Determination of Secondary Time Constant for Current Transformer Dimensioning A. H. A. Bakar, H. Mokhlis, N.Nazri, C.H.Wong UMPEDAC Research Centre Department of Electrical Engineering University of Malaya Kuala Lumpur, Malaysia a.halim@um.edu.my Abstract—In this paper, a study has been carried out to analyze the factors influencing the current transformer (CT) saturation factor (KS), in particular the secondary time constant (TS) of a CT. The study identifies and analyzes the optimum value for TS as this value varies. This paper also analyses and discusses the effect of TS to the KS factor in order to calculate the CT knee point voltage (VK) in dimensioning a CT. A comparison of guessed and measured value of TS is also done in this paper. CTs as TS is often a few or several seconds and the influence on KS is relatively small and almost negligible during the first 100 ms [7]. However, there was no further explanation on why TS was set to 3.0 s. Theoretically, TS is in order of few seconds. For TPX class CT, TS is 5.0 s or above whereas for TPY class CT, TS is 0 to 10.0 s. For TPZ class CT, CT’s has a linear core with a secondary time constant of 60 ± 6 ms for 50 Hz and 50 ± 5 ms for 60 Hz applications [8]. Keywords - Current transformer, saturation factor, secondary time constant, knee point voltage. In this paper, a study and an analysis on CT secondary time constant was carried out for TPS class CT for transformer differential protection in order to determine its optimum value and hence analyze its effect to the KS factor. Value for TS will be determined by means of iteration of KS factor. After obtaining KS, VK will then be calculated. Values obtained from the calculation will be compared to values obtained from measurement at the site. The measurement has been done on a 30 MVA 132/11kV transmission substation located at one of metropolitan substations in Kuala Lumpur [9]. I. INTRODUCTION In dimensioning a current transformer (CT), it is important to determine the optimum value of knee point voltage (VK). Beyond this point, CT will tend to saturate. Obtaining VK is by multiplying three factors. These factors are short circuit factor (KSSC), remanence flux factor (KR) and saturation factor (KS) [1]. II. In calculating CT saturation factor (KS), four parameters are required. The parameters are primary time constant (TP), secondary time constant (TS), time to saturation (t) and system frequency [2]–[5]. These four values will influence the value of KS factor which is to be calculated and therefore it is important to have precise value for these four parameters. KS factor is important as this value will influence the value of knee point voltage (VK) when dimensioning a CT for protection purposes. REQUIREMENTS OF SATURATION FACTOR (KS) AND KNEE POINT VOLTAGE (VK) As mentioned, in calculating VK for CT dimensioning, KS factor is an important factor which needs to be determined correctly. It is vital to design current transformer that will not saturate even when there is worst external fault to be expected. Various standards such as IEC 185, BS 3938 and ANSI/IEEE C57.13 have given the required transient knee point voltage by following expression [10]: Value for TP depends on system X/R ratio whereas value for t is depending on protection relay operating time. In practice, value for TS is difficult to obtain as it varies from site to site. Secondary time constant is actually a CT secondary loop time constant. It is determined by the CT magnetising inductance Lm and the sum of resistances in the secondary circuit [6]. VK = K0·KS·KR·I2·R2 (1) where: knee point voltage defined by the intersection of the VK = extensions of straight line portions of the excitation curve symmetrical fault current in secondary amps I2 = total secondary resistance burden including current R2 = transformer secondary, wiring loop resistance, lead resistance and load resistance the effect of the offset present during fault K0 = No study has been done on the value of TS especially for TPS and TPX Class CT. In dimensioning a CT for numerical protection relays, P.K. Gangadharan, T.S. Sidhu and J. Finlayson had taken the value of TS as three (3.0) seconds [1]. The value of 3.0 s was suggested by S.Holst and B. S. Palki [7]. This value is said to be a good estimate for high remanence ___________________________________ 978-1-61284-365-0/11/$26.00 ©2011 IEEE 58 KS = KR = saturation factor remanence flux factor START In this paper, remanence flux factor will not be considered in calculating the VK. Enter X/R value K0 depends on the fault inception angle. K0 will be maximum at 0° angle and minimum at 90° angle. For a full offset fault current, K0 is equal to 1.0 [7]. Enter maximum value of TS The saturation factor, KS is given by the following equation [1] - [5]: −t −t ω ⋅ TP ⋅ TS ⎛⎜ TS TP e −e KS = TS − TP ⎜⎝ where: TP = TS = ω= t= ⎞ ⎟ +1 ⎟ ⎠ Enter minimum value of TS (2) Enter value of (t) power system time constant CT secondary loop time constant system angular frequency time to saturation of CT Enter system frequency For TS min ≤ TS max, iterates KS factor KS is depending on protection relays operating time . Where high speed protection is employed, it is possible to reduce CT dimensions by allowing it to saturate only after both the protection relays and circuit breaker have tripped. With a given VK for the CT, time taken for the CT to go into saturation can be determined [9].Value of TS depends on the sum of the magnetizing and the leakage inductances (Ls) and the secondary loop resistance (Rs). This is given by the following equation [5]-[6]: END Figure 1. Flow chart of a developed programme IV. TS = Ls / Rs The developed programme has been tested in determining TS for a CT used in 500 and 132 kV system voltages. TABLE I show the parameters used which is normally used by utility [11]. Results of iteration are shown in TABLE II. Practically leakage inductances and secondary loop resistances is difficult to obtain. Leakage inductances vary from one type of CT to another type. The secondary loop resistance is depending on the winding resistances corrected to 75°C and external connected burden unless otherwise specified [5]. III. RESULTS AND DISCUSSIONS (3) Time to saturation used in the calculation is 30 ms. This is because high-speed operation of main protection relay must be ensured under transient condition with severe CT saturation due to DC transient current. Protection current transformer is required to provide more saturation free current transformation during this transient condition [11]. COMPUTER PROGRAMME DEVELOPMENT It is proposed TS value to be determined by an iteration of KS factor. A programme has been developed by using C/C++ to help the iteration process. In the developed programme, five parameters need to be entered. The parameters are system X/R, time to saturation, maximum and minimum estimation value of TS, and system frequency. TABLE I. DATA FROM UTILITY Voltage I1 I2* X/R TP level 500 kV 50 kA 12.5 A 20 64 ms 132 kV 31.5 kA 26.25 A 10 32 ms I1 = Maximum symmetrical fault current in primary amps *Current transformer turn ratio = 4000/1 (500 kV), 1200/1 (132 kV) [11]. After the programme stop iterating the KS factor, then values of TS and KS is observed. Value of TS should be taken at a point whenever KS starts to give constant value. The result is verified by using Matlab. Fig. 1 shows the flow chart of the C/C++ developed programme. In performing the iteration, a minimum and maximum value of TS needs to be guessed. Since TS is in order of few second [8], the estimation of TS should range between 1.0 s to 10.0 s. In this study, the estimation of TS minimum is 3.0 s as 59 suggested in reference [1] & [7] and TS maximum is set to 8.0 s. By using equation (2) and data in TABLE I, the KS factor of CT has been calculated and iterated. Results are shown in TABLE II and TABLE III. TABLE II. TS (s) 3.0 4.0 5.0 6.0 7.0 8.0 From TABLE II and TABLE III, it is observed that KS factor starts to give constant value after TS 3.0 s. Therefore, it is recommended that value for TS to be taken is 3.0 s or more. This value conforms to Fig. 2 and 3 and what has been stated in reference [8]. ITERATION OF KS FACTOR (500 KV) For comparison, iteration has also been made on the measured data of a CT. This is to compare between guessed and measured value of TS. KS 8.48 8.49 8.49 8.50 8.50 8.50 A study had been done on the transient phenomenon of the current transformer at one of the metropolitan substation located nearby Kuala Lumpur. In the study, a short circuit simulation was carried out. Computer-Aided Protection Engineering (CAPE) simulation software was used to perform this task. Simulation was done in order to find the maximum possible out of zone fault current that can occur at 11 kV system. Concurrently, TP was also obtained with the help of CAPE software [9]. For the case of metropolitan substation, maximum fault current will only occur during a three phase fault condition. For a single to ground fault, current was much lower since it was limited by the neutral earthing resistor. TABLE IV show parameters obtained from CAPE simulation [9]. TABLE IV. I1 12.129 kA TS (s) 3.0 4.0 5.0 6.0 7.0 8.0 I2* 6.74 A X/R 17.31 TP 55 ms I1 = Symmetrical fault current in primary amps *Current transformer turn ratio = 1800/1 Figure 2. Graph of Ks vs. Ts for t=30 ms and Tp=64 ms (500 kV) TABLE III. DATA FROM CAPE SIMULATION As for analysis, K0 = 1 since full offset primary fault current was assumed. ITERATION OF KS FACTOR (132 KV) KS 7.07 7.08 7.08 7.09 7.09 7.09 CT Analyzer test set from Omicron was used to measure the current transformer parameters used for protection scheme at the metropolitan substation. Results are shown in TABLE V [9]. TABLE V. Current Transformer Red Yellow Blue DATA FROM MEASUREMENT AT SITE VK (V) R2 (Ω) TS (s) 302.38 293.55 296.35 5.251 5.396 6.629 6.005 4.826 4.981 Time to saturation (t) 31.67 ms 29.10 ms 21.75 ms By using equation (2) and data in TABLE IV and TABLE V, the KS factor of CT for each phase has been calculated. Results are shown in TABLE VI. TABLE VI. SATURATION FACTOR (KS) Current Transformer Red Phase Yellow Phase Blue Phase Figure 3. Graph of Ks vs. Ts for t=30 ms and Tp=32 ms (132kV) 60 CT saturation factor, KS 8.54 8.08 6.63 As mentioned earlier, values of secondary time constant (TS) from TABLE V are measured values. It can be seen that the values measured are close to 5.0 s for yellow and blue phase CT whereas for red phase CT, TS is 6.005 s. These values of TS are actually close to the values of TS obtained from the iteration of KS factor. To verify these values and for comparison, iteration of KS factor was also done by using data in TABLE IV and TABLE V. The results are shown in TABLE VII, TABLE VIII and TABLE IX for red, yellow and blue phase CT respectively. TABLE VII. RED PHASE CURRENT TRANSFORMER TS (s) 3.0 4.0 5.0 6.0 7.0 8.0 KS 8.52 8.53 8.54 8.55 8.55 8.55 Figure 5. Graph of Ks vs. Ts for t=29.10 ms and Tp=55 ms (yellow phase CT) From TABLE VIII, value of KS factor is constant at TS 5.0 s to 7.0 s. This value of TS which is 5.0 s where KS starts to give constant value is actually close to the measured value in TABLE V where TS for yellow phase CT is 4.826 s. Values of KS factor obtained from iteration are still close to the calculated value in TABLE VI. Fig. 5 confirms the result. TABLE IX. TS (s) 3.0 4.0 5.0 6.0 7.0 8.0 BLUE PHASE CURRENT TRANSFORMER KS 6.62 6.63 6.63 6.63 6.63 6.64 Figure 4. Graph of Ks vs. Ts for t=31.67 ms and Tp=55 ms (red phase CT) From TABLE VII, it can be seen that value of KS factor is constant after TS 5.0 s. The value of TS where KS starts to give constant value is actually close to the measured value in TABLE V where TS for red phase CT is measured as 6.005 s. Values of KS factor obtained from iteration are also close to the calculated value in TABLE VI. Fig. 4 conforms the result. TABLE VIII. YELLOW PHASE CURRENT TRANSFORMER TS (s) 3.0 4.0 5.0 6.0 7.0 8.0 KS 8.06 8.07 8.08 8.08 8.08 8.09 Figure 6. Graph of Ks vs. Ts for t=21.75 ms and tp=55 ms (yellow phase CT) In TABLE IX, it is observed that value of KS factor is giving a constant value at TS 4.0 s until 7.0 s. It is encouraged to choose the value of TS to be 4.0 s since it started to give constant KS. However, the TS for blue phase measured on site is 4.981 s, which is slightly different to the simulation result. Since the TS 4.0 s and 5.0 s give same value of KS, therefore it does give any significant meaning to its knee point voltage. Once again, Fig. 6 confirms the result. 61 the value of TS which the CT analyzer gives. Therefore, without using a CT analyser, TS value of a CT can still be obtained by using the above mentioned method. However, in implementing the iteration of KS factor in order to determine the value of TS, it is important to get the accurate value of system X/R and time to saturation of a CT as these two values will have great influence to the KS factor value. By assuming TS 5.0 s and using data from TABLE IV, KS factor and knee point voltage for red, yellow and blue CTs are calculated by using equation (1) and (2). Results are shown in TABLE X. TABLE X. Current Transformer Red Yellow Blue CALCULATED VALUE KS R2 (Ω) 8.54 8.08 6.63 5.251 5.396 6.629 VK (V) 302.21 293.78 296.26 VI. This study has been done in order to obtain the optimum value of secondary time constant, TS. It has also shown how the TS will influence the KS factor. Even though TS has no great effect in determining KS factor, it is recommended that value of TS to be used is when it started to give two or more constant reading of KS factor. This range of TS is the best estimate for CTs with high remanence in order to get optimum value of KS. It is an evident that KS has a great influence to knee point voltage (VK). For comparison, say TS 6.0 s and using data from TABLE V, again KS factor and knee point voltage for red, yellow and blue CTs are calculated by using equation (1) and (2). Results are shown in TABLE XI. TABLE XI. Current Transformer Red Yellow Blue CALCULATED VALUE KS R2 (Ω) 8.55 8.08 6.63 5.251 5.396 6.629 VK (V) 302.37 293.78 296.26 REFERENCES [1] P.K. Gangadharan, T.S. Sidhu, G.J. Finlayson, “Current Transformer Dimensioning for Numerical Protection Relays”, IEEE Transactions on Power Delivery, Vol.22,No.1,2007. [2] IEC60044-1(2003-02), Instrument Transformers – Part 1: Current Transformers. [3] IEEE Standard Requirements for Instrument Transformers, IEEE Std. C57.13, 1993. [4] IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes, IEEE Std. C37.110, 1996. [5] IEC 60044-6(1992-03), Instrument Transformers – Part 6: Requirements for Protective Current Transformers for Transient Performance. [6] Ziegler.G., “Numerical Differential Protection: Principles and Application”, Khunkh Publicis Corporate Publishing, Earlangen, 2005. [7] S.Holst and B.S. Palki, “Co-ordination of Fast Numerical Relays and Current Transformers – Over Dimensioning Factors and Influencing Factors,” presented at the CIGRE 2001 Session, SC 34 Colloquium, Sibiu, Romania, Sep.2001, 305, unpublished. [8] W.A.Elmore., “Protective Relaying Theory and Applications 2nd ed., Revised and Expanded”, Marcel Dekker Inc., New York, 2004. [9] K.J. Abdul Jalil, A.H. Abu Bakar, W.N. Wan Mahadi, F.H. Mohamad Salleh, “Performance of Restricted Earth Fault Protection Scheme in the Presence of Current Transformer Remanence”, 2nd IEEE International Conf. On Power and Energy (PECon 08), Johor Baharu, Malaysia, Dec 1-3, 2008. [10] GE Publication No.: GER-3973B, “Dimensioning of Current Transformers for Protection Applications”. [11] Aminuddin Musa, Hasmarizal Hassan, “Current Transformer Application Guide”, Tenaga Nasional Berhad, Malaysia, 2003. From TABLE X and TABLE XI, it is observed that values of VK for each CT show a slight difference compared to measured value in TABLE V. The difference may be due to values of TS that had been used in the calculation. However, margin between measured and calculated values are still considered very small. V. CONCLUSIONS DISCUSSION The objective of performing iteration of current transformer saturation factor is to determine the value of secondary time constant. From the iteration done, it is recommended that the value for TS to be used is when it started to give two or more constant reading of KS factor. This range of values had been proved by comparing the measured with calculation values. It is observed that by taking TS 5.0 s or above, there is not much difference in KS factor value. It is also seen that, by means of iteration of KS factor by using guessed minimum and maximum value of TS, the point where TS starts to give constant KS value is almost the same to 62