented regulation systems consisted in forcing step changes of values set in active and reactive power control sloops. The influence of the operation of individual control sloops on each other and the speed of reaction to power spikes was also assessed. In order to compare the dynamic properties of the tested control systems, all systems underwent the same sequence of changes of setpoints. The simulation results are shown in fig. 8 and 9. The short duration of the active and reactive power step change sequence resulted from the small time constants of the generator. The examination of the reactor system reaction to a voltage dip consisted in forcing symmetrical voltage dips (of different depth and duration) on the machine stator side. The ability of the following control systems to attenuate oscillations of the power transmitted to the system and the range of the regulation system correct operation was assessed. The results of the experiments for dips lasting 200 ms are shown in fig. 10 and 11. a) simulation � 0 b) 0 ps ps -0.5 -0.5 0 0 qs qs -1 -1 2 z11 2 z 11 0 0 0 z 12 0 z12 -0.5 -0.5 1.5 1.5 z21 z 21 1.0 1.0 1 z22 1 z 22 0 0 0 50 100 time [ms] 0 50 100 time [ms] Fig. 8. Active power ps and reactive power qs runs on the DFIM stator side and multi-scalar variable runs for a controller model based on type “z” model dependencies with a sliding controller a) and a sliding control and observer b) Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips � 0 z 12 -0.5 2 z21 0 1 z22 0 0 50 100 time [ms] Fig. 9. Runs of multi-scalar variables recreated in the observer; runs as for the event shown in fig. 8b � 0.5 0 -0.5 ps qs ωr 1 0 -1 1 0 0.5 z 12 0 -0.5 uab 2 ubc 0 uca -2 isa 0.5 isb 0 isc -0.5 ira irb irc 2 0 -2 0 200 400 time [ms ] Fig. 10. DFIM reaction to a voltage dip (duration 200 ms and depth 70%) for a control system based on the type “z” model dependencies with a sliding controller (EXPERIMENT) 13 Krzysztof Blecharz / Gdańsk University of Technology 14 � 1 ps 0 -1 1 qs 0 -1 1 z12 0 -1 ωr 2 0 uab 2 ubc 0 uca -2 isa isb isc 1 0 -1 ira irb irc 2 0 -2 0 200 400 time [ ms] Fig. 11. DFIM reaction to a voltage dip (duration 200 ms and depth 60%) for a control system based on the type “z” model dependencies with a sliding controller and observer (EXPERIMENT) 7. SUMMARY On the basis of the conducted tests, it may be concluded that the developed regulation systems enable independent active and reactive power control on the doubly-fed induction machine stator side. The control systems are have high operation dynamics and the reaction of the control systems to step changes of the set power values, in individual control loop, is very fast. In the event of network voltage dips occurring, the control system ensures the generator’s continuous operation. The range of the generator’s correct operation depends on the maximum permissible voltage on the rotor side which can be generated by the machine converter. Among the examined control systems, the system with a sliding controller and observer has the best properties related to attenuation of active power oscillations. Control of a Doubly-fed Induction Machine Operating as a Generator in a Wind Power Plant in the Event of Voltage Dips REFERENCES 1. Standard: EN 61400-21: 2001 Wind turbine generator systems. Part 21: measurement and assessment of power quality characteristics of network connected wind turbines. 2. Jauch C, Sorensen P , Bak-Jensen B., International Review of Network Connection Requirements for Wind Turbines. Proc. of Nordic Wind Power Conference, 2004. 3. Matevosyan J., Ackermann T, Bolik S., Soder L, Comparison of International Regulations for Connection of Wind Turbines to the Network. Proc. of Nordic Wind Power Conference, 2004. 4. Krzemiński Z., Cyfrowe sterowanie maszynami asynchronicznymi. Wydawnictwo Politechniki Gdańskiej, 2001. 5. Blecharz K., Krzemiński Z., Kulesza K., Problemy dostosowana układu sterowania maszyną dwustronnie zasilaną do nowych wymagań. Modelowanie i Symulacja, Kościelisko, 2004. 6. Krzemiński Z., Sensorless Multiscalar Control of Double Fed Machine for Wind Power Generators. Proc. of PCC, Osaka 2002. 7. Blecharz K.: Sterowanie ślizgowe maszyną dwustronnie zasilaną. Materiały konferencyjne SENE, Łódź 2005. 8. Blecharz K.: Sterowanie maszyną dwustronnie zasilaną pracującą jako generator w elektrowni wiatrowej przy zmianach napięcia sieci zasilającej. PhD dissertation. Gdańsk, 2008. 9. Blecharz K., Krzemiński Z., Bogalecka E., Control of a Doubly-Fed Induction Generator in Wind Park during and after Line-Voltage Distortion. Proc. of Electromotion 2009, Lille. 10. PSE Operator SA (2006): Instrukcja ruchu i eksploatacji sieci przesyłowej. 11. Ko H.S., Jatskevitch J.: Increase of Fault Ride-Trough Capability for the Network-Connected Wind Farms. Power Engineering Society General Meeting, 2006. 12. Abo-Khalil A., Lee D.-C, Seok J.-K., Variable Speed Wind Power Generation System Based on Fuzzy Logic Control for Maximum Output Power Tracking. Proc. of 35th Annual IEEE Power Electronics Specialists Conference, Germany, 2004. 13. Koutroulis E., Kalaitzakis K., Design of a Maximum Power Tracking System for Wind-Energy-Conversion Applications, IEEE Transaction on Industrial Electronics, vol. 53, no. 2, 2006. 15