SECTION 10405
SIGNS
PART 1 GENERAL
1.01 SUMMARY
A. This Section specifies informational and accident prevention signs. Exit signs are not covered in this section.
1.02 QUALITY ASSURANCE
A. Referenced Standards: This Section incorporates by reference the latest revision of the following documents. These references are a part of this Section as specified and modified. In case of conflict between the requirements of this Section and those of the listed documents, the requirements of this Section shall prevail.
Reference Title
29 CFR 1910.145 OSHA Specification for Accident Prevention Signs and Tags
ANSI Z535.1
ANSI Z535.2
IFC
WAC 296-24 (Part B-2)
NFPA 704
Safety Color Code
Environmental and Facility Safety Signs
International Fire Code
WISHA Marking Physical Hazards
Standard System for the Identification of the Hazards of
Materials for Emergency Response
1.03 DESIGN REQUIREMENTS
A. General
1. Accident prevention signs shall conform to requirements ofWISHA Chapter 296-24 WAC
(Part B-2), OSHA29 CFR 1910.145, ANSI Z535.1 and ANSI Z535.2.
2. Exit signs shall conform to the requirements of IFC 1011 and the local administrative authority.
3. All signs shall have rounded corners and four mounting holes.
4. Number, size, type and placement of signs shall be as indicated in the schedules in Part 3 of this Section.
B. Sign size shall be as follows:
Size
A
B
C
D
Width x Height
14 inches x 20 inches
10 inches x 14 inches
7 inches x 10 inches
14 inches x 10 inches
C. Sign type shall be as follows:
IM Message
101
102
103
104
ELECTRICAL ROOM - DANGER - 480 VOL TS
DANGER-4160 VOLTS
DANGER - HIGH VOLTAGE
DANGER - CONFINED SPACE ENTER BY PERMIT ONLY
105
106
201
202
203
204
205
DANGER - CONFINED SPACE AUTHORIZED PERSONNEL ONLY
DANGER - HOT
WARNING -
WARNING -
WARNING -
WARNING -
WARNING -
Fremont Siphon Project C00762C14
December 2014
SIGNS
10405 - 1
603
604
605
901
902
903
502
503
504
505
506
601
602
306
401
402
403
404
405
406
501
206
301
302
303
304
305
WARNING -
CAUTION - NON POTABLE WATER DO NOT DRINK
CAUTION - CORROSIVE MATERIALS WEAR REQUIRED PROTECTION
CAUTION - HEARING PROTECTION REQUIRED
CAUTION -AUTOMATIC EQUIPMENT MAY START AT ANY TIME
CAUTION - LOW CLEARANCE
CAUTION - HIGH TEMPERATURE
NOTICE -AUTHORIZED PERSONNEL ONLY
NOTICE - KEEP THIS DOOR CLOSED
NOTICE-
NOTICE-
NOTICE-
NOTICE-
SAFETY FIRST - EMERGENCY SHOWER AND EYEWASH
SAFETY FIRST - PROTECTIVE GEAR REQUIRED WHILE SERVICING
SAFETY FIRST
SAFETY FIRST
SAFETY FIRST
SAFETY FIRST
PUMP ROOM
DIESEL GENERATOR ROOM
ODOR CONTROL AND EQUIPMENT ROOM
WET WELL
REST ROOM
WASHROOM
JANITOR
STAIR
1.04 SUBMITTALS
A Procedures: Section 01300
B. Samples of sign materials and mounting hardware and shop drawings of all signs.
PART 2 PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A Brady
B. Seton
C. Approved equal
2.02 FABRICATION
A. Accident prevention signs: fadeproof graphic permanently embedded 1/8 -inch-thick fiberglass reinforced plastic; guaranteed not to chip, fade or peel for 15 years.
B. Building identification signs:
1. 12-inch by 30-inch fiberglass with fadeproof graphic pennanently embedded 1 /8 -inch-thick fiberglass reinforced plastic; guaranteed not to chip, fade or peel for 15 years.
2. Brown background with a white border and white lettering. Helvetica light or medium lettering. a. Upper case lettering: 3 inches high. b. Lower case lettering: 2-1/4 inches high.
C. Blade-type signs: Wall or ceiling mounted, projecting outward with infonnation on both sides.
Fremont Siphon Project C00762C14
December 2014
SIGNS
10405 - 2
D. Chain-mounted signs: Provide information on both sides.
PART 3 EXECUTION
3.01 GENERAL
A Distribute signs as listed in Schedules.
1. Schedule 1: Accident Prevention Signs:
Location
Door 101
Door 102
Number
1
1
Size
A
A
2. Schedule 2: General Signs
Location Number
As Directed
As Directed
1
1
Size
B
12x30
IM
101
603
IM
Building Address
Building
Identification
3.02 EXECUTION
A Do not begin production until all shop drawings have been approved.
B. Fasten surface-mounted signs to wall with expansion bolts or suitable anchors.
C. Conceal all fasteners as much as possible.
D. Use backup materials as required to achieve concealed mounting.
E. Mount posts in accordance with drawings.
END OF SECTION
Mount
Surface
Surface
Mount
Surface
Surface
Fremont Siphon Project C00762C14
December 2014
SIGNS
10405 - 3
SECTION 10530
FIRE PROTECTION SPECIAL TIES
PART 1 GENERAL
1.01 THE REQUIREMENT
A. The Contractor shall provide fire protection equipment and appurtenant work, complete and in place, in accordance with the Contract Documents.
B. Fire protection equipment shall be products of a single manufacturer.
1.02 REFERENCE SPECIFICATIONS, CODES, AND STANDARDS
A. Codes
1. National Fire Protection Association publications (NFPA).
2. International Fire Code (IFC) as published by the International Code Council
1.03 CONTRACTOR SUBMITTALS
A. Furnish submittals in accordance with Section 01300.
B. Shop Drawings: Manufacturer's literature, installation instructions, and details shall be submitted.
PART 2 PRODUCTS
2.01 GENERAL
A. Fire protection equipment and installation shall comply with the Code, NFPA Pamphlet No 10, and the manufacturer's published recommendations and specifications.
2.02 MATERIALS
A. Fire Extinguisher Designated FE: FE fire extinguishers shall be 10 pound minimum capacity, carbon dioxide type with minimum UL rating of 1 OB:C.
B. Bracket: Mounting brackets shall be specially designed for extinguisher.
C. Other Materials: Other materials not specifically described but required for a complete and proper installation of fire fighting devices shall be as selected by the Contractor, subject to the review of the Project Representative.
2.03 MANUFACTURERS
A. Fire protection items shall be from the following manufacturers, or equal:
1. Larsen's Manufacturing Co.
2. Potter-Roemer
3. General Fire Extinguisher Co.
PART 3 EXECUTION
3.01 PRODUCT DELIVERY, STORAGE, AND HANDLING
A. Delivery of Materials: Manufactured materials shall be delivered in original unbroken packages, or containers bearing the manufacturer's label with manufacturer's name, product description, and rating.
Fremont Siphon Project C00762C14
December 2014
FIRE PROTECTION SPECIAL TIES
10530-1
B. Storage: Materials shall be carefully stored in an area that is protected from deleterious elements as recommended by the material manufacturer. Storage shall be in a manner that will prevent damage to the material and its finish.
3.02 LOCATIONS AND INSTALLATION
A Locations: Fire prevention equipment locations and mounting heights shall be verified with the
Fire Marshall before installation and shall be installed where directed. If locations are not directed by the Fire Marshall, the Project Representative will direct locations.
B. Installation: Installation shall be per NFPA Pamphlet No. 10 unless directed otherwise by the local
Fire Marshall.
C. Brackets: Fire extinguishers shall be provided with and installed on brackets or brackets within cabinets. The Contractor shall block and reinforce walls to support the fire extinguishers.
END OF SECTION
Fremont Siphon Project C00762C14
December 2014
FIRE PROTECTION SPECIAL TIES
10530 - 2